071420-CFP913-Halstead-3-FP-2 - stamped Hydraulic Information Remote Area 1-Bedroom OCCUPANCY CLASSIFICATION NFPA 13D Table 8.3.2.5(c) Temperature Ratings of Sprinklers in Specified Residential Areas DENSITY(gpm/ft') 0.05 for 400.00ft'(Actual 227.52ft2) TOTAL HOSE STREAMS 100.00 Minimum Distance from Minimum Distance from TOTAL HEADS FLOWING 2 Edge of Source to Edge of Source to K-FACTOR 4.9 Ordinary-Temperature Intermediate-Temperature TOTAL WATER REQUIRED 134.44 Sprinkler Sprinkler TOTAL PRESSURE REQUIRED 60.566 BASE of RISER(gpm) 34.44 Heat Source in. mm in. mm BASE of RISER(psi) 52.250 Side of open or recessed fireplace 36 914 12 305 SAFETY MARGIN(psi) +21.048(25.8%) Front of recessed fireplace 60 1524 36 914 Z Coal-or wood-burning stove 42 1067 12 305 0 Kitchen range 18 457 9 229 Wall oven 18 457 9 229 a 5/A2.00 � �B ooM a/a2.00 " - Hot air flues 18 457 9 229 A a/az.00 L r- 5/A2.00 Uninsulated heat ducts 18 457 9 229 w TY E 3 BEDROOM-2 4 A2.00 �' Uninsulated hot water pipes 12 305 6 152 LU \ / Side of ceiling-or wall-mounted 24 607 12 305 - BAtHRo_I- o rA = -� hot air diffusers � Jl _I / oo �_� Front of wall-mounted hot air 36 914 18 457 N N 4/A2.UU a/A2.UU 4/A2.OU N N } diffusers tatww w 6-6 7-4aa W/D N N } N N N N - N Hot water heater or furnace 6 152 3 76 Q W/p �. f N N - ^y< T ? Light fixture: W oin � ► T '� '\ /D 0 W-250 W 6 152 3 76 yc �• r ;� _�; �. , ;� ;� � C� 250 W-499 W 12 305 6 152 � o C r T �CAW.LC. r O O VC, _ a a N �i -, I-1 ��1 �� 00 o Q Q Table 8.4.9.1(a) Exposed Barrel Lengths for Dry Sprinklers (U.S.Customary Units) 1O z ti z MASTER BATHROOM MASTER Ambient Temperature Exposed Minimum Exposed Barrel Minimum Exposed Barrel Minimum Exposed Barrel z r-i z R I to Discharge End of Sprinkler Length when Exposed to 40"F Length when Exposed to 50"F Length when Exposed to 60"F /102 LINEN BATHROOM �'`� \ �/ N N C N N ("�/ (m.) (m.) (m.) O O O O iD LINEN _ 40 0 0 0 (� M u, � o � 30 O O 0 � o o 9 o " N 11 N u I \ r 20 4 0 0 �- r o) 10 8 1 O N 101 IN.I.C. r r r r a- O 12 3 O Z N o 0 0 0 -10 14 4 1 O W 00 -20 14 6 3 iv o o 3 MASTER -30 16 8 4 Q Q ,c'n A d o 0 /� 5'-4/ -40 18 8 4 _ - BEDROOM W.I.C. -50 20 10 6 Z o 9 9 w � ' c � -60 20 10 6 O 3 � ti o MASTER I W06 / \ LL ti o 9 0 0 BEDROOM - Z I m L Z �V - Z Notes for Installer. a s m z z � * Coordinate sprinklers with ceiling mounted devices in the field. Lighting type S1 o a J SECOND FLOOR , _ W_ locate in kitchens, living rooms and walk in closets is 1.1875" high. Residential w X C� pLL'p SECOND LAYER OF INSULATION Q a W� o J o TO RUN WITH PIPE. sprinkler shall be located minimum 1'-6" from the side of the lighting fixture or as a 2 a W o Q LU z•- ao Q w AFF ABOVE FINISH FLOOR allowed in NFPA 13. In common corridor light type AL1 is 1.22" high. Quick response Z ON W E _; g a INSULATION CLG CEILING �� z O y M H U U ELEV ELEVATION sprinkler shall be located minimum 1 -0 from the side of the lighting fixture or as FF FINISH FLOOR EXISTING PIPE PWM PUBLIC WATER MAIN SPRINKLER SPACING allowed in NFPA 13. Residential sprinklers shall be located minimum 24" from the NEWPIPE NVFLOOR INVERT RESIDENTIAL PENDENTS side of a ceiling mounted diffuser. Quick response sprinklers shall be located HANGER --- NITS NOT TO SCALE NIC NOT IN CONTRACT MAXIMUM 8'-0" FROM ANY WALL minimum 2'-6" from side of supply diffusers. Per NFPA 13 (2013) Table 8.3.2.5(c). 0 RISE OR DROP SPRINKLER PIPE TS TAMPER SWITCH MINIMUM 8'-0" BETWEEN SPRINKLERS BLANKET PIPE TO TY WITHAL O HYDRAULIC NODE MAXIMUM 16'-0" BETWEEN SPRINKLERS CREATE HEAT POCKET \ \ ROOF TRUSS DIN DOWN ,k „ - •� HYDRANT OSY OUTSIDE SCREW AND YOKE VALVE The barrel of dry sprinklers shall extend minimum 6 Into conditioned space. 1".�L BACKFLOW PREVENTER - CEILING FHV FIRE DEPARTMENT HOSE VALVE INTERSTITIAL UPRIGHTS 11 10 BUTTERFLY VALVE AHJ AUTHORITY HAVING JURISDICTION Proper length of dry sprinklers to be determined in the field. Follow NFPA 13 Table —� OS&YVALVE ZCV ZONE CONTROL VALVES MAXIMUM T-0" FROM ANY WALL RISER MANIFOLD FDC FIRE DEPARTMENT CONNECTION MINIMUM T-0" BETWEEN SPRINKLERS 8.4.9.1(a)guidelines. INSULATION DETAIL LOW LIMIT OF WORK MAXIMUM 14'-0" BETWEEN SPRINKLERS +�; POST INDICATOR VALVE NTS PIV POST INDICATOR VALVE ETR EXISTING TO REMAIN LEGEND WFS WATER FLOW SWITCH INSULATION NOTE: ABBREVIATIONS Contractor: 1.)INSULATION SHALL BE CHECKED FOR INTEGRITY DIFava Fire Protection TO INSURE PROPER COVERAGE,FOR FREEZE PROTECTION. of Ma, Inc. 4 Sheridan Road Wilmington, MA 01887 6'-0"x 42"HIGH Project: KNEE WALL,TYR Halstead Salem Station Building #3 � - 72 Flint St 2/A2.00 2/A2.00 67-71 Mason St o4 cc - 2/A2.00 �_°.�= Salem, MA 01970 6'-6 U_ - cc 1 1 �-, 1 1 - 1 1 ,-� 1 1 '-10 1 c��'� 1 5'-10 4 5'-10 5'-10 4 5'-10 5'-10 5'_10 __ ��Iq 1 r 5'-10 Building #i.3 3'-2 3'-2 -5 r 4 FIRST FLOOR d FIRST FLOOR , 2 2 FIRST FLOOR 'JI 1 2/A2.00 1 ti�a 2/A2.00 �ojl ti �3/A2.00 Site Plal?, F �o ti 3'-2 �'-2 3'-2 �'-2 ti0 �� do r �Q - �Q � I � 'T � 'J �Q �Q __ Details, Garage 1 --1 -From Garage 1 M M 1 1 M M 1 1 -1 -From Garage 5'-1 ' 5'-�p'!2 r qq pp'/z % 0'/z �p'/2 %q 0'/z 5'-1 5' p p'/2 CF P Design Project#: 913 �I� DIY \ T�pN \ \ D� IJN- \ \ DN \ �11P a h r ti N r ti DDI1 r 1� ti _p ICI �R �L III IIII{II N / � I i0 in iO iA ^ T C � � I— W ir1 E 1 1 �d o� dg 1 11 1 s SCALE 1/8"=1%0" 5'-10 5'-10 4) 4) r 5'-h0 " 5'11A 4) °� " 5'-1A 10 c 5'-10 5'-10 7'-3% " Drawn by: e WET PIPE SYSTEM Comprehensive Fire Protection I l q r r Minimum Flow and Residual Pressure (2)(3) 603-532-6388 q q v v v 1— s ® ® 00 Maximum Coverage Ordinary Temperature Rating Intermediate Temperature Rating Date: 7/14/2020 �r� 155 F (68 C) 175 F (79 C) Minimum -h Area ('► Deflector to Installation Spacing A royal b Fire Dept. pP Y� p 0 N 10 \ r 3 , - 3' 3 10 ft x ft Flow Pressure Flow Pressure Ceiling Type ft a UP uuP a �;\ / /�\ j\ I, a UP uuP a (m x m) gpm Psi gpm Psi (m) UP UIP UP � I1� (1/min) (bar) (1/min) (bar) O -� r � r 7'-11 ib 00 W 12 x 12 13 7.0 13 7.0 Smooth Q. C / (3,7 x 3,7) (49,2) (0,48) (49,2) (0,48) Ceilings E 4'-4 -341 4' 4'-4 1 r N 4'-4 4'-4 N 1 1 r N 4'-4 } 4'� N 1 — 4'-4 4'- 4'-4 14 x 14 13 7.0 13 7.0 1-1/4 in. to 4 in. Recessed s'-o 7'-6 4� 4' (4,3 x 4,3) (49,2) (0,48) (49,2) (0,48) - - - - - - - - - - - - - - - - - - - - - - - - - - - Beamed using Style 20 a, `O 16 x 16 13 7.0 13 7.0 Ceilings per Escutcheon or 8 x 4.9) (49,2) (0,48) (49,2) (0,48) I NFPA 13D non-recessed - or 13R per NFPA 13D, u, 18 x 18 17 12.0 17 12.0 1-1/4 in. to 13R, or 13 (5,5 x 5,5) (64,3) (0,83) (64,3) (0.83) 1-3/4 in. below 20 x 20 20 16.7 20 16.7 bottom of FIRSTFLOOR (6,1 x 6,1) (75,7) (1,15) (75,7) (1,15) beam. Notes: 1. For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. SHEET NUMBER 2. Requirement is based on minimum flow in gpm(Ipm)from each sprinkler.The associated residual pressures are calculated using the nominal K-factor.See Hydraulic Design under the Design Criteria section. T 3. For NFPA 13 residential applications,the greater of 0.1 gpm/ftz over the design area or the flow in accordance with the criteria in this table must be used. TABLE A WET PIPE SYSTEM FP=2 SERIES LFII RESIDENTIAL 4.9K PENDENT AND RECESSED PENDENT SPRINKLERS (TY2234) NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA OF 2