Loading...
AIR LEAKAGE REPORT U1-14 Air Leakage Property Organization HERS 50 St. Peter St Unit 1 Azimuth Home Energy Solutions Confirmed Salem, MA 01970 978-356-7501 2018-05-07 Marc Simon Rater ID:7618201 Weather:Salem, MA Salem Jail Builder 0013-0065-C1_Iron_Bar_LLC_50_S Iron Bar LLC t_Peter_St_Unit_1_MASS_QAD.big Whole House Infiltration Blower Door Test i Heating Cooling Natural ACH 0.13 0.10' ACH @ 50 Pascals 2.64 2.64 CFM @ 25 Pascals 333 333 CFM @ 50 Pascals 522 522 Eff. Leakage Area (sq.in) 28.728.7 Specific Leakage Area 0.00017 0.00017 ELA/100 sf shell (sq.in) 0.72 0.72 Duct Leakage Leakage to Outside Units s1 CFM @ 25 Pascals 35 CFM25 /CFMfan 0.0385 CFM25 /CFA 0.0302 CFM per Std 152 N/A CFM per Std 152 /CFA N/A CFM @ 50 Pascals 55 Eff. Leakage Area (sq.in) 3.02 Thermal Efficiency N/A Total Duct Leakage Units CFM25/CFA Total Duct Leakage 0.0388 Ventilation Mechanical Exhaust Only ASHRAE Sensible Recovery Eff. (%) 0.0 62.2-2010 Total Recovery Eff. (%) 0.0 Rate (cfm) 55 34 Hours/Day 24.0 24.0 Fan Watts 8.0 ASHRAE 62.2 - Ventilation Requirements The ASHRAE 62.2 flow rates shown above are the CONTINUOUS mechanical fresh air ventilation which will meet the'whole-building requirement under that version of the standard. Both values incorporate any appropriate'infiltration credit'. Intermittent mechanical ventilation may be used if the flow rate is adjusted accordingly. For example, the runtime can be reduced to 12 hours per day using a doubled flow rate,as long as the system provides ventilation at least once every 3 hours.For more detail, refer to the appropriate standard. This information does not constitute any warranty of energy cost or savings. O 1985-2016 Noresco, Boulder,Colorado. Air Leakage Property Organization HERS 50 St. Peter St Unit 2 Azimuth Home Energy Solutions Confirmed Salem,MA 01970 978-356-7501 2018-05-07 Marc-Simon Rater ID:7618201 Weather:Salem,MA Salem Builder 0013-0066-C1_Iron_Bar_LLC_50_S Iron Bar LLC t_Peter_St_Unit_2_MASS_QAD.big Whole House Infiltration Blower Door Test Heating Cooling Natural ACH 0.17 0.13 ACH @ 50 Pascals 2.76 2.76 CFM @ 25 Pascals 577 577 CFM C 50 Pascals 905 905 Eff. Leakage Area (sq.in) 49.7 49.7 Specific Leakage Area 0.00020 0.00020 ELA/100 sf shell (sq.in) 1.04 1.04 Duct Leakage Leakage to Outside Units s1 CFM @ 25 Pascals 37 CFM25 /CFMfan 0.0407 CFM25 /CFA 0.0211 CFM per Std 152 N/A CFM per Std 152 /CFA N/A CFM @ 50 Pascals 58 Eff. Leakage Area (sq.in) 3.19 Thermal Efficiency N/A Total Duct Leakage Units CFM25/CFA Total Duct Leakage 0.0211 Ventilation Mechanical Exhaust Only ASHRAE Sensible Recovery Eff. (%) 0.0 62.2-2010 Total Recovery Eff. (%) 0.0 Rate (cfm) 56 48 Hours/Day 24.0 24.0 Fan Watts ( 8.0 ASHRAE 62.2 - Ventilation Requirements The ASHRAE 62.2 flow rates shown above are the CONTINUOUS mechanical fresh air ventilation which will meet the'whole-buildins; requirement under that version of the standard. Both values incorporate any appropriate'infiitration credit'. Intermittent mechanical ventilation may be used if the flow rate is adjusted accordingly. For example, the runtime can be reduced to 12 hours per day using a doubled flow rate, as tong as the system provides ventilation at least once every 3 hours. For more detail, refer to the appropriate standard. This information does not constitute any warranty of energy cost or savings. ©1985-2016 Noresco, Boulder,Colorado. Air Leakage Property Organization HERS 50 St. Peter St Unit 3 Azimuth Home Energy Solutions Confirmed Salem, MA 01970 978-356-7501 2018-05-07 Marc Simon Rater[D:7618201 Weather:Barnstable AP, MA Salem Jail#3 Builder 0013-0067-Cl—iron—Bar—LLC-50—S Iron Bar LLC t_Peter St_Unit_3_MASS_QAD.big Whole House Infiltration Blower Door Test Heating Cooling Natural ACH 0.13 0.11 ACH @ 50 Pascals 2.68 2.681 CFM @ 25 Pascals 332 3321 CFM @ 50 Pascals 521 521j Eff. Leakage Area (sq.in) 28.61 28.6 Specific Leakage Area 0.00017I 0.00017 ELA/100 sf shell (sq.in) 0.72 0.72 CFM50/sf shell 0.13 0.13 Duct Leakage Leakage to Outside Units S1 CFM @ 25 Pascals 29 1 CFM25 / CFMfan 0.03191 CFM25 / CFA j 0.0255 I CFM per Std 152 N/A'. CFM per Std 152 / CFA N/A CFM @ 50 Pascals 46 Eff. Leakage Area (sq.in) 2.50 Thermal Efficiency N/A C Total Duct Leakage Units L CFM25/CFA Total Duct Leakage 0.0335! Ventilation Mechanical Exhaust Only ASHRAEI ASHRAE! Sensible Recovery Eff. (%) 0.01 62.2-20101 62.2-2013 Total Recovery Eff. (%) 0.0 Rate (cfm) 56� 34 57 Hours/Day 24.01 24.0; 24.0 Fan Watts 8.0; Cooling Ventilation Natural Ventilation ASHRAE 62.2 - Ventilation Requirements The ASHRAE 62.2 flow rates shown above are the CONTINUOUS mechanical fresh air ventilation which will meet the'whole-building requirement under that version of the standard. Both values incorporate any appropriate'infiltration credit'. Intermittent mechanical ventilation may be used if the flow rate is adjusted accordingly. For example, the runtime can be reduced to 12 hours per day using a doubled flow rate, as long as the system provides ventilation at least once every 3 hours. For more detail, refer to the appropriate standard. REM/Rate - Residential Energy Analysis and Rating Software v15.4.2 This information does not constitute any warranty of energy cost or savings. 0 1985-2017 Noresco, Boulder, Colorado. Air Leakage Property Organization HERS 50 St. Peter St Unit 4 Azimuth Home Energy Solutions Confirmed Salem,MA 01970 978-356-7501 2018-05-07 Marc Simon Rater ID:7618201 Weather:Salem,MA Salem Jail#4 Builder 0013-0068-C1 Iron Bar_LLC_50_S Iron Bar LLC t_Peter_St_Unit_4_MASS_QAD.big Whole House Infiltration Blower Door Test Heating Cooling Natural ACH 0.18 0.13 ACH @ 50 Pascals 2.86 2.86 CFM @ 25 Pascals 605 605 CFM @ 50 Pascals 950 950 Eff. Leakage Area (sq.in) 52.2j 52.2 Specific Leakage Area 0.00020 0.00020 ELA/100 sf shell (sq.in) 1.05 i 1.05 Duct Leakage Leakage to Outside Units S11 CFM @ 25 Pascals 33 CFM25 /CFMfan 0.0363 CFM25 /CFA 0.0186 CFM per Std 152 N/A CFM per Std 152 /CFA N/A CFM @ 50 Pascals 52 Eff. Leakage Area (sq.in) 2.84 Thermal Efficiency N/A Total Duct Leakage Units CFM25/CFA Total Duct Leakage 0.0186 Ventilation Mechanical Exhaust Only ASHRAE Sensible Recovery Eff. (%) 0.0 62.2-2010 Total Recovery Eff. (%) 0.0 Rate (cfm) 56 48 Hours/Day 24.0 24.0 Fan Watts 8.0 ASHRAE 62.2 - Ventilation Requirements The ASHRAE 62.2 flow rates shown above are the CONTINUOUS mechanical fresh air ventilation which will meet the'whole-building requirement under that version of the standard. Both values incorporate any appropriate'infiltration credit'. Intermittent mechanical ventilation may be used if the flow rate is adjusted accordingly. For example, the runtime can be reduced to 12 hours per day using a doubled flow rate, as long as the system provides ventilation at least once every 3 hours. For more detail, refer to the appropriate standard. 06 This information does not constitute any warranty of energy cost or savings. Q 1985-2016 Noresco, Boulder,Colorado. Air Leakage Property Organization HERS 50 St. Peter St Unit 5 Azimuth Home Energy Solutions Confirmed Salem, MA 01970 978-356-7501 2018-05-22 Marc Simon Rater ID:7618201 Weather:Beverly AP, MA Salem Jail#5 Builder 0013-0069-C1 Iron Bar_LLC_50 S Iron Bar LLC t_Peter_St_Unit_5_MASS_QAD.big Whole House Infiltration Blower Door Test Heating Cooling Natural ACH 0.141 0.12 ACH @ 50 Pascals 2.92 2.921 CFM @ 25 Pascals 328 328; CFM @ 50 Pascals i 515! 515 Eff. Leakage Area (sq.in) 28.3 28.3 Specific Leakage Area 0.00019: 0.00019 ELA/100 sf shell (sq.in) 0.64 0.64 CFM50/sf shell 0.12 0.12 Duct Leakage Leakage to Outside Units " s1 CFM @ 25 Pascals 34 CFM25 / CFMfan 0.0374 CFM25 / CFA 0.03291 CFM per Std 152 N/A i CFM per Std 152 / CFA N/A j CFM @ 50 Pascals 53 Eff. Leakage Area (sq.in) 2.93 Thermal Efficiency N/A Total Duct Leakage Units CFM25/CFA Total Duct Leakage 0.03291 Ventilation Mechanical Exhaust Only', ASHRAE'; ASHRAE Sensible Recovery Eff. (%) 0.0 62.2-2010 62.2-2013 Total Recovery Eff. (%) 0.0 Rate (cfm) 55j 33' 53 Hours/Day 24.01 24.0, 24.0 Fan Watts 8.0 Cooling Ventilation Natural Ventilation ASHRAE 62.2 - Ventilation Requirements The ASHRAE 62.2 flow rates shown above are the CONTINUOUS mechanical fresh air ventilation which will meet the'whole-building' requirement under that version of the standard. Both values incorporate any appropriate'infiltration credit'. Intermittent mechanical ventilation may be used if the flow rate is adjusted accordingly. For example, the runtime can be reduced to 12 hours per day using a doubled flow rate, as long as the system provides ventilation at least once every 3 hours. For more detail, refer to the appropriate standard. REM/Rate - Residential Energy Analysis and Rating Software v15.4.2 This information does not constitute any warranty of energy cost or savings. ©1985-2017 Noresco, Boulder, Colorado. Air Leakage Property Organization HERS 50 St. Peter St Unit 6 Azimuth Home Energy Solutions Confirmed Salem,MA 01970 978-356-7501 2018-05-07 Marc Simon Rater ID:7618201 Weather:Salem,MA Salem Jail#6 Builder 0013-0070-C1_Iron_Bar_LLC_50_S Iron Bar LLC t_Peter_St_Unit_6_MASS_QAD.big Whole House Infiltration Blower Door Test Heating Cooling Natural ACH 0.19 0.14 ACH @ 50 Pascals 2.98 2.98 CFM @ 25 Pascals 512 512 CFM @ 50 Pascals 803 803 Eff. Leakage Area (sq.in) 44.1 44.1 Specific Leakage Area 0.00021 0.00021 ELA/100 sf shell (sq.in) 1.02 1.02 Duct Leakage Leakage to Outside Units I s1 CFM @ 25 Pascals 53 CFM25 /CFMfan 0.0582 CFM25 /CFA 0.0369 CFM per Std 152 N/A CFM per Std 152 /CFA N/A CFM @ 50 Pascals 83 Eff. Leakage Area (sq.in) 4.57 Thermal Efficiency N/A Total Duct Leakage Units CFM25/CFA Total Duct Leakage 0.0369 Ventilation Mechanical Exhaust Only ASHRAE Sensible Recovery Eff. (%) 0.0 62.2-2010 Total Recovery Eff. (%) 0.0 Rate (cfm) 56 37 Hours/Day 24.0 24.0 Fan Watts 8.0 ASHRAE 62.2 - Ventilation Requirements The ASHRAE 62.2 flow rates shown above are the CONTINUOUS mechanical fresh air ventilation which will meet the'whole-building' requirement under that version of the standard. Both values incorporate any appropriate'infiltration credit'. Intermittent mechanical ventilation may be used if the flow rate is adjusted accordingly. For example, the runtime can be reduced to 12 hours per day using a doubled flow rate, as long as the system provides ventilation at least once every 3 hours. For more detail, refer to the appropriate standard. F, .,.., _ _ ,.,. :gat This information does not constitute any warranty of energy cost or savings. ©1985-2016 Noresco, Boulder,Colorado. Air Leakage Property Organization HERS 50 St. Peter St Unit 7 Azimuth Home Energy Solutions Confirmed Salem, MA 01970 978-356-7501 2018-05-22 Marc Simon Rater ID:7618201 Weather:Beverly AP, MA Salem Jail#7 Builder 0013-0071-C1_Iron_Bar_LLC_50_S Iron Bar LLC t_Peter St_Unit_7_MASS_QAD.big Whole House Infiltration Blower Door Test Heating Cooling Natural ACH 0.140.11 ACH @ 50 Pascals 2.841 2.84 CFM @ 25 Pascals 322 322 CFM @ 50 Pascals 5061 506 Eff. Leakage Area (sq.in) 27.8� 27.8 j Specific Leakage Area 0.00018 0.00018 ELA/100 sf shell (sq.in) 0.81 0.81 CFM50/sf shell 0.15 0.15 Duct Leakage Leakage to Outside Units S1 CFM @ 25 Pascals 33 CFM25 / CFMfan 0.0363 CFM25 / CFA 0.0316 CFM per Std 152 N/A CFM per Std 152 / CFA N/A CFM @ 50 Pascals 521 Eff. Leakage Area (sq.in) 2.8411 Thermal Efficiency N/A 11 Total Duct Leakage Units j CFM25/CFA 1 Total Duct Leakage 0.03161 Ventilation Mechanical Exhaust Only ASHRAE' ASHRAE Sensible Recovery Eff. (%) 0.0 62.2-2010 62.2-2013 Total Recovery Eff. (%) 0.01 Rate (cfm) 54j 33 54 Hours/Day 24.01 24.0 24.0 Fan Watts 8.0 Cooling Ventilation Natural Ventilation ASHRAE 62.2 - Ventilation Requirements The ASHRAE 62.2 flow rates shown above are the CONTINUOUS mechanical fresh air ventilation which will meet the'whole-building' requirement under that version of the standard. Both values incorporate any appropriate'infiltration credit'. Intermittent mechanical ventilation may be used if the flow rate is adjusted accordingly. For example, the runtime can be reduced to 12 hours per day using a doubled flow rate, as long as the system provides ventilation at least once every 3 hours. For more detail, refer to the appropriate standard. REM/Rate - Residential Energy Analysis and Rating Software v15.4.2 This information does not constitute any warranty of energy cost or savings. 0 1985-2017 Noresco, Boulder, Colorado. Air Leakage Property Organization HERS 50 St. Peter St Unit 1 Azimuth Home Energy Solutions Confirmed Salem,MA 01970 978-356-7501 2018-05-07 Marc Simon Rater ID:7618201 Weather:Salem,MA Salem Jail Builder 0013-0065-C1_Iron_Bar_LLC_50_S Iron Bar LLC t_Peter_St_Unit_1_MASS_OAD.blg Whole House Infiltration Blower Door Test Heating Cooling Natural ACH 0.13 0.10 ACH @ 50 Pascals 2.64 2.641 CFM @ 25 Pascals 333 333 CFM @ 50 Pascals 522 522 Eff. Leakage Area (sq.in) 28.7 28.7 Specific Leakage Area 0.00017 0.00017 ELA/100 sf shell (sq.in) 0.72 0.72 Duct Leakage Leakage to Outside Units s1 CFM @ 25 Pascals 35 CFM25 /CFMfan 0.0385 CFM25 /CFA 0.0302 CFM per Std 152 N/A i CFM per Std 152 /CFA N/A, CFM C 50 Pascals 55 Eff. Leakage Area (sq.in) 3.02 Thermal Efficiency N/A Total Duct Leakage Units CFM25/CFA Total Duct Leakage 0.0388 Ventilation Mechanical Exhaust Only ASHRAE Sensible Recovery Eff. (%) 0.0 62.2-2010 Total Recovery Eff. (%) 0.0 Rate (cfm) 55 34 Hours/Day 24.0 24.0 Fan Watts 8.0 ASHRAE 62.2 - Ventilation Requirements The ASHRAE 62.2 flow rates shown above are the CONTINUOUS mechanical fresh air ventilation which will meet the'whole-building' requirement under that version of the standard. Both values incorporate any appropriate'infiltration credit'. Intermittent mechanical ventilation may be used if the flow rate is adjusted accordingly. For example, the runtime can be reduced to 12 hours per day using a doubled flow rate, as long as the system provides ventilation at least once every 3 hours. For more detail, refer to the appropriate standard. This information does not constitute any warranty of energy cost or savings. ©1985-2016 Noresco, Boulder,Colorado. Air Leakage Property Organization HERS 50 St. Peter St Unit 2 Azimuth Home Energy Solutions Confirmed Salem,MA 01970 978-356-7501 2018-05-07 Marc Simon Rater ID:7618201 Weather:Salem,MA Salem Builder 0013-0066-Cl_Iron_Bar_LLC_50_S Iron Bar LLC t_Peter_St_Uni t_2_MASS_QAD.blg Whole House Infiltration Blower Door Test Heating Cooling Natural ACH 0.17 0.13 ACH @ 50 Pascals 2.76 2.76 CFM @ 25 Pascals 577 577 CFM @ 50 Pascals 905 905 Eff. Leakage Area (sq.in) 49.7 49.7 Specific Leakage Area 0.00020 0.00020 ELA/100 sf shell (sq.in) 1.04 1.04 Duct Leakage Leakage to Outside Units S1 CFM @ 25 Pascals 37 CFM25 /CFMfan 0.0407 CFM25 /CFA 0.0211 CFM per Std 152 N/A CFM per Std 152 /CFA N/A CFM @ 50 Pascals 58 Eff. Leakage Area (sq.in) 3.19 Thermal Efficiency N/A i Total Duct Leakage Units CFM25/CFA Total Duct Leakage 0.0211 Ventilation Mechanical Exhaust Only ASHRA( Sensible Recovery Eff. (%) 0.0 62.2-2010 Total Recovery Eff. (%) 0.0 Rate (cfm) 56 48 Hours/Day 24.0 24.0 Fan Watts 8.0 ASHRAE 62.2 - Ventilation Requirements The ASHRAE 62.2 flow rates shown above are the CONTINUOUS mechanical fresh air ventilation which will meet the'whole-buildins; requirement under that version of the standard. Both values incorporate any appropriate'infiltration credit'. Intermittent mechanical ventilation may be used if the flow rate is adjusted accordingly. For example, the runtime can be reduced to 12 hours per day using a doubled flow rate, as long as the system provides ventilation at least once every 3 hours. For more detail, refer to the appropriate standard. This information does not constitute any warranty of energy cost or savings. Q 1985-2016 Noresco, Boulder,Colorado. Air Leakage Property Organization HERS 50 St. Peter St Unit 3 Azimuth Home Energy Solutions Confirmed Salem, MA 01970 978-356-7501 2018-05-07 Marc Simon Rater ID:7618201 Weather:Barnstable AP, MA Salem Jait#3 Builder 0013-0067-C1_Iron_Bar_LLC_50_S Iron Bar LLC t_Peter_St_Unit_3_MASS_QAD.blg Whole House Infiltration Blower Door Test Heating Cooling Natural ACH 0.13 0.11 ACH @ 50 Pascals 2.68' 2.68 CFM @ 25 Pascals I 332 332 CFM @ 50 Pascals 15211 521 Eff. Leakage Area (sq.in) 28.6 28.6i Specific Leakage Area �� 0.000171 0.000171 ELA/100 sf shell (sq.in) 0.72{ 0.72 CFM50/sf shell 0.13 1 0.13 Duct Leakage Leakage to Outside Units S1 CFM @ 25 Pascals 29'I CFM25 / CFMfan 0.0319' CFM25 / CFA 0.0255 CFM per Std 152 N/Ali CFM per Std 152 / CFA i N/A CFM @ 50 Pascals 46 Eff. Leakage Area (sq.in) 2.50; Thermal Efficiency N/A Total Duct Leakage Units ; CFM25/CFA Total Duct Leakage i 0.03351 Ventilation Mechanical Exhaust Only ASHRAE'I ASHRAE Sensible Recovery Eff. (%) 0.01 62.2-2010 62.2-2013 Total Recovery Eff. (%) 0.0 Rate (cfm) 56 34� 57, Hours/Day j 24.0 24.0, 24.0 Fan Watts 8.0, Cooling Ventilation Natural Ventilation j ASHRAE 62.2 - Ventilation Requirements The ASHRAE 62.2 flow rates shown above are the CONTINUOUS mechanical fresh air ventilation which will meet the'whole-building' requirement under that version of the standard. Both values incorporate any appropriate'infiltration credit'. Intermittent mechanical ventilation may be used if the flow rate is adjusted accordingly. For example, the runtime can be reduced to 12 hours per day using a doubled flow rate, as long as the system provides ventilation at least once every 3 hours. For more detail, refer to the appropriate standard. REM/Rate - Residential Energy Analysis and Rating Software v15.4.2 This information does not constitute any warranty of energy cost or savings. © 1985-2017 Noresco, Boulder, Colorado. Air Leakage Property Organization HERS 50 St. Peter St Unit 4 Azimuth Home Energy Solutions Confirmed Salem,MA 01970 978-356-7501 2018-05-07 Marc Simon Rater ID:7618201 Weather:Salem, MA Salem Jail#4 Builder 0013-0068-C1_Iron_Bar_LLC_50_S Iron Bar LLC t_Peter_St_Unit_4_MASS_QAD.big Whole House Infiltration Blower Door Test Heating j Cooling Natural ACH 0.18 0.13 ACH @ 50 Pascals 2.86 2.86 CFM @ 25 Pascals 605 605 CFM @ 50 Pascals 950 950 Eff. Leakage Area (sq.in) 52.252.2 Specific Leakage Area 0.00020 0.00020 ELA/100 sf shell (sq.in) 1.05 1.05 Duct Leakage Leakage to Outside Units S1 CFM @ 25 Pascals 33 CFM25 /CFMfan 0.0363 CFM25 /CFA 0.0186 CFM per Std 152 N/A CFM per Std 152 /CFA N/A CFM @ 50 Pascals 52 Eff. Leakage Area (sq.in) 2.84 Thermal Efficiency N/A Total Duct Leakage Units CFM25/CFA Total Duct Leakage 0.0186 Ventilation Mechanical Exhaust Only ASHRAE Sensible Recovery Eff. (%) 0.0 62.2-2010 Total Recovery Eff. N 0.0 Rate (cfm) 56 48 Hours/Day 24.0 24.0 Fan Watts 8.01 ASHRAE 62.2 - Ventilation Requirements The ASHRAE 62.2 flow rates shown above are the CONTINUOUS mechanical fresh air ventilation which will meet the'whole-building requirement under that version of the standard. Both values incorporate any appropriate'infiltration credit'. Intermittent mechanical ventilation may be used if the flow rate is adjusted accordingly. For example, the runtime can be reduced to 12 hours per day using a doubled flow rate, as long as the system provides ventilation at least once every 3 hours. For more detail, refer to the appropriate standard. This information does not constitute any warranty of energy cost or savings. ©1985-2016 Noresco, Boulder,Colorado. Air Leakage Property Organization HERS 50 St. Peter St Unit 5 Azimuth Home Energy Solutions Confirmed Salem, MA 01970 978-356-7501 2018-05-22 Marc Simon Rater ID:7618201 Weather:Beverly AP, MA Salem Jail#5 Builder 0013-0069-Cl_Iron_Bar LLC_50_S Iron Bar LLC t_Peter_St_Unit_5_MASS_QAD.blg Whole House Infiltration Blower Door Test Heating i Cooling Natural ACH 0.14 0.12 ACH C 50 Pascals 2.92 i 2.92 CFM @ 25 Pascals 328� 328' CFM @ 50 Pascals 515! 515 Eff. Leakage Area (sq.in) 28.31, 28.3'i Specific Leakage Area 0.000191 0.00019 ELA/100 sf shell (sq.in) 0.64 0.64, CFM50/sf shell 0.12! 0.12 Duct Leakage Leakage to Outside Units S1 CFM @ 25 Pascals 341 CFM25 / CFMfan 0.03741 CFM25 / CFA 0.03291 CFM per Std 152 N/A CFM per Std 152 / CFA N/A' CFM @ 50 Pascals 53', Eff. Leakage Area (sq.in) 2.93 Thermal Efficiency N/A Total Duct Leakage Units CFM25/CFA Total Duct Leakage 0.0329 Ventilation Mechanical Exhaust Only!I ASHRAE' ASHRAE' Sensible Recovery Eff. (%) 0.0! 62.2-2010 62.2-2013 Total Recovery Eff. (%) 0.01 Rate (cfm) 55 33 53 Hours/Day 24.0; 24.0 24.0 Fan Watts 8.0 Cooling Ventilation Natural Ventilation ASHRAE 62.2 - Ventilation Requirements The ASHRAE 62.2 flow rates shown above are the CONTINUOUS mechanical fresh air ventilation which will meet the'whole-building' requirement under that version of the standard. Both values incorporate any appropriate'infiltration credit'. Intermittent mechanical ventilation may be used if the flow rate is adjusted accordingly. For example, the runtime can be reduced to 12 hours per day using a doubled flow rate, as long as the system provides ventilation at least once every 3 hours. For more detail, refer to the appropriate standard. REM/Rate - Residential Energy Analysis and Rating Software v15.4.2 This information does not constitute any warranty of energy cost or savings. ©1985-2017 Noresco, Boulder, Colorado. Air Property Organization HERS 50 St. Peter St Unit 6 Azimuth Home Energy Solutions Confirmed Salem,MA 01970 978-356-7501 2018-05-07 Marc Simon Rater ID:7618201 Weather:Salem,MA Salem Jail#6 Builder 0013-0070-C1_iron_Bar_LLC_50_S Iron Bar LLC t_Peter_St_Uni t_6_MASS_QAD.blg Whole House Infiltration Blower Door Test Heating Cooling Natural ACH 0.19 0.14 ACH @ 50 Pascals 2.98 2.98' CFM @ 25 Pascals 512 512 CFM @ 50 Pascals 803 803 Eff. Leakage Area (sq.in) 44.1 44.1 Specific Leakage Area 0.00021 0.00021 ELA/100 sf shell (sq.in) 1.02 1.02 Duct Leakage Leakage to Outside Units si CFM @ 25 Pascals I 53 CFM25 /CFMfan 0.0582 CFM25 /CFA 0.0369 CFM per Std 152 N/A I CFM per Std 152 /CFA N/A CFM @ 50 Pascals 83 Eff. Leakage Area (sq.in) 4.57 Thermal Efficiency N/A Total Duct Leakage Units CFM25/CFA Total Duct Leakage 0.0369 Ventilation Mechanical Exhaust Only ASHRAE Sensible Recovery Eff. (%) 0.0 62.2-2010 Total Recovery Eff. (%) 0.0 Rate (cfm) 56 37 Hours/Day 24.0 24.0 Fan Watts 8.0 ASHRAE 62.2 - Ventilation Requirements The ASHRAE 62.2 flow rates shown above are the CONTINUOUS mechanical fresh air ventilation which will meet the'whole-building requirement under that version of the standard. Both values incorporate any appropriate'infiltration credit'. Intermittent mechanical ventilation may be used if the flow rate is adjusted accordingly. For example, the runtime can be reduced to 12 hours per day using a doubled flow rate, as long as the system provides ventilation at least once every 3 hours. For more detail, refer to the appropriate standard. This information does not constitute any warranty of energy cost or savings. ©1985-2016 Noresco, Boulder,Colorado. Air Leakage Property Organization HERS 50 St. Peter St Unit 7 Azimuth Home Energy Solutions Confirmed Salem, MA 01970 978-356-7501 2018-05-22 Marc Simon Rater ID:7618201 Weather:Beverly AP, MA Salem Jail#7 Builder 0013-0071-C1_Iron_Bar_LLC_50_S Iron Bar LLC t_Peter_St_Unit_7_MASS_QAD.blg Whole House Infiltration I Blower Door Test Heating Cooling Natural ACH 0.14 0.11 ACH @ 50 Pascals 2 84� 2.84 CFM @ 25 Pascals 322 322 CFM @ 50 Pascals 506 5061 Eff. Leakage Area (sq.in) 27.81 27.8 Specific Leakage Area 0.000181 0.00018I ELA/100 sf shell (sq.in) 0.81 ! 0.81 CFM50/sf shell 0.15 0.15 Duct Leakage Leakage to Outside Units S1 j CFM @ 25 Pascals 33 CFM25 / CFMfan 0.03631 CFM25 / CFA 0.0316 CFM per Std 152 N/A CFM per Std 152 / CFA i N/A, CFM @ 50 Pascals 52 Eff. Leakage Area (sq.in) 2.84i Thermal Efficiency N/A j Total Duct Leakage Units CFM25/CFA Total Duct Leakage 0.0316; j Ventilation Mechanical Exhaust Only i ASHRAE1 ASHRAE Sensible Recovery Eff. (%) 0.01 62.2-2010' 62.2-2013 Total Recovery Eff. (%) 0.0I 1 Rate (cfm) 54 33154 Hours/Day 24.0 24.0 24.0 Fan Watts 8.0' Cooling Ventilation Natural Ventilation ASHRAE 62.2 - Ventilation Requirements The ASHRAE 62.2 flow rates shown above are the CONTINUOUS mechanical fresh air ventilation which will meet the'whole-building requirement under that version of the standard. Both values incorporate any appropriate'infiltration credit'. Intermittent mechanical ventilation may be used if the flow rate is adjusted accordingly. For example, the runtime can be reduced to 12 hours per day using a doubled flow rate, as long as the system provides ventilation at least once every 3 hours. For more detail, refer to the appropriate standard. REM/Rate - Residential Energy Analysis and Rating Software v15.4.2 This information does not constitute any warranty of energy cost or savings. © 1985-2017 Noresco, Boulder, Colorado. Air Leakage Property Organization HERS 50 St. Peter St Unit 8 Azimuth Home Energy Solutions Confirmed Salem,MA 01970 978-356-7501 2018-05-07 Marc Simon Rater ID:7618201 Weather:Salem, MA Salem Jail#8 Builder 0013-0072-C1_Iron_Bar_LLC_50_S Iron Bar LLC t_Peter_St_Unit_8_MASS_OAD.blg Whole House Infiltration Blower Door Test HeatingCooling Natural ACH 0.19 0.14 ACH @ 50 Pascals 2.99 2.99 CFM @ 25 Pascals 528 528 CFM @ 50 Pascals 829 829 Eff. Leakage Area (sq.in) 45.5 45.5 Specific Leakage Area 0.00021 0.00021 ELA/100 sf shell (sq.in) 1.07 1.07 Duct Leakage Leakage to Outside Units S1 CFM @ 25 Pascals 38 CFM25 /CFMfan 0.0418 CFM25 /CFA 0.0256 CFM per Std 152 N/A CFM per Std 152 /CFA N/A CFM @ 50 Pascals 60 Eff. Leakage Area (sq.in) 3.27 Thermal Efficiency N/A Total Duct Leakage Units CFM25/CFA Total Duct Leakage 0.02561 Ventilation Mechanical Exhaust Only ASHRAE Sensible Recovery Eff. (%) 0.0 62.2-2010 Total Recovery Eff. (%) 0.0 Rate (cfm) 56 45 Hours/Day 24.0 24.0 Fan Watts 8.0 ASHRAE 62.2 - Ventilation Requirements The ASHRAE 62.2 flow rates shown above are the CONTINUOUS mechanical fresh air ventilation which will meet the'whole-building' requirement under that version of the standard. Both values incorporate any appropriate'infiltration credit'. Intermittent mechanical ventilation may be used if the flow rate is adjusted accordingly. For example, the runtime can be reduced to 12 hours per day using a doubled flow rate, as long as the system provides ventilation at least once every 3 hours. For more detail, refer to the appropriate standard. This information does not constitute any warranty of energy cost or savings. ©1985-2016 Noresco, Boulder,Colorado.