Bosch Thermotechnology Corp. 112.2020 Data subject to change
3 Product Specifications
Decibels([dB(A)]
Max @ 100% load 77 79
Min @ min load 56 I 60
Compressor
RLA 19 29
LRA 45 58.1
Condenser Fan Motor
Horsepower (HP) 1/6 1/3
FLA 1.0 2.5
Refrigeration System
Refrigerant Line Size'
Liquid Line Size (OD) I 3/8" 3/8"
Suction Line Size (OD) 3/4' 7/8"
Refrigerant Connection Size
Liquid Valve Size (OD) 3/8' 3/8"
Suction Valve Size (OD) 3/4" 7/8"
Refrigerant Charge (R410-A, oz) 121 170
Expansion Device EEV EEV
Maximum Line Length 100 FT 100 FT
Maximum Elevation Difference 50 FT 50 FT
Operating Range
Cooling 40"F- 125"F
Heating 50E-860F
Electrical Data
Voltage-Phase-Hz 208/230-1-60 208/230-1-60
Minimum Circuit Ampacity' 24.8 38.8
Max. Overcurrent Protection' 40 I 60
Min/Max Volts 172V/270V
Weight
Net Weight (without packaging) 159 196
Gross Weight (including packaging)` 190 227
Dimensions
U nit LxWxH (in.) 29-1/8x29-1/8x24-15/16 29-1/8 x 29-1/8 x 33-3/16
Outdoor Coil
Net face area - sq.ft. OuterCoil 13.6 I' 18.4
Tube diameter-in. 9/32" (7mm) 9/32" (7mm)
No.of rows 2 2
Fins per inch 17 19
Table 1
' Tested and rated in accordance with AHRI Standard 210/240.
s Wire size should be determined in accordance with National Electrical Codes;
extensive wire runs will require larger wire sizes.
' Must use time-delay fuses orHACR-type circuit breakers of the same size as
noted.
• Always check the rating plate for electrical data on the unit being
` Weight values are estimated. installed.
1 • Unit is factory charged with refrigerant for 15' of '%" liquid line.
System charge must be adjusted per Installation Instructions Final
Charge Procedure.
TXV is required at indoor unit to match our outdoor unit.