Loading...
100617-CFP640-FP-2-River Rock TownhouseHydraulic Information Remote Area 4 - Storage OCCUPANCY CLASSIFICATION Ordinary Group II DENSITY 0.200gpm/ft2 for 900.00ft2 (Actual 904.40ft2) TOTAL HOSE STREAMS 250.00 TOTAL HEADS FLOWING 21 K-FACTOR 5.6 TOTAL WATER REQUIRED 593.05 TOTAL PRESSURE REQUIRED 60.217 BASE of RISER (gpm) 343.05 BASE of RISER (psi) 51.156 SAFETY MARGIN (psi) +11.152 (15.6%) NFPA 13 2007, 2010, & 2013 11.2.3.2.3 QUICK RESPONSE AREA REDUCTION * WET SYSTEM * LH or OH * 20 FT MAX CEILING HT Y=-3*CLG/2+55 FOR CLG <10 FT, Y = 40% REDUCTION FOR CLG >20 FT, Y = 0% REDUCTION THIS CLG = <10 FT = 40%REDUCTION 1,500 SQFT - 40%= 900 SQFT SIDEWALL SPRINKLER UNDER GARAGE DOOR(TYP.) 1' rMl 71. 2 1/2 " WET SPRINKLER 101-0 1 CAR GARAGE 10'-0 TH UNIT #72 1 6'-10 STORAGE ei ISER UP TYP. ZONE CONTROL ASSEMBLY 2-1/2" BUTTERFLY VALVE 2-1/2" CHECK VALVE 2-1/2" MANIFOLD Hydraulic Information Remote Area 5 - Garage OCCUPANCY CLASSIFICATION Ordinary Group I DENSITY 0.150gpm/ft2 for 1950.00ft2 (Actual 1982.13ft2) TOTAL HOSE STREAMS 250.00 TOTAL HEADS FLOWING 22 K-FACTOR 5.6 TOTAL WATER REQUIRED 706.54 TOTAL PRESSURE REQUIRED 50.016 BASE of RISER (gpm) 456.54 BASE of RISER (psi) 35.894 SAFETY MARGIN (psi) +21.111 (29.7%) 11.2.3.2.5* Dry Pipe and Double Interlock Preaction Systems. For dry pipe systems and double interlock preaction systems, the area of sprinkler operation shall be increased by 30 percent without revising the density. TEST/DRAIN AS PER NFPA 13-2013, FIGURE 8.16.2.5.3.5. PROVIDE LISTED HEAT TRACING FOR PIPE BY TYCO THERMAL CONTROLS, 8XL2-CT. INCLUDE HEATING CABLE, 1" INSULATION, 0910 CONTROLLER 9'/: 3'-1 H (18 /2'-g'�z 101-0 2'-7 1 CAR GARAGE 101-0 TH UNIT #74 0 3'-534 ri rl ri rl 1 a. -5'% 1 i0 3 1'-5 101-0 11111 . s 1 I CAR ARAGE 3'-0 10'-0 a NIT #76 26I 3'-1 (406) \ \ 10 /} 1 C` 1 e-`2'-41IT 4 v 1 1'/z if ti'1% 1'f: N 9'-0 2'-7N q r 2'-3 1'-0 ti g ;r, , g 10'-0 MI NM MI 1 CAR '• 0 GARAGE 3 2 V2 — .4> , 2 [.I 1 r.1 3'-8% 3 2'34 15'-11'3 Supply Flow Test Data Date of Test 12/7/2016 Location Boston Street Static Pressure 72.000 Residual Pressure: 70.000 Flow 1106.00 Hydr ant Elevation Level with BOR 3'-1 3 21 101-0 so a • 1 CAR GARAGE 3 7'-3 1 3'-8% 3 2'-9 IIT#80 STORAGE 22) N 1000' ESTIMATED 3'-1 101-0 1 GAR GARAGE STORAGE 23 1'-2 0'- 2'/z 4°-0 23 SPRINKLER ROOM r♦ PROVIDE LISTED HEAT TRACING FOR PIPE BY TYCO THERMAL CONTROLS, 8XL2-CT. INCLUDE HEATING CABLE, 1" INSULATION, 0910 CONTROLLER 2 MAIN DRAIN. PIPE TO EXTERIOR. LOW VOLTAGE ELECTRIC BELL /FIRE DEPARTMENT INLET CONNECTION. LOCATE PER LOCAL FIRE DEPARTMENT REQUIREMENTS. SYSTEM RISER. SEE DETAIL. 4" FIRE SERVICE 21/2 " WET SPRINKLER RISER UP TYP. ZONE CONTROL ASSEMBLY 2-1/2" BUTTERFLY VALVE 2-1/2" CHECK VALVE 2-1/2" MANIFOLD 20 W 0 a INSTALLATION INFORMATION MAXIMUM DISTANCE BETWEEN HANGERS 0 el < 2 0 - < z 74 o Lh r, �. z o � .- -- z e c - < z , .-1 < z 0 0 0 0 TN 9 9 9 9 .-1 N Ln 1-1- N ti 0 0 0 0 ry - N ., N ri c ro Q - - Q .,, - 9 (N _ c 0 - 0 a 0 0 0 e - .-1 N N N - o A — 0 0 o c ti N ry a < G o .o M Z Z m LO NOMINAL PIPE SIZE (in.) STEEL PIPE EXCEPT THREADED 0 -J COPPER TUBE 0>. z > = C7 H u Contractor: DiFava Fire Protection 4 Sheridan Road Wilmington, MA 01887 Project: River Rock Residences Townhouses 72-82 Boston Street Salem, MA GARAGE LEVEL Design Project # CFP640 1 .5 0 I I I 2 4 SCALE 1/4"=11-0" Drawn by: REC & RPG Date: 10/5/2017 Approval by: Fire Dept. SHEET NUMBER FP-2 OF 5 NOTE: USE OF THESE PLANS BY THE INSTALLING CONTRACTOR SHALL INDICATE ACCEPTANCE OF ALL THE INFORMATION PROVIDED ON THESE PLANS AND SHALL TRANSFER FINAL RESPONSIBILITY OF THE CORRECTNESS OF THE SYSTEM TO THE INSTALLING CONTRACTOR. ANY DESIGN ERRORS SHALL BE CORRECTED AT THE CONTRACTOR'S EXPENSE. NOTE: ADDIT IONAL SPRINKLER HEADS OVER AND ABOVE THOSE SPECIFICALLY NOTED ON THESE DRAWINGS MAYBE REQUIRED DEPENDING ON THE REQUIRED ROUTING AROUND TRUSSES, HVAC DUCTWORK, HOODS AND OTHER SIMILAR OBSTRUCTIONS. FIELD VERIFY EXISTING CONDITIONS DURING CONSTRUCTION AND PROVIDE ANY AND ALL ADDITIONAL HEADS AS REQUIRED FOR FULL COVERAGE AND A COMPLETE, CODE COMPLIANT SYSTEM.