B-17-786 - 0070 BOSTON STREET - Building Permit f • ,:. .++ - +'rem+t`.f }`�.i;�:`I •1: ! 1 9
as Xj
The Commonwealth of Massachusetts
Department of Public Safety
Massachusetts State Building Code(780 CUR)
Building Permit.Application for any Building other than a One-or Two-Family Dwelling
(This Section For Official Use Only)
Building Permit Number: Date Applied: Building Official:'
r SECTION 1:LOCATION(Please indicate Block#and Lot#for locations for which a street address is not available)
I '
E
C-- 70 Boston Street_"-' 'Salem, MA' (.01970 r' `River.Rock Residences '
No.and Street r 'City/Towne ' +' ' Zip Code`'' Name of Building(if applicable)
I SECTION 2:PROPOSED'WORK
Edition of MA State Code used 8th If New Construction check here®.or check all that apply in the two rows below
Existing Building❑ Repair❑ [-Alteration ❑ 1 Addition❑ Demolition ❑ (Please fill out and submit Appendix 1)
Change•of Use ❑ 1.Change of Occupancy ❑ Other ❑ Specify:
Are building plans and/or*construction documents being supplied as part of this permit application? Yes ® No ❑
Is an Independent Structural Engineering Peer Review required? - '' Yes ❑ .•NO.'Kl
Brief Descnption of Proposed Work:
Proposed new construction project of a three story Multi-Family dwelling with enclosed parking space wifta
756 sf retail space.
SECTION 3:COMPLETE THIS SECTION IF EXISTING BUILDING UNDERGOING RENOVATION.ADDITION,OR
CHANGE IN.USE OR OCCUPANCY
Check here if an Existing Building Investigation and Evaluation is enclosed(See 780 CMR 34) d
Existing Use Group(s): Proposed Use Group(s):
-SECTION BUILDING HEIGHT AND AREA _
Existing• Proposed
No.of Floors/Stories(include basement levels)&Area Per Floor(sq.ft.) ;, 4 17,600
69,993 .42'-3.1/2"
Total:Area(sq.ft.)and Total Height(ft.) •"` -
SECTION 5:USE GROUP(Check as applicable)
A: Assembly A-1❑ A-2❑ Nightclub ❑ A-3 ❑ A4❑ A-5❑ _ B:,Business ❑ E: Educational ❑
F: Facto F-1❑ F2❑ ,H:.High Hazard. H-1❑ _ H-2❑ 1-1 ❑ H-4❑ H-5❑
I: Institutional:I-1❑ I-2❑ I4,0 I-4❑ M: Mercantile® R. Residential R-10 R-2 M R-3❑ R-4❑
S: Storage S-1❑ S-2® U. Utility❑ Special Use❑and please describe below:
Special Use: {
SECTION 6:CO.NSTRUCTION TYPE(Check as applicable)
IA ❑ IB ® I'llA ❑ 11B,❑ IIIA ❑ JHB ❑ IV ❑ VA ❑ VB
SECTION 7:SITE INFORMATION(referto,7$0•CMR 111.0 for;details;on each.item)
Water Supply:"' -Flood Zone Information:"'' Trench Permit: Debris Removal:• Sewage Disposal: -
A trench will not be Licensed Disposal Site❑
Public® Check if outside Flood Zone IN 'Indicate municipal® required®or trench or specify:
Private❑. or indentify Zone: or on site system❑ permit is enclosed❑ '
Railroad right-of-way: Hazards to'Air Navigation: MA Historic Commission Review Process:
Not Applicable IN Is Structure within airport approach area? Is their review completed?
or Consent to Build enclosed❑ Yes❑ or No® Yes❑ No ❑ y
SECTION 8:CONTENT OF CERTIFICATE OF OCCUPANCY >
Edition of Code: 8th Use Group(s): S-2,M,R-2 Type of Construction: IB,VB Occupant Load per Floor: 103 average
Does the building contain an Sprinkler System?: Yes Special Stipulations:
- 1
SECTION 9 PROPERTY OWNER AUTHORIZATION
Name and Address of Property Owner
LAR Properties, Inc. - 282 Bennington Street East Boston, MA 02128
Name(Print) No.and Street .°: City/Town' `. Zip w
Property Owner Contact Information:
Anthony Roberto 617 _293. 1215 = _ anthony@spinellis.com
Title General Manager Telephone No.(business) Telephone No. (cell) e-mail address
If applicable,the property owner hereby authorizes
Jeffrey Alley 672 Suffolk Street, Suite 200 Lowell MA 01854
Name Y Street Address City/Town`. State Zip
to act on the property owner's behalf,in all matters relative to work authorized by this building permit application..
SECTION 10:CONSTRUCTION CONTROL(Please fill out Appendix 2)
f building is less'than 35,600 cu.ft.of enclosed space and/or;not under Construction Control then check here❑and skip Section 10:1
10.1 Registered Professional Res onsible fo .
r Con,struction.Control,
Jai Singh Khalsa 617.591 _8682 jkhlasa@tkgeast.com 6042
Name(Registrant) - Telephone No. e-mail address Registration Number
17 lvaloo Street, Suite 400 Sommerville MA 02143 Architectural 8.30.2017
Street Address City/Town State Zip Discipline Expiration Date
102 General Contractor .. '.
Aberthaw Construction Company, Inc.
Company Name
John J Klem CS90248 U
Name of Person Responsible for Construction License No. and Type if Applicable
161 Cotuit St ,. ..`. ,N Andover • MA • 01845
Street Address City/Town + State Zip
978. 654 4500 978 _7359617 John.klem@Aberthawcc.com
Telephone No.(business) Telephone No. cell e-mail address
-:SECTION 11::WORKERS,COMPENSATIONINSURANCE AFFIDAVrr M.G.L.c.152§25C 6
A Workers'Compensation Insurance Affidavit from the MA Department of Industrial Accidents must be completed and
submitted with this application. Failure to provide this affidavit will result in the denial of the issuance of the building permit.
Is a signed Affidavit submitted with this application? Yes® No ❑
SECTION 12:CONSTRUCTION COSTS AND PERMIT FEE
Estimated Costs:(Labor
Item and Materials) Total Construction Cost(from Item 6)_$ 10,612,696 -
1.Building $ 8,019,618 Building Permit Fee=Total Construction Cost x 111 (Insert here
2.Electrical $ 726,964 appropriate municipal factor)=$ 116,740
3.Plumbing $ 978,145
4.Mechanical (HVAC) $ 706 930 Note:Minimum fee=$ (contact municipality)
5.Mechanical Other $ 181,037 Enclose check payable to -;City of Salem
6.Total Cost. $ 10,612,696 (contact municipality)and write check number here
SECTION 11 SIGNATURE OF BUILDING PERMIT APPLICANT
By entering my name below,I hereby attest under the pains and penalties of perjury that all of the information contained in this
application is true and accurate to the best of my knowledge and understanding.
Jeffrey Alley Vice President 978 654 A500 x108
Ple rint sign name Title Telephone No. Date
672 Suffol reet, Suit 0 Lowell MA 01854
Street Address City/Town . State Zip
Municipal Inspector to fill'out this sec tiowupow#pplicanon approval 4 ✓ 3
Nane Date
i
Initial Construction Control Document
H To be submitted with the building permit application by a
Registered Design Professional
I
for work per the 8th edition of the
5av Massachusetts State Building Code, 780 CMR, Section 107.6.2
Project Title: River Rock Residence&Retail Date: June 5,2017
Property Address: 70 Boston Street& 13 Goodhue Street, Salem,MA
Project: Check(x) one or both as applicable: [x] New construction [ ] Existing Construction
Project description: The project is a new 44-Unit Apartment building with a small retail area New construction 3-
story plus a Garage level building.
I, Zbivniew M. Wozny, MA Registration Number: 34029 Expiration date: June 30, 2018, am a registered design
professional, and hereby certify, to the best of my knowledge, information and belief, that I have prepared or directly
supervised the preparation of all design plans, computations and specifications concerning':
[ ] Entire Project [ ] Architectural [ ] Structural [x] Mechanical
[ ] Fire Protection [ ] Electrical [x] Other: Plumbing
for the above-named project and that such plans, computations and specifications meet the applicable provisions of the
Massachusetts State Building Code, (780 CMR), and accepted engineering practices for the proposed project. I
understand and agree that I (or my designee) shall perform the necessary professional services in accordance with the
Professional Standard of Care, and be present on the construction site on a regular and periodic basis to:
1. Review, for conformance to this code and the design concept, shop drawings, samples and other submittals by the
contractor in accordance with the requirements of the construction documents. Such review shall not diminish or
relieve the Contractor of its submittal and other responsibilities.
2. Perform the duties for registered design professionals in 780 CMR Chapter 17, as applicable.
3. Be present at intervals appropriate to the stage of construction to become generally familiar with the progress and
quality of the work and to determine if the work is being performed in a manner consistent with the approved
construction documents and this code. The Contractor shall be responsible for performing the work in accordance
with the contract documents and shall be exclusively responsible for its construction means, methods, sequences
and procedures, and for construction safety.
4. The performance of the services shall not require any special testing or inspections unless specifically stated in the
Code.
When required by the building official, I shall submit field/progress reports (see item 3.) together with pertinent
comments, in a form acceptable to the building official.
Upon completion of the work, I shall submit to the building official a `Final Construction Control Document'. 4 `"
I � -
I N Of 4t,
Enter in the space to the right a"wet"or moo`, ZBIGNIEW
electronic signature and seal: M. m
O WOZNY y y�
U MECHANICAL
No.34029
a
FIDAA E. BA 'BAR
Phone number: 781-826-4144 ASS NAI NOTARY PUBLIC
Email: zwozn wbaen meers.com coMfdpNWEAl7H OF MA spCHUSETTS
Y@ g� 1, My Comm.Expires Oct.27,2017
Building Official Use Only
Building Official Name: Permit No.: Date:
JA16148 River Rock Residential Salem\Affidavits\lnitial Constr Ctrl M-P Resid-Retail 06-05-17.doc
. Initial Construction Control Document
y To be submitted with the building permit application by a
Registered Design Professional
for work per the 81h edition of the
Massachusetts State Building Code, 780 CMR, Section 107.6.2
Project Title: River Rock Residence&Retail Date: June 5,2017
Property Address: 70 Boston Street& 13 Goodhue Street, Salem,MA
Project: Check(x)one or both as applicable: [x]New construction [ ] Existing Construction
Project description: The project is a new 44-Unit Apartment building with a small retail area.New construction 3-
story plus a Garage level building.
I, M. Salim Afsar, MA Registration Number: 39083 Expiration date: June 30, 2018, am a registered design professional,
and hereby certify, to the best of my knowledge, information and belief, that I have prepared or directly supervised the
preparation of all design plans, computations and specifications concerning':
[ ] Entire Project [ ] Architectural [ ] Structural [] Mechanical
[ ] Fire Protection [x] Electrical [x] Other: Fire Alarm
for the above-named project and that such plans, computations and specifications meet the applicable provision
s of the
Massachusetts State Building Code, (780 CMR), and accepted engineering practices for the proposed project. I
understand and agree that I (or my designee) shall perform the necessary professional services in accordance with the
Professional Standard of Care,and be present on the construction site on a regular and periodic basis to:
1. Review, for conformance to this code and the design concept, shop drawings, samples and other submittals by the
contractor in accordance with the requirements of the construction documents. Such review shall not diminish or
relieve the Contractor of its submittal and other responsibilities.
2. Perform the duties for registered design professionals in 780 CMR Chapter 17, as applicable.
3. Be present at intervals appropriate to the stage of construction to become generally familiar with the progress and
quality of the work and to determine if the work is being performed in a manner consistent with the approved
construction documents and this code. The Contractor shall be responsible for performing the work in accordance
with the contract documents and shall be exclusively responsible for its construction means, methods, sequences
and procedures, and for construction safety.
4. The performance of the services shall not require any special testing or inspections unless specifically stated in the
Code.
When required by the building official, I shall submit field/progress reports (see item 3.) together with pertinent
comments, in a form acceptable to the building official_
Upon completion of the work, I shall submit to the building official a `Final Construction Control Document'.
lr.w
A`,
Enter in the space to the right a"wet"or s,90
electronic signature and seal: �o M.SALim
AFSAR U'
cUi ELEC i RICAL
lv'o.39p83
,c,�� FIDAA E. BARBAR
Phone number: 781-826-4144 �►Aj NOTARY PUBLIC
Email: safsar@wbaengineers.com COWNWEXTH OF MUSACHUSEMWMy Gomm,Upiros Oct,27,2017
Building Official Use Only
Building Official Name: Permit No.: Date:
1\16148 River Rock Residential Salem\Affidavits\Initial Constr Ctrl Elec Resid-Retail 06-05-17.doc
Initial Construction Control Document
u To be submitted with the building permit application by a
d Registered Design Professional
for work per the 8th edition of the
M s�ov Massachusetts State Building Code, 780 CMR, Section 107.6.2
Project Title: River Rock Residence&Retail Date: June 5,2017
Property Address: 70 Boston Street& 13 Goodhue Street, Salem, MA
Project: Check(x)one or both as applicable: [x] New construction [ ] Existing Construction
Project description: The project is a new 44-Unit Apartment building with a small retail area.New construction 3-
story plus a Garage level building.
I, Grzegorz B. Womy, MA Registration Number: 39170 Expiration date: June 30, 2018, am a registered design
professional, and hereby certify, to the best of my knowledge, information and belief, that I have prepared or directly
supervised the preparation of all design plans,computations and specifications concerning':
[ ] Entire Project [ ] Architectural [ ] Structural [ ] Mechanical
[x] Fire Protection [ ] Electrical Other:
for the above-named project and that such plans, computations and specifications meet the applicable provisions of the
Massachusetts State Building Code, (780 CMR), and accepted engineering practices for the proposed project. I
understand and agree that I (or my designee) shall perform the necessary professional services in accordance with the
Professional Standard of Care,and be present on the construction site on a regular and periodic basis to:
1. Review, for conformance to this code and the design concept, shop drawings, samples and other submittals by the
contractor in accordance with the requirements of the construction documents. Such review shall not diminish or
relieve the Contractor of its submittal and other responsibilities.
2. Perform the duties for registered design professionals in 780 CMR Chapter 17, as applicable.
3. Be,present at intervals appropriate to the stage of construction to become generally familiar with the progress and
quality of the work and to determine if the work is being performed in a manner consistent with the approved
construction documents and this code. The Contractor shall be responsible for performing the work in accordance
with the contract documents and shall be exclusively responsible for its construction means, methods, sequences
and procedures, and for construction safety.
4. The performance of the services shall not require any special-testing or inspections unless specifically stated in the
Code.
When required by the building official, I shall submit field/progress reports (see item 3.) together with pertinent
comments, in a form acceptable to the building official.
Upon completion of the work, I shall submit to the building official a `Final Construction Control Document'' _
Enter in the space to the right a"wet"or (H OF MASS
electronic signature and seal: GRZEGORZ �CyG f
rs i
B.
O m �F
WOZNY
v FIRE PROTECTION N
No.39170
Phone number: 781-826-4144 (i �y�p/�••••
Email: gwozny@wbaengineers.com S ENG� FIDAA E. BARBAR
NOTARY PUBLIC
i;
COMMONWEALTH OF MASSACHUSETTs
my comm.Expires Oct,27,2017
Building Official Use Only
Building Official Name: Permit No.: - Date:
JA16148 River Rock Residential Salem\Affidavits\lnitial Constr Ctrl FP Resid-Retail 06-05-17.doc
Initial Construction Control Document
To be submitted with the building permit application by a
r
p d Registered Design Professional
for work per the 81h edition of the
Massachusetts State Building Code, 780 CMR, Section 107
Project Title: River Rock Residences & Retail Date: 6-8-2017
Property Address: 70 Boston Street& 13 Goodhue Street, Salem, MA
Project: Check one or both as applicable: �J New construction ❑ Existing Construction
Project description: New Construction of 69.993 sf.mixed-use huildinq conai g of a 3-story multi-family
dwelling (R-2) of VB construction which contains 44- residential dwelling units over 1-story of partially
enclosed parking garage (S-2) of type IB construction at grade which contains 41 parking spaces, separated
from above by a 2 hour horizontal fire separation There is also 756 SF mercantile use space on lowest level
I Jai Sinqh Khalsa MA Registration Number: Fn4? Expiration date: 06/31/97 , am a
registered design professional, and I have prepared or directly supervised the preparation of all design plans,
computations and specifications concerning:
Architectural [ ] Structural [ ] Mechanical
[ ] Fire Protection [ ] Electrical [ ] Other
for the above named project and that to the best of my knowledge, information, and belief such plans, computations and
specifications meet the applicable provisions of the Massachusetts State Building Code, (780 CMR),and accepted
engineering practices for the proposed project. I understand and agree that I(or my designee) shall perform the necessary
professional services and be present on the construction site on a regular and periodic basis to:
1. Review, for conformance to this code and the design concept, shop drawings, samples and other submittals by the
contractor in accordance with the requirements of the construction documents.
2. Perform the duties for registered design professionals in 780 CMR Chapter 17, as applicable.
3. Be present at intervals appropriate to the stage of construction to become generally familiar with the progress and
quality of the work and to determine if the work is being performed in a manner consistent with the approved
construction documents and this code.
Nothing in this document relieves the contractor of its responsibility regarding the provisions of 780 CMR 107.
When required by the building official,I shall submit field/progress reports (see item 3.)together with pertinent
comments, in a form acceptable to the building official.
Upon completion of the work,I shall su ilding official a `Final Construction Control Document'.
�r
Enter in the space to the right a
electronic signature and seal:
No BR1�GE v4L
0
M A zJ
v
Phone number: _ _8682 Email: ikhalsala�tkaeast.com
ding Official Use Only
Building Official Name: Permit No.: Date:
Version 06 11 2013
I
tI
Initial Construction Control Document
To be submitted with the building permit application by a`
Registered Design Professional
for work per the 8a'edition of the
Massachusetts State Building Code, 780 CMR, Section 107.6.2
r
I
Project Title: Riverrock Residences&Retail Date: 6-1-17
Property Address: 70 Boston St&13 Goodhue St.,Salem, MA i
i
Project: Check one or both as applicable:xxkwew construction ❑ Existing Construction
Project description: new residential building
i
I Brent R.Goldstein MA Registration.Number: 36782 Expiration date: 6-30-18 ,am a
registered design professional, and hereby certify that I have prepared or directly supervised the preparation of all design
plans,computations and specifications concerning:
[ ] Entire Project [ 1 Architectural Structural. [ ] Mechanical.
[ ] Fire Protection [ ] Electrical. [ ] Other I
i
for the above named project and that such plans,computations and specifications meet the applicable provisions of the
Massachusetts State Building Code,(780 CVTR),and accepted engineering practices for the proposed project. I
understand and agree that I(or my designee)shall perform the necessary professional:services and be present on the
construction site on a regular and periodic basis to:
I. Review,for conformance to this code and the design concept;shop drawings,samples and other submittals by the
contractor in accordance with the requirements of the construction documents.
2. Perform the duties for registered design professionals in 780 CMR Chapter,17,as applicable.
3. Be present at intervals appropriate to the stage of construction to become generally familiar with the progress and
quality of the work and to determine if the work is being performed in a manner consistent with the approved
construction documents and this code.
When required by the building official, I shall submit field/progress reports(see item 3.)together with pertinent
comments,in a form acceptable to the building official.
Upon completion of the work;I shall..submit to the building official a I`Final Construction Control Doc
Enter in the space to the right a"wet"or
electronic signature and seal: F
Phone number: . 781-670-9990 Email: brg@gm-se.com
Building Official Use Only
Building Official Name: Permit No.: Date:
Ai
Trial Version 10 09 2012
OF^'�►sS tiG
Womy/Barbar& Associates, Inc. qp
VVB&A CONSULTING ENGINEERS O2 G�EGORZ
FIRE PROTECTION NARRATIVE 0 W TECTIO
LRI PROPERTIES LLC . : 0: . RE 70
72-82 BOSTON ST
�p
Ftv
SALEIVI;MA.
JUNE 5,2017
SS►
BASIS (METHODOLOGY)OF DESIGN
Section 1.—.Residential Building.Description py�N OFF
�`SS
� 9
1 :Building."Use"Group: R-2,(residential) O`er M.SALIM
2. Total square:footage of Building, 16,997.sq.ft, AFSAR n
- 3 Building height: 39'-0
LECTRICAL
No. '083
4. Number of floors above grade: 3
5. Number of floors below grade: . ... 1:
6. Square footage per floor: :. Garage—4310 sq.ft. FSS�OpjAL
First Floor 4,402 sq..ft..
Second Floor-4,279 sq.ft.
Third.Floor. . 4,006 sq,ft. ... .. .. .....
7. Type(s)of occupancies(hazards): . Light Hazard residential
8. _ Type(s)of construction: _ VB
9. Hazardous material usage and storage.:. Non
10. Height storage of commodities within a
building stored over 12 ft. N/A
Site access arrangement See civil drawings
Section 2 Applicable Laws.and Governing Codes...
1. Building Code;Massachusetts State Buildi.ng,Code,780 CMR, 8th Edition
2. Referenced Standards:NFPA 13-2013,.NFPA 25—2011,NFPA 72.-2010,
3. :Applicable Sections of M.G.L.,Chapter 148, "Fire.Protection."
4. Applicable Sections of 527 CMR"Fire Prevention Regulations."
5. Applicable Specialized,Codes(plumbing,electrical and architectural access.)
6, Applicable Federal Laws such as OSHA,ADA,etc.
Section:3—Design Responsibility
1, WoznyBarbar and Associates(WB&A).is providing a design and design criteria including .
specifications. Hydraulic calculations are required and.have been provided.The design has been
based on Fire Protection Systems,Chapter 9,Guidelines for the Preparation of Narrative Reports.
2. Fire Protection drawings will indicate sprinklers in the most remote areas only,as per"guidelines
for the Preparation of the Narrative Reports 780 CMR-903.1.1".WB&A Associates is providing a
:partial.design and the design criteria which will be used by the installing contractor who will
finalizes the system layout,as per Guidelines for the preparation of Fire Protection System
Narrative Reports,WB&A will review.sprinkler contractor shop drawings for conformance with
the design documents and NFPA requirements:In addition,WB&A will provide periodic
inspection during:construction.
3. The Professional Fire Protection:Engineer of record responsible for the fire suppression will be
Grzegorz B.Wozny,PE,Massachusetts No. 39170,and the electrical engineer:of record
responsible for fire alarm system will:be.Salim Afsar,PE,Massachusetts No.39083,
Section 4—Fire Protection System to be Installed
1 Sprinkler System
1076 Washington Street,Hanover,MA 02339-Te1781.826.4144.•Fax 781.924.5792•www.wbaengineers.com
161 Exchange Street,31d Floor,Pawtucket,RI 02860
c;
Page'2
a. The building will be provided with a 4"fire service and 4"double check valve assembly
installed in vertical position.
b. The fire service will be located in a water service room attached to the building.
C. Fire department inlet connection will be installed within 100 feet from a fire hydrant.
d. Standpipes are not required and will not be provided.
e. Each unit will be a dedicated sprinkler zone.
f. All parking garages will be a single dry pipe sprinkler zone.
g. The sprinkler system design will be based on NFPA 1302-13 requirements.
h. Spaces above ceiling will be provided with listed sprinklers.The spacing of those
sprinklers will be 12'x12' maximum.
i. Residential sprinklers will be provided inside apartments and dry,quick response
sprinklers in garages.
j. The hydrant flow test was performed on December 7,2016 by Williams Sparage,the
results are as follow:
• Static pressure - 72 psi
• Residual pressure- 70 psi
• Flow - 1106 gpm
2. Fire Alarm System
a. The building shall include a complete independent addressable fire detection and alarm
system with complete audio/visual evacuation signaling. Equipment shall be UL listed
and shall meet the requirements of the local fire department and State Fire Marshal.
1) Alarm notification shall be via ADA-compliant audio and visual signaling
devices,located in common spaces,corridors and public toilets.Low frequency
520HZ mini horns shall be installed in bedrooms and the living rooms of the
dwelling units.
2) Smoke detectors spaced approximately 30' apart or per manufacturers
recommended distances. Smoke detectors shall be located in all common areas,
electric rooms and storage rooms. Remote indicators shall be installed above all
locked doors with detectors inside the room.
3) Pull stations shall be located at the egress to each floor and at all exits from the
building.
4) Audible alarm signals shall sound at march time cadence(120 ppm).The system
shall also be capable of temporal(NFPA 72-2.2.2.2).
5) Flash an alarm LED and sound an audible signal at the FACP.Upon
acknowledgment,the alarm LED shall light steadily and the audible shall
silence. Subsequent alarms shall re-initiate this sequence.
6) Visually indicate the alarm initiating device,type and location via the alpha-
numeric display located at the FACP.
7) Flow,tamper and pressure switches will be wired to the building fire alarm
control panel.
8) A knox/key box shall be installed at all entrances to the building.
9) The fire control panel annunciator will be located at the entry door.A rotating
beacon shall be located on the exterior of the building. The FACP shall be
connected to a Master Box and listed Central Station for transmission of alarms
to the Fire Department
10) 120 volt smoke detectors shall be provided in bedrooms and outside each
bedroom. Detectors shall be equipped with battery backup.
11) 120 volt carbon monoxide detectors shall be provided in outside each bedroom.
Detectors shall be equipped with battery backup.
12) An auto dialer will be provided.
Section 5—Sequence of Operation
1. Sprinkler System
a. Wet System—When a single heat activated sprinkler fuses and discharges water,flow
switch at a floor control valve assembly is actuated and sends an alarm signal to the main
fire alarm control panel.
-2-
Page'3 '
a. Dry System—When a single heat activated sprinkler fuses and discharges water,pressure
switch at a dry pipe valve is actuated and sends an alarm signal to the main fire alarm
control panel.
2. Fire Alarm System
a. The operation of a dual action(lift and pull)manual station or activation of any automatic
alarm initiating device(system smoke,heat, waterflow, and pressure switch)shall
automatically:
1) Initiate the transmission of an alarm to the Municipal Fire Station and a listed
Central Station for transmission of alarms to the Fire Department.
2) Audible alarm signals shall sound at march time cadence(120 ppm).The system
shall also be capable of temporal(NFPA 72-2.2.2.2).
3) Flash all visual signals throughout the building in a synchronized manner.Turn
on the exterior beacon at the primary entrance.
4) Flash an alarm LED and sound an audible signal at the FACP.Upon
acknowledgment,the alarm LED shall light steadily and the audible shall
silence. Subsequent alarms shall re-initiate this sequence.
5) Visually indicate the alarm initiating device,type and location via the alpha-
numeric display located at the FACP and at the remote control annunciator.
6) Tampering with any of the supervised control valves shall flash a supervised
signal at the Fire Alarm Control Panel.
Section 6—Testing Criteria
1. Sprinkler System,
a. Notify the authority having jurisdiction and Owner's representative of the time and date
of the test.
b. Perform all required acceptance test as required by NFPA 13 and NFPA 25.
C. Complete and sign the appropriate Contractor's material and test Certificate(s).
2. Fire Alarm System
a. The system shall be fully tested by a UL certified testing company in accordance with UL
guidelines and NFPA standards.Each and every device shall be tested.A copy of NFPA
Record of Completion documentation to Fire Marshall prior to the fire department walk-
through.At a minimum perform the following tests:
1) Before energizing the cables and wires,check for correct connections and test
for short circuits,ground faults,continuity,and insulation.
2) Close each sprinkler system flow valve and verify proper supervisory alarm at
the FACP.
3) Verify activation of all waterflow and pressure switches.
4) Open initiating device circuits and verify that the trouble signal actuates.
5) Open and short signaling line circuits and verify that the trouble signal actuates.
6) Open and short notification appliance circuits and verify that trouble signal
actuates.
7) Ground all circuits and verify response of trouble signals.
8) Check presence and audibility of tone at all alarm notification devices.
9) Check installation,supervision, and operation of all intelligent smoke detectors
using the walk test.
10) Each of the alarm conditions that the system is required to detect should be
introduced on the system.Verify the proper receipt and the proper processing of
the signal at the FACP and the correct activation of the control points.
11) When the system is equipped with optional features,the manufacturer's manual
shall be consulted to determine the proper testing procedures.This is intended to
address such items as verifying controls performed by individually addressed or
grouped devices,sensitivity monitoring,verification functionality and similar.
b. A copy of the final test report and UL certification shall be submitted indicating proper
-3 -
Page 4
functioning of the system and conformance to the specifications.The test shall be
performed by UL certified and factory-trained qualified technicians.Each and every
device shall be tested,and standalone operation of remote panels shall be verified.UL
certification shall be performed by the same company that will hold and execute the Test
and Inspection contract.
Equipment and Tools
During the pre- and final acceptance testing of the systems, the installing contractor will provide the following
equipment at the site.
1. Sprinkler system testing notification announcements to the occupants of the building;
2. All devices within limits of construction shall be tested in strict accordance with manufacturer's
instructions: (i.e. all manual pull stations will be activated and reset with key; all smoke detectors
will be tested with magnets; all AN units will be activated and monitored for audible and visual
notification;etc.);
3. Construction Documents and approved Shop Drawings or As-Built Drawings;
4. Approved narrative description(sequence of operation);
Approval Requirements
The following approvals are necessary prior to the start of work:
1. Salem Fire Department, Permit for Fire Protection System. This permit is for installation of the
fire alarm system and automatic sprinkler system.
2. A verbal approval at time of testing followed by a written documentation shall be issued indicating
all Code requirements have been satisfied.
3. The contractor, in conjunction with the alarm manufacturer, shall rectify all portions of the system
that fail acceptance testing.
4. The contractor and the alarm manufacturer will issue final inspection reports along with
Certificate of Completion verifying all systems affected by construction are in compliance.
5. All documentation for personnel contact regarding emergency notification shall be submitted by
the owner's representative.
JA16148 River Rock\Narrative\FP Narrative 70 Boston Street 02-17-17.doc
-4-
i
RIVER ROCK RESIDENTIAL TOWNHOUSES
Fire Sprinkler Reports
for
r,
Khalsa;Desi60n
�1Tlvalao Si Suite 400 h =
K
SOmeMlle AMA-02143 ;
Wozny/Barbar&Associates,Inc.
W B&AC ENGINEEIIS
1076 Washington Street,Hanover;MA 02339
TEL 781.826A144 FAX 781:924.5792
www wbaengineers.com,
�r114 OF
GRZEG RZ Prepared By:
Wozny/Barbar&Associates
Wozny/Barbar&Associates
1076 Washington St.
.>� Hanover, MA 02339
E 781-826-4144
1/30/2017
Fire fiF�re Sprinkler Hydraulics Calculation Program,. Ehte Software Development,Inc
I Wq'zh/Barbar&associates
. Y River Rock Residential TowriFiouseS
Hanover,MA;02339Page.2
General Project Data Report
General, Data - - �
Project Title: River Rock Residential Townhouses Project File Name: #2..fiw
Designed By: Wozny/Barbar&Associates Date: 1/30/2017
Code Reference: NFPA 1-2013, NFPA 13-2013, Approving Agency: Salem Fire Department
NFPA 14-2013
Client Name: Khalsa Design Inc. Phone: 617-591-8682
Address: 17 Ivaloo St Suite 400 City, State Zip Code: SOmerville, MA 02143
Company Name: Wozny/Barbar&Associates Representative: Tom Hamwey
Company Address: 1076 Washington St. City And State: Hanover, MA 02339
Phone: 781-826-4144
Building Name: River Rock Residences Building Owner:
Townhouses
Contact at Building: Phone at Building:
Address Of Building: 70-92 1/2 Boston St City, State Zip Code: Salem, MA
Project Data Xtr
Description Of Hazard: Ordinary 1 Sprinkler System Type: Dry
Design Area Of Water Application: 333 ft2 Maximum Area Per Sprinkler: 256 ft2
Default Sprinkler K-Factor: 5.60 K Default Pipe Material: SCHED 40 DRY
GALVANIZED
Inside Hose Stream Allowance: 0.00 gpm Outside Hose Stream Allowance: 250.00 gpm
In Rack Sprinkler Allowance: 0.00 gpm
Sprinkler Specifications
Make: Model:
Size: 1/2 Temperature Rating: 175 F
#2, Dry Garage Sprinklers
Water-S I Test .Data
pp
Source Of Information: Williams Sparages
Test Hydrant ID: Date Of Test: 12-7-2016
Hydrant Elevation: 0 ft Static Pressure: 72.00 psi
Test Flow Rate: 1106.00 gpm Test Residual Pressure: 70.00 psi
Calculated System Flow Rate: 442.00 gpm Calculated Inflow Residual Pressure: 51.03 psi
Available Residual Pressure At
System Flow: 71.63 psi
Cal il-aw oo -'Project ,
w
,. y �.
Calculation Mode: Demand
HMD Minimum Residual Pressure: 7.00 psi Minimum Desired Flow Density: 0.15 gpm/ft2
Number Of Active Nodes: 26
Number Of Active Pipes: 25 Number Of Inactive Pipes: 0
Number Of Active Sprinklers: 9 Number Of Inactive Sprinklers: 0
J:\...\#2.fiw Monday, June 05, 2017, 2:31 PM
EFeer,Hydraulics Calculation Program Elite Software Devel�cssociates' River Rock fiesidential Townhouseer,MA`.02339
...a t,Pa a 3;
Fire;Sprinkler Output Data
Ow-rali P,ip P v
e Out ut Data
Beg. Nodal Elevation Spk/Hose Residual Nom. Dia. q (gpm) F. L./ft Pipe-Len. PF-(psi)
si/ft) Fit-Len.
End. KFactor Discharge Pressure Inside Dia. Q (gpm) (p PE-(psi)
Node (K) (feet) (gpm) (psi) C-Value Velocity Fittings Tot-Len. PT-(psi)
(fps) Type-Grp (ft)
1 0.00 -7.00 0.00 51.03 12.00 0.00 0.00005 150.00 .0.007
2 0.00 -5.00 0.00 50.16 11.910 192.00 G 8.00 0.866
CAST IRON, CEMENT 140 0.55 0 158.00 0.873
2 0.00 -5.00 0.00 50.16 4.00 0.00 0.01143 100.00 1.478
3 0.00 -5.00 0.00 48.68 3.850 192.00 TG 29.30 0.000
CAST IRON, CEMENT 140 5.29 0 129.30 1.478
3 0.00 -5.00 0.00 48.68 4.00 0.00 0.01143 5.00 0.209
4 0.00 0.00 0.00 46.31 3.850 192.00 E 13.30 2.165
CAST IRON, CEMENT 140 5.29 0 18.30 2.374
4 0.00 0.00 0.00 46.31 4.00 0.00 0.00929 10.00 0.121
5 0.00 10.00 0.00 41.86 4.260 192.00 G 3.00 4.330
SCHED 10 WET STEEL 120 4.32 0 13.00 4.451
5 Backflo 10.00 41.86 192.08
Prev
6 8.00 psi 10.00 33.85
6 0.00 10.00 0.00 33.85 4.00 0.00 0.00929 3.00 0.149
7 0.00 10.00 0.00 33.70 4.260 192.00 E 13.00 0.000
SCHED 10 WET STEEL 120 4.32 0 16.00 0.149
7 0.00 10.00 0.00 33.70 2.00 0.00 0.13861 3.00 2.578
30 0.00 10.00 0.00 31.12 2.067 102.79 TGC 15.60 0.000
SCHED 40 DRY GALVANIZED 100 9.83 9 18.60 2.578
7 0.00 10.00 0.00 33.70 2.00 0.00 0.07612 3.00 1.903
8 0.00 10.00 0.00 31.80 2.067 89.21 TGC 22.00 0.000
SCHED 40 WET STEEL 120 8.53 0 25.00 1.903
8 0.00 10.00 0.00 31.80 2.00 0.00 0.07612 24.00 3.349
9 0.00 10.00 0.00 28.45 2.067 89.21 2ET 20.00 0.000
SCHED 40 WET STEEL 120 8.53 0 44.00 3.349
9 0.00 10.00 0.00 28.45 2.00 0.00 0.07612 100.00 8.830
10 0.00 10.00 0.00 19.62 2.067 89.21 ETG 16.00 0.000
SCHED 40 WET STEEL 120 8.53 0 116.00 8.830
10 0.00 10.00 0.00 19.62 2.00 0.00 0.07612 2.00 0.913
35 0.00 10.00 0.00 1&71 2.067 89.21 T 10.00 0.000
SCHED 40 WET STEEL 120 8.53 4 12.00 0.913
J:\...\#2.fiw Monday, June 05, 2017, 2:31 PM
Fire-sFire Sprinkler Hydraulics Calcwlation:Program ; �� Elite Software Develo meet Inc
Wo`zri .. w_ ,.. �, �"". Pam«...:
y/Barbar&Associates River Rock<Residential To"vnhouses"
Hanover•,Mk 02339.
Fire Sprinkler Output Data
DverallPipe°Output.Data:(cont'd) k b
r
Beg. Nodal Spk/Hose Residual Nom. Dia. q (gpm) F. L./ft Pipe-Len. PF-(psi)
Elevation Q (gpm) (psi/ft) Fit-Len.
End. KFactor Discharge Pressure Inside Dia. PE-(psi)
Node (K) (feet) (gpm) (psi) C-Value Velocity Fittings Tot-Len. PT-(psi)
(fps) Type-Grp (ft)
30 0.00 10.00 0.00 31.12 2.00 0.00 0.13861 3.00 1.386
31 0.00 10.00 0.00 29.74 2.067 102.79 2E 7.00 0.000
SCHED 40 DRY GALVANIZED 100 9.83 9 10.00 1.386
31 0.00 10.00 0.00 29.74 2.00 0.00 0.13861 86.00 11.920
32 0.00 10.00 0.00 17.82 2.067 102.79 ----- 0.00 0.000
SCHED 40 DRY GALVANIZED 100 9.83 9 86.00 11.920
32 0.00 10.00 0.00 17.82 1.25 0.00 0.35123 10.00 3.512
33 0.00 10.00 0.00 14.31 1.380 58.66 ----- 0.00 0.000
SCHED 40 DRY GALVANIZED 100 12.58 2 10.00 3.512
32 0.00 10.00 0.00 17.82 1.00 21.93 0,21624 8.00 2.487
2001 5.60 10.00 21.93 15.33 1.049 21.93 T 3.50 0.000
SCHED 40 DRY GALVANIZED 100 8.14 1 11.50 2.487
32 0.00 10.00 0.00 17.82 1.00 22.20 0.22126 6.00 2.102
2002 5.60 10.00 22.20 15.72 1.049 22.20 T 3.50 0.000
SCHED 40 DRY GALVANIZED 100 8.24 1 9.50 2.102
33 0.00 10.00 0.00 14.31 1.00 19.87 0.18026 6.00 1.712
2003 5.60 10.00 19.87 12.59 1.049 19.87 T 3.50 0.000
SCHED 40 DRY GALVANIZED 100 7.38 1 9.50 1.712
33 0.00 10.00 0.00 14.31 1.25 0.00 0.16339 6.00 1.667
34 0.00 10.00 0.00 12.64 1.380 38.79 T 4.20 0.000
SCHED 40 DRY GALVANIZED 100 8.32 2 10.20 1.667
34 0.00 10.00 0.00 12.64 1.00 19.29 0.17068 1.00 0.768
2004 5.60 10.00 19.29 11.87 1.049 19.29 T 3.50 0.000
SCHED 40 DRY GALVANIZED 100 7.16 1 4.50 0.768
34 0.00 10.00 0.00 12.64 1.00 19.49 0.17395 3.00 0.522
2005 5.60 10.00 19.49 12.1.2 1.049 19.49 ----- 0.00 0.000
SCHED 40 DRY GALVANIZED 100 7.24 1 3.00 0.522
35 0.00 10.00 0.00 18.71 1.25 0.00 0.14815 8.00 1.185
36 0.00 10.00 0.00 17.52 1.380 44.15 ----- 0.00 0.000
SCHED 40 WET STEEL 120 9.47 2 8.00 1.185
35 0.00 10.00 0.00 18.71 1.25 23.48 0.21567 1.00 1.121
2006 5.60 10.00 23.48 17.58 1.380 45.07 T 4.20 0.000
SCHED 40 DRY GALVANIZED 100 9.67 2 5.20 1.121
36 0.00 10.00 0.00 17.52 1.25 23.01 0.20758 1.00 0.644
2008 5.60 10.00 23.01 16.88 1.380 44.15 E 2.10 0.000
SCHED 40 DRY GALVANIZED 100 9.47 2 3.10 0.644
J:\...\#2.fiw Monday, June 05, 2017, 2:31 PM
i
i
Fire 'Fire Spr�nkier'Hydraulics Calculation Program ` sF Elite Software Development,Inc
Wozny/Barbara:&Associates River Rock Resitlential Townhouses
1' %Over,_MA"-02339 _ 0
R4ge 6
Fire Sprinkler Output Data
�weraliPipae;:0utput Data (cont'd) �
i t s.?., l' 'i
Beg. Nodal Spk/Hose Residual Nom. Dia. q (gpm) F. L./ft Pipe-Len. PF-(psi)
Elevation Q (gpm) (psi/ft) Fit-Len.
End. KFactor Discharge Pressure Inside Dia. PE-(psi)
(feet) Velocity Fittings Tot-Len.
Node (K) (gpm) (psi) C-Value (fps) Type-Grp (ft) PT-(psi)
2006 5.60 10.00 23.48 17.58 1.00 21.58 0.21002 13.00 2.730
2007 5.60 10.00 21.58 14.85 1.049 21.58 ----- 0.00 0.000
SCHED 40 DRY GALVANIZED 100 8.01 1 13.00 2.730
2008 5.60 10.00 23.01 16.88 1.00 21.14 0,20210 13.00 2.627
2009 5.60 10.00 21.14 14.25 1.049 21.14 ----- 0.00 0.000
SCHED 40 DRY GALVANIZED 100 7.85 1 13.00 2.627
i
J:\...\#2.fiw Monday, June 05, 2017, 2:31 PM
i
Fire=<FireSprnkler.Hydraulics calculation program =" x' F ,.x Elite Software Develo meet Inc:
Wozri /Barbar&Associates 1
Y River Rock Residential Townhouses
%Hanover MA`02339•_ ' x: ' :..,: ,: >.. ,_ ,
Fire Sprinkler Output Data
Overall.,S�riinkler,.�utput ,Data:
a
Flowing Area Group Sprinkler Sprinkler Residual Flowing Area Flowing Sprinkler
Sprinkler Code KFactor(K) Elevation Pressure (ft2) Density Discharge
Node No. (feet) (psi) ( pm/ft2) ( pm)
2001 A 5.60 10.00 15.33 130.00 0.169 21.93
2002 A 5.60 10.00 15.72 130.00 0.171 22.20
2003 A 5.60 10.00 12.59 130.00 0.153 19.87
2004 A 5.60 10.00 11.87 100.00 0.193 19.29
2005 A 5.60 10.00 12.12 130.00 0.150 19.49
2006 A 5.60 10.00 17.58 130.00 0.181 23.48
2007 A 5.60 10.00 14.85 130.00 0.166 21.58
2008 A 5.60 10.00 16.88 130.00 0.177 23.01
2009 A 5.60 10.00 14.25 130.00 0.163 21.14
Sub Totals For Group A 1140.00 0.168 192.00
Totals For All Groups 1140.00 0.168 192.00
J:\...\#2.fiw Monday, June 05, 2017, 2:31 PM
I
€.Fire-Fire Sprinkler Hydraulics Calculation Program' ;`. ;;' Elite.Software Development,Inc:
Wozny/Barbar&Associates \ River Rock Residential Townhouses
Hanover,1MA'02339_
,ag 7�:
Fire Sprinkler Output Summary
Hydraulically Most Dern . r le y and�n,g Sprinkler Node =
v, � t
HMD Sprinkler Node Number: 2004
HMD Actual Residual Pressure: 11.87 psi
HMD Actual GPM: 19.29 gpm
SPrier SUmma -
Sprinkler System Type: Dry
Specified Area Of Application: 333.00 ft2
Adjusted Area Of Application: 432.90 ft2
Minimum Desired Density: 0.150 gpm/ft2
Application Average Density: 0.577 gpm/ft2
Application Adjusted Density(not required by NFPA 13): 0.444 gpm/ft2
Application Average Area Per Sprinkler: 37.00 ft2
Adjusted Area Per Sprinkler (not required by NFPA 13): 48.10 ft2
Sprinkler Flow: 192.00 gpm
Average Sprinkler Flow: 21.33 gpm
sFlow_Velocity And Imbalance Suinrnary
Maximum Flow Velocity( In Pipe 32 - 33) 12.58 ft/sec
Maximum Velocity Pressure ( In Pipe 32- 33) 1.07 psi
Allowable Maximum Nodal Pressure Imbalance: 0.0100 psi
Actual Maximum Nodal Pressure Imbalance: 0.0062 psi
Actual Average Nodal Pressure Imbalance: 0.0012 psi
Actual Maximum Nodal Flow Imbalance: -0.0808 gpm
Actual Average Nodal Flow Imbalance: 0.0062 gpm
`Overall Network Summary` 4
Number Of Unique Pipe Sections: 25
Number Of Flowing Sprinklers: 9
Pipe System Water Volume: 984.02 gal
Sprinkler Flow: 192.00 gpm
Non-Sprinkler Flow: 0.00 gpm
Demand Flow Excluding Exterior Hose Flow: 192.00 gpm
Exterior Hose Flow: 250.00 gpm
Minimum Required Residual Pressure At System Inflow 51.03 psi
Node:
Demand Flow At System Inflow Node: 442.00 gpm
J:\...\#2.fiw Monday, June 05, 2017, 2:31 PM
Fire-.Fire Sprinkler Hydraulics Calculation Program x Elite Software Development,Inc.,
Wozn /Barbar'&Associates k x
! Y River Rock Residential Townhouses°
Pa e.8
Fire Sprinkler Output Data
Hydraulic pp mop,' Gea ph ='k
w
100
90
80
72
70 70
6
Q
60
L
U) 50
I1 40
30
20
10
0
2 4 6 8 10 12 14 16 18 20
Flowrate(x100) gpm
Supply Curve Data
Static Pressure: 72 psi
Test Residual Pressure: 70 psi
Test Flow Rate: 1106 gpm
Demand Curve Data
Calculated Residual Pressure: 51.03 psi
Calculated Flow Rate: 442.00 gpm
Exterior Hose Flow: 250.00 gpm
Excess Available Residual Pressure At Calculated Flow: 20.6 psi
Pressure Required For First Sprinkler Downstream From Inflow Node To Flow: 15.36 psi
J:\...\#2.fiw Monday, June 05, 2017, 2:31 PM