100617-CFP640-FP-5-River Rock TownhouseHydraulic Information Remote Area 1- Unit 72 OCCUPANCY CLASSIFICATION Residential DENSITY 0.10ogpm/ft2 for 900.00ft2 (Actual 451.65ft2) TOTAL HOSE STREAMS 100.00 TOTAL HEADS FLOWING 4 K-FACTOR 5.6 TOTAL WATER REQUIRED 199.51 TOTAL PRESSURE REQUIRED 62.426 BASE of RISER (gpm) 99.51 BASE of RISER (psi) 53.797 SAFETY MARGIN (psi) +9.489 (13.2%) G.C.TO PROVIDE SOFFIT FOR SPRINKLER PIPING (TYP. FOR ALL UNITS) (G� i J 1-1/4" FROM BELOW BALCONY 1 -F51 Oe MASTER BEDROOM 91-10" X 14'-6" TH UNIT # 1" FROM BELOW UNIT #72 BATH (18 1-1/2" FROM BELOW STOR. FS1 Oa LIN. 1" FROM BELOW Hydraulic Information Remote Area 1- Unit 74 3rd OCCUPANCY CLASSIFICATION Residential DENSITY 0.100gpm/ft2 for 900.00ft2 (Actual 365.75ft2) TOTAL HOSE STREAMS 100.00 TOTAL HEADS FLOWING 4 K-FACTOR 5.6 TOTAL WATER REQUIRED 204.03 TOTAL PRESSURE REQUIRED 64.820 BASE of RISER (gpm) 104.03 BASE of RISER (psi) 56.468 SAFETY MARGIN (psi) +7.092 (9.9%) 81-0 TH UNIT #74 FS1 TH UNIT #2 - Co L 6'-11% (19 J 1-1/2" F OM BELOW TH NIT #3 1" FROM BELOW 8'-0 MASTER BEDROOM 16-0" X 14'-5" TH UNIT #76 !20 O , 8'-0 MASTER BEDROOM 16-0" X 14'-5" TH UNIT #78 1 • 5'-9 DN 1-1/2" FROM BELOW li TH UNIT #4 `i 8 Tr% 116 1'-4 A� CL. ti BATH /r TUB STOR. T 21 8'-0 MASTER BEDROOM 16-0" X 14'-5" TH UNIT #80 1/2" FROM BELOW iUH UNI #5 BATH TUB 1" FROM BELOW 1" FROM BELOW 21 1-1/4" FROM BELOW/ BALCONY MASTER BEDROOM 11-10" X 14'-6" TH UNIT #82 TH UNIT #6 8'-0 1" FROM BELOW (47N) O 7'-0„ CLG. HEIGHT 5'-0" CLG. HEIGH CLG.I 7'-0" CLG. HEIGH 47) /BBi (G ) H INSTALLATION INFORMATION MAXIMUM DISTANCE BETWEEN HANGERS o < 2 9 - < 2 - o ti 2 O - 2 v 0 '^ ti -1 N 2 f., o V1 el O WI el 0 (V el 0 o ri TN 0 0 ? 0 - it u1 (- m (NI-+ - O 0 0 TN N N rl O C0 0 0 0 - n CV 0 C o 0 O e ., N - N - O - co - o 0 o O ti .Ni w .b o L0 m 2 2 0 tn NOMINAL PIPE SIZE Un.) STEEL PIPE EXCEPT THREADED THREADED LIGHTWAI L COPPER TUBE > a 0 Contractor: DiFava Fire Protection 4 Sheridan Road Wilmington, MA 01887 Project: River Rock Residences Townhouses 72-82 Boston Street Salem, MA THIRD FLOOR Design Project # CFP640 1 .5 3 I 1 2 4 SCALE 1/4"=1'-0" Drawn by: REC & RPG Date: 10/5/2017 Approval by: Fire Dept. SHEET NUMBER FP-5 OF5 NOTE: USE OF THESE PLANS BY THE INSTALLING CONTRACTOR SHALL INDICATE ACCEPTANCE OF ALL THE INFORMATION PROVIDED ON THESE PLANS AND SHALL TRANSFER FINAL RESPONSIBILITY OF THE CORRECTNESS OF THE SYSTEM TO THE INSTALLING CONTRACTOR. ANY DESIGN ERRORS SHALL BE CORRECTED AT THE CONTRACTOR'S EXPENSE. NOTE: ADDITIONAL SPRINKLER HEADS OVER AND ABOVE THOSE SPECIFICALLY NOTED ON THESE DRAWINGS MAYBE REQUIRED DEPENDING ON THE REQUIRED ROUTING AROUND TRUSSES, HVAC DUCTWORK, HOODS AND OTHER SIMILAR OBSTRUCTIONS. FIELD VERIFY EXISTING CONDITIONS DURING CONSTRUCTION AND PROVIDE ANY AND ALL ADDITIONAL HEADS AS REQUIRED FOR FULL COVERAGE AND A COMPLETE, CODE COMPLIANT SYSTEM.