Permit No.
To the Commissioner:
Re: Northeast Animal Shelter Ward
I certify that to the best of my knowledge, information and belief, the plans and computations accompanying the attached
application concerning the locus at
347 Highland Avenue Salem, MA
Ward are in accordance
with the requirements of the Massachusetts State Building Code and all other pertinent laws and ordinances.
G\S�EFEp ARCy/ AR H T- MASS.7. NO. 3386
A_ y F William A. Yuhas
o COMPANY
MARBLEHEAD, ti Architect
p2` MASS. JyW ADDRESS '
y'�JH 0 MPSSp4 80 Lafayette Street, Marblehead, MA 01956
PHONE 781.631.7039
Commonweal of Massachusetts
County of dam_On this_�day ofa4e C/ 0 d ,before me, the undersigned notary public,personally appeared
11l rA lie WJ6= proved to me through satisfactory evidence of identification,which were
Personal I{nowledpe to be the person whose name is signed on the preceding or attached
document,and who swore or affirmed to me that the contents of the document are truthful and accurate to the best of
his/her knowledge and belief.
Before me,
My Commission expires
NEAS.C.C.ArchDesgin.080107.doc
McBrie. LLC
160 Sylvan Street l \/\/\/\%\/\/ Telephone: 978-646-0097
Danvers, MA 01923 y Structural Design & Sales Fax: 978-646-0087
www.mcbrie.com
AFFIDAVIT
STRUCTURAL DESIGN AND INSPECTIONS
TO: Mr. Peter Beaudoin
Groom Construction Co., Inc.
96 Swampscott Road
Salem, MA 01970
RE: Northeast Animal Shelter
347 Highland Ave.
Salem, MA
McBrie, LLC Job#: 7-017
I certify that to the best of my knowledge, information and belief, the plans and computations for the
captioned building modifications was designed in accordance with the structural requirements of the
6d'edition of the Massachusetts State Building Code and all other pertinent laws and ordinances.
I also certify that I, or my authorized representative, in conformance with Section 116.0, Construction
Control, and Section 1705.0 of the 6a' edition of the Massachusetts State Building Code, will inspect
the work during construction. This will include the inspection and review responsibilities outlined in
Section 116 and as indicated as SER on the Program of Structural Tests and Inspections. We shall also
oversee the testing agencies and will require all tests reports be submitted to our office for review.
Upon completion of the construction, a Final affidavit indicating that the Program of Structural Tests
and Inspections submitted for permit have been satisfactorily completed and all discovered defects
have been corrected will be issued upon request.
No. 41143
mw of M Structural Engineer MA Reg. No.
�O b
o H AMm 160 Sylvan Street, Danvers, MA 01923
WTURAL y Address
No.41143
�TEP� (978) 646-0097
FSS oN LE" d6/e 7 Telephone
Mt
McBrie, LLC 08/06/07
Structural Engineers Date
7-017 Affidavit-Design and Inspections.doe Page 1 of 1
CITY OF SALEM
FIRE DEPARTMENT - FIRE PREVENTION BUREAU
29 Fort Avenue
�c Salem, Massachusetts 01970-5232
8e (978) 745-7777 _
'ERMIT TO INSTALL:
Date
'prinkf er and/or Standpipe System
.)wner'st4ame: i3Or !'i�
Tstaller's Name:
permit is hereby granted based on approved plans,to install the system designated above. All plans are approved solely
:)r identification of type and location of fire protection devices. All plans are subject to approval of any other authority
aving jurisdiction and issuance of a permit by said authority. Upon completion, the Installer shall request a test and file a
:ertificate of Completion or Inspection_/
fuM1 locelbn sY alieel end no.,.,dexnbe In such manrwr ss b povlde adeQuAe ide MKcelbn e(brelbnf
IOTICE: CONTRACTOR TO REQUEST FINAL INSPECTION. sae ,a �sh9�
his Perrn t will expire �/0
(THIS PERMIT MUST BE CONSPICUOUSLY POSTED UPON THE PREMISES.)
>rrn 991E (Rev 9ry7)
t
EI`ZOF
PUBLIC PROPERTY
a DEPARTMENT
KIMBERi.EY DRISCOLL
MAYOR 120 WASHINGTON STREET 0 SALIE .MAssACHLSka-M 01970
TEL 978-74S-9S9S R FAx.978-740-95"
APPLICATION FOR THE REPAIR, RENOVATION, CONSTRUCTION.
DEMOLITION OR CHANGE OF USE OR OCCUPANCY, FOR ANY EXISTING
STRUCTURE OR BUILDING
1.0 SITE INFORMATION
Location Name: Building:
Property Address: Z47 H-%a#441V2a Av,=A/0 =
qsu Aff'Y7 , 114 A 0/9,70
property is located in a; Conservation Area YIN Al Historic DisMct Y/N /V
2.0 OWNERSHIP INFORMATION
2.f Owner of Land _
Name: W,6Z r#E'A---�T .dNs�-sr9 L Stl LTL �no� ,
Address: 5417 1.1z4:57d/4AAjz> .AV/ IILE'
AIA Q/9 70
Telephone: 9'78 -• r24,& - 9f3S 8
3.0 COMPLETE THIS SECTION FOR WORK IN EXISTING BUILDINGS ONLY
Addition Existing /
Renovation y/ Number of Stories Renovated /
Change in Use New /
Demolition Existing /3;000 +/-
Approximate year of Area per floor (sf) Renovated 8 600 '1 /-
construction or renovation
of existing building New 5. 000 +/-
Brief Description of Proposed Work:
f-=7= 0,gr
AAF4,0 4c!')2/J' r✓C'sx�a-rlcvcT�orJ .c5 ti! x�'s;-zA�i
Q Ji/1 /*7,04-
l✓br�rat �sr AA1i7,
�— -- -- Mail Permit to: tg0t0Y1✓7 i yt�rio �1� S�-✓err co r- /�ox� -----
What is the current use of the Building? �/✓O CCU
Material of Building? "d"RONZ Y If dwelling, how many units? M�r4
Will the Building Conform to Law? �� Asbestos? A/M
Architect's Name /� LLZANt ,Q ' f�Llf/OS
So GRs� j78/-d;3f- 703q
Address and Phone , AdA
Mechanic's Name
Address and Phone 26 ;SGt/Am PS•G Ate"
Construction Supervisors License# 040379 HIC Registration#
Estimated Cost of Project$JOr 000 Permit Fee Calculation
Permit Fee$ 14, --To s-• Oo Estimated Cost X$7/$1000 Residential
Estimated Cost X$11/$1000 Commercial
An Additional $5.00 is added as an
Administrative charge.
Make sure that all fields are properly and legibly written to avoid delays in processing.
The undersigned does hereby apply for a Building Permit to bull t e above stated
specifications. Signed under penalty of perjury /�
Date 8 a
�I
yz J N
N a
9 ti,
1
I
Fire Suppression Inc.
For excellence in fire protection
PROPERTY AT
347 HIGHLAND AVE.
Salem, Mass.
THE BUILDING IS TO BE OCCUPIED BY
A PET CENTER/ANIMAL SHELTER
780 CMR 903.1.1 FIRE PROTECTION NARRATIVE REPORT
903.1.1
(1.A) BASIS (METHODOLOGY) OF DESIGN
SECTION 1 — BUILDING DESCRIPTION
a) Use Group: B, Business,
b) Number of floors above grade: One
c) Types of occupancy (hazards) within the building:
Ordinary Hazard Offices , Service Areas
d) Site access arrangement for emergency response vehicles: Existing
e) Building wall construction: Masonry— Meal Deck Roof.
f) Building height under 20 feet
SECTION 2—APPLICABLE LAWS. REGULATIONS AND STANDARDS
• 527 CMR— Fire Prevention Regulation 24.00
• 780 CMR—The Massachusetts State Building Code, sixth edition; Section
906.0, 915.0, 917.0, 918.0.
NFPA 13 Standard for the Installation of Fire Sprinkler Systems
NFPA 25 — Inspection, Testing and Maintenance of Water-Based Fire
Protection Systems
NFPA 72 — National Fire Alarm Code
SECTION 3 — DESIGN RESPONSIBILITY FOR FIRE PROTECTION SYSTEMS
Fire Sprinkler System Ellis Fire Suppression Inc.
10 Brandt Drive
Woburn, MA 01801
781-389-6921
1
Tel: 781.389.6921 10 Brandt Drive, Woburn, MA 01801 Fax: 781.933.0988
ty ,
(page 2)
SECTION 4— FIRE PROTECTION SYSTEMS TO BE INSTALLED
Automatic Sprinkler System Description:
The building is to be equipped with a wet pipe sprinkler system covering the
entire building. A hydrant flow test was taken prior to design and the results so
Noted on the sprinkler design drawings.
Design responsibilities: The professional engineer (P. E.) will design the
sprinkler system as per NFPA 13 2002 edition and specified the fire protection
system to be installed. He reviews and approves the installation.
The P E is considered the engineer of record and certifies the installation
for code:
903.1.1
(1.b) SEQUENCE OF OPERATION
SECTION 1
Wet-Pipe Automatic Sprinkler System:
Heat produced from a fire melts the fusible element in one or more of
group of sprinkler heads.
On a wet pipe system: The sprinkler head(s) is opened and water is immediately
discharged to control the fire. Water flow alarms are tripped upon sprinkler flow
indicating an alarm condition. Water will continue to flow from the open sprinkler
head(s) until the valve serving that area is manually closed.
Fire Alarm System:
The operation of the wet valve shall automatically ring a local alarm bell and
forward a signal directly to the Fire Department.
2
(page 3)
TESTING CRITERIA
SECTION 1 —TESTING CRITERIA
The system is equipped with an inspectors test valve located at strategic location
able to generate a flow of water equivalent to one sprinkler head which should
generate an audible and or visual alarm. NFPA requires a minimum of yearly
testing and certification following the procedures outlined in NFPA 25 with
documentation.
Acceptance test criteria shall be per NFPA 13 and NFPA 72, and shall include
but not be limited to:
1. 200 psi, 2-hour hydrostatic testing of the sprinkler system piping per
NFPA 13.
2. Not greater that 60-second response time on flow switches.
Recommended response time of flow switches of 30-45 seconds`.
3. Tamper switches to ring supervisory when partially closed`.
4. Verified Notification of Fire Department of alarm signals*.
- optional; may be done at annual fire sprinkler test.
SECTION 2— EQUIPMNENT AND TOOLS
All required equipment, tools, and literature shall be supplied by the appropriate
contractor at the time of testing including, but not limited to:
• Manufacturer's literature
• This approved Narrative report
• Flow measuring devices
• Gauges
• Communication radios
• Hydrostatic testing equipment
SECTION 3—APPROVAL REQUIREMENTS
The following shall be supplied to the Fire Department upon final completion and
acceptance of the systems:
• Name, address, and telephone number of installing contractor for each
system
• Contractor's Material and Test Certificate
END OF NARRATIVE
3
HYDRAULIC CALCULATIONS
FOR
NORTHEAST ANIMAL SHELTER
347 HIGHLAND AVE
SALEM, MA. 01970
DATE: 7/19/2007
-DESIGN DATA-
OCCUPANCY CLASSIFICATION: LIGHT HAZARD
DENSITY: . 10 gpm/sq. ft .
AREA OF APPLICATION: REMOTE 900 sq. ft .
COVERAGE PER SPRINKLER: 120 sq. ft .
NUMBER OF SPRINKLERS CALCULATED: 11 SPRINKLERS
TOTAL SPRINKLER WATER FLOW REQUIRED: 182 . 8 gpm _
TOTAL WATER REQUIRED (including hose) : 282 . 8 gpm
FLOW AND PRESSURE (REQ' D @ SOURCE) : 282 . 8 gpm @ 27 . 5 psi
FLOW AND PRESSURE (AVAIL.. @ SOURCE) : 282 . 8 gpm @ 79. 6 psi
SPRINKLER ORIFICE SIZE: 1/2 inch
SPRINKLER K FACTOR: 5. 6 K
CALCULATIONS BY HASS COMPUTER PROGRAM
HRS SYSTEMS, INC.
TUCKER, GA 30084 aa�
yes__`,,_ _u..•,
e o JAn1:Es
4 McHUG1 `
cr FIRE PROTECTION �
NO.3B572
�?ISlF � \
r^r
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 7/20/2007 E : \SPRINK DESIGN\MB\NE ANIMAL SHELTER 7-19-07 .SDF
JOB TITLE : NE ANIMAL SHELTER
WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ' D
NODE PRESS . PRESS . @ PRESS . @ DEMAND PRESS .
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
1 80 . 0 75 . 0 1090 . 0 79 . 6 282 . 8 27 . 5
Available pressure is 52 . 1 psi (1900) greater than required pressure .
AGGREGATE FLOW ANALYSIS :
TOTAL FLOW AT SOURCE 282 . 8 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 100 . 0 GPM
OTHER HOSE STREAM ALLOWANCES 0 . 0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 182 . 8 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
1 2 . 0 SOURCE 27 . 5 182 . 8
2 2 . 0 - - - - 27 . 4 - - -
3 2 . 0 - - - - 27 . 4 - - -
4 2 . 0 - - - - 21 . 9 - - -
5 10 . 0 - - - - 18 . 0 - - -
6 12 . 0 - - - - 11 . 4 - - -
7 12 . 0 - - - - 11 . 2 - - -
8 12 . 0 - - - - 11. 2 - - -
9 12 . 0 K= 5 . 60 8 . 0 15 . 9
10 12 . 0 K= 5 . 60 7 . 3 15 . 2
11 12 . 0 K= 5 . 60 7 . 1 14 . 9
12 12 . 0 K= 5 . 60 7 . 0 14 . 8
13 12 . 0 K= 5 . 60 8 . 1 15 . 9
14 12 . 0 K= 5 . 60 7 . 4 15 . 2
15 12 . 0 K= 5 . 60 7 . 1 14 . 9
16 12 . 0 K= 5 . 60 7 . 0 14 . 8
17 12 . 0 K= 5 . 60 8 . 2 16. 0
18 12 . 0 K= 5 . 60 7 . 5 15 . 3
19 12 . 0 K= 5 . 60 7 . 2 15 . 0
20 12 . 0 K= 5 . 60 7 . 1 14 . 9
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 7/20/2007 E: \SPRINK DESIGN\MB\NE ANIMAL SHELTER 7-19-07 . SDF
JOB TITLE: NE ANIMAL SHELTER
PIPE DATA
PIPE TAG Q (GPM) DIA(IN) LENGTH PRESS .
END ELEV. NOZ. PT DISC. VEL (FPS) HW (C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 1 182 . 8 6. 280 PL 38 . 00 PF 0. 1
1 2 . 0 SRCE 27 . 5 (N/A) 1 . 9 140 FTG TG PE 0 . 0
2 2 . 0 0 . 0 27 . 4 0 . 0 0 . 001 TL 90 . 00 PV
Pipe: 2 182 . 8 6 . 280 PL 7 . 00 PF 0 . 0
2 2 . 0 0 . 0 27 . 4 0 . 0 1 . 9 140 FTG E PE 0 . 0
3 2 . 0 0 . 0 27 . 4 0. 0 0 . 001 TL 29 . 00 PV
Pipe: 3 FIXED PRESSURE LOSS DEVICE
3 2 . 0 0 . 0 27 . 4 0 . 0 5 . 5 psi, 182 . 8 gpm
4 2 . 0 0 . 0 21 . 9 0. 0
Pipe: 4 182 . 8 4 . 260 PL 7 . 00 PF 0. 4
4 2 . 0 0 . 0 21 . 9 0 . 0 4 . 1 120 FTG EGA PE -3. 5
5 10 . 0 0 . 0 18 . 0 0 . 0 0 . 008 TL 49 . 00 PV
Pipe 5 182 . 8 3 . 260 PL 144 . 00 PF 5. 7
5 10 . 0 0. 0 18 . 0 0 . 0 7 . 0 120 FIG 4E PE -0 . 9
6 12 . 0 0 . 0 11. 4 0 . 0 0 . 031 TL 184 . 00 PV
Pipe : 6 121 . 6 3 . 260 PL 10 . 00 PF 0 . 1
6 12 . 0 0 . 0 11 . 4 0 . 0 4 . 7 120 FTG ---- PE 0. 0
7 12 . 0 0 . 0 11 . 2 0 . 0 0 . 015 TL 10 . 00 PV
Pipe: 7 60 . 7 3 . 260 PL 10 . 00 PF 0. 0
7 12 . 0 0 . 0 11 . 2 0 . 0 2 . 3 120 FIG ---- PE 0 . 0
8 12 . 0 0 . 0 11 . 2 0 . 0 0 . 004 TL 10 . 00 PV
Pipe: 8 60 . 7 1 . 610 PL 17 . 00 PF 3. 2 ,
8 12 . 0 0 . 0 11 . 2 0 . 0 9 . 6 120 FTG T PE 0. 0
9 12 . 0 5 . 6 8 . 0 15. 9 0. 126 TL 25 . 00 PV
Pipe: 9 44 . 8 1 . 610 PL 10 . 00 PF 0. 7
9 12 . 0 5 . 6 8 . 0 15. 9 7 . 1 120 FTG ---- PE 0. 0
10 12 . 0 5 . 6 7 . 3 15. 2 0 . 072 TL 10 . 00 PV
Pipe: 10 29 . 7 1 . 610 PL 8 . 00 PF 0. 3
10 12 . 0 5 . 6 7 . 3 15 . 2 4 . 7 120 FTG ---- PE 0. 0
11 12 . 0 5 . 6 7 . 1 14 . 9 0 . 034 TL 8 . 00 PV
Pipe : 11 14 . 8 1 . 610 PL 8 . 00 PF 0 . 1
11 12 . 0 5 . 6 7 . 1 14 . 9 2 . 3 120 FTG ---- PE 0 . 0
12 12 . 0 5 . 6 7 . 0 14 . 8 0 . 009 TL 8 . 00 PV
Pipe : 12 60. 8 1 . 610 PL 17 . 00 PF 3.2
7 12 . 0 0 . 0 11 . 2 0 . 0 9. 6 120 FTG T PE 0 . 0
13 12 . 0 5. 6 8 . 1 15 . 9 0 . 126 TL 25 . 00 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 7/20/2007 E: \SPRINK DESIGN\MB\NE ANIMAL SHELTER 7-19-07 .SDF
JOB TITLE : NE ANIMAL SHELTER
PIPE TAG Q (GPM) DIA(IN) LENGTH PRESS .
END ELEV. NOZ . PT DISC. VEL (FPS) HW (C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe : 13 44 . 9 1 . 610 PL 10 . 00 PF 0 . 7
13 12 . 0 5 . 6 8 . 1 15. 9 7 . 1 120 FTG ---- PE 0 . 0
'14 12 . 0 5 . 6 7 . 4 15 . 2 0 . 072 TL 10 . 00 PV
Pipe : 14 29 . 7 1 . 610 PL 8 . 00 PF 0 . 3
14 12 . 0 5 . 6 7 . 4 15 . 2 4 . 7 120 FTG ---- PE 0 . 0
15 12 . 0 5. 6 7 . 1 14 . 9 0 . 034 TL 8 . 00 PV
Pipe: 15 14 .8 1 . 610 PL 8 . 00 PF 0 . 1
15 12 . 0 5 . 6 7 . 1 14 . 9 2 . 3 120 FTG ---- PE 0 . 0
16 12 . 0 5. 6 7 . 0 14 . 8 0 . 009 TL 8 . 00 PV
Pipe: 16 61 . 2 1 . 610 PL 17 . 00 PF 3 . 2
6 12 . 0 0. 0 11 . 4 0 . 0 9 . 7 120 FTG T PE 0 . 0
17 12 . 0 5 . 6 8 . 2 16. 0 0 . 128 TL 25 . 00 PV
Pipe: 17 45 .2 1 . 610 PL 10 . 00 PF 0 . 7
17 12 . 0 5 . 6 8 . 2 16. 0 7 . 1 120 FTG ---- PE 0 . 0
18 12 . 0 5 . 6 7 . 5 15 . 3 0 . 073 TL 10 . 00 PV
Pipe : 18 29 . 9 1 . 610 PL 7 . 00 PF 0 . 2
18 12 . 0 5 . 6 7 . 5 15 . 3 4 . 7 120 FTG ---- PE 0 . 0
19 12 . 0 5. 6 7 . 2 15 . 0 0 . 034 TL 7 . 00 PV
Pipe: 19 14 . 9 1. 610 PL 10 . 00 PF 0 . 1
19 12 . 0 5 . 6 7 . 2 15 . 0 2 .3 120 FTG E PE 0 . 0
20 12 . 0 5 . 6 7 . 1 14 . 9 0 . 009 TL 14 . 00 PV
NOTES :
(1) Calculations were performed by the HASS 7 . 8 computer program
under license no. 5002007210 granted by
HRS Systems, Inc.
4792 LaVista Road
Tucker, GA 30084
(2) The system has been calculated to provide an average
imbalance at each node of 0 . 004 gpm and a maximum
imbalance at any node of 0 . 074 gpm.
(3) Total pressure at each node is used in balancing the system.
Maximum water velocity is 9 . 7 ft/sec at pipe 16.
(4) PIPE FITTINGS TABLE
Pipe Table Name : CUSTOM. PIP
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE: 7/20/2007 E : \SPRINK DESIGN\MB\NE ANIMAL SHELTER 7-19-07 . SDF
JOB TITLE : NE ANIMAL SHELTER
PAGE: A MATERIAL: S40-TW HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D N
Ell Tee LngEll ChkVly BfyVly GatVly AlmChk DPVly NPTee
1 . 610 4 . 00 8 . 00 2 . 00 9 . 00 6 . 00 1 . 00 10 . 00 10 . 00 8 . 00
3 . 260 10 . 00 20 . 00 7 . 00 22 . 00 14 . 00 1 . 00 18 . 00 18 . 00 20. 00
4 . 260 13 . 00 26 . 00 8 . 00 29. 00 16. 00 3 . 00 26. 00 26. 00 26. 00
PAGE: D MATERIAL: DIRON HWC: 140
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G N. .
Ell Tee LngEll ChkVly BfyVly GatVly NPTee
6. 280 22 . 00 47 . 00 14 . 00 51 . 00 16 . 00 5. 00 47 . 00
C4 7
O J
w H
C7
WATER SUPPLY ANALYSIS
100. 0 Static: 80. 00 psi Resid: 75. 00 psi Flow: 1090.0 gpm y
LEGEND v
0
Available pressure
N
1 79.59 psi @ 282.8 gpm Z 0 0
Required pressure 0
2 27.48 psi @ 282.8 gpm z
A. Source Supply Curve H
G 80 . 0 _1 B. System Demand Curve 3�
A r
ro
U x H
G ro z
E y r
M
P 60.0 to
R' H c
z �
E x
S o a
S � m
U H K
E 40. 0 >
mr
/ H
( n
z
P 2 > z
s H r
i > v
20. 0 tr H
In
ti
r
H
C+7
0. 0 B
H
I
0 'd
M m
-14.7
� rn
400 600 800 1000 1200 1400 1600 1800 2000
FLOW (GPM)
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7
DATE: 7/20/2007 E: \SPRINK DESIGN\MB\NE ANIMAL SHELTER 7-19-07 .SDF
JOB TITLE: TIE ANIMAL SHELTER
WATER SUPPLY CURVE
84+
I
0 \\\\\\\
* <-75 . 0 psi @ 1090 gpm
I Flow Test Point
I
70+
i
I
I
63+
I
I
I
P 56+
R
E I
S
S 49+
U I
R I
E I
42+
( I
P I
S I
1 35+
I
I
I
28+ X
I
i
i
21+
----------------------------
I
14+ LEGEND "
I X = Required Water Supply
1 27 . 48 psi @ 282. 8 gpm
7+
I 0 = Available Water Supply "
I 79. 59 psi @ 282 . 8 gpm "
' I "
0++-+---+----+-----+------+--------+--------+---------+-----------+
400 600 800 1000 1200 1400 1600 1800 2000
FLOW (GPM)