Loading...
5 BRISTOL STREET - BUILDING JACKET q 5 BItTSTOT.'-STREET `', I � C�xe ie 9e-`Ipaatl - A&Y AGBom-d of-O&d4 ry 97a"ond and Aamdawcda 1Viov F. Weld G ✓t'LCCooxrnaa�C Cate Q Governor one�7J 9" - Room moi Kentaro Tsuisulni ✓FJoeCon, � u4ella 02108 Chairman (617) 727-3200 Charles J. Dinezio Administrator April 19, 1991 Pyro Industries, Inc. 11625 Airport Road Everett, WA 98204 Attention: Dr. O. J. Whitfield Subject: Massachusclts Approval Status of Certain of Pyro Industries Wood Pellet Stove Svslenhs Dcar Dr. Whitfield: At its March 26, 1991 monthly meeting, the 00RS voted approval of certain wood pellet burning stoves and heaters for use in Massachusclts - the following information identifies these products and any voled stipulations and/or requirements. I'1io Industries, Inc. of hn'ece11 11'uehin Alun Whitfield Automatic Fecd, '11mmostaticAly Contolled, Mcchenically and Naiumlly DmItc(I Wood Pcllcl Funning Room I lcalm. -. 1) ADVAN I'A(d 11-1ireplace inscrl m )dels); 2) RENAISSANCE; 3) PRODIGY The cited wood pellet burning appli:mccs,as specified in the application materials dated February 6, 1991,me approved for use in Massachusetts subject tb conformance with all other applicable Slate and Federal regulations as well as any requirenhenis of the Manufacturer - where mechanically vented equipment is specified by the Manufacturer for through the side wall venting of such appliances,such venting systems shall be installed in accordance with the Manufacturer's installation manual. As part of the approval of these wood pellet burning heating appliances, it is required that these products be installed in accordance with all applicable sections of the Fifth Edition of the State Building Code(the Code) and that specifically, clearances to combustible construction shall be in accordance with the requirements of Section 3409.4 of the Code; i.e., Section 3409.4 docs allow for reduced clearances to combustibles when exposed combustible construction is protected with noncombustible materials affording the necessary fire protection resistance; additionally, clearances may be reduced to the manufacturer's tested clearances when such clearances are identified on the listing label of such products. These approvals are for those wood pellet stoves/heaters as described in the cited application materials and any change in name,design,equipment,installation or intended usewill require Pyro Industries,Inc. to submit these products again to the CMSB for consideration of approval. Pyro Industries, Inc. is cautioned that any recommendation for approval by the Construction Materials Safety Board (CMSB) and any actual approvals granted by the State Board of Building Regulations and Standards (SBBRS) are based on an approval process consisting of an evaluation of only the safety aspects of product design,construction, installation procedures and intended use, based on the application materials submitted. Neither the CMSB nor the SBBRS evaluate product efficiency or the advisability of using (Inc product as opposed to any other product and therefore approval as discussed herein is not to he utilized in advertising or promotion of said products. Very truly yours, S 6T�O61�21, 0-/L C� OFB IL lG REGULONS AND STANDARDS Charles J. Din;g74 Administrator CJD/un r cc: Mr. Charles R. Brewster, Jr., Caner, MA 02339 ol9uge A William F.Weld Governor �iae Ja6/u�u+t m0f G� , ,�(amoo�ivaetYd 0,208 Kentaro Tsutsuml (617) 727-3200 Chairman Charles J. Dinezio SOLID FUEL BURNING PELLET STOVE AFFIDAVIT Administrator FOR PELLET STOVES SATISFYING-NEGATTVE PRESSURE"TESTING (FAIL.(99l/WINTER 1992 HEATING SEASON) To the State Board of Building Regulations and Standards: Date 1/21/ 1992 1. Drew McDaniel as Assistant Manager, Sales & Marketing on behalf of Pyro Industries , Inc . a manufacturer of solid fuel burning pellet stovWhealersiT're place inserts(circle appropriate products), hemby eerafy that the following pellet heating appliances,by explicit model Idenancatlon; model(s): WP2 - Advantage Freestanding and Insert WW1/WW1A Renaissance and Erin Freestanding WP3 Prodigy I and Prodigy IZ Freestanding have been tested.or tested/listed (circle appropriate information)per the negative pressure test requirements of either ULC 5627/CSA Standard 8366.2,or via methods/requimments of similar nationally recognized standards,and found to satisfy the applicable criteria of ULC 5627/CSA Standard B366.2 or other nationally recognized standards;additionally,bumback did not occur either during normal or abnormal"negative pressure"testing. f: MANUFACTURER P rolIndustries , Inc. SIGNED: r TYPED OR PRINT NAME ABOVE Andrew K. McDaniel TITLE /��(, Assistant Manager Sales & Marketing On this J04-4 day of 194^1 .then personally appeared before me,the above named Ll MARICELA V. VALDWA and made oath that the above statements by him/her,arc true. Notary Pubic STATE OF WASHINGTON MY Commisslon Expiles BEFORE ME December 29, 1993 - NOTARY PUBLIC _ _ /�-• ,S Gy 19 p MY COMMISSION EXPIRES: WW�/t ci7 x�lnt _ Page 2 of 2 .- al A STATE BOARD OF BUILDING REGULATIONS AND STANDARDS M Ilium F. sPeld I;m enurr _ CODEWORD Kentaro '1'smtsumi - Chairman December, 199t Charles J. Dinczio Administrator PELLET STOVES - AT ISSUE With the high cost of sources of energy and the heating season upon us once again, many people are looking Towards alternate or supplementary methods of providing warmth for themselves and their families. Passive wooit v,..-cs (devices that need to he manually stoked) have been a favorite over theyears, both for their handsome appearance and for their Cory supply of heat. 'The pellet stove has evolved from these earlier solid fuel burning models. Pellet stoves allow a person to fill a storage bin that is attached to the unit with fuel. The fuel (pellet) is then auger-fed to the burn chamber at a specific ime to keep the fire and heat roaring. This, of course, frees the person who would normally tend the fire at per lorm other (asks, such as sit back and enjoy the flame. The December. 1") issue of CODMORD announced the approval of certain direct vent versions of a solid fuel horning device that uses corn as its source a fuel. Certainly, this is an innovative method for dealing with heating issues in terms of the environment (less destruction of trees) and in terms of the costs (of wood products). Although many pellet stoves are fueled by wcxtd products, they, toxo, can be operated with creative alternate s000ces such as corn kernels, rice coal or even walnut shells. (I he type of stove would dictate the type of fuel.) I lowesc.r. with innovation sometimes comes problems, m least for regulators. All new ideas are subject to improvement as lessons are learned through operation. The test methods identi(ird in the appendices of lire building code are dcsignrd tr help avoid expensive lessons. "Ihese tests are meant to chalicnge the operation of devices as they normally would perforin when installed. The listing laboratory then labels the proxluct to assure the buying public that some hpc of performance test was administered and the results were favorable. We all recognize the seal of Ilttdrl,srltcrs laboratory (UL) as the most common marking. When a new product such as the pellet stove is introduced to the market, testing becomes a problem. 'I he standard tests for solid fuel burning appliances are intended to test passive devices, not actively-fed models. Alihoueh in some respects this may not be a great concern, it docs raise at least one issue: how dues the unit respond to negative pressure (not currently part of the required testing pro(ess). Thus, in the interest of public safety, the hoard of Building Regulations and Standards has voted to take steps to address this matter. The following firticle details the path that the manufacturer, consumer and building official must take when selling or installing a pellet stove in the Commonwealth for the cited periods of time. In the future, proper testing may make much of this procedure unnecessary. Until such time, the following action is required. hiblic3tionNo.17,007-10 1 I 12 91-.21 C.R. , Appmved by:Philmore Anderson III,State Purchasing Agent ' PFI.I EI' STOVE 13111LI)ING PFItNIIT ItI`QIIIItFIN EN'I'S F(3R 1'IIF. F.AI,L 1991,1WINTE'll 1992 IIFjVIING SEASON NOTE 1I1F. ROLLrnt 1A71 1.A'Fr7R,11.477(JN IS /.S.SUEI r IN L/F[) UF',1 ,tlF,l/r)f2IA'L)UH PA I lfl t 11/1r.')1, .SFN7 70 PFLLFT ,11;1,\'I'Ft< 7URERS SFFRLVG ;1!'1`IUn .11 IrcR ,S.4LF ;IN!) INST11, AII( W rtl I.1'I.LFT APPLL INCF_S LV MASSAc:'1111SF.'M. Pellet stovcs/heaters/fireplace inserts are heating appliances that burn wood pellets, but may also he designed To burn rice coal, kernel corn, walnut shells, or other pelletized types of solid fuels. Such appliances typically "possess numerous electro-mechanical devices that are subject to potential failure or abnormal operation. "Because the existing Building Code requirements for solid fuel burning equipment did not anlicipale pellet stove technology (the existing Code requirements - Section 3409 -were written some 10 to 15 years ago and were intended to deal largely with "passive", as opposed to eleciro-mechanically "active", solid fuel burning equipment), the State Board of Building Regulations and Standards (SBBRS) at it's December In, 1991 meeting has approved an "AFFIDAVIT PROGRAM" foreP Ilet appliances for the Fall 1991/Winter 1992 heating season. In summary, each pellet appliance manufacturer must provide an affidavit to the S1313RS and to the i manufacturer's sales representatives. To obtain the necessary building permit, the end-user shall provide to the local building department a copy of the affidavit referring to the specific pellet appliance which is to be installed. Pellet appliances, in addition to being UL 1482 or ANSUUL 737 labeled (which have been Traditional requirements of the Building Code for all solid fuel burning appliances - Section 3409.2) will either: a) have been tested to ULC 5627 or ASTM draft standard E-91, revised draft 5/28/91• in a "ncizialive pressure" environment and have demonstrated acceptable performance under such test conditions (acceptable performance includes satisfying requirements for minimum CO release into tate test enclosure and additionally; demonstrating that burnback into the fuel hopper does not occur for either nut mal or abnormal operating states in a test enclosure at "negative pressure", relative to bulk air pfcssulcl: OR b) if not so tested, the manufacturer shall provide a carbon monoxide (CO) gas alarm with Illc sale of the pellet appliance. 'lhese requirements are imposed on pellet appliances because there exists the possibility Ihnl should mechanical draft in the pellet stove fail and the building in which the pellet appliance is operating is Reilly constructed, the pressure in the building could be lower than the bulk atmospheric pressure - particularly if the building has bathroom, kitchen or other exhaust tans operating. Under such Conditions, a pellet appliance c might backdraft into the building, or even burnback into the fuel hopper, where, depending on the manufacturer, from 20 to 150 pounds of pellets may he stored (note that even if the pellet appliance docs not rely on mechanical (Irrt(t, these "negative pressure" issues still exist). From lite perspective of the local huilding departments, it will only he necessary to advise applicants seeking a permit to install a pellet appliance that he must got the required affidavit from the manufacturer, and that the affidavit must he filed with the permit application. 111cre, are Iwo (Z) types of aflidavils, titles ate sho(an on the next page. 1'AGIi 2 ----- 1 PELLETSTOVE REQUIRENIENTS - CONTINUED FROM PAGE 2 One affidavit is entitled: SOLID FUEL BURNING VELLE,r STOVE AFFI nAVIT FOR PELLET STOVES SATISFYING "NECA'17VE PRESSnRE" TES"PING (FALI. I9911WINTF.R 1992 IIFAIING SEASON) the other is entitled: SOLID FUEL BURNING I'F-LLE'F STOVE AFFIDAVIT FOR PELLET STOVES SOLD WITII CARBON MONOXIDE: (CO) GAS AI.ARNIs (FALI. MOVINTER 1992 IIFA77NG SEASON) Please note that the affidavit dealing with CO gas alarms, refers to requirements found on "page V of that affidavit (page I of this affidavit is simply the instruction shccr on how to properly complete the allidavit). As this is an important issue that ulav allec( many building ollicials in the. coming months, we have reproduced below that portion of the instruction page addressing CO gas alarm requifentcnts. (Note that it is the responsibility of the manufacturer to choose an approptiale gas alarm.) REQUIREMENI'S CO GAS ALARNIED PELLET APDL-IANCESZ For the Fall 1991/Winler lOQ2 heating season. if 'negnlive pressure" listing testing, per the nu•tho(oloe� of IJLCS627/CSAStandard 8106.2, S"I'ANDARU FOR SPACE IIEYTERS I Olt USE WI IIt SOLID FUtil-S. Section 12.3, or via the requirements of draft standard ASI TI E-91, revised (halt 5/28/91, S:IANDARD SAFETY SPECIFICATION FOR ROOM HEA-MtS PELLET FUEL BURNING TYPE, Section 10.1.5. has not been performed on product inventory intended for sale in this heating season, it will still be rcyuiled that pellet stoves, as solid fuel burning devices, be tested/listed to UL 1482 and/or ANSI/III. 717, as applicable (per Section 3409.2 of the Fifth Edition of the Massachusetts State Building Code); additionalhr, it will be necessary that manufacturers provide a carbon monoxide gas alarm, with the pellet appliance - the selection of the CO gas alarm shall be the responsibility of the pellet stove manufacturer, but said gas alarm will possess CO detection capability/sensitivity consistent with generally accepted national standards tckitinh to safety, and be of such a design that a sufficiently audible alarm is sounded in the event of excessive backdrafting or in the event of burnback; both types of events causing excessive CO release to file habitable space of the building. The CO gas alarm shall be located either in the room in which the pellet sane is operating or shall otherwise be located to ensure early warning in the event of abnormal pellet stove operation (the gas alarm installation shall be per the alarm manufacturer's instructions and otherwise he in accordance with all applicable local, State and Federal requirements, and any additional requirements imposed by the pellet stove manufacturer). Should the gas alarm be energized via battery, the alarm should. ` if possible, be designed to warn the user of low battery voltage, or weakened charge. "Ilse pellet sloe manufacturer shall provide the gas alarm and any and all necessary gas alarm instruction materials. ,a part of the equipment and materials furnished at the time of sale of the pellet stove. Pages four (4) and five (5) that follow are samples of the affidavits that a building official must rcceisr sshcn all individual is applying for a permit to install a pellet stove. Please remember that this action is onh required for pellet devices, not for passive devices that would be labeled through the notnrtl Icstinc procedure. PAGE, 3 i. .STOVE INSTALLATION CONFIGURATIONS r t F YOUR WHITFIELD MAY BE INSTALLED AS: l • A freestanding unit with a pedestal placed on a non-combustible floor pad. 1 • A hearth set fireplace insert into a masonry or factory built fireplace. A built-in stove placed on an insulated floor pad. A mobile home heater placed on a non-combustible floor pad, while being bolted and electrically grounded to the chassis of the home. FLOOR PROTECTION Your Whitfield pellet stove must be installed on a noncombustible protective floor pad of minimum 3/8" thickness material or a masonry hearth. The hearth or floor pad must extend a minimum of 6" in front of It and from each side of the stove(and 6" behind, in a freestanding/inside vertical installation configuration) or to the nearest permitted combustible material (if less than 6"). re � lr i I I � I h,Fte th P d MI t EHte d f AM 0I6 to 11 S,1 t (I; - A fEo tOfltoSto 1 1 -I'Ir 6 In Tho,n .at In A 1- t 1 nd 1n ' - yyI - - InsiAc V'Hwal L,elnll�ron Cor dipiu�fon pIpIIpIlllplAM11111111GV l CLEARANCES TO COMBUSTIBLES The stove must be installed with the following minimum clearances to combustible materials. I' 1" Clearance Behind Stove 1 1"Clearance From Front Of 1"Clearance To The Corner Hopper To Back Of Stove i 6"13clearance From Front s Of Hopper To The Door _ 18" Clearance Above The Stove I 1 I I Although a 1"clearance to a combustible is a minimum, you should have at least 1.5" of clearance to allow the hopper lid I' to open all the way. Keep all combustible material at least 18" (horizontally) away from glass. v 10 i Section 4: Floor Protection & Clearances Floor Protection ii The Whitfield Prodigy II Pellet Stove must be installed if on a noncombustible protective floor pad of minimum Floor protector must extend 3/8" thickness material or on a masonry hearth. The ✓ `KT at least 6" from the fare of the hearth or floor pad must extend a minimum of 6"from stove, and 0" to the sides and °j the face of the stove OR TO THE NEAREST PER- °,krear of the stove. MITTED COMBUSTIBLE MATERIAL IF IT IS LESS THAN 6" from the back or sides of the stove. (See i Figure 1). _ Noncombustible Clearances to Combustibles '.__--- 8 Floor Protector I The stove must be installed with the following mini- mum clearances from the side and back wall to the i nearest combustible materials. (See Figure 2). Figure 1 - Floor Protector Size �i 1 r r -A -- — - - - i 6 v 6" j i 6" t 1 arc < } 2 x r ii ii VI Figure 2- Clearances to Combusible Materials 4 FLOOR PROTECTION & CLEARANCES FLOOR PROTECTION The Whitfield Renaissance Pellet Stove must be installed on a noncombustible protective floor pad of minimum 3/8" thickness, or on a masonry hearth. The hearth or floor pad must extend a minimum of 6" from the face of the stove forward and from each side of the stove OR TO THE NEAREST PERMITTED COMBUSTIBLE MATERIAL IF IT IS LESS THAN 6"from the back or sides of the stove (See Figure 9). NOTE' FLOOR PROTCTION MUST EXTEND TO AREAS BENEATH THE VENT PIPE. n Floor Protector must extend at least 6"from the face of the stove and 0"to the sides and rear of the stove. T 6" Noncombustible Floor Protection ®, Figure 9 CLEARANCES TO COMBUSTIBLES The stove must be installed with the following minimum clearances from the side and back wall to the nearest combustible materials: See Figures 10, 11,and 12. ® 1"Clearance to back wall 6 lop) 6- Figure Figure 11 Figure 12 A - ure 10 6 i INSTALLATION AND ® MAINTENANCE • •• INSTRUCTIONS ThisOmea symbol on then listed y L means the product Is listed by g' Underwriters Laboratories,Inc. PELLET CHIMNEY ASSEMBLY General Assembly Instructions: -" ALIGN THE PIPE. PUSH TOGETHER. TWIST TO LOCK. 4 i 2 3 i , I TO unlock: REVERSE THE PROCEDURE. 5. A Metal-Fab Chimney Cap should be used on all installations,either horizontal orvertical,to prevent back General Installation Notes drafts and to keep out rain and debris. 1. The pipes are presealed with a fiber rope. Do not 6. To increase Pellet Chimney life, coat all exterior remove the rope and take care when twisting,so as not to metals with high-temperature, rust-proof paint, partic- bind up the rope. ularly in areas near the ocean. NOTE: If fly ash leakage occurs,seal casing joints with a 7. Inspect each part for damage, before installing. 'r silicone-type sealer rated for use at 400° F or higher. 8. Maintain a 3"minimum clearance to combustibles 2. Consult local building or fire officials about restric- when passing through a combustible wall, ceiling or tions and Installation inspection in your area. roof. Always use a Firestop when penetrating a floor or 3. Metal-Fab Pellet Chimney (vent) and Fittings are ceiling. intended for installation to form a continuous passage- NOTE: Combustible materials Include: materials made way from the appliance to the termination of the chim- of or surfaced with wood, compressed paper, plant ney, either above the roof or horizontally through the fibers,plastics or other materlal that will Ignite and bum. wall, including the chimney cap. To comply with UL Such material Is considered combustible even though listings and Metal-Fab warranty, use only chimney parts flame proofed, fire retardant, or plastered. defined by these instructions or Metal-Fab brochure. 9. When horizontally vented,maintain a clearance of 4. Metal-Fab Pellet Chimney and Fittings are ap- 24" from doors, windows and public walkways. proved for venting listed pellet stoves and gas and oil furnaces that do not exceed 570° F at the outlet 10. An Increaser may be used at any point in the temperature. chimney system to meet stove manufacturer's require- ments. 11 .Before installing, consider the design and con- Rear Stove Exhaust, with Exterior Venting struction of the building so as to minimize the need to f. pass through existing structural supports. (See Figure 2.) J " 1. Begin installation by following steps 1 through 3 'Cr- 12 The maximum height of the Pellet Chimneyshould for direct horizontal venting. not exceed 60 feet. A support is required at 30 feet. 2. Install the Tee to the chimney.Slip a Support Band 13. Elbow joints are designed to fit tight and are not over the lower portion of the Tee. Install the Tee Support adjustable.All direction changes must be made at 450 or so that the Tee extends through the hole approximately a . 900. 3/16". Rest the flange of the Support Band on the Tee Support and tighten the two bolts securely to the Band. Installation Instructions NOTE: A minimum at 3" clearance to combustible's Direct Horizontal Venting (See Figure 1.) exterior surface from the vent Is required. 1. Attach and secure the Stove Adaptor to the appliance 3. Install chimney sections vertically,starting at the Tee flue outlet.Sheet metal screws may be used to secure the outlet. Attach a Wall Bracket approximately every six feet Stove Adaptor to the appliance flue outlet. to secure the vent. NOTE:Seal as needed using sealerrated for4000 For 4. If the chimney is to pass through the-roof or ,. higher. overhang,a hole 93/4"square for 3"pipe andl0Y4"square 2. On the same centerline as the appliance outlet, cut for 4" pipe is required. See,Figures 2 and 6. a hole into the outside wall, 6'/e" diameter for 3" pipe and 5. Slide the Flashing over the pipe and secure to roof. 9'/2"diameter for 4"pipe. Caution is needed to assure no Apply mastic tape where chimney passes through the wires or pipes within the wall are damaged. Flashings. Apply a thick ring of mastic around the chimney. Slide the Storm Collar down into the mastic 3. Install the Wall Thimble by inserting the larger of ring and secure. See Figure 5a. the two parts on the appliance side and the other half through the outside wall, 6. Install any additional chimney sections terminating at NOTE: The two horizontal cylinders of the Thimble must the Chimney Cap. See Figures 5a and 5b for minimum engage a minimum of two Inches. height above the roof. 4. Install the Pellet Chimney sections to allow 3" minimum clearance to the exterior of the building. 5. It is recommended that a House Shield be used to keep the ash from forming on the exterior of the building. If used, secure the Shield to the wall using the screws supplied. 6. Install the horizontal Chimney Cap by positioning the Cap over the chimney end and securing by tightening the two bolts/nuts. i --- BY."for 3" PIPE 1045"for 4" PIPE i 3"MINIMUM C .. ' - 3"MINIMUM CLEARANCE — I STOVE ADAPTOR '-CLEARANCE ��WALL BRACKET (REQUIRED RY HORIZONTAL WALL 6FT.) VENT CAP 24"CLEARANCE THIMBLE TO DOORS, T WINDOWS STOVE AND PUBLIC ADAPTOR 'TEE (OR ROUND WALKWAYS _ _ ^ CLEANOUT TEE) OPENING 6%"for /'HOUSE 3" PIPE I/ SHIELD SUPPORT BAND 0'6'for (SEE NOTE, 4"PIPE FIG. 4) TEECAP \TEE SUPPORT FIG. 1 FIG. 2 -2- r Rear Stove Exhaust, with Interior VentingCHIMNEY STRAP 9VV' SQUARE BOLT On NAIL FOR 3' PIPE (See Figure 3.) SECURELY TO 101V'SQUARE STRUCTURAL BEAM l FOR 4" PIPE —SEE NOiE) '�: � 1. When installing the chimney from the rear outlet, a 3" MINIMUM minimum of 3" to combustible surfaces is required. go- TO COMBUSTIBLES ELBOW 2. Attach and secure the Stove Adaptor to the appliance flue outlet. Sheet metal screws may e used secure the be tFIRESTOP SPACER Stove Adaptor to the appliance flue outlet. AND SUPPORT BAND — (2)4s° (SEE NOTE. FIGA) ELBOWS NOTE: Seal as needed using sealer rated for 400° For f LESS THAN 10' __- PIPE ..A.. 1 - p 3" 915"sq. minimum - - jiiilli"j /�MASTIC 4" /0'/."sq. minimum 2 MIN. MINIMUM t. ..A., TERMINATION LESS THAN 10 FEET - O FROM RIDGE, WALL OR PARAPIT FIG. 6 FIG. SA i �--MORE THAN IO'- HEIANY HT"OOF ABOVE Maintenance Instructions -- 10' SURFACE ROFACE WITHIN 10' 1. It Is recommended that the chimney system be in- HORIZONTALLY spected and cleaned at least once each month during the c heating season.Also,inspectand clean thechimney system 2 -=17 before each heating season. \\ MIN I' 2. For cleaning and/or inspection of the Pellet Chimney, ` the Caps may be removed.To remove the vertical Cap,twist TERMINATION ? ' counter clockwise and pull straight off. To remove the MORE THAN 10 FEET .horizontal Cap, loosen the nut on the retaining band and FROM RIDGE, - - � G;�, ., pull Cap off. - WALL OR-PARAPIT T FIG. 58 i f &ETLTA ;NC. MANUCTURERPRODUCTS ENMRONMEL �-� P. O. BOX 1138 . WICHITA, KANSAS 67201 Lilho in u.s.A. 316-943-2351 • FAX 316-943-2717 Form No.L1033-4191 -4- R Movie a2 �e tiExiy I CC-11' J �hn� �h/3 p/ars �crs nory aR ¢,N -� ✓0AW �QNs i Go iaors�C/ /n 4ccorc%r�c¢ W///7o ) fh¢ A411405 4 .�equ/cr,//or/s o� ✓p//N /�. ,(,l�1 N y 'P D 2 fh2 QQgisfero of Deeo'.� N05°/4 40 35.25 � 2 - COr/G. wil 90.08 Zr ^ m A 2. �o 42 lilt v Ui D YYELL/NG L QB Cz3121,57-OL VL1z/LtBLE i!'/OT��� i i F750/ex,! 2�J TO 3E- 'C0"01HEO TO OME- LOT CONT. 5722 t v= daPr'ZQvgL uNLZ�� �c�ao/v��.oN FLAN of LARD /N CON72 OL Lilly R Q S,4 LE III, &1A SS. NoT�.• Laare: Thi.3 p/oma rra� comoi/� �ibrn G1�cc/a � P2�P112�D �2 P/nr/,s o/' 2ecoITI 4 a ,a:71'7'1a/ /'IC IL-1 .::r/-//eY ��rT '�4�y Tf* /� �Nr/N��/z/NC, -.dSSOC/,4T��, /NC• M '� �- LL229 p - Fc�ST£R+ox SC4/e .. . //nch s 201aC4 � ANO SURE ' S,4[.z`M P�.ANN/NG :80.420 /O o /0 ZO 30 40 .50 i /2�2 Har [I li 49 s (I�itn of �ttlem, �4RaSsttrl useTr CLD - tfasS �1', 1 t u c: -goarb of vpeal DECISION-ON-THE PETITION OF JERROLD & ANN HOUGHTON FOR VARIANCES AT• 5 BRISTOL ST (R-1 ) A hearing on this petition was held May 15, 1991 with the following Board Members present: Richard Bencal, Chairman; Edward Luzinski, Vice Chairman; Joseph Correnti, Secretary; Richard Febonio and Mary Jane Stirgwolt. Notice of the hearing was sent to abutters and others and notices of the hearing were properly published in the Salem Evening News in accordance with Massachusetts General Laws Chapter 40A. Petitioners, owners of the property, are requesting Variances from side and rear setbacks to allow an existing deck in this R-1 district. The Variances which have been requested may be granted upon a finding by this Board that: a. Special conditions and circumstances exist which especially affect the land, building or structure involved and which are not generally affecting other land, building or structures in the same district. b. Literal enforcement of the provisions of the Zoning Ordinance would involve substantial hardship, financial or otherwise, c. Desirable relief may be granted without substantial detriment to the public good and without nullifying or substantially derogating from the intent of the district or the purpose of the Ordinance. The Board of Appeal, after careful consideration of the evidence presented at the hearing, and after viewing the plans, makes the following findings of fact: 1 . The deck in question has been in existance since 1986. 2. The size of the lot creates a hardship as this is the only practical location for the deck. 3. The deck in question allows the inhabitants a fuller use of their property and will not be detrimental to the neighborhood. On the basis of the above findings of fact, and on the evidence presented at the hearing, the Board of Appeal concludes as follows: 1 . Special conditions exist which especially affect the subject property but not the district in general. 2. Literal enforcement of the provisions of the Zoning Ordinance would involve substantial hardship to the petitioners. 3. Desirable relief can be granted without substantial detriment to the public good and without nullifying or substantially derogating from the intent of the district or the purpose of the Ordinance. I/ DECISION ON THE PETITION OF JERROLD & ANN HOUGHTON FOR VARIANCES AT 5 BRISTOL STREET, SALEM page two uu o 49 Therefore the ZoningBoard of A 11t grant th Appeal voted unanimously, 5-0, to grant the Variances requested, subject to the following conditions: CITY ; ; S 1 . All construction be done as per existing city and state building codes. 2. All constructions be done as per plans and dimensions submitted. 3. Exterior finishes to be in harmony with present structure. 4. Petitioner obtain a legal building. 5. All requirements of the Salem Fire Department relative to smoke and fire safety be strictly adhered to. Variances Granted May 15, 1991 �" � � r � Richard A. Bencal, Chairman, Board of Appeal A COPY OF THIS DECISION HAS BEEN FILED WITH THE PLANNING BOARD AND THE CITY CLERK Appeal from this decision, if any, shall be made pursuant to Section 17 of the Mass. General Laws, Chapter 808, and shall be filed within 20 days after the date of filing of this decision in the office of the City Clerk. Pursuant !o Mass. Genera! Laws, Ch:rater 808, Section 11, the variance or ?pecni P+rmit granted h3,ein shad nut take effect until a copy of the decision, be-rin� the certification of the City Clerk that 20 days have elapsed an no appeal has been filed, or that, if such appeal has been filed, that it has been dismisses; or denied is recorded In the South Essex Registry of Deeds and indexed under the name or the owner of record or Is recorded and noted On the owner's certificate of Title_ BOARD OF APPS U! YSLirl September 16, 1983 Ms. Josephine Fusco City Clerk City Hall ' Salem, MA 01970 Dear Ms. Fusco: At a regularly scheduled meeting of the Sal-p-_ Planning Board held on September 15, 1983, it was voted to endorse "Approval Under Sub- division Control Law Not Required" on the following described plan: 1. Applicant: Jerrold S. and Ann Houghton 5 BristolStreet - Salem, MA. 01970 2. Location and Description - Lots 2 and 3 are to be combined to form one contiguous lot as shown on plan prepared by T & M Engineering dated September 12, 1983, entitled "Plan of Land in Salem, MA. prepared for Jerrold and Ann Houghton." Deed of property records in Essex South District Registry. Sincerely, d�V Walter Power III Chairman S4P/sm Holyoke Mutual p Insurance Company, p l in Salem Holyoke Square,Salem,MA 01970,Tel.(617)744-6123 Form of Notice of Casualty Loss to Building Under Massachusetts General Laws, Chapter 139, Section 3B TO: Building Commissioner or Board of Health or Inspector of Buildings Board of Selectmen addresses S RE: Insured: Property address: y Eys�'�f��Jf^�e.[ _ � mss. Policy No. Loss of 19 �lp File or Claim No. a3 i a j.3 Claim has been made involving loss, damage or destruction of the above-captioned property, which may either exceed $1,000.00 or cause Massachusetts General Laws, Chapter 143, Section 6 to be applicable. If any notice under Massachusetts General Laws, Chapter 139, Section 3B is appropriate, please direct it to the attention of the writer and include a reference to the captioned insured, location, policy number, date of loss and claim or file number. Title , On this date, I caused copies of this notice to be sent to the persons named above at the addresses indicated abo by first class mail. / Signature and date 145-767 / (' Our heritage.comes from Dr.Edward A.Holyoke,1728-1829.Pioneer of medicine and patron of the arts. lof 'Salem, 'fflassarhuse##s RFC,EI .' sr, �� �lttnning �nxr� �0, '83 SEP 14 P2 :(11 (lite pall CITY C C .'ti" ',)FF!CE �alem, [assac(tusetts 01970 NOTICE TO BE ATTACHED TO FORM "A"APPLICATIONS See Form "A" applications for complete instructions for filing. All insertions shall be typewritten or printed neatly in ink. Date:���G / --— City Clerk Salem, Massachusetts 01970 Dear Sir: I hand you herewith two copies of Form A, an application submitted by me this day to the Plan- ning Board of the City of Salem requesting a determination and an endorsement on a plan filed with said application that Planning Board approval under the Subdivision Control Rules and Regulations is not required. The land shown on the accompanying plan is located at --'0- LflR'� ------ - (insert street and street numbers here) n Signature of Owner 11 Street Address = -- ---- -- — — — City/Town&State /`" ------------------------- -- — — Telephone Number ---/_!Yir7 Z_�JSe-------------------------------------------------- IIttleztt, tt �zcusE## { aug Hull FORM A APPLICATION FOR ENDORSEMENT CITY CLE S LrF ICE OF PLAN BELIEVED NOT TO REQUIRE 3AB I'I APPROVAL In accordance with provisions of Section II-B, the applicant must file, by delivery, or registered mail, a Notice with the City Clerk stating the date of sub- mission for such determination. The notice shall be attached to two copies of this Form A application. The notice and both copies of the application must he "date stamped' by the City Clerk and then one copy of this Form A, with the Plan, filed with the Planning Board by the applicant. All notices and applications shall be typewritten or neatly printed in ink. Salem, Mass-- - -- - -19d-C3— To the Planning Board: The undersigned,believing that the accompanying plan of his property in the City of Salem does not constitute a subdivisEunudthin the me ning ofie Subdivision Control Law because (See Sect. II-A d st to specific reasons) d- 4' _ _ _ f� _ r1J_1_� /5lf��s i---- D - / eAAL -=---------------- - ---------------- ----------------------------------------------------------------•-------------------------------------------------------- and herewith submits said plan for a determination and endorsement that Planning Board approval under the Subdivision C trol Law i no require Name of Owner _ ____ __ _ _•_ _C,__'__ __ _ _ - - -- -------- 1. N Addres -- ---- 1 -lL�!/11L-��___----------------------------------- 2. Name of Engineer or Surveyor ---------- --------- - ----- ---- ---------------------------------------=-------- Address - Q ---- - 3. Deed of property records in __________ __ _ ___________ 1A�� egistry i v Book ----0&------------------ 7Pa as - (/ 4. oc/a�ti�on andW�scr�iption of Pro rty: ,_�/2J liYCsf --- -= L�(L �l_ -%4_ =c - -- - -- ----- --- -°-- � i----1 -.`---------------------------- --------------------------------------------------------------- ----- -- ---------------------------------------------------- -------------------------------------------------------------------------------------------------------------------------------------------------- ---------------------------------------------------------------------------------------------------------------------------------------------------- ----------------------------------------------------------------------------------------------------------------------------------- ---------- ------------------------------------------------------------------------------------------------- ------------------------------------------------- --------------------------------------------------------------------------------------------------------------------------------------------------- 5. All streets and abutting lot lines shall be show on the Plan to ether with the names o -t$e Owners of the abutting lots. Signature of Owne = ��' �!ti�/� L Addres ----------- -------- Telephone Number --- 'Yto/ ----------------------`----------------------