Loading...
236 JEFFERSON AVE - BUILDING INSPECTION (5) • f q �, �2� �c� _ Tip-tit - I� jo 5� The Commonwealth of Massachusetts I SFE81Trt���� I RV10ES Board of Building Regulations and Standards Massachusetts State Building Code, 780 CMR SALEM O�J Building Permit Application To Construct,Repair, Renovate Or Demolish a One-or Two-Family Dwelling In yl This Section For Offi 'al Use Only Building Permit Number: Da Applied: J Building Official(Print Name) Signature Date _ SECTION 1:SITE INFORMATION LIoRe O d ess• ' ' n 1.2 Assessors Map&Parcel Numbers Y+ ) L I a Is this an accepted street?yes no Map Number Parcel Number 1.3 Zoning Information: 1.4 Property Dimensions: Zoning District Proposed Use Lot Area(sq 11) Frontage(tl) 1.5 Building Setbacks(ft) Front Yard Side Yards Rear Yard Required Provided Required Provided Required Provided 1.6 Water Supply: (M.G.L c.40,§54) 1.7 Flood Zone Information: 1.8 Sewage Disposal System: Zone: Outside Flood Zone? Public❑ Private❑ Municipal❑ On site disposal system ❑ Check ifyes❑ SECTION 2: PROPERTY OWNERSHIP' 2.1 Owner'of Rem eheryl Jalbert Salem, MA. 01970 Name(Print) City,State,ZIP 236 Jefferson Ave 978-741-5679 Djejrrmj@comcast.net No.and Street Telephone Email Address SECTION 3:DESCRIPTION OF PROPOSED WORK(check all that apply) New Construction[3 Existing Building❑ Owner-Occupied ❑ Repairs(s) ❑ Alteration(s) ❑ 1 Addition ❑ Demolition ❑ Accessory Bldg. ❑ Number of Units_ I Other ❑ Specify: Brief Description of Proposed Work'': if)Silaj n 5CAP.t A S1�4'�etM !, S VI'7 SECTION 4: ESTI ATED CONSTRUCTION COSTS Item Estimated Costs:(Labor and Materials) Official Use Only I.Building $ I I as.uo 1. Building Permit Fee:$ Indicate how fee is determined: 2.Electrical $ -a(.p Zg.Ob ❑Standard City/Town Application Fee ❑Total Project CosC'(Item 6)x multiplier x 3.Plumbing $ 2. Other Fees: $ 4.Mechanical (HVAC) $ List: 5.Mechanical (Fire $ -Suppression) Total All Fees:$ Check No. Check Amount: Cash Amount: 6.Total Project Cost: S a�DSO' ❑Paid in Full 11 Outstanding Balance Due: SECTION 5: CONSTRUCTION SERVICES 5.1 Construction Supervisor License(CSL) Ot ,�2�� LQ Jamks SllP rrYL�.1'� License Number Expiration Date Name of CSL Holder UF- (k_ M0_Q_) _e A List CSL Type(see below) U No.and Street ` ,f/ C/�` Type Description �`lNU� U Unrestricted(Buildings u to 35,000 cu.ft. /l/�✓ t r lY/\ "I R Restricted l&2 Family Dwelling City/Towq State,2I M Masonry RC Roofing Covering WS Window and Siding �n_ [ SF Solid Fuel Burning Appliances -11,I )slmw� MrnJU�,� lIU\yl{(} \((Y I Insulation -Telephone Email address D Demolition 5.2 Registered Home Improvement Contractor(HIC) V\y \n-t' �()I \'lo4s�i FS \Ohl\Lo HIC Registration Number Expiration Dare HIC Corppgy�N-m r,.jilC,Registlant Name No.an �v[1lreet ``u UJJ(,v aAwo., ` ..f 2z� Email address pfoQ-City/Town,State,ZIP `� Telephone SECTION 6:WORKERS'COMPENSATION INSURANCE AFFIDAVIT(M.G.L.c. 152.§ 25C(6)) Workers Compensation Insurance affidavit must be completed and submitted with this application. Failure to provide this affidavit will result in the denial of the Issuance of the building permit. Signed Affidavit Attached? Yes ..........❑ No...........❑ SECTION 7a:OWNER AUTHORIZATION TO BE COMPLETED WHEN OWNER'S AGENT OR CONTRACTOR APPLIES FOR BUILDING PERMIT I,as Owner of the subject property,hereby authorize V\V\`f1 t SD\Cky- to act on my behalf,in all matters relative to work authorized by this building permit application. 11/15/14 Print Owner's Name(Electronic Signature) Date SECTION 7b: OWNER' OR AUTHORIZED AGENT DECLARATION By entering my name below,I hereby attest under the pains and penalties of perjury that all of the information contained in this application is true and accurate to the best of my knowledge and understanding, l ' G er st L/ ( i7— a 11 f 1 Print Owner's or Authorized Agent' a(Ele nic Signature) Date NOTES: I. An Owner who obtains a building permit to do his/her own work,or an owner who hires an unregistered contractor (not registered in the Home Improvement Contractor(HIC)Program),will not have access to the arbitration program or guaranty fund under M.G.L.c. I42A.Other important information on the HIC Program can be found at wlww.mass.sovloca Information on the Construction Supervisor License can be found at www.mass.gov/dpss 2. When substantial work is planned,provide the information below: Total floor area(sq.ft.) (including garage,finished basement/attics,decks or porch) Gross living area(sq.ft.) Habitable room count Number of fireplaces Number of bedrooms Number of bathrooms Number of half/baths Type of heating system Number of decks/porches Type of cooling system Enclosed Open 3. "Total Project Square Footage"may be substituted for"Total Project Cost' l7 i V ill {I U O so I G r 3301 North Thanksgiving Way,Suite 500 Structural Group Lehi, UT84043 P: (801) 234-7050 Scott E. Wyssling, PE Head of Structural Engineenng scoff-wysslingC vivintso/ar.com October 28 2014 Mr. Dan Rock, Project Manager Vivint Solar 24 Normac Road Woburn MA 01801 Re: Structural Engineering Services Jalbert Residence 236 Jefferson Avenue, Salem MA S-4039258 5.61 kW System Dear Mr. Rock: Pursuant to your request, we have reviewed the following information regarding solar panel installation on the roof of the above referenced home: 1. Site Visit/Verification Form prepared by a Vivint Solar representative identifying specific site information including size and spacing of rafters for the existing roof structure. 2. Design drawings of the proposed system including a site plan, roof plan and connection details for the solar panels. This information was prepared by the Design Group and will be utilized for approval and construction of the proposed system. 3. Photovoltaic Rooftop Solar System Permit Submittal identifying design parameters for the solar system. 4. Photographs of the interior and exterior of the roof system identifying existing structural members and their conditions. Based on the above information we have evaluated the structural capacity of the existing roof system to support the additional loads imposed by the solar panels and have the following comments related to our review and evaluation: Description of Residence: The existing residence is typical wood framing construction with the roof system consisting of: • Sections 1 & 3 (rear and side sections): 2 x 8 lumber at 19.2"on center. • Section 2(front section): 4 x 8 lumber at 19.2"on center. The attic space is unfinished and photos indicate that there was free access to visually inspect the size and condition of the roof rafters. All wood material utilized for the roof system is assumed to be Spruce- Pine-Fir#2 or better with standard construction components. Our review of the photos of the exterior roof does not indicate any signs of settlement or misalignment caused by overstressed underlying members. Stability Evaluation: A. Wind Uplift Loading 1. Refer to attached Ecolibrium Solar calculations sheet for ASCE/SEI 7-10 Minimum Design Loads for Buildings and other Structures, wind speed of 100 mph based on Exposure Category "B" and 10 and 45 degree roof slopes on the dwelling areas. Ground snow load is 40 PSF for Exposure "B", Zone 2 per (ASCE/SE17-10). 2. Total area subject to wind uplift is calculated for the Interior, Edge and Corner Zones of the dwelling. vivi t. s o i a r Page 2 of 2 B. Loading Criteria • 10 PSF= Dead Load roofing/framing 40 PSF= Live Load (ground snow load) • 5 PSF= Dead Load solar panels/mounting hardware Total Dead Load=15 PSF The above values are within acceptable limits of recognized industry standards for similar structures. Analysis performed of the existing roof structure utilizing the above loading criteria indicates that the existing rafters will support the additional panel loading without damage, if installed correctly. C. Roof Structure Capacity 1. The photographs provided of the attic space and roof rafters show that the framing is in good condition with no visible signs of damage caused by prior overstressing. D. Solar Panel Anchorage 1. The solar panels shall be mounted in accordance with the most recent "Ecolibrium Solar Installation Manual', which can be found on the Ecolibrium Solar website (ecolibriumsolar.com). If during solar panel installation, the roof framing members appear unstable, deteriorated, structurally compromised or deflect non-uniformly, our office should be notified before proceeding with the installation. 2. Maximum allowable pullout per lag screw is 235 Ibs/inch of penetration as identified in the National Design Standards (NDS) of timber construction specifications for Hem-Fir (North Lumber) assumed. Based on our evaluation, the pullout value, utilizing a penetration depth of 2 1/2", is less than what is allowable per connection and therefore is adequate. Based on the variable factors for the existing roof framing and installation tolerances, using a thread depth of 2 Yd' with a minimum size of 5/16" lag screw per attachment point for panel anchor mounts should be adequate with a sufficient factor of safety. 3. Considering the roof slopes, the size, spacing, condition of roof, the panel supports shall be placed at and attached to no greater than every third roof rafter as panels are installed perpendicular across rafters and no greater than the panel length when installed parallel to the rafters (portrait). No panel supports spacing shall be greater than three (3) rafter spaces or 57.6" o/c, whichever is less. 4. Panel supports connections shall be staggered to distribute load to adjacent rafters. Based on the above evaluation, it is the opinion of this office that with appropriate panel anchors being utilized the roof system will adequately support the additional loading imposed by the solar panels. This evaluation is based on information supplied to us at the time of this report and current industry standards and practices. Should you have any questions regarding the above or if you require further information do not hesitate to contact me. Ve truly yours, OF _P� r o CfV, Scott E. Wyssf PE ° °0 MA License N . 50 9p� EGiSi FSSlONAL vivi t. S O i a r F- - -- ---- -------- - U ' V INTERCONNECTION POINT, LOCKABLE DISCONNECT SWITCH, ANSI METER LOCATION, a= 80'OF 1-PVC CONDUIT <°'w & V) m FROM JUNCTION BOX TO ELEC PANEL UTILITY METER LOCATION I O N<D EI z V/ z �+m—� LNwO 13 cu Q a , co , gm Q •� ( C JUNCTION BOX ATTACHED TO O ARRAY USING ECO HARDWARE TO ry KEEP JUNCTION BOX OFF ROOF I co o m V/ a N m m0 (D > za wmm w wwzm (D w z (22)Yinali Enemy YL255P-290 MODULES WITH A h h ¢ K ( Enohase M215�60-2LLS2z-ZC MICRO-INVERTER ( M z z p MOUNTED ON THE BACK OF EACH MODULE ` ' SHEET NNAME: ( PV SYSTEM SIZE: I H g 5.61 kW DC I U) a L—_ — ————_— ———————— ————————— I SHEET J NUMBER: PV SYSTEM SITE PLAN o SCALE: 3/32"= V-0" > a CIRCUIT#1: `O 12 MODULES (� a C $ Q1 PLUMBING VENTS in c o m @-ZN� z L lEi �nN0 ry TIE INTO METER# U COMP.SHINGLE 95429989 ¢ 13 COMP.SHINGLE ` V ! • N •0 � Roof Section 2 Roof Section 1 RoofAnmAR 170 Roorra as Roof Azimuth:260 Roof TiB:45 v, m o n Lo ¢ m m v m K U j m Q U' W .. COMP.SHINGLEKIM m rc m m w j w m Z ¢ F � SHEET NAME: LL Z O � a Roof Section 3 v clRculr#z: i RoofAzrt 170 10 MODULES SHEET RW 71t 10 NUMBER: PV SYSTEM ROOF PLAN 4 N SCALE: 3/16"= 1'-0" > d EcolibriumSolar Layout Skirt o Coupling O Clamp Warning: PV Modules may need to be shifted with respect to roof trusses to comply with 40 Bonding Jumper maximum allowable overhang. EcolibriumSolar Layout n f� I — I Skirt e Coupling O Clamp Warning: PV Modules may need to be shifted with respect to roof trusses to comply with ® Bonding Jumper maximum allowable overhang. EcolibriumSolar Layout r-� Skirt o Coupling O Clamp Warning: PV Modules may need to be shifted with respect to roof trusses to comply with 0 Bonding Jumper maximum allowable overhang. EcolibriumSolar Layout r1 r1 r-, Skirt e Coupling O Clamp Warning: PV Modules may need to be shifted with respect to roof trusses to comply with ® Bonding Jumper maximum allowable overhang. EcolibriurnSolar Layout n Skirt e Coupling O Clamp Warning: PV Modules may need to be shifted with respect to roof trusses to comply with ® Bonding Jumper maximum allowable overhang. EcolibriumSolar Layout r� Skirt e Coupling O Clamp Warning: PV Modules may need to be shifted with respect to roof trusses to comply with ® Bonding Jumper maximum allowable overhang.