BUILDING 4 - FP1-1 (002)Job: PROPOSED MULTI -UNIT RESIDENTIAL BUILDING Address: 9 SOUTH MASON ST - BUILDING 4 City: SALEM State: MA Zip/Postal Code: 01970 Contract #: 380-008 Contractor: VILLAGE FIRE PROTECTION Address: 86 MILFORD ST City: MILFORD Date: 10/15/2018 Designer: JFP SOLUTIONS, INC. State: NH Zip/Postal Code: 03055 Phone: (603) 672-6267 Fax: Email: Approving Authority: SALEM FD Design Defaults Default Sprig Size: Default Sprig Material: Default Sprig Elevation: 1 CPVC 0 Standards: NFPA 13R Default Drop Size: 1 Default Drop Material: CPVC Default Drop Elevation: 0 FIRE PROTECTION NOTES/NARRATIVE: THE PURPOSE OF THIS FIRE PROTECTION DRAWING AND THE ASSOCIATED HYDRAULIC CALCULATIONS IS TO INDICATE THE PROPOSED AUTOMATIC SPRINKLER SYSTEM TO BE INSTALLED WITHIN BUILDING 4, LOCATED AT 9 SOUTH MASON STREET IN SALEM, MASSACHUSETTS. THIS BUILDING (BUILDING 4) WILL BE A NEW THREE -LEVEL RESIDENTIAL BUILDING WITH NON-COMBUSTIBLE INACCESSIBLE CRAWLSPACE BELOW. PER DISCUSSIONS WITH THE SALEM BUILDING DEPARTMENT, THE CRAWLSPACE WILL NOT BE CONSIDERED PART OF THE AGGREGATE LIVING AREA OF THE BUILDING, RESULTING IN A TOTAL AGGREGATE AREA OF LESS THAN 12,000 SF. ACCORDINGLY, THE SPRINKLER SYSTEM PROTECTING THIS BUILDING HAS BEEN DESIGNED AND WILL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF THE 9TH EDITION OF THE INTERNATIONAL BUILDING CODE AND THE REQUIREMENTS OF NFPA 13R (2013 EDITION). THE SPRINKLER CONTRACTOR SHALL FOLLOW THE LATEST REQUIREMENTS OF NFPA 13R (2013 EDITION), MASSACHUSETTS STATE BUILDING CODE AND THE SALEM FIRE DEPARTMENT REQUIREMENTS. THIS SYSTEM WILL BE SUPPLIED BY A NEW 4" FIRE SERVICE, TAPPED OFF THE EXISTING WATER MAIN ON SOUTH MASON STREET. THE 4" SERVICE SHALL BE DESIGNED, INSTALLED, FLUSHED AND TESTED IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA 24 BY A LICENSED UNDERGROUND CONTRACTOR AND WILL ENTER THE HEATED UTILITY ROOM AS INDICATED ON THIS DRAWING (DESIGNED BY OTHERS) THE SPRINKLER CONTRACTOR WILL PROVIDE A 4" VIC-FLANGE, 4" BACKFLOW PREVENTER AND 4" MANIFOLD AS INDICATED ON THIS DRAWING. A 2" STRAIGHT -PIPE RISER WILL SUPPLY THE RESIDENTIAL SPRINKLER PROTECTION (SEE DETAIL THIS SHEET) THE SYSTEM HAS BEEN HYDRAULICALLY CALCULATED IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA 13R, INCLUDING THE FOUR HYDRAULICALLY MOST DEMANDING HEADS IN A SINGLE COMPARTMENT BASED ON THE REQUIREMENTS OF THE SPECIFIC SPRINKLER HEAD AND THE SPACING USED IN THIS DESIGN (16'x16' REQUIRING A MINIMUM OF 16 GPM @ 7.6 PSI OR THE MINIMUM PRESSURE REQUIRED TO MEET 0.10 GPM/SF OVER THE ACTUAL COVERAGE AREA). REMOTE AREAS, DENSITIES AND HOSE STREAM ALLOWANCES ARE INDICATED ON THIS DRAWING. SYSTEM DEMANDS HAVE BEEN COMPARED TO HYDRANT FLOW DATA PERFORMED ON THE WATER MAIN IN SOUTH MASON STREET. COPIES OF THE CALCULATIONS HAVE BEEN SUBMITTED WITH THESE DRAWINGS TO THE SALEM FIRE DEPARTMENT AND BUILDING DEPARTMENT FOR REVIEW. INSTALLATION NOTES: ALL WORK SHALL BE PERFORMED BY A MASSACHUSETTS LICENSED SPRINKLER CONTRACTOR. THE SPRINKLER CONTRACTOR SHALL FOLLOW THE LATEST REQUIREMENTS OF NFPA 13R (2013 EDITION), MASSACHUSETTS STATE BUILDING CODE (9TH EDITION) AND THE SALEM FIRE DEPARTMENT. THE ARCHITECTURAL BACKGROUND OF BUILDING MAY DIFFER SLIGHTLY FROM ACTUAL LAYOUT. DRAWINGS ARE NOT INTENDED TO SHOW ALL OFFSETS AND PIPING ELEVATION CHANGES. CONTRACTOR SHALL FIELD VERIFY ALL MEASUREMENTS PRIOR TO FABRICATION. CONTRACTOR SHALL HYDROSTATICALLY TEST ALL SPRINKLER PIPING AT 200 PSI FOR 2 HOURS AND IS RESPONSIBLE FOR THE COMPLETION OF ALL ABOVE GROUND TEST CERTIFICATES, SUPPLIED TO THE OWNER. ALL PIPING SHALL BE UL LISTED CPVC SPRINKLER PIPING AND SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA 13 (2013 EDITION) AND ALL MANUFACTURERS INSTALLATION RECOMMENDATIONS. SPRINKLER CONTRACTOR SHALL PROVIDE PROTECTIVE PLATES WHERE CPVC PIPING IS RUN THROUGH STUDS TO PREVENT PUNCTURING OF THE SPRINKLER PIPING DURING DRYWALL INSTALLATION AS REQUIRED BY NFPA STANDARDS. ALL SPRINKLER HEADS SHALL BE RESIDENTIAL PENDENT AND SIDEWALL HEADS AND SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S REQUIREMENTS AND THE REQUIREMENTS OF NFPA 13R (2013 EDITION). THE BUILDING OWNER IS RESPONSIBLE FOR MAINTAINING THIS SPRINKLER SYSTEM IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA 25, INCLUDING THE PROVISION OF HEAT IN ALL AREAS CONTAINING SPRINKLER PIPING AND HEADS TO PREVENT PIPE FROM FREEZING. JFP SOLUTIONS, INC. AND THE ENGINEER OF RECORD TAKE NO RESPONSIBILITY FOR ANY DAMAGES CAUSED BY FREEZE UPS. 2" SYSTEM FEED 2" STRAIGHT -PIPE RISER WITH PRESSURE GAUGE, FLOW SWITCH AND I " COMBINATION TEST S DRAIN 2%2"AMES C200 BACKFLOW PREVENTER WITH MONITORED BUTTERFLY VALVES 4x2%2" VIC-FLANGE 2" GROOVED CHECK BALL DRIP SPARE HEAD BOX O 241 GROOVED TEE WITH CAP (FOR FORWARD FLOW TESTING OF BACKFLOW) 4.9 Z 0 (V M 4" SERVICE (INSTALLED, FLUSHED, TESTED $ CUT TO HEIGHT, BY OTHERS) RISER DETAIL SCALE: NOT TO SCALE ELECTRIC BELL WITH BACKER -BOX (WIRED BY OTHERS) 4" PVC PIPE WITH TWO (2) FEMALE ADAPTERS GLUED TO EACH END AND THREADED PLUGS INTO ADAPTERS. SECURE PIPE TO WALL WITH METAL STRAPS. LABEL TUBE; "SPRINKLER DRAWINGS" SINGLE -INLET 2-1/2" FDC CONNECTION (CONFIRM AND MOUNT PER FD REQUIREMENTS) I " x 2'-0 GALVI (THD BY THD) THROUGH WALL WITH 45° EL AND WALL PLATE Seal the clearance space around the sprinkler barrel to avoid leakage of air into the protected area and consequent formation of condensate around -the sprinkler frame, which could Inhibit oper- ation or cause premature operation. Refer to Figure 10 below. If humidity and temperature differential causes corbdensation on the exposed dry sprinkler barrel, consider wrapping the exposed barrel with Insulation, foam Insulating tape, or equivalent. Install 1 inch NPT threaded end of dry sidewall sprinkler Into the 1 inch NPT outlet of a malleable iron tee fitting per ANSI B 16,3 (Class 150) or cast Iron threaded tee Fitting per ANSI 16.4 (Class 125) only. Minimum watt opening: diameter; L-3/4' (44,5 nn) Maximum wall opening diameter: 2-1/4' (57 rim). Ambient Tenperutwe Barrel Ambient 'Temperature 40TF/4•C1507irci60•F/i6•C aF P. otected h•ea at � Discharge (me of the Sprinkler Exposed Hki✓w.r+ Barrel Lengtheee Face of the Tee to the dater Surfaca of the Wall In. free) In (n) in. On) 40'F ;4•c: 0 0 0 3o•F (-1`C) 0 0 0 2o•F (-7'C) 4 (low) 0 0 KIT (-12'C) $ (21/3) 1 (25.4) 0 0'F (-WC) 12 (305) 3 (76) 0 1 (25.4)' -10'F (-23'C) 14 (356) 4 (102) -20'f (-29'C)14 (356) 6 (152) 3 (76) -30'f (-34'C) 16 (406) 8 (203) 4 (l02) -40"F (-4WD 18 (457) 8 (203) 4 c102) -5o.4" (-46'C) 20 (508)10 (254) 6 (152) 6 (152) -60•f (-51•C) 20 Mar 10 (254) 13/16' Cewing (20.6 me) 4' (102 rn) MlrtIrnn 6' (152 nn) hhxInum (Protected Area) Cuter Surface of the Vail 1 /8' (15.9 ram) 3-1/16' (77,8 mm) (38.1 mm) diameter. Sleeve finish matches escutcheon finish Up to 2' (50.8 mr+) of adjustment Is available. 5-1/4' (133.4 rim) maximum NOTE. To locate the Deflector at deflector at the Moadlnun Distance maxbqum distance from from VGLI the wall, with no adjustment avaaable. order the standard dry horizontal side - wall sprinkler 1' longer than the 'A' dimension. 3-1/4' (82,6 elm) NOTE; To locate the deflector at the einimun distance from the wall, with no adjustment available, order the standard dry horizontal side - wall sprinkler 1' shorter than the 'A' dimension Deflector at m inum Distance Fran Vail *May be allowed up to 18' (457 mm) for certain FM installations. Refer -to the appropriate Installation standards, Including NFPA 13 and/or FM Loss Prevention Data Sheet 2-0. wwThe protected area refers to the area below the ceiling, The ambient temperature Is the temperature at the discharge end of the sprinkler.. For protected area temperatures that occur between the values listed, use the next cooler temperature, wwwThe minimum required) barrel length is not the sane as the 'A' dimension. Refer to Figures 3, 5, and 7 for the 'A' dimension. Exposed minimum barrel lengths are Inclusive up to 30 mph wind velocities. WOOD JOIST CONSTRUCTION RESIDENTIAL CONCEALED SPRINKLER HEAD (K=4.9) TYPICAL MAINTAIN NFPA 13R OBSTRUCTION CRITERIA (TYPICAL) CPVC MAIN LOCATED WITHIN HVAC SOFFIT FEEDING BRANCHLINES LOCATED WITHIN JOIST CHANNELS (TYPICAL) GYPSUM BOARD CEILING ON WOOD STRAPPING TYPICAL RESIDENTIAL PENDENT SPRINKLER INSTALLATION NOT TO SCALE L CO a 12 REF Z . UP UP DECK + 13'-0" AHO 7407 UNCOV RED I: �, K. 3'-0 IF.� E CV 2-412 1-0 2 Tee with same :outlet size as. s. I_'r i n k. I e r t h rea d _size. -;e ' Irril-Ic)rt.arlt Installation Information", Later rl this; i_li:'i:_.i_irrierit UP Fo 4-312 JPVIT #112 REF PROVIDE DRY-SIDEWALL HEADS BELOW COMBUSTIBLE OVERHANGS (TYPICAL) NOTE: SPRINKLER CONTRACTOR TAKES FULL RESPONSIBILITY FOR PROPER LENGTH SELECTION AND PROPER INSTALLATION OF ALL DRY-SIDEWALL HEADS IN ACCORDANCE WITH THE MANUFACTURER'S LISTING (Min. 1 .;a') Recessed UP DECK + 13'-O" C / 1 FA:" 2N:' UP Dia. UP 4-312 Ln 0 A UP REF NOTE: SPRINKLER HEAD LOCATIONS HAVE NOT BEEN COORDINATED WITH CEILING -MOUNTED FIXTURES OR OTHER POTENTIAL OBSTRUCTIONS. ACTUAL LOCATIONS OF HEADS SHALL BE FIELD -COORDINATED IN ACCORDANCE WITH THE OBSTRUCTION RULE OF NFPA 13 (2013 EDITION). r%/I•Al•I///////////////O�//�//d'//d' r o 1-0' 2 0 UNCOVERED GROUND LEVEL SPRINKLER LAYOUT SCALE: %4" = 1'-0" /0 3-7 UP 2-612 5-0 A nao 0 066 > C 7-8 6-4 A UNIT #6 I Ir N i 6-2V UNI #5 z 0 6-212 - 7-912 2 1 4/4 2-0 - 9-0 112 --o 3-1' 2 12 2-0 CO UNCOVERED �rrnll" -1 1 2 s-0 err FREEZE PR❑TECTI❑N THE BUILDING OWNER IS RESPONSIBLE FOR PROVIDING HEAT IN ALL AREAS CONTAINING SPRINKLER PIPING AND HEADS TO PREVENT PIPE FROM FREEZING. ANY AREAS THAT RAISE CONCERN WITH REGARD TO FREEZING POTENTIAL SHALL BE BROUGHT TO THE ENGINEER'S ATTENTION, IN WRITING, PRIOR TO INSTALLATION. JFP SOLUTIONS, INC. AND THE ENGINEER OF RECORD TAKE NO RESPONSIBILITY FOR DAMAGES CAUSED BY FREEZE -UPS OF THE SPRINKLER SYSTEM. O/ e, a`: -al �r 7 0 0 3-1012 UNIT #4 I a CO 4112. 14 IA o.° REF L 00 REF 0 O _-. Z PROVIDE 4" STORZ CONNECTION (TYPE AND FINAL LOCATION TO BE VERIFIED WITH SALEM FIRE DEPARTMENT PRIOR TO INSTALLATION) 4" FIRE SERVICE (DESIGNED, INSTALLED, FLUSHED AND TESTED PER NFPA 24, BY OTHERS) 2 %2" BACKFLOW PREVENTER, 2" STRAIGHT -PIPE RESIDENTIAL RISER AND FDC FEED (SEE DETAIL, THIS SHEET) UNCOVERED ENTRYWAY • UP UNCOVERWO ENTRYWAY UP UP PROVIDE BULK RESIDENTIAL 2" CPVC MAIN RUNNING THROUGH SOFFIT ON GROUND LEVEL (FIELD -VERIFY LOCATION) Source Information Date of Flow Test / Info : 3/6/2018 Location of flow test data : END OF BUFFUM ST. EXT. Source of flow test data : JFP SOLUTIONS Source Data Points Pressure Flow 80.00 0.00 60.00 750.00 Pump Data Points Pressure Flow O s E W DESIGNED BY: REVISIONS HEAD BLOCK JFP SOLUTIONS, INC. 1;1 FIRE PROTECTION CONSULTING SERVICES P.O. Box 1234 Lynnfield, Massachusetts 01940 Telephone: (781) 389-7999 E-Mail: TDJFP 1 @Yahoo. Com DATE DESCRIPTION BY SYM CNT POSITION FINISH TEMP NPT MFG. -.,, 97 RES PENDENT WHITE 155 5.80 1/2" REL. No 5 DRY SIDEWALL WHITE 155 5.60 1/2" REL. 37 RES. SIDEWALL BRASS 155 5.80 1/2" REL. CPVC SPRINKLER PIPING STEEL SPRINKLER PIPING - SPRINKLER CONTRACTOR VILLAGE FIRE PROTECTIO 86 MILFORD STREET MILFORD, NH 03055 (603) 672-6267 \EW AUTOMATIC NFPA 13. SPRINKLER SYSTEM BUILD-I\G 4 9 SOUTH MASON STREET SALEM, MASSACHUSETTS 03055 PROJECT ADDRESS SPRINKLER SYSTEM PERMIT SET PERMIT NO. CONTRACT NO. 380-008 APPROVAL SALEM FD DRAWN BY T. JENKINS SCALE 1 /4"=1'-0" DATE 10/15/2018 REVISED FP1of2 o z 0 . • 1 N OF Mqs JASON M.C. KAHAN FIRE PROTECTION o. 4838 /STER m PLOTTED