Loading...
FP Narrative 70 Boston 13 Goodhue Street 10-02-18 1076 Washington Street, Hanover, MA 02339•Tel 781.826.4144•Fax 781.924.5792•www.wbaengineers.com 161 Exchange Street, 3rd Floor, Pawtucket, RI 02860 WB&A Wozny/Barbar & Associates, Inc. C O N S U L T I N G E N G I N E E R S FIRE PROTECTION NARRATIVE LRI PROPERTIES LLC 70 BOSTON STREET & 13 GOODHUE STREET SALEM, MA. OCTOBER 02, 2018 BASIS (METHODOLOGY) OF DESIGN Section 1 – Residential Building Description 1. Building “Use” Group: R-2 (residential), S-2 (garage) 2. Total square footage of Building: 169,993 sq. ft. 3. Building height: 42’-3½” 4. Number of floors above grade: 4 5. Number of floors below grade: 0 6. Square footage per floor: Garage – 17,231 sq. ft. First Floor –17,772 sq. ft. Second Floor- 17,598 sq. ft. Third Floor- 17,392 sq. ft. 7. Type(s) of occupancies (hazards): Light Hazard – residential, Ordinary Hazard I – garage, storage, mechanical rooms 8. Type(s) of construction: IB & VB 9. Hazardous material usage and storage: Non 10. Height storage of commodities within a building stored over 12 ft. N/A 11. Site access arrangement See civil drawings Section 2 – Applicable Laws and Governing Codes 1. Building Code: Massachusetts State Building Code, 780 CMR, 8th Edition 2. Referenced Standards: NFPA 13 - 2013, NFPA 14-2013, NFPA 25 – 2011, NFPA 72 - 2010, 3. Applicable Sections of M.G.L., Chapter 148, “Fire Protection.” 4. Applicable Sections of 527 CMR “Fire Prevention Regulations.” 5. Applicable Specialized Codes (plumbing, electrical and architectural access.) 6. Applicable Federal Laws such as OSHA, ADA, etc. Section 3 – Design Responsibility 1. Wozny/Barbar and Associates (WB&A) is providing a design and design criteria including specifications. Hydraulic calculations are required and have been provided. The design has been based on Fire Protection Systems, Chapter 9, Guidelines for the Preparation of Narrative Reports. 2. Fire Protection drawings will indicate sprinklers in the most remote areas only, as per “guidelines for the Preparation of the Narrative Reports 780 CMR-903.1.1”. WB&A Associates is providing a partial design and the design criteria which will be used by the installing contractor who will finalizes the system layout, as per Guidelines for the preparation of Fire Protection System Narrative Reports. WB&A will review sprinkler contractor shop drawings for conformance with the design documents and NFPA requirements. In addition, WB&A will provide periodic inspection during construction. 3. The Professional Fire Protection Engineer of record responsible for the fire suppression will be Grzegorz B. Wozny, PE, Massachusetts No. 39170, and the electrical engineer of record responsible for fire alarm system will be Salim Afsar, PE, Massachusetts No.39083. Section 4 – Fire Protection System to be Installed Page 2 - 2 - 1. Sprinkler System a. The building will be provided with a 6” fire service and 6” double check valve assembly. b. The fire service will be located in the garage in the sprinkler room. c. Fire department inlet connection will be installed within 100 feet from a fire hydrant. d. Two (2) combination standpipe / sprinkler riser will be located in each staircase. e. Each floor will be a dedicated sprinkler zone. Floor control valve assemblies will be located in the staircases. f. Parking garage, located in the basement, will be a dedicated dry pipe sprinkler zone with upright sprinklers. Dry pipe valve will be located at the garage level in the sprinkler room. g. The sprinkler and standpipe system design will be based on NFPA 1302-13and NFPA 14-2013requirements. h. Spaces above ceiling will be provided with listed sprinklers. The spacing of those sprinklers will be 12’x12’ maximum. i. Residential sprinklers will be provided inside apartments and quick response sprinklers outside apartments. j. The hydrant flow test was performed on December 7, 2016 by Williams Sparage, the results are as follow: • Static pressure - 72 psi • Residual pressure - 70 psi • Flow - 1106 gpm 2. Fire Alarm System a. The building shall include a complete independent addressable fire detection and alarm system with complete audio / visual evacuation signaling. Equipment shall be UL listed and shall meet the requirements of the local fire department and State Fire Marshal. 1) Alarm notification shall be via ADA - compliant audio and visual signaling devices, located in common spaces, corridors and public toilets. 2) Low frequency 520HZ mini horns shall be installed in bedrooms and the living rooms of the dwelling units. 3) Smoke detectors spaced approximately 30’ apart or per manufacturers recommended distances. Smoke detectors shall be located in all common areas, electric rooms and storage rooms. Remote indicators shall be installed above all locked doors with detectors inside the room. 4) Pull stations shall be located at the egress to each floor and at all exits from the building. 5) Audible alarm signals shall sound at march time cadence (120 ppm). The system shall also be capable of temporal (NFPA 72 - 2.2.2.2). 6) Flash an alarm LED and sound an audible signal at the FACP. Upon acknowledgment, the alarm LED shall light steadily and the audible shall silence. Subsequent alarms shall re-initiate this sequence. 7) Visually indicate the alarm initiating device, type and location via the alpha- numeric display located at the FACP. 8) Flow, tamper and pressure switches will be wired to the building fire alarm control panel. 9) A knox / key box shall be installed at all entrances to the building. 10) The fire alarm annunciator panel will be located at the entry door. A rotating beacon shall be located on the exterior of the building. The FACP shall be connected to a Master Box and listed Central Station for transmission of alarms to the Fire Department. 11) 120 volt smoke detectors shall be provided in bedrooms and outside each bedroom. Detectors shall be equipped with battery backup. 12) 120 volt carbon monoxide detectors shall be provided in outside each bedroom. Detectors shall be equipped with battery backup. 13) An auto dialer will be provided. Page 3 - 3 - Section 5 – Sequence of Operation 1. Sprinkler System a. Wet System – When a single heat activated sprinkler fuses and discharges water, flow switch at a floor control valve assembly is actuated and sends an alarm signal to the main fire alarm control panel. a. Dry System – When a single heat activated sprinkler fuses and discharges water, pressure switch at a dry pipe valve is actuated and sends an alarm signal to the main fire alarm control panel. 2. Fire Alarm System a. The operation of a dual action (lift and pull) manual station or activation of any automatic alarm initiating device (system smoke, heat, waterflow, and pressure switch) shall automatically: 1) Initiate the transmission of an alarm to the Municipal Fire Station and a listed Central Station for transmission of alarms to the Fire Department. 2) Audible alarm signals shall sound at march time cadence (120 ppm). The system shall also be capable of temporal (NFPA 72 - 2.2.2.2). 3) Flash all visual signals throughout the building in a synchronized manner. Turn on the exterior beacon at the primary entrance. 4) Flash an alarm LED and sound an audible signal at the FACP. Upon acknowledgment, the alarm LED shall light steadily and the audible shall silence. Subsequent alarms shall re-initiate this sequence. 5) Visually indicate the alarm initiating device, type and location via the alpha- numeric display located at the FACP and at the remote control annunciator. 6) Tampering with any of the supervised control valves shall flash a supervised signal at the Fire Alarm Control Panel. Section 6 – Testing Criteria 1. Sprinkler System, a. Notify the authority having jurisdiction and Owner’s representative of the time and date of the test. b. Perform all required acceptance test as required by NFPA 13 and NFPA 25. c. Complete and sign the appropriate Contractor’s material and test Certificate(s). 2. Fire Alarm System a. The system shall be fully tested by a UL certified testing company in accordance with UL guidelines and NFPA standards. Each and every device shall be tested. A copy of NFPA Record of Completion documentation to Fire Marshall prior to the fire department walk- through. At a minimum perform the following tests: 1) Before energizing the cables and wires, check for correct connections and test for short circuits, ground faults, continuity, and insulation. 2) Close each sprinkler system flow valve and verify proper supervisory alarm at the FACP. 3) Verify activation of all waterflow and pressure switches. 4) Open initiating device circuits and verify that the trouble signal actuates. 5) Open and short signaling line circuits and verify that the trouble signal actuates. 6) Open and short notification appliance circuits and verify that trouble signal actuates. 7) Ground all circuits and verify response of trouble signals. 8) Check presence and audibility of tone at all alarm notification devices. 9) Check installation, supervision, and operation of all intelligent smoke detectors using the walk test. 10) Each of the alarm conditions that the system is required to detect should be introduced on the system. Verify the proper receipt and the proper processing of the signal at the FACP and the correct activation of the control points. Page 4 - 4 - 11) When the system is equipped with optional features, the manufacturer’s manual shall be consulted to determine the proper testing procedures. This is intended to address such items as verifying controls performed by individually addressed or grouped devices, sensitivity monitoring, verification functionality and similar. b. A copy of the final test report and UL certification shall be submitted indicating proper functioning of the system and conformance to the specifications. The test shall be performed by UL certified and factory - trained qualified technicians. Each and every device shall be tested, and standalone operation of remote panels shall be verified. UL certification shall be performed by the same company that will hold and execute the Test and Inspection contract. Equipment and Tools During the pre- and final acceptance testing of the systems, the installing contractor will provide the following equipment at the site. 1. Sprinkler system testing notification announcements to the occupants of the building; 2. All devices within limits of construction shall be tested in strict accordance with manufacturer’s instructions: (i.e. all manual pull stations will be activated and reset with key; all smoke detectors will be tested with magnets; all A/V units will be activated and monitored for audible and visual notification; etc.); 3. Construction Documents and approved Shop Drawings or As-Built Drawings; 4. Approved narrative description (sequence of operation); Approval Requirements The following approvals are necessary prior to the start of work: 1. Salem Fire Department, Permit for Fire Protection System. This permit is for installation of the fire alarm system and automatic sprinkler system. 2. A verbal approval at time of testing followed by a written documentation shall be issued indicating all Code requirements have been satisfied. 3. The contractor, in conjunction with the alarm manufacturer, shall rectify all portions of the system that fail acceptance testing. 4. The contractor and the alarm manufacturer will issue final inspection reports along with Certificate of Completion verifying all systems affected by construction are in compliance. 5. All documentation for personnel contact regarding emergency notification shall be submitted by the owner’s representative. J:\16148 River Rock\Narrative\FP Narrative 70 Boston & 13 Goodhue Street 10-02-2018.doc