34 Summer Street LetterVSE Project Number: U1876.1774.201 June 22, 2020 Boston Solar 55 Sixth Road Woburn, MA 01801 REFERENCE: Bombardier, Jessica Residence: 34 Summer Street, Salem, MA 01970 Solar Array Installation To Whom It May Concern: Per your request,we have reviewed the existing structure at the above referenced site.The purpose of our review was to determine the adequacy of the existing structure to support the proposed installation of solar panels on the roof as shown on the panel layout plan. Based upon our review, we conclude that the existing structure is adequate to support the proposed solar panel installation. Design Parameters Code: Massachusetts State Residential Code (780 CMR Chapter 51, 9th Edition (2015 IRC)) Risk Category: II Design wind speed: 127 mph (3-sec gust) per ASCE 7-10 Wind exposure category: C Ground snow load: 50 psf Designed for snow guards: Yes Existing Roof Structure Roof structure: 3x5 rafters @ 30" O.C. Roofing material: asphalt shingles Roof slope: 35° Connection to Roof Mounting connection: (1) 5/16" lag screw w/ min. 2.25" embedment into framing at max. 30" o.c. along rails Use (4) #10 wood screws at rail ends as required. Racking system: SnapNrack Conclusions Based upon our review,we conclude that the existing structure is adequate to support the proposed solar panel installation. See attached calculations. 651 W. Galena Park Blvd., Ste. 101 / Draper, UT 84020 / T (801) 990-1775 / F (801) 990-1776 / www.vectorse.com VSE Project Number: U1876.1774.201 Bombardier, Jessica Residence 6/22/2020 The solar array will be flush-mounted (no more than 6"above the roof surface)and parallel to the roof surface.Thus,we conclude that any additional wind loading on the structure related to the addition of the proposed solar array is negligible. The attached calculations verify the capacity of the connections of the solar array to the existing roof against wind (uplift), the governing load case.Because the increase in lateral forces is less than 10%,this addition meets the requirements of the exception in Section 807.5 of the 2015 IEBC as referenced in 780 CMR Chapter 34,9th Edition.Thus the existing lateral force resisting system is permitted to remain unaltered.Any non-structural changes to the plans will not affect the conclusions in this letter. Limitations Installation of the solar panels must be performed in accordance with manufacturer recommendations.All work performed must be in accordance with accepted industry-wide methods and applicable safety standards.The contractor must notify Vector Structural Engineering,LLC should any damage,deterioration or discrepancies between the as-built condition of the structure and the condition described in this letter be found.Connections to existing roof framing must be staggered,except at array ends,so as not to overload any existing structural member.The use of solar panel support span tables provided by others is allowed only where the building type,site conditions,site-specific design parameters,and solar panel configuration match the description of the span tables.The design of the solar panel racking (mounts,rails,etc.)and electrical engineering is the responsibility of others.Waterproofing around the roof penetrations is the responsibility of others.Vector Structural Engineering assumes no responsibility for improper installation of the solar array. VECTOR STRUCTURAL ENGINEERING, LLC 06/22/2020 _______________________________________________________ Jacob Proctor, P.E. MA License: 54953 - Expires: 06/30/2022 Project Engineer Enclosures JSP/ych 06/22/2020 651 W. Galena Park Blvd., Ste. 101 / Draper, UT 84020 / T (801) 990-1775 / F (801) 990-1776 / www.vectorse.com JOB NO.:U1876.1774.201 SUBJECT:WIND PRESSURE PROJECT:Bombardier, Jessica Residence Label:Note: Calculations per ASCE 7-10 SITE-SPECIFIC WIND PARAMETERS: Basic Wind Speed [mph]:127 Notes: Exposure Category:C Risk Category:II Importance Factor, I: ADDITIONAL INPUT & CALCULATIONS: Height of Roof, h [ft]:25 (Approximate) Comp/Cladding Location:Hip?No Enclosure Classification: Zone 1 GCp:1.0 Figure 30.4-2C (enter negative pressure coefficients) Zone 2 GCp:1.2 Zone 3 GCp:1.2 α:9.5 Table 26.9-1 zg [ft]:900 Table 26.9-1 Kh:0.95 Table 30.3-1 Kzt:1 Equation 26.8-1 Kd:0.85 Table 26.6-1 Velocity Pressure, qh [psf]:33.2 Equation 30.3-1 GCpi:0 Table 26.11-1 PRESSURES:Equation 30.9-1 Zone 1, p [psf]:33.2 psf (1.0 W, Interior Zones, beyond 'a' from roof edge) Zone 2, p [psf]:39.8 psf (1.0 W, End Zones, within 'a' from roof edge) Zone 3, p [psf]:39.8 psf (1.0 W, Corner Zones, within 'a' from roof corner) (a= 3 ft) Solar Panel Array Gable Roofs 27° < θ ≤ 45° Enclosed Buildings Components and Cladding Wind Calculations ()()piphGCGCqp−= JOB NO.:U1876.1774.201 SUBJECT:CONNECTION PROJECT:Bombardier, Jessica Residence Calculate Uplift Forces on Connection Pressure (0.6 Wind) (psf) Max Connection Spacing1 (ft) Max Trib. Area2 (ft2) Max Uplift Force (lbs) Zone 1 19.9 2.5 7.0 139 Zone 2 23.9 2.5 7.0 167 Zone 3 23.9 2.5 7.0 167 Calculate Connection Capacity Lag Screw Size [in]:5/16 Cd:1.6 NDS Table 2.3.2 Embedment3 [in]:2.25 Grade: Nominal Capacity [lbs/in]:205 NDS Table 12.2A Number of Screws:1 Prying Coefficient:1.4 Total Capacity [lbs]:527 Determine Result Maximum Demand [lbs]:167 Lag Screw Capacity [lbs]:527 Result:Capacity > Demand, Connection is adequate. Notes 1. 'Max Connection Spacing' is the spacing between connections along the rails. 2. 'Max Trib Area' is the product of the 'Max Connection Spacing' and 1/2 the panel width/height perpendicular to the rails. (2) rails per row of panels. Length or panels perpindicular to the rails shall not exceed 67". SPF (G = 0.42) 3. Embedment is measured from the top of the framing member to the beginning of the tapered tip of the lag screw. Embedment in sheathing or other material is not effective. The length of the tapered tip is not part of the embedment length. VECTOR STRUCTURAL ENGINEERS JOB NO.:U1876.1774.201 SUBJECT:GRAVITY LOADS PROJECT:Bombardier, Jessica Residence CALCULATE ESTIMATED GRAVITY LOADS Roof Pitch: 8.4 :12 ROOF DEAD LOAD (D) Increase due to pitch Material weight [psf] Asphalt Shingles 1.22 2.0 1/2" Plywood 1.22 1.0 Framing 1.00 3.0 Insulation 1.22 0.5 1/2" Gypsum Clg.1.22 2.0 M, E & Misc 1.00 3.5 Total Original Roof DL PV Array DL 1.22 3 DL:1.22 ROOF LIVE LOAD (Lr) Existing Design Roof Live Load [psf]20 ASCE 7-10, Table 4-1 Roof Live Load With PV Array [psf]20 SNOW LOAD (S):w/ Solar Array Roof Slope [x:12]:8.4 Roof Slope [°]:35 Snow Ground Load, pg [psf]:50 ASCE 7-10, Section 7.2 Terrain Category:C ASCE 7-10, Table 7-2 Exposure of Roof:Fully Exposed ASCE 7-10, Table 7-2 Exposure Factor, Ce:0.9 ASCE 7-10, Table 7-2 Thermal Factor, Ct:1.1 ASCE 7-10, Table 7-3 Risk Category:II ASCE 7-10, Table 1.5-1 Importance Factor, Is:1.0 ASCE 7-10, Table 1.5-2 Flat Roof Snow Load, pf [psf]:35 ASCE 7-10, Equation 7.3-1 Minimum Roof Snow Load, pm [psf]:0 ASCE 7-10, Section 7.3.4 Unobstructed Slippery Surface?No ASCE 7-10, Section 7.4 Slope Factor Figure:Figure 7-2b ASCE 7-10, Section 7.4 Roof Slope Factor, Cs:1.00 ASCE 7-10, Figure 7-2 Sloped Roof Snow Load, ps [psf]:35 ASCE 7-10, Equation 7.4-1 Design Snow Load, S [psf]:35 1.00 35 Design material weight [psf] 2.4 1.2 3.0 0.6 2.4 3.5 13.2 3.7 #VALUE! Existing 35 8.4 35 50 C Fully Exposed 0.9 1.1 II 1.0 35 0 No Figure 7-2b Abbrev GRADES Fbxx (psi) Fvxx (psi) g (lb/ft3) JOB NO.:U1876.1774.201 DFL#1 DFL#1 1,000 180 32 DFL#2 DFL#2 900 180 32 DF1 (5X)DFL#1 5X5 & LARGER 1,350 170 32 SPF#2 SPF#2 875 135 26.2 SP#2 SP#2 1,100 175 34.3 PROJECT:Bombardier, Jessica Residence SUBJECT:BEAMS 24F-V4 24F-V4 2,400 240 32 24F-V8 24F-V8 2,400 240 40 LVL (1.9)LVL (1.9X106E)2,600 285 40 DESIGN LOADS:Load Types:Snow Live Dead LVL (2.0)LVL (2.0X106E)2,200 285 42 Roof 35 20 13 CRITERIA (L/)DTL DLL DDL LSL LSL (1.3X106E)1,700 400 42 Solar 3.7 A(BLANK)180 240 STL36 GRADE 36 STEEL 21,600 14,400 490 STL46 GRADE 46 STEEL 27,700 16,500 490 STL50 GRADE 50 STEEL 30,000 20,000 490 Label Length 'L' (ft) Roof Trib (ft) Floor Trib (ft) Wall Trib (ft) Add'l Live Load (plf) Add'l Solar Load (plf) Point Load From React (A,B)Dist 'a' (ft) Point Live Load 'PLL' (lb) Point Dead Load 'PDL' (lb)# PLIESGrade Size "BM/HDR"D CRITERIACr CD CF,V Ra (lb)Rb (lb) Mmax (ft-lb) Mallow (ft-lb) Vmax (lb) Vallow (lb) DTL (in) DTLallow (in) DLL (in) DLLallow (in) 1.5DL GLB Camb Check Rafter 5.75 2.5 9.2 (1)SPF#2 3x5 1.00 1.15 1.00 370 370 532 1048 317 1553 0.072 0.383 0.049 0.288 0.51 M 29,000,000 2,000,000 1,300,000 1,400,000 1,600,000 1,600,000 1,400,000 Exx (psi) 1,800,000 29,000,000 29,000,000 1,700,000 1,800,000 1,900,000