Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
CANAL STREET-NORTH BUILDING Fire Alarm Equipment
SALEM, MA. NORTH CHELMSFORD, MA. www.mammothfire.com FIRE ALARM SYSTEM SUBMITTAL LOCATION: CANAL STREET REALTY - NORTH BUILDING CANAL STREET INSTALLER: July 18, 2019 “Servicing the installer before and after the installation.” BRUNELLE BROS. ELECTRIC, INC. SALES (978) 934-9130 1-800-995-9808 FAX (978) 934-9131 Mammoth Fire Alarms Incorporated 176 Walker Street Lowell, MA 01854 PAGE QTY PART #DESCRIPTION 1-10 1 FX-2003-6DSK FACP 1/SLC 4/NAC 6A W/CABINET 1-10 1 UDACT/300AP DIGITAL ALARM COMMUNICATOR (1000/2000) 1-10 1 RAX/LCD FX2000 LCD ANNUNCIATOR 11-12 1 BB-1001DR ENCLOSURE FOR RAM/RAX (INDOOR) 13-14 2 INX-10A 10 AMP SIGNAL BOOSTER 5 CLASS A/B CKTS 15-16 4 PS12120 12 AH 12V SEALED BATTERY 15-16 2 PS12180 18 AH 12V SEALED BATTERY 17-18 2 BATTERY CALCULATION SHEETS FOR INX-10A 19-20 1 STANDBY BATTERY CALCULATION SHEET 21-22 4 MIX-M500MAP ADDRESSABLE MONITOR MODULE 21-22 1 MIX-M501MAP ADDRESSABLE MONITOR MODULE 23-24 7 MIX-M500DMAP DUAL MONITOR MODULE (2 ADDRESS) 25-26 6 MIX-M500RAP RELAY CONTROL MODULE 25-26 8 MIX-M500SAP SIGNAL CONTROL MODULE 27-28 15 MS-710APU ADDRESSABLE DBL ACTN PULL STAT W/BRK ROD 29-30 33 MIX-2251AP ANALOG PHOTO DETECTOR 29-30 33 B210LP ANALOG BASE FOR SYSTEM SENSOR DEVICES 29-30 5 RA100Z REMOTE ALARM INDICATOR W/RESISTOR 31-32 1 MIX-5251AP ANALOG THERMAL SENSOR FIXED TEMP 135 31-32 1 B210LP ANALOG BASE FOR SYSTEM SENSOR DEVICES 33-34 2 DNR ANALOG DUCT DET HOUSING W/O RELAYS 33-34 2 MIX/2251BR ANALOG PHOTO DETECTOR W/REMOTE TEST 33-34 2 DST/5 5' SAMPLING TUBE DUCT WIDTHS 4-8 FT 33-34 2 RTS151KEY REMOTE TEST STATION (KEYED) 35-36 1 CO1224TR 12/24VDC CO DET W/RELAY & SNDR (ROUND) 37-38 4 MR201/T RELAY DPDT TRACK (10 AMP) 39-42 1 P2RL/15 WALL MOUNTED RED HORN/STROBE 15CD 39-42 4 P2RL/30 WALL MOUNTED RED HORN/STROBE 30CD 39-42 17 SRL/15 WALL MOUNTED RED STROBE 15CD 43-46 9 PC2RL/30 CEILING MOUNTED RED HORN/STROBE 30CD 47-50 44 HR-LF 520HZ RED HORN 47-50 6 P2RH-LF177 520HZ WALL MOUNT RED HORN/STROBE 177CD 51 6 490S/1280R RED 12-80VDC STROBE LIGHT 51 6 FMSL/4RA RED FLANGE MOUNT KIT FOR 490/500 STROBE 4 FS/SBO FLOW SWITCH - SUPPLIED BY OTHERS (Not Shown) 7 TS/SBO TAMPER SWITCH - SUPPLIED BY OTHERS (Not Shown) 1 PS/SBO PRESSURE SWITCH - SUPPLIED BY OTHERS (Not Shown) 52-55 1 ADDRESS DIRECTORY 56 1 FIRE ALARM SYSTEM OPERATION MATRIX 57 1 WIRING ESTIMATOR 58 1 MAMMOTH FIRE ALRMS, INC. POLICIES 59-62 4 PROPERTY PROTECTION MONITORING, INC. LITERATURE SALEM, MA. BRUNELLE BROS. ELECTRIC, INC. FIRE ALARM SYSTEM FOR CANAL STREET REALTY - NORTH BUILDING CANAL STREET INTELLIGENT FIRE ALARM CONTROL PANEL FX-2000 SERIES Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specifications and models and also to discontinue models. Description Mircom’s FX-2000 Series Microprocessor Based Intelligent Fire Alarm Control Panel is designed to provide maximum flexibility of analog system requirements while also providing easy installation and operation at a cost-effective price. The FX-2000 base panel consists of one intelligent analog loop controller capable of supporting 99 Analog Sensors and 99 Addressable Modules which can be wired in Class A (Style 6 or 7) or Class B (Style 4). The system can be expanded by adding additional Analog Loop Controller Modules. In addition the base panel supports 16 conventional hardwire adder modules such as the DM-1008A Initiating Circuit Module, SGM- 1004A Indicating Circuit Module and the RM-1008A Relay Circuit Module. Additional conventional hardwire adder modules can be added with the ALC-H16 Adder Hardwire Loop Controller Module, which allows the system to support an additional 16 conventional adder modules. The base panel also consists of 4 Class A/B (Style Z/Y) Indicating Circuits rated at 1.7 Amps each and either a 6 or 12 Amp Power Supply. Equipped with a large 4 x 20 Back-lit Alphanumeric LCD display, the FX-2000 utilizes a simple Menu system complete with a directional keypad, common control switches and LEDs, Alarm Queue switches and LEDs and two configurable input switches. Features • Listed to UL 864, 9th edition • Large system capacity • Modular design • Each Analog Loop is capable of supporting 99 Analog Sensors and 99 Addressable Modules which can be wired in Class A (Style 6 or 7) or Class B (Style 4) • Base system supports 16 conventional hardwired modules with the provision to add more using the ALC-H16 Hardwire Loop Controller Module • 6 or 12 Amp power supply • Four Class A/B (Style Z/Y) Indicating Circuits rated at 1.7 Amps each • Configurable for Two Stage operation • Three level password protection with field programmable definition which enables the installer to determine what functions are accessible for each password level • Panel Security to protect site configurations • Manual Control Enable which allows password protection for all front panel function switches • Correlatable Switch Inputs which allows for multi- functional outputs • Four Alarm Queues with selector switches and LEDs for Alarm, Supervisory, Monitor and Trouble • Auxiliary relay contacts for Common Alarm, Common Supervisory and Common Trouble • RS-232 output for remote system printer or CRT • Two Event History Logs comprised of a 1000 Alarm History Log for alarm related events and a 2000 Event Log for all events • Front Panel Auto-Configure and/or Computer laptop Programmable • Large 4 by 20 character Back-lit LCD Display with user friendly menu • Common Control switches and/or indicating LEDs for System Reset, Signal Silence, Fire Drill, Acknowledge, General Alarm, Lamp Test, A.C. On, Pre-Alarm and Ground Fault • Built-in One Man Walk Test operation • Configurable for Coded Operation • Supports an RS-485 interface to the QX-5000 Voice Evacuation System • Panel selection for Canadian (ULC) or U.S.A. (UL) requirements for smoke sensors (sensitivity) via computer laptop • Capability to adjust Intelligent Smoke Detector sensitivity level 5910NOT TO BE USED FOR INSTALLATION PURPOSES. S7010 S7010 7165-1477:111 7170-1477:119 City ofChicago MEA approved 313-97-E APPROVED 3013980 Class I (Con) E15095Class II (Con) E15096Class I (Add) E15097Class II (Add) E15098Highrise CATALOG NUMBER 1 NOT TO BE USED FOR INSTALLATION PURPOSES. The FX-2000 is field programmable via the front panel auto configuration or a laptop computer. In addition, it allows for a three level password protection that can be field defined via a laptop computer. This unique feature allows the installer to determine what functions are accessible for each password level. The system is also equipped with two Event History Logs; one for Alarm and the other for full panel sequence events. The Alarm History Log (1000 events) contains all alarm related functions while the Event Log (2000 events) provides a full sequence log of all operations, as well as alarms and troubles. Both Event History Logs can be used during the One Man Walk Test operation. This allows the event logs to be downloaded to a laptop or printer for a permanent record. The FX-2000 is a very flexible system which supports both internal and external annunciation modules. The internal annunciation modules consist of the RAX-1048TZDS Programmable Zone LED Annunciator, the IPS-2424DS Programmable Input Switches Module, the FDX-008 Fan Damper Module and the AGD-048 Adder Graphic Driver Module. All of these modules mount within the panel and are driven from the main LCD display. The external annunciator modules include the RAM-1032TZDS and RAX-1048TZDS LED Remote Annunciators, the MGD-32 Master Graphic Driver Module, and the RAX-LCD Remote LCD Shared Display. The RAX-LCD Remote LCD Shared Display provides the same features as the main display on the FX-2000. In addition the RAX-LCD also acts as a driver module that allows for the RAX-1048TZDS, IPS-2424DS, FDX-008 and AGD-048 to be connected to it. The RAX-LCD is required as a driver module any time any of the above mentioned external annunciator modules are programmed differently from those on the main panel or are mounted remote from the main panel. In addition to these adder modules, the FX-2000 also supports the UDACT-300A Digital Communicator Module and the PR-300 Polarity Reversal/City Tie Module. The FX-2000 also supports an RS-485 interface to the QX-5000 Emergency Zoned Audio System. Operation Input Correlations All input circuits (addressable or hardwired) can be configured for non-verified alarm, verified alarm, waterflow, latching/non-latching supervisory, monitor, trouble only or remote switch inputs. All of the input configuration types listed above, with the exception of remote switch can be programmed to operate relays, signal and strobe circuits for hardwired or addressable devices. Please refer to the chart below for correlations. The input circuits configured as non- latching will cause the output circuits configured to them to follow the state of the input device. This feature allows for the connection of multiple panels together for signal operation. The Remote Switch input, which must be momentary, allows any input type device (addressable or hardwired) to be configured as a common control functions such as fire drill, system reset, signal silence etc. The remote switches operate in a momentary mode like the control switches on the FX- 2000 main panel. For functions such as fire drill, the remote switch functions in a toggle mode, with one press for “on” and one press for “off”. The remote switch is supervised for “stuck in on” positions, where the switch input is activated (stuck) for more than 30 seconds. If this occurs, a trouble is generated and clears when the input goes away. Intelligent or Conventional Input Types Output Control SwitchesRelay Signal Strobe Non-Verified Alarm Yes Yes Yes No Verified Yes Yes Yes No Waterflow Yes Yes Yes No Non-Latching Supervisory Yes Yes Yes No Latching Supervisory Yes Yes Yes No Monitor Yes Yes Yes No Trouble Only Yes Yes Yes No Remote Switch Input No No No Yes CAT. 5910 page 2 of 10 2 FX-2017-12ADS Mid-Size Main Control Unit The FX-2017-12ADS Mid-Size Main Control Unit comes complete with one intelligent Signaling Line Circuit (SLC) Four Style Z/Y (Class A/B) NAC Circuits (1.7 Amps each), a 4 line by 20 character back-lit LCD display and a 12 Amp Power Supply which charges 17-55 AH batteries. The FX-2017-12ADS has space for up to 17 adder modules and 3 internal annunciator adder modules. The FX-2017-12ADS mounts in the BBX-1072ADS enclosure. ECX-0012 Expander Chassis The ECX-0012 Expander Chassis for the FX-2009-12DS/FX-2009S-12 supports up to 12 adder modules and has space for 2 internal annunciator modules. The ECX-0012 mounts in the BB-5000 series enclosures. FX-2000 Standard Series FX-2009-12DS Large Size Main Control Unit The FX-2009-12DS Large Size Main Control Unit comes complete with one Analog Loop Controller (99 Analog Sensors and 99 Addressable Modules), 4 Class A/B (Style Z/Y) Indicating Circuits (1.7 Amps each), a 4 line by 20 character back-lit LCD display and a 12 Amp Power Supply which charges 17-55 AH batteries. The FX-2009-12DS supports 16 conventional adder modules and provides space for up to 9 adder modules and 3 internal annunciator adder modules. The FX-2009-12DS mounts in the BB-5000 Series enclosures. NOT TO BE USED FOR INSTALLATION PURPOSES. FX-2000 Standard Series System Maximums • 495 Input Circuits • 150 Output Circuits • 5 Intelligent Addressable Loops • 4 Remote LCD Annunciators • 4 Main LED Annunciators • 100 Manual Control Switches CAT. 5910 page 3 of 10 FX-2003-6DS-16LED Compact Main Control Unit The FX-2003-6DS-16LED Compact Main Control Unit come complete with one Intelligent Signaling Line Circuit, Four Style Z/Y (Class A/B) Notification Appliance Circuits rated at 1.7 Amps each and a 4 line by 20 character back-lit LCD display with 16 LEDS for annunciation (DSPL-420-16TZDS). This display is functionally equivalent to the classic FX-2000 main display, but more compact adding in the 16 LEDs for annunciation in addition to all the standard functions.The FX-2003-6DS-16LED is equipped with a 6 Amp Power Supply which charges 10-24 AH batteries. The FX-2003-6DS-16LED provides space for 3 adder modules and 2 internal annunciator adder modules. The FX-2003-6DS-16LED mounts in a separate ordered UB-1024DS Backbox FX-2003-6DS/FX-2003-12DS Compact Main Control Units The FX-2003-6DS and FX-2003-12DS Compact Main Control Units come complete with one Intelligent Signaling Line Circuit, Four Style Z/Y (Class A/B) Notification Appliance Circuits rated at 1.7 Amps each and a 4 line by 20 character back-lit LCD display. The FX-2003-6DS is equipped with a 6 Amp Power Supply which charges 10-24 AH batteries while the FX-2003-12DS includes a 12 Amp Power Supply which charges 17-55 AH batteries. The FX-2003-6DS/FX-2003-12DS provides space for 3 adder modules and 2 internal annunciator adder modules. The FX-2003-6DS/FX-2003-12DS mount in a UB-1024DS backbox. 3 NOT TO BE USED FOR INSTALLATION PURPOSES. ALC-198S Single Analog Loop Controller Module The ALC-198S Single Analog Loop Controller Module provides an additional analog loop to the FX-2000 consisting of 99 Analog Sensors and 99 Addressable Modules. The ALC-198S occupies one module slot in the FX-2000 main or expander chassis. Adder Auxiliary Modules Adder Hardwire Modules DM-1008A Eight Initiating Circuit Module The DM-1008A provides 8 Class B (Style B) or 4 Class A (Style D) Initiating Circuits configurable for Alarm, Supervisory or Trouble zones. The DM-1008A occupies one module slot in the FX-2000 main or expander chassis. PR-300 Polarity Reversal/City Tie Module The PR-300 Polarity Reversal/City Tie Module provides the system with a supervised City Tie (24 VDC/200 mA max.) and Polarity Reversal connection (24 VDC (open circuit), 8 mA max. (shorted)). The PR-300 mounts in the FX-2000 main chassis. RM-1008A Eight Relay Circuit Module The RM-1008A provides the FX-2000 with 8 individual configurable relays per module. Each relay provides one Form C contact rated at 28 VDC @1 Amp (resistive load). The RM-1008A occupies one module slot in the FX-2000 main or expander chassis. SGM-1004A Four Indicating Circuit Module The SGM-1004A provides 4 Class A/B (Style Z/Y) Indicating Circuits configurable as Silenceable or Non-Silenceable. Each Indicating Circuits is rated at 1.7 Amps. Each of the indicating circuits have individual signal silence inputs which are jumper selectable. The SGM-1004A occupies one module slot in the FX-2000 main or expander chassis. ALC-H16 Hardwire Loop Controller Module The ALC-H16 Hardwire Loop Controller Module allows the FX-2000 to support an additional sixteen (16) conventional hardwire adder modules. The hardwire modules consist of the DM-1008 Eight Initiating Circuit Module, SGM- 1004 Four Indicating Circuit Module and the RM-1008 Eight Relay Circuit Module. The ALC-H16 occupies one module slot in the FX-2000 main or expander chassis. ALC-396S Dual Analog Loop Controller Module The ALC-396S Dual Analog Loop Controller Module provides two additional analog loops to the FX-2000 consisting of 99 Analog Sensors and 99 Addressable Modules per loop. The ALC-396S occupies one module slot in the FX-2000 main or expander chassis. Adder Loop Controller Modules CAT. 5910 page 4 of 10 UDACT-300A Digital Alarm Communicator Module The UDACT-300A Digital Alarm Communicator Module allows the FX-2000 to transmit addressable point information to a central station. The UDACT-300A can be configured locally via the on-board keypad and the CFG-300 Configuration Tool or with a UIMA programming tool and a computer with an available serial or USB port. The UDACT- 300A occupies one module slot in the FX-2000 main or expander chassis. 4 NOT TO BE USED FOR INSTALLATION PURPOSES. Programmable Modules RAX-1048TZDS Programmable Zone LED Annunciator Module The RAX-1048TZDS Programmable Zone LED Annunciator Module provides 48 programmable bi- coloured LEDs. The RAX-1048TZDS connects to the main panel or the RAX-LCD Shared Display when mounted remotely. The RAX-1048TZDS occupies one display position in the BB-1000 or BB-5000 enclosures. IPS-2424DS Programmable Input Switches Module The IPS-2424DS Programmable Input Switches Module provides 24 programmable switches that can be configured for ancillary functions such as zone bypass or added common control functions. The switches operate in a toggle operation with one press for “on” and one press for “off”. The IPS-2424DS connects to main panel or the RAX-LCD when mounted remotely. The IPS-2424DS occupies one display position in the BB-1000 or BB-5000 enclosures. FDX-008 Fan Damper Module The FDX-008 Fan Damper Module provides individually programmed circuits which can be used for fan or damper control. Each circuit has a slide-in label, a three position selector switch, green “run or open” LED and an amber “off or closed” LED. The three-position selector switch has a centre “auto” position, a left “off or close” position and a right “on or open” position. The FDX- 008 connects to the main panel or the RAX-LCD when mounted remotely. It uses MIX-M500CH for control of fans or dampers and two MIX-M501A for status. The FDX-008 occupies one display position in the BB-1000 or BB-5000 enclosures. CAT. 5910 page 5 of 10 Electrical Ratings Current Consumption Model Standby Alarm FX-2003-6DS-16LED 230 mA 380 mA FX-2003-6DS FX-2003-12DS 230 mA 380 mA FX-2017-12ADS 230 mA 380 mA FX-2009-12DS 230 mA 380 mA ALC-198S/ALC-396S 35 mA 50 mA ALC-H16 35 mA 50 mA DM-1008A 80 mA 100 mA SGM-1004A 35 mA 150 mA RM-1008A 25 mA 150 mA PR-300 50 mA 300 mA UDACT-300A 40 mA 60 mA RAX-LCD 100 mA 150 mA IPS-2424DS 10 mA 144 mA FDX-008 10 mA 100 mA MGD-32 35 mA 1.6 Amps AGD-048 25 mA 2.4 Amps RAM-1032TZDS 50 mA 150 mA RAX-1048TZDS 15 mA 100 mA 5 NOT TO BE USED FOR INSTALLATION PURPOSES.CAT. 5910 page 6 of 10 RAX-LCD Remote Shared Display The RAX-LCD Remote Shared Display is a remote annunciator that provides the same functions as the main display on the fire alarm control panel, less the 16 zone LEDs. In addition to operating as a remote annunciator, it can also be used as a driver module for standard LED annunciation or reduced zone annunciation (different from the main panel annunciation), graphic drivers programmed different from the main annunciators, programmable switch modules with a unique configuration and fan damper control also with a unique configuration. Each time a different type of annunciation configuration is needed an additional RAX-LCD is required. The RAX-LCD occupies one display position in the BB-1000 or BB-5000 enclosures. Remote Annunciators RAX-1048TZDS Adder Remote LED AnnunciatorThe RAX-1048TZDS Adder Remote LED Annunciator provides an additional 48 points of LED annunciation. The RAX-1048TZDS is an expandible module that connects to the RAM-1032TZDS. The RAX-1048TZDS occupies one display position in the BB-1000 or BB-5000 enclosures. RAM-1032TZDS Main Remote LED AnnunciatorThe RAM-1032TZDS Main Remote LED Annunciator provides common annunciator functions and 32 points of LED annunciation. Each display point can be identified by the slide-in label that slides in beside the LED. The RAM-1032TZDS is equipped with sealed membrane-like buttons for Common Control functions. The RAM-1032TZDS allows for the control switches to be disabled on a per function basis for areas that do not require certain common control functions to be remotely located from the fire alarm control panel. The RAM-1032TZDS can be programmed differently than the main panel annunciator or a remote RAX-LCD. All RAM-1032TZDS remote annunciators on the system must be programmed the same. The RAM-1032TZDS occupies one display position in the BB-1000 or BB-5000 enclosures. MGD-32 Master Graphic Driver Module The MGD-32 Master Graphic Driver Module provides common control inputs for the common control switches such as System Reset, Signal Silence, Auxiliary Disconnect, Fire Drill, Lamp Test, Acknowledge and General Alarm. Any or all of these switch inputs can be used. There are supervised outputs for all of the support LEDs and the common control switches. The MGD-32 can also drive up to 32 supervised outputs. These output points are capable of driving LEDs or incandescent lamps. Mounts in a graphic annunciator wallbox or in the BB-5000 enclosures. External power supply required for incandescent lamps and lamp test. Graphic Annunciator Driver Modules AGD-048 Adder Graphic Driver Module The AGD-048 Adder Graphic Driver Module can be used with the MGD-32 Master Graphic Driver modules, or if located remotely it must be connected and mounted with the RAX-LCD Shared Display. The AGD-048 will support an additional 48 supervised outputs. As with the master modules, the AGD-048 will support both LEDs and incandescent lamps. Mounts in a graphic annunciator wallbox or in the BB-5000 enclosures. NOTE: The combined total of RAM-1032TZDS and MGD-32 per system is eight. All RA-1000 Series annunciators or Graphic driver modules must have the zoned LED or graphic LED correlated to the same combination of addressable devices or hardwired zones . However, the zoned LED annunciator on the FX-2000 main panel can be programmed differently from the annunciators mounted remotely. 6 NOT TO BE USED FOR INSTALLATION PURPOSES.CAT. 5910 page 7 of 10 Enclosures BB-5008 The BB-5008 is a lobby control centre enclosure which is capable of handling one FX-2009-12DS Large Main Control Unit which supports 2 internal annuciator modules such as the IPS-2424DS, FDX-008, RAX-1048TZDS, etc. In addition the BB-5008 allows for 4 footprints for mounting Audio Lobby Control modules, Fire Fighter’s Lobby Control modules and FX-2000 Internal Annunciator modules. The cabinet hold up to 24 AH batteries. Door and Chassis hardware are ordered seperately. Dimensions: 36”H x 30”W x 7”D BBX-1072ADS The BBX-1072ADS enclosure is capable of handling one FX-2017-12ADS Mid-Size Main Control Unit as well as up to 24 AH Batteries. The cabinet features the universal CAT-30 lock and a removable door for easy installation and servicing. The cabinet is available in a white or red exterior (BBX-1072ARDS). Dimensions (minus built-in trim ring): 32.5”H x 25”W x 6 .5”D BB-5014 The BB-5014 is a lobby control centre enclosure which is capable of handling one FX-2009-12DS Large Main Control Unit which supports 2 internal annuciator modules such as the IPS-2424DS, FDX-008, RAX-1048TZDS, etc. In addition the BB-5014 allows for 10 footprints for mounting Audio Lobby Control modules, Fire Fighter’s Lobby Control modules and FX-2000 Internal Annunciator modules. The BB-5014 can also support a graphic annunciator in place of these modules. The cabinet holds up to 24 AH batteries. Door and Chassis hardware are ordered seperately. Dimensions: 60”H x 30”W x 7”D Other Enclosures BB-1001: 9”H x 12.75”W x 1.2”D BB-1002: 18”H x 12.75”W x 1.2”D BB-1003: 26.4”H x 12.75”W x 1.2”D BB-1008: 33”H x 22.5”W x 1.25”D BB-1012: 45”H x 22.5”W x 1.25”D DOX-1024DS(R) Door The DOX-1024DS mounts on the UB-1024DS backbox. The door features the universal CAT-30 lock and is available in a white (DOX-1024DS) or red exterior (DOX-1024DSR). UB-1024DS Universal Backbox The UB-1024DS Universal Backbox houses the FX-2003- 6DS or FX-2003-12DS main control unit and provides space to mount up to 17 AH batteries. A DOX-1024DS(R) door is ordered separately. Dimensions (minus built-in trim ring): 26”H x 14.5”W x 4.2”D DOX-1024DS DOX-1024DSR 7 NOT TO BE USED FOR INSTALLATION PURPOSES.CAT. 5910 page 8 of 10 Typical FX-2000 Panel Wiring Class B (Style 4) );'6/DUJH0DLQ&KDVVLVLQD %%HQFORVXUHFZ(&; ([SDQGHU&KDVVLV5$;7='6,36'6 )';DQG$*',QFOXGHV'0$ &RQYHQWLRQDO,QGLFDWLQJ&LUFXLW0RGXOHV ([WHUQDOSRZHUVXSSO\LVUHTXLUHGIRU LQFDQGHVFHQWODPSVDQGODPSWHVW %%HQFORVXUHFZ 5$;/&'5$;7='6 DQG,36'6 %%HQFORVXUHFZ5$;/&' 5$;7='6,36'6DQG)'; 8 NOT TO BE USED FOR INSTALLATION PURPOSES.CAT. 5910 page 9 of 10 Ordering Information Model Description FX-2000 Standard Series FX-2003-6DS-16LED Compact Main Control Unit c/w one Intelligent Signaling Line Circuit, Four Style Z/Y (Class A/B) Notification Appliance Circuits rated at 1.7 Amps each and a 4 line by 20 character back-lit LCD display with 16 LEDS for annunciation (DSPL-420-16TZDS). This display is functionally equivalent to the classic FX-2000 main display, but more compact adding in the 16 LEDs for annunciation in addition to all the standard functions.TheFX-2003-6DS-16LED is equipped with a 6 Amp Power Supply which charges 10-24 AH batteries. The FX-2003-6DS-16LED provides space for 3 adder modules and 2 internal annunciator adder modules. Order UB-1024DS and DOX-1024DS(R) separately. FX-2003-6DS Compact Main Control Unit c/w one Intelligent Analog Loop Controller (99 Analog Sensors and 99 Addressable Modules), 4 x 20 Back-lit LCD display, 4 Class A/B (Style Z/Y) Indicating Circuits (1.7 Amps each), a 6 Amp power supply and a backbox. Supports up to 16 Conventional Adder Mod- ules. Provides space for 3 Adder Modules and 2 internal annunciation modules. Order UB-1024DS and DOX-1024DS(R) separately. FX-2003-12DS Compact Main Control Unit c/w one Intelligent Analog Loop Controller (99 Analog Sensors and 99 Addressable Modules), 4 x 20 Back-lit LCD display, 4 Class A/B (Style Z/Y) Indicating Circuits (1.7 Amps each), a 12 Amp power supply and a backbox. Supports up to 16 Conventional Adder Mod- ules. Provides space for 3 Adder Modules and 2 internal annunciation modules. Order UB-1024DS and DOX-1024DS(R) separately. FX-2017-12ADS Mid-Size Main Control Unit c/w one Intelligent Analog Loop Controller (99 Analog Sensors and 99 Addressable Modules), 4 x 20 Back-lit LCD display, 4 Class A/B (Style Z/Y) Indicating Circuits (1.7 Amps each) and a 12 Amp power supply. Supports up to 16 Conventional Adder Modules. Provides space for 17 Adder Modules and 3 Internal Annunciation modules. Mounts in the BBX- 1072ADS enclosure. FX-2009-12DS Large Main Control Unit c/w one Intelligent Analog Loop Controller (99 Analog Sensors and 99 Addressable Modules), 4 x 20 Back-lit LCD display, 4 Class A/B (Style Z/Y) Indicating Circuits (1.7 Amps each) and a 12 Amp power supply. Supports up to 16 Conventional Adder Modules. Pro- vides space for 9 Adder Modules and 3 Internal Annunciation modules. Mounts in the BB-5000 series enclosures. ECX-0012 Expander Chassis for the FX-2009-12DS c/w space to add up to 12 adder modules and 2 Internal Annunciation modules. Mounts in the BB-5000 series enclosures Adder Loop Controller Modules ALC-198S Single Loop Intelligent Analog Loop Controller Module (99 Analog Sensors and 99 Addressable Modules) ALC-396S Dual Loop Intelligent Analog Loop Controller Module (198 Analog Sensors and 198 Addressable Modules) ALC-H16 Hardwire Loop Controller Module. Supports 16 Conventional Hardwired Modules Adder Hardwire Modules DM-1008A Eight Class B (Style B) or 4 Class A (Style D) Initiating Circuit Module SGM-1004A Four Class A/B (Style Z/Y) Indicating Circuit Module (Rated at 1.7 Amps per circuit) RM-1008A Eight Relay Circuit Module c/w eight form C relays (Rated for 28 VDC @ 1 Amp max. per relay) Adder Auxiliary Modules UDACT-300A Digital Alarm Communicator Transmitter/Dialer Module PR-300 Polarity Reversal and City Tie Module Programmable Modules RAX-1048TZDS Programmable Zone LED Annunciator Module c/w 48 bi-coloured LEDs. IPS-2424DS Programmable Input Switches Module c/w 24 selector switches and 24 bi-coloured LEDs FDX-008 Fan Damper Control Module c/w 8 programmable switches Remote Annunciators RAM-1032TZDS Main Annunciator Chassis c/w Common Control Features, Indicators and 32 Bi-Coloured LEDs RAX-1048TZDS Adder Annunciator Chassis c/w 48 Bi-Coloured LEDs RTI-1 Remote Trouble Indicator Remote Shared Display Annunciators RAX-LCD Remote Shared Display LCD Annunciator c/w Display Queues and Common Controls Graphic Annunciator Driver Modules MGD-32 Master Graphic Driver Module c/w Fire Alarm Common Control Switch Inputs and 32 Supervised Outputs AGD-048 Adder Graphic Driver Module c/w 48 Supervised Outputs 9 Ordering Information cont’d Canada 25 Interchange Way Vaughan, Ontario L4K 5W3 Telephone: (905) 660-4655 Fax: (905) 660-4113 Web page: http://www.mircom.com Email: mail@mircom.com Distributed by: CAT. 5910 Rev. 11 NOT TO BE USED FOR INSTALLATION PURPOSES. U.S.A. 4575 Witmer Industrial Estates Niagara Falls, NY 14305 Toll Free: (888) 660-4655 Fax Toll Free: (888) 660-4113 Enclosures UB-1024DS Universal backbox for FX-2003-6DS/FX-2003-12DS. Order DOX-1024DS separately DOX-1024DS White door for UB-1024DS backbox DOX-1024DSR Red door for UB-1024DS backbox BBX-1072ADS Black backbox enclosure for FX-2000 c/w removable door and CAT-30 lock and key. Houses one FX- 2017-12ADS Mid-Size Main Control Unit and up to 24 AH batteries. Includes White door BBX-1072ARDS Black backbox enclosure for FX-2000 c/w removable door and CAT-30 lock and key. Houses one FX-2017-12ADS Mid-Size Main Control Unit and up to 24 AH batteries. Includes Red door BB-5008 Lobby Control Centre Wallbox Enclosure. Supports 8 Module Footprints DOX-5008M White Metal Door for BB-5008 DOX-5008MR Red Metal Door for BB-5008 CCH-5008 Custom Mounting Kit for BB-5008. One required per BB-5008 BB-5014 Lobby Control Centre Wallbox Enclosure. Supports 14 Module Footprints DOX-5014M White Metal Door for BB-5014 DOX-5014MR Red Metal Door for BB-5014 CCH-5014 Custom Mounting Kit for BB-5014. One required per BB-5014 10 BB-1001D Semi-Flush Enclosure The BB-1001D comes complete with a backbox, door and hinge. The enclosure door comes with a lexan window, two keys and a durable lock. The door comes hinged to the left side of the box. The box is capable of handling one RAM-1032TZDS Main Annunciator Chassis which provides up to 32 points of annunciation. BB-1002D Semi-Flush Enclosure The BB-1002D comes complete with a backbox, door and hinge. The enclosure door comes with lexan windows, two keys and a durable lock. The door comes hinged to the left side of the box. The enclosure is capable of handling one RAM-1032TZDS Main Annunciator Chassis and one RAX-1048TZDS Adder Annunciator Chassis. CAT. 5505 page 3 of 4 BB-1003D Semi-Flush Enclosure The BB-1003D comes complete with a backbox, door and hinge. The enclosure door comes with lexan windows, two keys and a durable lock. The door comes hinged to the left side of the box. The enclosure is capable of handling one RAM-1032TZDS Main Annunciator Chassis and two RAX-1048TZDS Adder Annunciator Chassis. BB-1008D Semi Flush Enclosure The BB-1008D comes complete with a backbox, door and hinge. The enclosure door comes with lexan windows, two keys and a durable lock. The door comes hinged to the left side of the box. The enclosure is capable of handling up to one RAM-1032TZDS Main Annunciator Chassis, four RAX-1048TZDS Adder Annunciator Chassis and three additional slots for a combination of either fan damper modules, zoned audio paging modules and zoned fire fighters’ telephone modules. BB-1012D Semi Flush Enclosure The BB-1012D comes complete with a backbox, door and hinge. The enclosure door comes with lexan windows, two keys and a durable lock. The door comes hinged to the left side of the box. The enclosure is capable of handling up to one RAM-1032TZDS Main Annunciator Chassis, four RAX-1048TZDS Adder Annunciator Chassis and seven additional slots for a combination of either fan damper modules, zoned audio paging modules and zoned fire fighters’ telephone modules. BB-1001D BB-1002D BB-1003D NOTE: All BB-1000D Series Enclosures are available in a white colour for the Canadian market and a red exterior for the U.S. and International markets. NOT TO BE USED FOR INSTALLATION PURPOSES. 11 BB-1008D Enclosure: 33”H x 22.5”W x 1.85”D BB-1012D Enclosure: 45”H x 22.5”W x 1.85”D Ordering Information Model Description Modules RAM-1016TZDS Main Annunciator Chassis c/w Common Control Features, Indicators and 16 Bi-Coloured LEDs and 16 Trouble LEDs RAM-1032TZDS Main Annunciator Chassis c/w Common Control Features, Indicators and 32 Bi-Coloured LEDs and 32 Trouble LEDs RAX-1048TZDS Adder Annunciator Chassis c/w 48 Bi-Coloured LEDs and 48 Trouble LEDs Backboxes BB-1001D Annunciator backbox with keylock door (Houses 1 module) BB-1002D Annunciator backbox with keylock door (Houses 2 modules) BB-1003D Annunciator backbox with keylock door (Houses 3 modules) BB-1008D Annunciator backbox with keylock door (Houses 8 modules) BB-1012D Annunciator backbox with keylock door (Houses 12 modules) Note: For U.S. and International enclosures add suffix ‘R’ (Red exterior) Canada 25 Interchange Way Vaughan, Ontario L4K 5W3 Telephone: (905) 660-4655 Fax: (905) 660-4113 Web page: http://www.mircom.com Email: mail@mircom.com Distributed by: CAT. 5505 Rev.10 BB-1001D Enclosure: 9”H x 12.75”W x 1.85”D BB-1002D Enclosure: 18”H x 12.75”W x 1.85”D BB-1003D Enclosure: 26.4”H x 12.75”W x 1.85”D Dimensions NOT TO BE USED FOR INSTALLATION PURPOSES. U.S.A. 4575 Witmer Industrial Estates Niagara Falls, NY 14305 Toll Free: (888) 660-4655 Fax Toll Free: (888) 660-4113 NOTE: Annunciator wiring must be as shown. Star type or ‘T’ tap connections are not allowed. The RA-1000 Series Remote Annunciators must be wired in a loop configuration. Typical Remote Annunciator Wiring Diagram SYSTEMRESET FIREDRILL ACKNOWLEDGE GENERALALARM SIGNALSILENCE BUZZERSILENCE AUXILIARYDISCONNECT LAMPTEST TEST/CONFIGMODE REMOTEFAILURE COMMONTROUBLE A.C. ON SYSTEMRESET FIREDRILL ACKNOWLEDGE GENERALALARM SIGNALSILENCE BUZZERSILENCE AUXILIARYDISCONNECT LAMPTEST TEST/CONFIGMODE REMOTEFAILURE COMMONTROUBLE A.C. ON COMMONALARM COMMONSUPERVISORY BATTERYTROUBLE GROUNDFAULT SIGNALTROUBLE 1 SIGNALTROUBLE 2 SIGNALTROUBLE 3 SIGNALTROUBLE 4 SYSTEMRESET FIREDRILL ACKNOWLEDGE GENERALALARM SIGNALSILENCE BUZZERSILENCE AUXILIARYDISCONNECT LAMPTEST TEST/CONFIGMODE REMOTEFAILURE COMMONTROUBLE A.C. ON 1 Twisted Shielded Pair for Communications 1 Untwisted Unshielded Pair for 24 VDC Power The RS-485 wiring needs to be twisted shielded pair. The wire gauge may be 22 AWG up to 4000 ft., 20 AWG up to 6000 feet or 18 AWG up to 8000 ft. Fire Alarm Control Unit RA-1000 Series Remote Multiplex Annunciator (BB-1001 Enclosure) RA-1000 Series Remote Multiplex Annunciator (BB-1001 Enclosure) 12 INTELLIGENT NAC EXPANDER/POWER SUPPLY INX-10A Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specifications and models and also to discontinue models. 5321NOT TO BE USED FOR INSTALLATION PURPOSES. CATALOG NUMBER Description Mircom’s INX-10A is an Intelligent NAC expander/ power supply that is compatible with the FX-2000 and FleX-Net Series Intelligent fire alarm control panels. Available in a 10 Amp configuration, the INX-10A can extend the power capabilities of existing notification appliance circuits as well as provide power for other ancillary devices. In addition, the INX-10A has the ability to operate with any UL/ULC Listed 24 VDC conventional fire alarm control panel to provide Notification Appliance Circuit expansion. The INX-10A is equipped with five individual Class B (Style Y) or Class A (Style Z) output circuits that can be independently configured for NAC operation or auxiliary power. The INX-10A provides the option of configuring all five circuits as an output to provide general purpose power. In addition output circuits four and five can be configured to provide auxiliary power for four-wire detectors or door holders. Each output circuit is rated for 2.5 Amps. When configured for NAC operation the outputs can be set for Steady, Temporal Code, California Code or March Time. In addition the output circuits have field selectable built-in strobe and horn synchronization protocols to support Amseco, System Sensor, Wheelock and Gentex devices, eliminating the need for additional external synchronization modules. Features 10 Amp output• 120 / 240V operation• Compatible with Mircom’s FX-2000 and FleX-Net • Series Intelligent Fire Alarm Control panels Easily configured using DIP switches• One isolated input from the host panel• Five Class B (Style Y) or Class A (Style Z) • synchronized output circuits DC regulated outputs• Configurable AC Power fail delay• Ground fault enable or disable• Option available on configuration to enable or • disable the battery charger on activation From 7 to 15 Address functions (Combination of • inputs and outputs, depending on the application) Outputs individually controllable• Separate Relay for Ground Fault and Common • Trouble available on terminals Horn/Strobe synchronization protocols • include Amseco, Gentex, System Sensor and Wheelock Two-wire horn/strobe Sync Mode allows audible • notification appliances (horns) to be silenced while visual notification appliances (strobes) continue to operate Audible signals may be configured for Steady, • Temporal Code, California Code and March Time Output circuits four and five can be configured to • provide auxiliary power for four-wire detectors or door holders. Canadian two stage operation• Output fault notification to fire alarm control panel• Ability to sync outputs for multiple INX-10A units• 2.5 Amp max. current per output• 1.7 Amp auxiliary power output• Built-in charger for sealed lead acid or gel type • batteries Unit includes power supply, charger, red enclosure, • cam lock, transformer and battery leads Compatible with any UL/ULC listed 24VDC • conventional fire alarm control panel to provide Notification Appliance Circuit expansion 7315-1477:0163S5434S5434 13 Canada 25 Interchange Way Vaughan, Ontario L4K 5W3 Telephone: (905) 660-4655 Fax: (905) 660-4113 U.S.A. 4575 Witmer Industrial Estates Niagara Falls, NY 14305 Toll Free: (888) 660-4655 Fax Toll Free: (888) 660-4113 Web page: http://www.mircom.com Email: mail@mircom.com Distributed by: NOT TO BE USED FOR INSTALLATION PURPOSES. CAT. 5321 Rev. 1 Specifications Model Description INX-10A Intelligent NAC Expander, 10 Amps c/w backbox and red door FA-300-TRB Flush Trim Ring, Black Ordering Information Dimensions 20”H x 14½”W x 4½”D AC Line Voltage 120V 60Hz / 240V, 50Hz 2 Amps / 1 Amp (primary) NAC Circuits 24VDC regulated, Power Limited 10A Total, 2.5A maximum per circuit Battery 24VDC, Gel-Cell/Sealed Lead-Acid Charging Capability Up to 40 AH batteries Current Consumption Standby 200 mA Alarm 350 mA Common Indicators Power OnAddressable Line Activity/AlarmCommon TroubleBattery Charger/TroubleCPU Fail Trouble LEDs Auxiliary Output TroubleSynchronized Output TroubleGround Fault Trouble Other LEDs Addressable (SLC) Loop Indicators (3 LEDs)Synchronized Input Indicators (2 LEDs)Synchronized Output Indicators (2 LEDs)Trouble LED IndicatorAlarm Relay Indicator Controls Acknowledge ButtonConfiguration DIP Switches Modes of Operation Intelligent NAC Expander (INX) Modes The INX-10A features three modes of NAC Expander operation: INX Mode with Internal Sync• INX Mode with External Sync• INX Mode with Redundant Input• Input Mode with Internal Sync In this mode all signal and sync strobe rates are produced in the INX-10A. INX Mode with External Sync When one of the Sync Inputs is activated, the INX-10A outputs follow the signal pattern of the Sync Input. The INX-10A must be configured as a slave to operate in this mode. INX Mode with Redundant Input The system continuously monitors the SLC loop. If there is no activity for a notable time, an SLC trouble is generated. While the SLC trouble is active, if either of the Sync Inputs are activated then all NAC outputs follow. Power Supply Modes In addition to the NAC expander modes, some or all of the NAC outputs on the INX-10A can be configured for the following power supply modes of operation: NAC Outputs as Power Supply Outputs• NAC Outputs for Door Release• NAC Outputs for 4-Wire Smoke Supply• NAC Outputs as Power Supply Outputs This mode allows any NAC output to be configured as a power supply. The SLC and Sync inputs are ignored for the power supply outputs. NAC Outputs for Door Release This mode allows NAC circuits 4 and/or 5 to provide power for door holders. NAC Outputs for 4-Wire Smoke Supply This mode allows NAC circuits 4 and/or 5 to provide auxiliary power for 4-wire smoke detectors. 14 Specifications are provided for information only and are believed to be accurate. However, no responsibility is assumed by Mammoth Fire Alarms, Inc. for their use. Specifications subject to change without notice. © 1999 All Rights Reserved 176 Walker Street, Lowell, MA 01854-3126 Sales (800) 995-9808 Fax (978) 934-9131 www.mammothfire.com Mammoth Fire Alarms Incorporated PS12180 PS12350, PS12550 PS12120 PS1270 The rechargeable batteries are of sealed lead calcium maintenance- free construction with a fully gelled electrolyte in a polypropylene case. These batteries will not leak or spill even if left upside down for extended periods of time. ELECTRICAL SPECIFICATIONS Nominal voltage 12 volts Charging voltage Float 13.5 - 13.8 VDC Cycle 14.4 - 14.8 VDC Operating Temp. Range Discharge -76o F to +122o F (-60o C to +50o C) Charge -4o F to +122o F (-20o C to +50o C) BATTERY FEATURES zzzzz Long Life zzzzz Completely Sealed zzzzz Charge and Discharge in any Position zzzzz Low Self Discharge zzzzz Maintenance Free SPECIFICATIONS Model CapacityTerminal Type Dimensions Weight (20 hr. rate) PS1270 7 AH Faston tab “.187” series 5.11 cm L x 10.03 cm H x 6.6 cm W 5.75 lbs. (2.61 kg) 5.95" L x 3.95" H x 2.6" W PS12120 12 AH Faston tab “.250” series 12.48 mm L x 5.97 mm H x 4.72 mm W 9.33 lbs. (4.24 kg) 5.94” L x 3.70” H x 3.98” W PS12180 18 AH Terminal posts w/5 mm 18.11 cm L x 16.69 cm H x 7.59 cm W 13.2 lbs. (5.99 kg) nut & bolt connectors 7.13" L x 6.57" H x 2.99" W PS12350 35 AH " L” blade w/.6.4 mm 19.69 cm L x 18.54 cm H x 12.95 cm W 2 4 lbs. (10.89 kg) hole 7.75" L x 7.3" H x 5.1" W PS12550 55 AH "L” blade w/6.4 mm 26.04 cm L x 22.23 cm H x 17.27 cm W 39 lbs. (17.69 kg) hole at negative, 8.9 mm 10.25” L x 8.75” H x 6.8” W sq. cutout at positive BATTERIE1LT-SEALED LEAD ACID RECHARGABLE PS1270 BATTERIES 15 Specifications are provided for information only and are believed to be accurate. However, no responsibility is assumed by Mammoth Fire Alarms, Inc. for their use. Specifications subject to change without notice. © 1999 All Rights Reserved 176 Walker Street, Lowell, MA 01854-3126 PS1270 PS12180 PS12350, PS12550 ORDERING INFORMATION Model Description PS1270 Sealed lead calcium battery, 7 AH PS12120 Sealed lead calcium battery, 12 AH PS12180 Sealed lead calcium battery, 18 AH PS12350 Sealed lead calcium battery, 35 AH PS12550 Sealed lead calcium battery, 55 AH PS12120 16 7/10/2019 BRUNELLE BROS. ELECTRIC, INC.CANAL STREET REALTY - NORTH BUILDING 109 TYNGSBOROUGH ROAD CANAL STREET NORTH CHELMSFORD, SALEM MA MA Check your part #s SIGNAL CKT #AREA P2RL/15P2RL/30PC2RL/30HR-LFP2RH-LF177SRL/15490S/1280RMIX-M500SAPMR201/TCO1224TRINX-10ARemote Panel - 1 6 Remote circuits available INX-10A 1 1ST FL UNITS 01 & 02 4 5 - INX-10A 2 1STFL UNITS 03 & 04 4 6 - INX-10A 3 1ST FL UNIT 05 & ELEV LOBBY 1 1 4 1 0.3200 13% INX-10A 4 2ND FLOOR 11 - INX-10A 5 2ND FLOOR 11 - INX-10A SYN 1 INX #2 TRIP 1 INX-10A SYN 2 SPARE - INX-10A AUX AUX POWER 5 8 3 1 1.7200 69% - 2.04 INX-10A Available Power from selected device 10.00 Ring Time, in Mins 15 (Total Alarm Current / (60 / Ring Time))0.51 Standby Time, in Hrs 24 (Total Supervisory Current * Standby Time)5.28 AH Required ----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------->5.79 Standby Reserve @ 20%----------------------------------------------------------------------------------------------------------------------------------------------------------------------->6.9517 7/10/2019 BRUNELLE BROS. ELECTRIC, INC.CANAL STREET REALTY - NORTH BUILDING 109 TYNGSBOROUGH ROAD CANAL STREET NORTH CHELMSFORD, SALEM MA MA Check your part #s SIGNAL CKT #AREA P2RL/15P2RL/30PC2RL/30HR-LFP2RH-LF177SRL/15490S/1280RMIX-M500SAPMR201/TCO1224TRINX-10ARemote Panel - 2 6 Remote circuits available INX-10A 1 2ND FLOOR 2 3 1 - INX-10A 2 3RD FLOOR 11 - INX-10A 3 3RD FLOOR 11 - INX-10A 4 3RD FLOOR 2 3 1 - INX-10A 5 SPARE NAC - INX-10A SYN 1 SPARE - INX-10A SYN 2 SPARE - INX-10A AUX AUX POWER - - INX-10A Available Power from selected device 10.00 Ring Time, in Mins 15 (Total Alarm Current / (60 / Ring Time)) Standby Time, in Hrs 24 (Total Supervisory Current * Standby Time)4.80 AH Required ----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------->4.80 Standby Reserve @ 20%----------------------------------------------------------------------------------------------------------------------------------------------------------------------->5.7618 Mammoth Fire Alarms Incorporated 176 Walker Street, Lowell, MA 01854-3126 Tel. (978) 934-9130 Sales 1-800-995-9808 Fax (978) 934-9131 STANDBY BATTERY CALCULATIONS Created:5/9/2019 SOLD TO:Updated:7/10/2019 BRUNELLE BROS. ELECTRIC, INC. 109 TYNGSBORO ROAD NORTH CHELMSFORD, MA. 01863 JOB NAME CANAL STREET REALTY - NORTH BUILDING CANAL STREET SALEM MA Fire Alarm SUP ALARM QTY PART #DESCRIPTION CURRENT CURRENT FACP 1 FX-2003-6DSK FACP 1/SLC 4/NAC 6A W/CABINET 0.2300 0.3800 1 UDACT/300AP DIGITAL ALARM COMMUNICATOR (1000/2000)0.0400 0.0600 INDOOR REMOTE LCD ANNUNCIATOR 1 RAX/LCD FX2000 LCD ANNUNCIATOR 0.1000 0.1500 1 BB-1001DR ENCLOSURE FOR RAM/RAX (INDOOR)- - BDA MONITORING 2 MIX-M500DMAP DUAL MONITOR MODULE (2 ADDRESS)0.0015 0.0019 1 MIX-M500MAP ADDRESSABLE MONITOR MODULE 0.0004 0.0052 SPRINKLER 4 FS/SBO FLOW SWITCH - SUPPLIED BY OTHERS 7 TS/SBO TAMPER SWITCH - SUPPLIED BY OTHERS 1 PS/SBO PRESSURE SWITCH - SUPPLIED BY OTHERS 5 MIX-M500DMAP DUAL MONITOR MODULE (2 ADDRESS)0.0038 0.0049 2 MIX-M500MAP ADDRESSABLE MONITOR MODULE 0.0008 0.0104 PULL STATION 15 MS-710APU ADDRESSABLE DBL ACTN PULL STAT W/BRK ROD 0.0060 0.0825 HEAT DETECTOR 1 MIX-5251AP ANALOG THERMAL SENSOR FIXED TEMP 135 0.0003 0.0050 1 B210LP ANALOG BASE FOR SYSTEM SENSOR DEVICES - - SMOKE DETECTOR 33 MIX-2251AP ANALOG PHOTO DETECTOR 0.0099 0.1650 33 B210LP ANALOG BASE FOR SYSTEM SENSOR DEVICES - - 5 RA100Z REMOTE ALARM INDICATOR W/RESISTOR 0.0500 DUCT SMK DET. 2 DNR ANALOG DUCT DET HOUSING W/O RELAYS 2 MIX/2251BR ANALOG PHOTO DETECTOR W/REMOTE TEST 0.0007 0.0140 2 MIX-M500RAP RELAY CONTROL MODULE 0.0006 0.0102 2 DST/5 5' SAMPLING TUBE DUCT WIDTHS 4-8 FT - - 2 RTS151KEY REMOTE TEST STATION (KEYED)- 0.1600 24VDC CO DET. 1 MIX-M501MAP ADDRESSABLE MONITOR MODULE 0.0004 0.0020 NOTIFICATION APPLIANCES 5 MIX-M500SAP SIGNAL CONTROL MODULE 0.0020 0.0260 Page 2 of 3 19 Mammoth Fire Alarms Incorporated 176 Walker Street, Lowell, MA 01854-3126 Tel. (978) 934-9130 Sales 1-800-995-9808 Fax (978) 934-9131 STANDBY BATTERY CALCULATIONS Created:5/9/2019 SOLD TO:Updated:7/10/2019 BRUNELLE BROS. ELECTRIC, INC. 109 TYNGSBORO ROAD NORTH CHELMSFORD, MA. 01863 JOB NAME CANAL STREET REALTY - NORTH BUILDING CANAL STREET SALEM MA Fire Alarm SUP ALARM QTY PART #DESCRIPTION CURRENT CURRENT ELEVATOR RECALL 3 MIX-M500RAP RELAY CONTROL MODULE 0.0009 0.0153 1 MIX-M500SAP SIGNAL CONTROL MODULE 0.0004 0.0052 1 MIX-M500MAP ADDRESSABLE MONITOR MODULE 0.0004 0.0052 CARD ACCESS OVERRIDE 1 MIX-M500RAP RELAY CONTROL MODULE 0.0003 0.0051 SMOKE DAMPER RELAY/CONTROL 2 MIX-M500SAP SIGNAL CONTROL MODULE 0.0008 0.0104 MR201/T FALSE 2 PS12180 18 AH 12V SEALED BATTERY TOTAL 0.3992 1.1683 15 Ring Time, in Min (Total Alarm Current / (60 / Ring Time))0.2921 ALM A/H 24 Standby Time, in Hrs (Total Supervisory Current * Standby Time)9.5808 SUP A/H Total Amp Hours Required 9.8729 20 Standby Reserve 20%20 11.8475 Page 3 of 3 20 ADVANCED PROTOCOL INTELLIGENT MONITOR MODULES MIX-M500AP SERIES Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specifications and models and also to discontinue models. 5950 NOT TO BE USED FOR INSTALLATION PURPOSES. S5434 S5434 7300-1477:0167 CATALOG NUMBER Description Mircom's intelligent monitor modules are designed to meet a wide range of applications. The monitor modules provide an interface to contact devices, such as, manual stations, conventional smoke or heat detectors, waterflow switches, and more. The monitor modules are addressed with easy-to-use rotary code switches. Mircom’s Advanced Protocol (AP) devices use a high speed communication protocol that greatly increases the speed of communication between the intelligent devices. Mircom’s Advanced Protocol uses a superior group polling method as well as an interrupt feature that provide for a faster response to an alarm condition. In addition, the Advanced Protocol allows for greater system capacity with support for up to 318 devices per SLC circuit. The AP devices are backwards compatible to operate in CLIP mode for legacy system applications. MIX-M500MAP Monitor Module Mircom’s MIX-M500MAP monitor module is a standard- sized module that supervises either a Style D (Class A) or Style B (Class B) circuit of dry-contact input devices. The MIX-M500MAP is intended for use in intelligent, two-wire systems, where the individual address of each module is selected using the built-in rotary decade switches. It provides either a 2-wire or 4-wire fault tolerant initiating circuit for normally open contact fire alarm, supervisory, or security devices. The module has a panel controlled LED indicator. MIX-M501MAP Mini Monitor Module The MIX-M501MAP is a miniature monitor module that supervises a Style B (Class B) circuit of dry-contact input devices. The small size of the module allows it to fit inside devices or junction boxes behind devices. The MIX-M501MAP is intended for use in intelligent, two-wire systems where the individual address of each module is selected using rotary decade switches. It provides a twowire initiating circuit for normally open contact fire alarm and security devices. MIX-M502MAP Zone Interface Module The MIX-M502MAP Zone Interface Module is a standard- sized module that monitors and supervises compatible two-wire, 24 volt, smoke detectors on a Style D (Class A) or Style B (Class B) circuit. The module allows Mircom's intelligent panels to interface and monitor two- wire conventional smoke detectors. All two-wire detectors being monitored must be UL or ULC compatible with the module. The MIX-M502MAP is addressed through the communication line of an intelligent Mircom system. It transmits the status of one zone of two-wire detectors to the fire alarm control panel. Status conditions are reported as normal, open, or alarm. The interface module supervises the zone of detectors and the connection of the external power supply. Features • Designed to meet a wide range of applications • SEMS screws for easy wiring • Panel controlled status LED (except MIX- M501MAP) • Rotary switches for direct-dial entry of address. Each unit can have address set for 01-159 for Advanced Protocol mode and 01-99 for CLIP mode (except MIX-M500X) • Low standby current • Mount in 4” square junction box 21 Canada 25 Interchange Way Vaughan, Ontario L4K 5W3 Telephone: (905) 660-4655 Fax: (905) 660-4113 Web page: http://www.mircom.com Email: mail@mircom.com Distributed by: CAT. 5950 Rev. 0 NOT TO BE USED FOR INSTALLATION PURPOSES. U.S.A. 4575 Witmer Industrial Estates Niagara Falls, NY 14305 Toll Free: (888) 660-4655 Fax Toll Free: (888) 660-4113 Specifications Ordering Information Model Description MIX-M500MAP Monitor Module MIX-M501MAP Mini Monitor Module MIX-M502MAP Zone Interface Module MIX-M500X Isolator Module Add suffix "A" for ULC listed model. MIX-M500MAP Monitor Module Normal Operating Voltage 15 to 32 VDC Max. Alarm Current (LED on)5.0mA (LED on) Average Operating Current 400 μA, 1 communication every 5 sec, 47k EOL EOL Resistance 47K Ohms Max. IDC wiring resistance 40 Ohms Maximum IDC Voltage 11 Volts Maximum IDC Current 400μA Temperature Range 32˚F to 120˚F (0˚C to 49˚C) Humidity 10% to 93% Non-condensing Dimensions 4.5” H x 4” W x 1.25” D M500X Isolator Module The M500X Isolator Module is a standard-sized module that enables part of the communications loop to continue operating when a short circuit occurs on it. An LED indicator blinks in the normal condition and turns on during a short circuit condition. The module will automatically restore the entire communications loop to the normal condition when the short circuit is removed MIX-M501MAP Mini Monitor Module Nominal Operating Voltage 15-32 VDC Max. Alarm Current 600 uA Average Operating Current 400 μA, 1 communication every 5 seconds, 47k EOL EOL Resistance 47K Ohms Max. IDC Wiring Resistance 40 Ohms Maximum IDC Voltage 11 Volts Maximum IDC Current 400μA Temperature Range 32°F to 120°F (0°C to 49°C) Humidity 10% to 93% Non-condensing Dimensions 1.3˝ H × 2.75˝ W × 0.65˝ D MIX-M502MAP Zone Interface Module Normal Operating Voltage 15 to 32 VDC Maximum Alarm Current 5.1mA (LED on) Average Operating Current 400μA, 1 communication and 1 LED flash every 5 seconds, 3.9k EOL EOL Resistance 3.9K Ohms Max. IDC wiring resistance 25 Ohms IDC Supply Voltage Regulated DC Voltage 24 VDC power limited Ripple Voltage 0.1 Volts RMS maximum Current 90mA per module Temperature Range 32˚F to 120˚F (0˚C to 49˚C) Humidity 10% to 93% Non-condensing Dimensions 4.5˝ H x 4˝ W x 1.25˝ D M500X Isolator Module Normal Operating Voltage 15 - 32 VDC Stand-by Current 450 μA (not isolating) Maximum Current Draw 17mA (device in isolation) Temperature Range 32°F to 120°F (0°C to 49 °C) Humidity 10 to 93% Non-condensing Dimensions 4.5˝ H x 4˝ W x 1.25˝ D 22 INTELLIGENT ADDRESSABLE MODULES MIX-500 SERIES Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specifi cations and models and also to discontinue models. 5903 NOT TO BE USED FOR INSTALLATION PURPOSES. S5434 S5434 MEA approved APPROVED 3017996427-91-E (MIX-M500, MIX-M501M) 87-01-E (MIX-M500R, MIX-M500S) 227-03-E (MIX-M500DM) 7300-1477:113 (MIX-M501M, MIX-500R, MIX-500S & MIX-M502M) 7300-1477:126 (MIX-M500DM) 7300-1477:127 (MIX-M500M) CATALOG NUMBER Description Mircom's intelligent module products are designed to meet a wide range of applications. Monitor and control modules can be used to supervise and activate sounders, strobes, door closers, pull stations, waterfl ow switches, conventional smoke detectors, and more. Each module is rigorously de- signed and tested for electromagnetic compatibility and environmental reliability, in many cases exceeding industry standards. Modules are addressed with easy-to-use rotary code switches. Full size modules mount in standard 4" x 4" x 2 ⅛" junction box. Wiring terminals are easily accessible for troubleshooting purposes. MIX-M500M Monitor Module, MIX-M501M Mini Monitor Module and MIX-M500DM Dual Input Monitor Module Mircom’s monitor modules provide an interface to contact devices, such as security contacts, waterfl ow switches, or manual stations. They are capable of Styles A and B supervised wiring to the load device (MIX-M500M is capable of Style D). Conventional 4-wire smoke detectors can be monitored through their alarm and trouble contacts, wired as an initiating loop to the module. In addition to transmitting the supervised state of the monitored device (normal, open, or short), the full analog supervision measurement is sent back to the panel. This allows impedance changes in the supervised loop to the monitored device to be detected. The MIX-M500DM is capable of monitoring two separate Class B circuits simultaneously, making it ideal for waterfl ow tamper switch and fl ow switch monitoring. The small size of the MIX-M501M allows it to fi t inside devices or junction boxes behind devices. MIX-M500R Relay Module The MIX-M500R Relay Module contains two isolated sets of Form-C contacts, which operate as a DPDT switch. The module allows the control panel to switch these contacts on command. No supervision is provided for the relay contacts. MIX-M502M Zone Interface Module The MIX-M502M Zone Interface Module allows Mircom's intelligent panels to interface and monitor two-wire conventional smoke detectors. All two-wire detectors being monitored must be UL or ULC compatible with the module. The MIX-M502M is addressed through the communication line of an intelligent Mircom system. It transmits the status of one zone of two-wire detectors to the fi re alarm control panel. Status conditions are reported as normal, open, or alarm. The interface module supervises the zone of detectors and the connection of the external power supply. MIX-M500S Supervised Control Module The MIX-M500S Supervised Control Module provides supervised monitoring of wiring to load devices that require an external power supply to operate, such as horns, strobes, or bells. It is capable of Styles Y and Z supervision. Upon command from the control panel, the MIX-M500S will disconnect the supervision and connect the external power supply across the load device. The disconnection of the supervision provides a positive indication to the panel that the control relay actually turned on. The external power supply is always relay isolated from the communication loop, so that a trouble condition on the power supply will never interfere with the rest of the system. Full analog measurement of the supervised wiring is transmitted back to the panel and can be used to detect impedance changes or other special test functions. Features Designed to meet a wide range of applications• SEMS screws for easy wiring• Panel controlled status LED (except MIX-M501M)• Analog communications• Rotary address switches (except MIX-M500X)• Low standby current• Mounts in 4” square junction box• 23 Canada 25 Interchange Way Vaughan, Ontario L4K 5W3 Telephone: (905) 660-4655 Fax: (905) 660-4113 Web page: http://www.mircom.com Email: mail@mircom.com Distributed by: CAT. 5903 Rev. 6 NOT TO BE USED FOR INSTALLATION PURPOSES. U.S.A. 4575 Witmer Industrial Estates Niagara Falls, NY 14305 Toll Free: (888) 660-4655 Fax Toll Free: (888) 660-4113 Specifi cations Ordering Information General Specifi cations Operating Voltage 15-32 VDC Communication Line Loop Impedance 40 Ω max. Temperature Range 32° to 120°F (0° to 49°C) Relative Humidity 10% to 93%: noncondensing Dimensions MIX-M501M 2.7"W x 1.7:"H x 0.5"D Others: 4.25"W x 4.65"H x 1.1"D Shipping Weight M501M: 1.2 oz (37g) Others: 6.3 oz (196g) MIX-M502M Specifi cations Standby Current 300 μA max @ 24 VDC (one communication every 5 sec. with LED enabled) External Power Supply 18-28 VDC (100 mV ripple max.) End-of-Line Resistance 3.9 kΩ (included) External Supply Standby Current 11.5 mA @ 24 VDC (nominal) External Supply Alarm Current 80 mA @ 24 VDC (nominal) MIX-M500M, MIX-M500S, MIX-M501M Specifi cations Standby Current 400 μA max @ 24 VDC (one communication every 5 sec. with 47k EOL) 550 μA max @ 24 VDC (one communication every 5 sec. with EOL<1k) 5.5 mA (with LED latched on) End-of-Line Resistance 47 kΩ (included) MIX-M500R Specifi cations Standby Current 300 μA @ 24 VDC (one communication every 5 sec. with LED enabled) LED Current 5.5 mA (with LED latched on) Relay Contact Ratings 3.0 A @ 30 VDC resistive 0.9 A @ 110 VDC resistive 0.9 A @ 125 VAC resistive 0.5 A @ 125 VAC inductive (PF=.35) 0.7 A @ 75 VAC inductive (PF=.35) MIX-M500DM Specifi cations Standby Current 750 μA max. @ 24 VDC (one communication every 5 sec. with 47k EOL) Alarm Current 970 μA max. (one communication every 5 sec.) 6 mA (with LED latched on) End-of-Line Resistance 47 kΩ (two included) MIX-M500X Specifi cations Standby Current 450 μA max Isolation Current 5 mA max Fault Detection Delay 250 ms min. Fault Detection Threshold 4 Volts Line Restoration Threshold 7 Volts Model Description MIX-M500M Monitor Module MIX-M500R Relay Module MIX-M500S Supervised Control Module MIX-M501M Mini Monitor Module MIX-M502M Zone Interface Module MIX-M500X Isolator Module MIX-M500DM Dual Input Monitor Module Add suffi x "A" for Canadian model. M500X Isolator Module The M500X Isolator Module is an automatic switch that opens when the line voltage drops below four volts. Isolator modules should be spaced between groups of sensors or modules in a loop to protect the rest of the loop. If a short occurs between any two isolators, then both isolators immediately switch to an open circuit state and isolate the devices between them. The remaining units on the loop continue to fully operate. No more than 25 devices are recommended for each group. 24 ADVANCED PROTOCOL CONTROL MODULES MIX-M500SAP/MIX-M500RAP Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specifications and models and also to discontinue models. 5951 NOT TO BE USED FOR INSTALLATION PURPOSES. S5434 S5434 APPROVED CATALOG NUMBER Description Mircom’s intelligent control and relay modules are designed to meet a wide range of applications. The control modules can be used to supervise and activate Notification Appliances while the relay modules provide the system with dry contact outputs for activatey a variety of auxiliary devices. The control and relay modules are addressed with easy-to-use rotary code switches. Mircom’s Advanced Protocol (AP) devices use a high speed communication protocol that greatly increases the speed of communication between the intelligent devices. Mircom’s Advanced Protocol uses a superior group polling method as well as an interrupt feature that provide for a faster response to an alarm condition. In addition, the Advanced Protocol allows for greater system capacity with support for up to 318 devices per SLC circuit. The AP devices are backwards compatible to operate in CLIP mode for legacy system applications. MIX-M500RAP Relay Control Module The MIX-M500RAP Relay Control Module contains two isolated sets of Form-C contacts, which operate as a DPDT switch to provide the system with outputs for activating a variety of auxiliary devices, such as fans, dampers, control equipment, etc. The module allows the control panel to switch these contacts on command. No supervision is provided for the relay contacts. Features • Designed to meet a wide range of applications • SEMS screws for easy wiring • Panel controlled status LED • Rotary switches for direct-dial entry of address. Each unit can have address set for 01-159 for Advanced Protocol mode and 01-99 for CLIP mode • Low standby current • Mount in 4” square junction box MIX-M500SAP Supervised Control Module The MIX-M500SAP Supervised Control Module provides supervised monitoring of wiring to load devices that require an external power supply to operate, such as horns, strobes, or bells. It is capable of Styles Y and Z supervision. Upon command from the control panel, the MIX-M500SAP will disconnect the supervision and connect the external power supply across the load device. The disconnection of the supervision provides a positive indication to the panel that the control relay actually turned on. The external power supply is always relay isolated from the communication loop, so that a trouble condition on the power supply will never interfere with the rest of the system. Full analog measurement of the supervised wiring is transmitted back to the panel and can be used to detect impedance changes or other special test functions. 7300-1477:0167 25 Canada 25 Interchange Way Vaughan, Ontario L4K 5W3 Telephone: (905) 660-4655 Fax: (905) 660-4113 Web page: http://www.mircom.com Email: mail@mircom.com Distributed by: CAT. 5951 Rev. 2 NOT TO BE USED FOR INSTALLATION PURPOSES. U.S.A. 4575 Witmer Industrial Estates Niagara Falls, NY 14305 Toll Free: (888) 660-4655 Fax Toll Free: (888) 660-4113 Specifications Ordering Information Model Description MIX-M500RAP Relay Control Module MIX-M500SAP Supervised Control Module Add suffix "A" for ULC listed model. MIX-M500SAP Supervised Control Module Normal Operating Voltage 15 to 32 VDC Maximum Alarm Current 6.5mA (LED On) Average Operating Current 400 μA max., 1 communica- tion every 5 seconds 47k EOL resistor, 485 uA max.(Com- municating, NAC shorted). Maximum NAC Line Loss 4 VDC External Supply Voltage Maximum (NAC)Regulated 24VDC Maximum (Speakers)70.07 V RMS, 50 W Max. NAC Current Ratings For class B wiring system, the current rating is 3A; For class A wiring system, the current rating is 2A Temperature Range 32˚F to 120˚F (0˚C to 49˚C) Humidity 10% to 93% Non-condensing Dimensions 4.5˝ H × 4˝ W × 1.25˝ D MIX-M500RAP Relay Control Module Normal Operating Voltage 15 to 32 VDC Maximum Alarm Current 6.5mA (LED on) Average Operating Current 300 μA, 1 communication every 5 seconds EOL Resistance Not used Temperature Range 32˚F to 120˚F (0˚C to 49˚C) Humidity 10% to 93% Non-condensing Dimensions 4.5˝ H x 4˝ W x 1.25˝ D Relay Contact Ratings Current Rating Maximum Voltage Load Description Application 3 A 30 VDC Resistive Non-coded 2 A 30 VDC Resistive Coded 0.46 A 30 VDC (L/R= 20ms)Non-coded 0.9 A 125 VDC Resistive Non-coded 0.5 A 125VAC (PF=0.75)Non-coded 0.3 A 125 VAC (PF=0.35)Non-coded 0.7 A 70.7 VAC (PF=0.35)Non-coded 0.2 A 25 VAC (PF=0.35)Non-coded 26 ADVANCED PROTOCOL INTELLIGENT MANUAL STATION MS-710APU Features • Dual Action • Key resettable • Permanently attached Intelligent Addressable Module • Rotary switches for direct-dial entry of address. Each unit can have address set for 01-159 for Advanced Protocol mode and 01-99 for CLIP mode • High-gloss red enamel finish • Plastic breakrod • Meets ADA 5 lb. maximum manual-force • Mounts on standard single gang box, Mircom’s BB-700 surface metal backbox or BB-700WP weather proof backbox Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specifications and models and also to discontinue models. 5954 NOT TO BE USED FOR INSTALLATION PURPOSES. Operation The MS-710APU Dual Action Intelligent Manual Station is operated by pushing the bar labelled “PUSH BAR” and then pulling down the handle marked “PULL HANDLE”. The MS-710APU is reset by opening the station with the key, placing the handle in the normal upright position and re-locking the station. Specifications The manual station shall be Mircom’s MS-710APU. Operating instructions shall be in raised English lettering and the unit shall be constructed of high quality die-cast metal and finished in red enamel paint to provide quick identification. Pulling the handle shall initiate immediate operation of the intelligent addressable module. All manual fire alarm stations shall be installed as per the specific requirements outlined in the UL codes, as well as all other applicable national or local codes. Final acceptance is subject to the local authority having jurisdiction. S7005 S7005 CATALOG NUMBER Description Mircom’s MS-710APU Advanced Protocol Intelligent Manual Station is made of a high quality, die-cast metal and is available as a dual-action device with key resets and a permanently attached intelligent module. The intelligent manual station has a pair of rotary decimal switches which allows for two digit address setting. Pulling the handle initiates the operation of the intelligent module. The manual station is available with CAT-30 keys and mounts on a standard single gang backbox, Mircom model BB-700 interior surface metal backbox, or BB-700WP weather proof backbox. Mircom’s Advanced Protocol (AP) devices use a high speed communication protocol that greatly increases the speed of communication between the intelligent devices. Mircom’s Advanced Protocol uses a superior group polling method as well as an interrupt feature that provide for a faster response to an alarm condition. In addition, the Advanced Protocol allows for greater system capacity with support for up to 318 devices per SLC circuit. The AP devices are backwards compatible to operate in CLIP mode for legacy system applications. 27 Canada 25 Interchange Way Vaughan, Ontario L4K 5W3 Telephone: (905) 660-4655 Fax: (905) 660-4113 Web page: http://www.mircom.com Email: mail@mircom.com Distributed by: CAT. 5954 Rev. 0 Ordering Information Model Description MS-710APU Advanced Protocol Intelligent Key Resettable Dual Action Manual Station BB-700 Series 700 Interior Surface Mount Backbox, Red Finish BB-700WP Series 700 Weatherproof Surface Mount Backbox, Red Finish NOT TO BE USED FOR INSTALLATION PURPOSES. U.S.A. 4575 Witmer Industrial Estates Niagara Falls, NY 14305 Toll Free: (888) 660-4655 Fax Toll Free: (888) 660-4113 Wiring Diagram Surface Mount Backboxes BB-700 Surface Mount Backbox Dimensions: 5” H x 3.6” W x 2.0” D BB-700WP Weatherproof Surface Mount Backbox Dimensions: 5” H x 3.6” W x 2.2” D MANUAL STATION 4” GANG BOX SCREW SCREW SCREW HOLE BACK OF MANUAL STATION SCREW HOLE FROM TO NEXT STATION OR END OF LINE DEVICE -BLACK +RED}- -+ + ADDRESSABLE MODULE PREVIOUS STATION }Mounting Diagram Specifications Dimensions 4.93” H x 3.56” W x 2.9” D Nominal Operating Voltage 15–32 VDC Maximum Alarm Current @ 24V 600 μA Average Operating Current @ 24V 400 μA 28 Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specifications and models and also to discontinue models. 5952 NOT TO BE USED FOR INSTALLATION PURPOSES. S6295 S6965 7271-1477:0159 (MIX-1251AP)7272-1477:0161 (MIX-2251AP/TAP/TMAP) CATALOG NUMBER Description Mircom's low profile intelligent plug-in smoke detectors with integral communications provide features that surpass conventional detectors. Sensitivity is continuously monitored and reported to the panel where the desired detector sensitivity can be programmed. Point ID capability allows each detector’s address to be set with decade address switches, providing exact detector locations for selective maintenance when chamber contamination reaches an unacceptable level. Mircom’s Advanced Protocol (AP) devices use a high speed communication protocol that greatly increases the speed of communication between the intelligent devices. Mircom’s Advanced Protocol uses a superior group polling method as well as an interrupt feature that provide for a faster response to an alarm condition. In addition, the Advanced Protocol allows for greater system capacity with support for up to 318 devices per SLC circuit. The AP devices are backwards compatible to operate in CLIP mode for legacy system applications. MIX-1251AP Intelligent Ionization Smoke Sensor The MIX-1251AP ionization sensor incorporates a unique single source, dual chamber design to respond quickly and dependably to a broad range of fires. MIX-2251AP Intelligent Photoelectric Smoke Sensor The MIX-2251AP provides a unique optical sensing chamber that senses smoke produced by a wide range of combustion sources. Model MIX-2251AP sensor mounted in a B210LP base Features • Sleek, low profile design • Available with photoelectric or ionization technology • Photoelectric detectors are available with additional fixed temperature detection • Dual LEDs indicate communications and activate steady when in alarm • Low profile base provides easy interchangeability • Low standby current • Rotary switches for direct-dial entry of address. Each unit can have address set for 01-159 for Advanced Protocol mode and 01-99 for CLIP mode • Magnetic test feature • Superior EMI protection • Sealed against dirt, insects, and back pressure ADVANCED PROTOCOL INTELLIGENT SMOKE SENSORS MIX-1251AP/MIX-2251AP MIX-2251TAP Intelligent Photoelectric Smoke Sensor with 135°F Fixed Temperature Heat Detector The MIX-2251TAP adds dual electronic thermistors to the MIX-2251AP to provide 135°F (57°C) fixed temperature thermal sensing. MIX-2251TMAP Intelligent AcclimateTM Multicriteria Smoke Sensor The MIX-2251TMAP is a photoelectric smoke detector with supplementary 135°F thermal. Also known as Acclimate™, it uses advanced on-board software to combine the signals from the photo and thermal elements. The MIX-2251TMAP is a true multicriteria detector capable of rejecting nuisance sources, but still responding quickly to real fires. Acclimate has the capability of adjusting its sensitivity according to the type of environment that it is installed in.and rate- of-rise thermal detection. These thermal detectors provide cost effective, intelligent property protection in a variety of applications. 29 Canada 25 Interchange Way Vaughan, Ontario L4K 5W3 Telephone: (905) 660-4655 Fax: (905) 660-4113 Web page: http://www.mircom.com Email: mail@mircom.com Distributed by: CAT. 5952 Rev. 0 NOT TO BE USED FOR INSTALLATION PURPOSES. U.S.A. 4575 Witmer Industrial Estates Niagara Falls, NY 14305 Toll Free: (888) 660-4655 Fax Toll Free: (888) 660-4113 Specifications Model Description Intelligent Smoke Sensors MIX-1251AP Intelligent Ionization Smoke Sensor MIX-2251AP Intelligent Photoelectric Smoke Sensor MIX-2251TAP Intelligent Photoelectric Sensor with 135°F Fixed Temperature Heat Detector MIX-2251TMAP Intelligent Acclimate TM Multicriteria Smoke Sensor Bases B501 Intelligent Flangeless Mounting Base B210LP Intelligent Flanged Mounting Base B224RB Intelligent Relay Base B224BI Intelligent Isolator Base B200SR Intelligent Standard Sounder Base (Compatible wih B501BH Series) Accessories RA-100Z Remote LED Annunciator Add suffix "A" for ULC listed model. Ordering Information Voltage Range 15 to 32 VDC Standby Current 300 uA @ 24 VDC (one communication every 5 sec. with LED blink enabled) LED Current (max.) 6.5 mA @ 24 VDC (on) Height 2.0 inches (51 mm) Diameter 6.1 inches (155 mm) installed in B210LP Base 4.1 inches (104 mm) installed in B501 Base Shipping Weight Photoelectric models: 5.2 oz. (147 g) Ionization model: 5.4 oz. (153 g) Operating Humidity Range 10% - 93% non-condensing Operating Temperature Range MIX-1251AP/MIX-2251AP: 32°F to 120°F (0°C to 49°C) MIX-2251TAP/MIX-2251TMAP: 32°F to 100°F (0°C to 38°C) UL Listed Velocity Range Ion: 0 - 1200 fpm (0 - 6.1 m/sec) Photo/Photo with Thermal: 0 - 4000 fpm (0 - 20 m/sec) (suitable for installation in ducts) 30 ADVANCED PROTOCOL INTELLIGENT THERMAL SENSORS MIX-5251AP/RAP/HAP Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specifications and models and also to discontinue models. 5953 NOT TO BE USED FOR INSTALLATION PURPOSES. S6299 S7498 7270-1477:0160 CATALOG NUMBER Description Mircom’s low profile intelligent plug-in thernal detectors with integral communications provide features that surpass conventional detectors. Point ID capability allows each detector’s address to be set with decade address switches, providing exact detector locations. These intelligent sensors utilize a state-of-the-art thermistor sensing circuit for fast response and are designed to provide open area protection with 50 foot spacing capability. Mircom’s Advanced Protocol (AP) devices use a high speed communication protocol that greatly increases the speed of communication between the intelligent devices. Mircom’s Advanced Protocol uses a superior group polling method as well as an interrupt feature that provide for a faster response to an alarm condition. In addition, the Advanced Protocol allows for greater system capacity with support for up to 318 devices per SLC circuit. The AP devices are backwards compatible to operate in CLIP mode for legacy system applications. MIX-5251AP Intelligent Heat Detector, 135°F Fixed Temperature The MIX-5251AP uses an innovative thermistor sensing circuit to produce 135°F fixed temperature detection in a low profile package. This thermal detector provides cost effective, intelligent property protection in a variety of applications. MIX-5251RAP Intelligent Heat Detector, 135°F fixed temperature with Rate-of-Rise Detection The MIX-5251RAP provides both 135°F fixed and rate-of-rise thermal detection. This thermal detector provides cost effective, intelligent property protection in a variety of applications. MIX-5251HAP Intelligent High Temperature Heat Detector, 190°F Fixed Temperature The MIX-5251HAP provides 190°F (88°C) fixed temperature detection for high temperature applications. Model MIX-5251AP sensor mounted in a B210LP base Features • Sleek, low profile design • Available as 135°F fixed temperature, 135°F fixed temperature with rate-of-rise detection and high temperature 190°F fixed temperature • Dual LEDs indicate communications and activate steady when in alarm • Low profile base provides easy interchangeability • Low standby current • Rotary switches for direct-dial entry of address. Each unit can have address set for 01-159 for Advanced Protocol mode and 01-99 for CLIP mode • Superior EMI protection • Sealed against dirt, insects, and back pressure 31 Canada 25 Interchange Way Vaughan, Ontario L4K 5W3 Telephone: (905) 660-4655 Fax: (905) 660-4113 Web page: http://www.mircom.com Email: mail@mircom.com Distributed by: CAT. 5953 Rev. 0 NOT TO BE USED FOR INSTALLATION PURPOSES. U.S.A. 4575 Witmer Industrial Estates Niagara Falls, NY 14305 Toll Free: (888) 660-4655 Fax Toll Free: (888) 660-4113 Specifications Model Description Intelligent Heat Sensors MIX-5251AP Intelligent Heat Detector, 135°F Fixed Temperature MIX-5251RAP Intelligent Heat Detector, 135°F Fixed Temperature with Rate-of-Rise Detection MIX-5251HAP Intelligent High Temperature Heat Detector, 190°F Fixed Temperature Bases B501 Intelligent Flangeless Mounting Base B210LP Intelligent Flanged Mounting Base B224RB Intelligent Relay Base B224BI Intelligent Isolator Base B200SR Intelligent Standard Sounder Base (Compatible wih B501BH Series) Accessories RA-100Z Remote LED Annunciator Add suffix "A" for ULC listed model. Ordering Information Voltage Range 15 - 32 volts DC peak Standby Current 300 uA @ 24 VDC (one communication every 5 sec. with LED enabled) LED Current (max.) 6.5 mA @ 24 VDC (on) Height 2.0 inches (51 mm) Diameter 6.1 inches (155 mm) installed in B210LP Base 4.1 inches (104 mm) installed in B501 Base Shipping Weight 4.8 oz. (137 g) Operating Humidity Range 10% - 93% noncondensing Thermal Ratings Fixed Temperature Setpoint: 135°F (57°C) Rate of Rise Detection: 15°F/min. (8.3°C/min.) High Temperature: 190°F (88°C) Operating Temperature Range MIX-5251AP/MIX-5251RAP: -4°F to 100°F (-20°C to 38°C) MIX-5251HAP: -4°F to 150°F (-20°C to 66°C) 32 INTELLIGENT NON-RELAY PHOTOELECTRIC DUCT SMOKE DETECTOR DNR Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specifications and models and also to discontinue models. 5932 NOT TO BE USED FOR INSTALLATION PURPOSES. CATALOG NUMBER Features Photoelectric, integrated low-flow technology• Air velocity rating from 100 ft/min to 4000ft/min • (0.5m/s to 20.32m/sec) Versatile mounting options: square or rectangular • configuration Broad ranges for operating temperature (-4°F to • 158°F) and humidity (0% to 95% non-condensing) Patented sampling tube installs from front or back of • the detector with no tools required Cover tamper signal• Increased wiring space with a newly added 3/4-inch • conduit knockout Available space within housing to accommodate • mounting of relay module Easily accessible code wheels on photoelectric • sensor head (sold separately) Clear cover for convenient visual inspection• Remote testing capability• Requires com line power only• NEMA Type 4 UL listed for non-hazardous indoor • and outdoor applications (DNRW only) UV Resistant, UL listed housing and cover material • (DNRW only) Architectural/Engineering Specifications The air duct smoke detector shall be a System Sensor InnovairFlex™ DNR Intelligent Non-Relay Photoelectric Duct Smoke Detector and DNRW Watertight NEMA4 Duct Smoke Detector. The detector housing shall be UL listed per UL 268A specifically for use in air handling systems. The flexible housing of the duct smoke detector fits both square and rectangular footprints. The detector shall operate at air velocities of 100 ft/min to 4000 ft/min (0.5 m/sec to 20.32 m/sec). The unit shall be capable of providing a trouble signal in the event that the sensor cover is removed or improperly installed. It shall be capable of local testing via magnetic switch or remote testing using the RTS151KEY remote test station. Terminal connections shall be of the strip and clamp method suitable for 12–18 AWG wiring. Description The InnovairFlex DNR intelligent non-relay photoelectric duct smoke detector and DNRW watertight non-relay photoelectric duct smoke detector feature a pivoting housing that fits both square and rectangular footprints capable of mounting to a round or rectangular duct. DNRW duct smoke detector, with its NEMA 4 rating, is listed as a watertight enclosure providing protection against falling dirt, rain, and windblown dust, splashing and hose directed water, allowing operators to use the detector in the most extreme environments. These units sense smoke in the most challenging conditions, operating in airflow speeds of 100 to 4000 feet per minute, temperatures of -4°F to 158°F, and a humidity range of 0 to 95 percent (non-condensing). An improved cover design isolates the sensor head from the lowflow feature for simple maintenance. A cover tamper feature was added to indicate a trouble signal for a removed or improperly installed sensor cover. The InnovairFlex housing provides a ¾ inch conduit knockout and ample space to facilitate easy wiring and mounting of relay module. The InnovairFlex duct smoke detector can be customized to meet local codes and specifications without additional wiring. The new InnovairFlex product line is compatible with all previous Innovair models, including remote test accessories. WARNING: Duct smoke detectors have specific limitations. DUCT SMOKE DETECTORS ARE: NOT a substitute for an open area smoke detector, NOT a substitute for early warning detection, and NOT a replacement for a building’s regular fire detection system. Refer to NFPA 72, 90A and CAN/ULC S524 for additional duct smoke detector application information. 33 Canada 25 Interchange Way Vaughan, Ontario L4K 5W3 Telephone: (905) 660-4655 Fax: (905) 660-4113 Web page: http://www.mircom.com Email: mail@mircom.com Distributed by: CAT. 5932 Rev. 1 NOT TO BE USED FOR INSTALLATION PURPOSES. U.S.A. 4575 Witmer Industrial Estates Niagara Falls, NY 14305 Toll Free: (888) 660-4655 Fax Toll Free: (888) 660-4113 Model Description DNR*Intelligent non-relay photoelectric low-flow duct smoke detector housing. Requires photoelectric smoke detector (sold separately). DNRW Watertight intelligent non-relay photoelectric low-flow duct smoke detector housing. (UL Listed only) Requires photoelectric smoke detector (sold separately). MIX-2251B*Addressable low-profile photoelectric smoke detector MIX-2251BR* Remote test capable addressable low-profile photoelectric smoke detector Accessories DCOIL 2-wire remote test coil required with RTS151/RTS151KEY DST3 Metal sampling tube duct widths 2 ft to 4 ft (0.6 to 1.2 m) DST5 Metal sampling tube duct widths 4 ft to 8 ft (1.2 to 2.4 m) DST10 Metal sampling tube duct widths 8 ft to 12 ft (2.4 to 3.7 m) ETX Metal exhaust tube duct width 1ft (0.3m) DH400OE-1 Weatherproof Enclosure RA100Z*Remote annunciator alarm LED RTS151 Remote test station RTS151KEY*Remote test station with key lock * Add suffix “A” for Canadian models.Note: DNR(W) duct detectors with a date code of 0013 or higher do not require a DCOIL or auxiliary 24VDC for remote test applications when used with a remote test capable smoke detector. DNR(W) duct detectors with a data code of 0012 or earlier require a DCOIL and auxiliary power for remote test applications. Ordering Information Accessories RTS151KEY Remote Test Station with Key RTS151 Remote Test Station RA100Z Remote Annunciator A variety of accessories are available, including remote test stations, and several different means of visible and audible system annunciation. Installing the InnovairFlex Sampling Tube DNR(A) Wiring Diagram Accessory Current Loads @ 24 VDC Device Standby Alarm RA100Z(A)0 mA 12 mA Max. RTS151 / RTS151KEY(A)0 mA 12 mA Max. The InnovairFlex sampling tube may be installed from the front or back of the detector. The tube locks securely into place and can be removed by releasing the front or rear locking tab. Physical Specifications Size: (Rectangular)14.38 in (37 cm) Length; 5 in (12.7 cm) Width; 2.5 in (6.36 cm) Depth Size: (Square)7.75 in (19.7 cm) Length; 9 in (22.9 cm) Width; 2.5 in (6.35 cm) Depth Weight: 1.6 lb (0.73 kg) Operating Temp. Range: -4°F to 158°F (-20°C to 70°C) Storage Temp. Range: –22°F to 158°F (–30° to 70°C) Operating Humidity Range: 0% to 95% relative humidity non-condensing Air Duct Velocity: 100 to 4000 ft/min (0.5 to 20.32 m/sec) COMM. LINE (+) UL/ULC//FM LISTED CONTROL PA NEL 1ST DETECTOR IN LOOP 2ND DETECTOR IN LOOP COMM. LINE (–) COMM. LINE 34 SYSTEM SENSOR CARBON MONOXIDE DETECTORS CO1224T/CO1224TR Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specifications and models and also to discontinue models. 5172 NOT TO BE USED FOR INSTALLATION PURPOSES. CATALOG NUMBER Description The System Sensor CO1224T and CO1224TR (round) Carbon Monoxide (CO) Detectors use a highly accurate and reliable electrochemical sensing cell to provide early warning of dangerous CO levels. With RealTest® technology, the CO gas sensing cell used in the CO1224T and CO1224TR CO detectors can be tested using a CO gas agent, fully meeting the requirements of NFPA 720: 2009. Simply put the detector into RealTest mode, spray a small amount of CO into the detector per the installation instructions, and within seconds the detector will alarm, indicating successful gas entry. (See the reverse page or the user manual for complete instructions.) When dangerous amounts of CO are detected, the CO1224T and CO1224TR detectors alert residents by sounding and flashing a temp 4 signal alarm. With 24/7 central station monitoring, residents are guaranteed protection whether they are away from home, sleeping, or already suffering from the effects of CO. The CO1224T and CO1224TR are designed for system operation. These detectors are fully listed to UL 2075 and offer a code-required trouble relay to send a sensor failure or end-of-life signal to the control panel and the central station. The CO1224T and CO1224TR also use SEMS-type terminal Philips head screws for quicker and more positive wiring connections and code-required wiring supervision. Features RealTest• ® enables a functional test using canned CO Full compliance with UL 2075• A code-required trouble relay• Wiring supervision with SEMS terminals• A six-year end-of-life timer• 12/24 VDC• A low current draw of 20 mA in standby and 40 • mA in alarm Versatile mounting for wall and ceiling• Accurate and reliable electrochemical sensing • technology Optional CO-PLATE CO Detector Replacement • Plate to upgrade previously installed competitor detectors to the CO1224T With a low current draw, these detectors enable more devices to be connected to the panel, limiting the need to purchase extra power supplies or more expensive panels. As 12/24 VDC detectors, the CO1224T and CO1224TR will operate on most industry security and fire alarm control panels. Architectural/Engineering Specifications Carbon monoxide detector shall be a System Sensor model number CO1224T or CO1224TR listed to Underwriters Laboratories UL 2075 for Gas and Vapor Detectors and Sensors. The detector shall be equipped with a sounder and a trouble relay. The detector’s base shall be able to mount to a single-gang electrical box or direct (surface) mount to the wall or ceiling. Wiring connections shall be made by means of SEMS screws. The detector shall provide dual color LED indication that blinks to indicate normal standby, alarm, or end- of-life. When the sensor supervision is in a trouble condition, the detector shall send a trouble signal to the panel. When the detector gives a trouble or end-of- life signal, the detector shall be replaced. The detector shall provide a means to test CO gas entry into the CO sensing cell. The detector shall provide this with a test mode that accepts CO gas from a test agent and alarms immediately upon sensing CO entry. 35 Canada 25 Interchange Way Vaughan, Ontario L4K 5W3 Telephone: (905) 660-4655 Fax: (905) 660-4113 Web page: http://www.mircom.com Email: mail@mircom.com Distributed by: CAT. 5172 Rev. 3 NOT TO BE USED FOR INSTALLATION PURPOSES. U.S.A. 4575 Witmer Industrial Estates Niagara Falls, NY 14305 Toll Free: (888) 660-4655 Fax Toll Free: (888) 660-4113 Operation Mode Green LED Red LED Sounder Normal (standby)Blink 1 per minute —— Alarm —Blink in temp 4 pattern Sound in temp 4 pattern Operation Modes RealTest® Feature:The System Sensor CO1224T and CO1224TR Carbon Monoxide Detectors with RealTest enable evaluation of the functionality of the CO sensing cell using a canned CO test agent. Push and hold the Test/Hush button for two seconds to enter RealTest mode. The green LED will flash once every second to indicate RealTest mode has started. Spray canned CO agent into the detector. Verify CO sensing at the control panel. The detector will automatically exit RealTest alarm mode after about 20-60 seconds. NOTE: Check with local codes and the AHJ to determine whether or not a functional gas test is desired for an installation. Hush Feature: Pushing the Test/Hush button will silence the sounder for 5 minutes (except in RealTest mode). Trouble Feature:When the detector is in a trouble condition, it will send a trouble signal to the panel. End-of-life Timer:After the detector’s internal sensor has reached the end of its life, a trouble signal will be sent to the panel. This will indicate that it is time to replace the detector. An electrochemical carbon monoxide detector lifespan is approximately six years, and the detector must be replaced by the date marked on the inside of the product. CO-PLATE:System Sensor also offers the CO-PLATE CO Detector Replacement Plate to cover the footprint (when necessary) of previously installed competitive carbon monoxide detectors that require replacement.CO-PLATE Electrical Specifications Operating Voltage 12/24 VDC Audible Signal 85 dB in alarm Standby Current 20 mA Alarm Current 40 mA (75 mA test) Alarm Contact Ratings 0.5 A @ 30 VDC Trouble Contact Ratings 0.5 A @ 30 VDC Physical Specifications Size CO1224T Length: 5.1˝, Width: 3.3˝, Height: 1.3˝ CO1224TR Diameter: 6”, Height: 1.3” Approximate Weight CO1224T: 7 oz; CO1224TR: 11 oz Operating Temperature Range 32° – 104° F (0° – 40° C) Operating Humidity Range 22 – 90% RH Input Terminals 14 – 22 AWG Mounting Single-gang back box; surface mount to wall or ceiling Model Description CO1224T 12/24 volt, 4-wire system-monitored carbon monoxide detector with RealTest® Technology CO1224TR 12/24 volt, 4-wire system-monitored round carbon monoxide detector with RealTest® Technology CO-PLATE CO detector replacement plate to cover the footprint of previously installed competitive detectors as necessary Ordering Information 36 MR-100, 200 SERIES MULTI-VOLTAGE CONTROL RELAYS PRODUCT DESCRIPTION The MR Series Multivoltage Control Relays offer SPDT or DPDT 10 Amp resistive contacts which may be operated by one of four input control voltages. A single relay may be energized from a voltage source of 24VDC, 24VAC, 120VAC or 230VAC by wiring to appropriate input terminals. Each relay position contains a red LED which indicates the relay coil is energized. Relays may be “snapped apart” from a standard 4 module assembly and used independently. These Devices are Ideal for applications where local contacts are required for system status, remote contacts for control of electrical loads and general purpose switching. They are suitable for use with HVAC, Temperature Control, Fire Alarm, Security, Energy Management and Lighting Control Systems. FEATURES v Relays may be energized from a voltage source of 18 to 35VDC or VAC, 120VAC or 230VAC v Each relay position contains a red LED, which illuminates when the coil is energized. This provides a time saving device when checking an installed system – no metering is required v Single, dual or triple relay modules may be “snapped apart” from standard 4-position master v DC control inputs are polarized v For continuous duty use at 24VAC, 24VDC, 120VAC, or 230VAC v Available in dust resistant enclosures with LED viewing port(s) v /C versions mounted in enclosures v /C/R versions with red covers for NYC and other uses v /T versions come complete with track mounting hardware which facilitates installation in standard cabinets v UL recognized relays rated at 10,000,000 mechanical operations v UL listed as Control Unit Accessory WIRING(TYPICAL FOR ONE MODULE POSITION) Distributed By:Air Products and Controls is a Brand of Apollo America 25 Corporate Drive Auburn Hills, MI 48326 (248) 332-3900 Phone (888) 332-2241 Toll free (248) 332-8807 Fax www.ap-c.com MEA ACCEPTED CSFM LISTED You in Control ANDAIR PRODUCTS CONTROLS WIRING AND APPLICATION DIAGRAMS MR-200 SERIES MR-100 SERIES WIRING AND APPLICATION DIAGRAMS MR-200 SERIES MR-100 SERIES © Air Products and Controls Inc. 2006 1749 East Highwood Pontiac, MI 48340 Ph. (248) 332-3900 Fax (248) 332-8807 www.ap-c.com WIRING LOAD POWER SOURCE LOAD -/N +/AC+/AC -/N CAUTION: DE-ENERGIZE ALL POWER BEFORE INSTALLATION OR SERVICE! NC C NO ON MR-101 SPDT CONTACT RESISTIVE: 7A @ 30VDC, 10A @ 125VAC, 7A @ 250VAC INDUCTIVE: .25HP 125/250VAC (N.C.), .33 HP 125/250VAC (N.O.) RELAY ENERGIZED LED INPUT CONTROL VOLTAGES FOR ADDITIONAL APPLICATION INFORMATION AND/OR ASSISTANCE, PLEASE CONTACT OUR TECHNICAL SUPPORT HOTLINE. (888) 332-2241 (TYPICAL FOR ONE MODULE POSITION) 0 18/24 115 230 L1 H A.C.A.C. N L2 (+)(-) NC C NO ON MR-201 DPDT CONTACTS RESISTIVE: 7A @ 30VDC, 10A @ 125VAC, 7A @ 250VAC INDUCTIVE: .25HP 125/250VAC (N.C.), .33 HP 125/250VAC (N.O.) RELAY ENERGIZED LED NC C NO INPUT CONTROL VOLTAGES 0 18/24 115 230 L1 H A.C.A.C. N L2 (+)(-) RECOGNIZED COMPONENT WHEN RELAY COIL ENERGIZES, “NC” CONTACTS ARE SWITCHED TO OPEN POSITION, REMOVING POWER TO TURN OFF LOAD APPLICATION EXAMPLE NC C NO ON 0 18/24 115 230 RELAY POWER SUPPLY -/N +/AC MEA ACCEPTED CSFM LISTED RELAY OUTPUTS UL LISTED FOR “COMMON” USE NOTE: THE INPUT CURRENT SHALL NOT EXCEED THE MARKED RATING OF THE PRODUCT INST APD0021 F060407 Issue 1 24VDC @ 15mA 120VAC @ 21mA 24VAC @ 48mA 230VAC @ 19mA 24VDC @ 28mA 120VAC @ 45mA 24VAC @ 69mA 230VAC @ 36mA NOTE: INPUT POWER SUPPLY SHOULD BE UL LISTED FOR FIRE PROTECTIVE SIGNALING SYSTEMS WHEN USED IN FIRE ALARM APPLICATIONS NOTE: DC COIL INPUT IS POLARIZED © Air Products and Controls Inc. 2006 1749 East Highwood Pontiac, MI 48340 Ph. (248) 332-3900 Fax (248) 332-8807 www.ap-c.com WIRING LOAD POWER SOURCE LOAD -/N +/AC+/AC -/N CAUTION: DE-ENERGIZE ALL POWER BEFORE INSTALLATION OR SERVICE! NC C NO ON MR-101 SPDT CONTACT RESISTIVE: 7A @ 30VDC, 10A @ 125VAC, 7A @ 250VAC INDUCTIVE: .25HP 125/250VAC (N.C.), .33 HP 125/250VAC (N.O.) RELAY ENERGIZED LED INPUT CONTROL VOLTAGES FOR ADDITIONAL APPLICATION INFORMATION AND/OR ASSISTANCE, PLEASE CONTACT OUR TECHNICAL SUPPORT HOTLINE. (888) 332-2241 (TYPICAL FOR ONE MODULE POSITION) 0 18/24 115 230 L1 H A.C.A.C. N L2 (+)(-) NC C NO ON MR-201 DPDT CONTACTS RESISTIVE: 7A @ 30VDC, 10A @ 125VAC, 7A @ 250VAC INDUCTIVE: .25HP 125/250VAC (N.C.), .33 HP 125/250VAC (N.O.) RELAY ENERGIZED LED NC C NO INPUT CONTROL VOLTAGES 0 18/24 115 230 L1 H A.C.A.C. N L2 (+)(-) RECOGNIZED COMPONENT WHEN RELAY COIL ENERGIZES, “NC” CONTACTS ARE SWITCHED TO OPEN POSITION, REMOVING POWER TO TURN OFF LOAD APPLICATION EXAMPLE NC C NO ON 0 18/24 115 230 RELAY POWER SUPPLY -/N +/AC MEA ACCEPTED CSFM LISTED RELAY OUTPUTS UL LISTED FOR “COMMON” USE NOTE: THE INPUT CURRENT SHALL NOT EXCEED THE MARKED RATING OF THE PRODUCT INST APD0021 F060407 Issue 1 24VDC @ 15mA 120VAC @ 21mA 24VAC @ 48mA 230VAC @ 19mA 24VDC @ 28mA 120VAC @ 45mA 24VAC @ 69mA 230VAC @ 36mA NOTE: INPUT POWER SUPPLY SHOULD BE UL LISTED FOR FIRE PROTECTIVE SIGNALING SYSTEMS WHEN USED IN FIRE ALARM APPLICATIONS NOTE: DC COIL INPUT IS POLARIZED NOTE: DC COIL INPUT IS POLARIZED NOTE: DC COIL INPUT IS POLARIZED WIRING AND APPLICATION DIAGRAMS MR-200 SERIES MR-100 SERIES WIRING AND APPLICATION DIAGRAMS MR-200 SERIES MR-100 SERIES © Air Products and Controls Inc. 2006 1749 East Highwood Pontiac, MI 48340 Ph. (248) 332-3900 Fax (248) 332-8807 www.ap-c.com WIRING LOAD POWER SOURCE LOAD -/N +/AC+/AC -/N CAUTION: DE-ENERGIZE ALL POWER BEFORE INSTALLATION OR SERVICE! NC C NO ON MR-101 SPDT CONTACT RESISTIVE: 7A @ 30VDC, 10A @ 125VAC, 7A @ 250VAC INDUCTIVE: .25HP 125/250VAC (N.C.), .33 HP 125/250VAC (N.O.) RELAY ENERGIZED LED INPUT CONTROL VOLTAGES FOR ADDITIONAL APPLICATION INFORMATION AND/OR ASSISTANCE, PLEASE CONTACT OUR TECHNICAL SUPPORT HOTLINE. (888) 332-2241 (TYPICAL FOR ONE MODULE POSITION) 0 18/24 115 230 L1 H A.C.A.C. N L2 (+)(-) NC C NO ON MR-201 DPDT CONTACTS RESISTIVE: 7A @ 30VDC, 10A @ 125VAC, 7A @ 250VAC INDUCTIVE: .25HP 125/250VAC (N.C.), .33 HP 125/250VAC (N.O.) RELAY ENERGIZED LED NC C NO INPUT CONTROL VOLTAGES 0 18/24 115 230 L1 H A.C.A.C. N L2 (+)(-) RECOGNIZED COMPONENT WHEN RELAY COIL ENERGIZES, “NC” CONTACTS ARE SWITCHED TO OPEN POSITION, REMOVING POWER TO TURN OFF LOAD APPLICATION EXAMPLE NC C NO ON 0 18/24 115 230 RELAY POWER SUPPLY -/N +/AC MEA ACCEPTED CSFM LISTED RELAY OUTPUTS UL LISTED FOR “COMMON” USE NOTE: THE INPUT CURRENT SHALL NOT EXCEED THE MARKED RATING OF THE PRODUCT INST APD0021 F060407 Issue 1 24VDC @ 15mA 120VAC @ 21mA 24VAC @ 48mA 230VAC @ 19mA 24VDC @ 28mA 120VAC @ 45mA 24VAC @ 69mA 230VAC @ 36mA NOTE: INPUT POWER SUPPLY SHOULD BE UL LISTED FOR FIRE PROTECTIVE SIGNALING SYSTEMS WHEN USED IN FIRE ALARM APPLICATIONS NOTE: DC COIL INPUT IS POLARIZED © Air Products and Controls Inc. 2006 1749 East Highwood Pontiac, MI 48340 Ph. (248) 332-3900 Fax (248) 332-8807 www.ap-c.com WIRING LOAD POWER SOURCE LOAD -/N +/AC+/AC -/N CAUTION: DE-ENERGIZE ALL POWER BEFORE INSTALLATION OR SERVICE! NC C NO ON MR-101 SPDT CONTACT RESISTIVE: 7A @ 30VDC, 10A @ 125VAC, 7A @ 250VAC INDUCTIVE: .25HP 125/250VAC (N.C.), .33 HP 125/250VAC (N.O.) RELAY ENERGIZED LED INPUT CONTROL VOLTAGES FOR ADDITIONAL APPLICATION INFORMATION AND/OR ASSISTANCE, PLEASE CONTACT OUR TECHNICAL SUPPORT HOTLINE. (888) 332-2241 (TYPICAL FOR ONE MODULE POSITION) 0 18/24 115 230 L1 H A.C.A.C. N L2 (+)(-) NC C NO ON MR-201 DPDT CONTACTS RESISTIVE: 7A @ 30VDC, 10A @ 125VAC, 7A @ 250VAC INDUCTIVE: .25HP 125/250VAC (N.C.), .33 HP 125/250VAC (N.O.) RELAY ENERGIZED LED NC C NO INPUT CONTROL VOLTAGES 0 18/24 115 230 L1 H A.C.A.C. N L2 (+)(-) RECOGNIZED COMPONENT WHEN RELAY COIL ENERGIZES, “NC” CONTACTS ARE SWITCHED TO OPEN POSITION, REMOVING POWER TO TURN OFF LOAD APPLICATION EXAMPLE NC C NO ON 0 18/24 115 230 RELAY POWER SUPPLY -/N +/AC MEA ACCEPTED CSFM LISTED RELAY OUTPUTS UL LISTED FOR “COMMON” USE NOTE: THE INPUT CURRENT SHALL NOT EXCEED THE MARKED RATING OF THE PRODUCT INST APD0021 F060407 Issue 1 24VDC @ 15mA 120VAC @ 21mA 24VAC @ 48mA 230VAC @ 19mA 24VDC @ 28mA 120VAC @ 45mA 24VAC @ 69mA 230VAC @ 36mA NOTE: INPUT POWER SUPPLY SHOULD BE UL LISTED FOR FIRE PROTECTIVE SIGNALING SYSTEMS WHEN USED IN FIRE ALARM APPLICATIONS NOTE: DC COIL INPUT IS POLARIZED NOTE: DC COIL INPUT IS POLARIZED NOTE: DC COIL INPUT IS POLARIZED 37 DS-RL-2 D120607© Air Products and Controls Inc. 2012 NOTICE: The information contained in this document is intended only as a summary and is subject to change without notice. The products described have specific instructional/installation documentation, which covers various technical, approval, code, limitation and liability information. Copies of this documentation along with any gen- eral product warning and limitation documents, which also contain important information, are provided with the product and are also available from Air Products and Controls Inc. The information contained in all of these documents should be considered before specifying or using the products. Any example applications shown are subject to the most current enforced local/national codes, standards, approvals, certifications, and/or the authority having jurisdiction. All of these resources, as well as the specific manufacturer of any shown or mentioned related equipment, should be consulted prior to any implementation. For further information or assistance concerning the products, contact Air Products and Controls Inc. Air Products and Controls Inc. reserves the right to change any and all documentation without notice. PRODUCT SPECIFICATIONS MODEL NUMBER: MR-101/T MR-101/C MR-101/C/R MR-104/T MR-104/C MR-104/C/R MR-201/T MR-201/C MR-201/C/R MR-204/T MR-204/C MR-204/C/R COIL VOLTAGE: MR-100: 24(18-35)VDC, 24(18-35)VAC, 120VAC, 230VAC MR-200: 24(18-35)VDC, 24VAC, 120VAC, 230VAC (Pull in voltage: 75% of nominal max. @ 25°C; Drop out voltage: 25% of nominal min. @ 25°C) POLARIZED: DC input only ENERGIZED LED INDICATOR: One per module position CURRENT REQUIREMENT: Per module position: MR-100 Series = 48mA max/ MR-200 Series = 69mA max CONTACT RATINGS: 7A @ 28VDC / 10A (NO:1/6HP, NC:1/8HP) @ 120VAC / 7A @ 230VAC CONTACT CONSTRUCTION: Dry Form “C” ENVIRONMENTAL: 32°F to 120°F (0°C to 49°C) @ 85% RH (@ 32°F), Non-condensing, Non-freezing WIRING: Solid or stranded; #14 to #22 AWG terminals /T VERSIONS: 3.5” wide, low profile plastic snap track provided with mounting screws /C VERSIONS: Backbox: 18ga CRS, plated with 1/2” conduit knockouts top and bottom *UOXX=Control Unit Accessories, System; 2=Component; 7=Certified for Canada MODULE POSITIONS 1 1 1 4 4 4 1 1 1 4 4 4 CONTACT CONFIGURATION PER POSITION SPDT SPDT SPDT SPDT SPDT SPDT DPDT DPDT DPDT DPDT DPDT DPDT TRACK MOUNTED H X W X D 3.25” (82mm) 2.125” (54mm) 1.50” (38mm) 3.25” (82mm) 8.50” (215mm) 1.50” (38mm) 3.25” (82mm) 2.125” (54mm) 1.50” (38mm) 3.25” (82mm) 8.5” (215mm) 1.50” (38mm) ENCLOSURE MOUNTED H X W X D 5.125” (130mm) 3.125” (79mm) 2.50” (63mm) 5.125” (130mm) 9.50” (241mm) 2.50” (63mm) 5.125” (130mm) 3.125” (79mm) 2.50” (63mm) 5.125” (130mm) 9.50” (241mm) 2.50” (63mm) COVER MATERIAL Grey ABS-94VO Plastic Red ABS-94VO Plastic Plated 18ga CRS Red 18ga CRS Grey ABS-94VO Plastic Red ABS-94VO Plastic Plated 18ga CRS Red 18ga CRS UL* FILE S3403 UOXX2 UOXX UOXX2 UOXX7 UOXX2 UOXX UOXX2 UOXX7 UOXX2 UOXX UOXX2 UOXX7 UOXX2 UOXX UOXX2 UOXX7 MEA FILE 73-92-E Vol. 14 Vol. 22 Vol. 14 Vol. 16 Vol. 22 Vol. 16 CSFM FILE 7300-1004 :106 :101 :106 :101 :106 :101 :106 :101 38 Agency Listings 7125-1653:0504 7135-1653:0503 S5512 S4011 FM approved except for ALERT models 3057383, 3057072 Features • Updated Modern Aesthetics • Small profile devices for Horns and Horn Strobes • Plug-in design with minimal intrusion into the back box • Tamper-resistant construction • Automatic selection of 12- or 24-volt operation at 15 and 30 candela • Field-selectable candela settings on wall units: 15, 30, 75, 95, 110, 135, and 185 • Horn rated at 88+ dBA at 16 volts • Rotary switch for horn tone and two volume selections • Mounting plate for all standard and all compact wall units • Mounting plate shorting spring checks wiring continuity before device installation • Electrically Compatible with legacy SpectrAlert and SpectAlert Advance devices • Compatible with MDL3 sync module • Listed for wall mounting only The System Sensor L-Series offers the most versatile and easy-to-use line of horns, strobes, and horn strobes in the industry with lower current draws and modern aesthetics. With white and red plastic housings, standard and compact devices, and plain, FIRE, and FUEGO-printed devices, System Sensor L-Series can meet virtually any application requirement. The L-Series line of wall-mount horns, strobes, and horn strobes include a variety of features that increase their application versatility while simplifying installation. All devices feature plug-in designs with minimal intrusion into the back box, making installations fast and foolproof while virtually eliminating costly and time-consuming ground faults. To further simplify installation and protect devices from construction damage, the L-Series utilizes a universal mounting plate for all models with an onboard shorting spring, so installers can test wiring continuity before the device is installed. Installers can also easily adapt devices to a suit a wide range of application requirements using field-selectable candela settings, automatic selection of 12- or 24-volt operation, and a rotary switch for horn tones with two volume selections. Indoor Selectable- Output Horns, Strobes, and Horn Strobes for Wall Applications System Sensor L-Series audible visible notification products are rich with features guaranteed to cut installation times and maximize profits with lower current draw and modern aesthetics. 39 L-Series Specifications Architect/Engineer Specifications General L-Series standard horns, strobes, and horn strobes shall mount to a standard 2 x 4 x 1 7/8-inch back box, 4 × 4 × 1½-inch back box, 4-inch octagon back box, or double-gang back box. L-Series compact products shall mount to a single-gang 2 × 4 × 17⁄8 -inch back box. A universal mounting plate shall be used for mounting ceiling and wall products for all standard models and a separate universal mounting plate shall be used for mounting wall compact models. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, L-Series products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 30, 75, 95, 110, 135, and 185. Strobe The strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have two audibility options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns on horn strobe models over a single pair of wires. The module shall mount to a 411 ⁄16 × 411 ⁄16 × 21 ⁄8-inch back box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F (0°C to 49°C) Humidity Range 10 to 93% non-condensing Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC or regulated 24 DC/FWR1,2 Operating Voltage Range 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Operating Voltage Range MDL3 Sync Module 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Wall-Mount Dimensions (including lens)5.6˝ L × 4.7˝ W × 1.91˝ D (143 mm L × 119 mm W × 49 mm D) Compact Wall-Mount Dimensions (including lens)5.26” L x 3.46” W x 1.91” D (133 mm L x 88 mm W x 49 mm D) Horn Dimensions 5.6˝ L × 4.7˝ W × 1.25˝ D (143 mm L × 119 mm W × 32 mm D) Compact Horn Dimensions 5.25” L x 3.45” W x 1.25” D (133mm L x 88mm W x 32mm D) 1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs. 2. Strobe products will operate at 12 V nominal only for 15 cd and 30 cd. 40 Horn and Horn Strobe Output (dBA) Switch Position Sound Pattern dB 8–17.5 Volts 16–33 Volts DC DC FWR 1 Temporal High 84 89 89 2 Temporal Low 75 83 83 3 Non-Temporal High 85 90 90 4 Non-Temporal Low 76 84 84 5 3.1 KHz Temporal High 83 88 88 6 3.1 KHz Temporal Low 76 82 82 7 3.1 KHz Non-Temporal High 84 89 89 8 3.1 KHz Non-Temporal Low 77 83 83 9*Coded High 85 90 90 10*3.1 KHz Coded High 84 89 89 * Settings 9 and 10 are not available on the 2-wire horn strobes. UL Max. Strobe Current Draw (mA RMS) Candela 8–17.5 Volts 16–33 Volts DC DC FWR Candela Range 15 88 43 60 30 143 63 83 75 N/A 107 136 95 N/A 121 155 110 N/A 148 179 135 N/A 172 209 185 N/A 222 257 UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, Candela Range (15–115 cd) DC Input 8-17.5 Volts 16-33 Volts 15cd 30cd 15cd 30cd 75cd 95cd 110cd 135cd 185cd Temporal High 98 158 54 74 121 142 162 196 245 Temporal Low 93 154 44 65 111 133 157 184 235 Non-Temporal High 106 166 73 94 139 160 182 211 262 Non-Temportal Low 93 156 51 71 119 139 162 190 239 3.1K Temporal High 93 156 53 73 119 140 164 190 242 3.1K Temporal Low 91 154 45 66 112 133 160 185 235 3.1K Non-Temporal High 99 162 69 90 135 157 175 208 261 3.1K Non-Temporal Low 93 156 52 72 119 138 162 192 242 FWR Input 16-33 Volts 15cd 30cd 75cd 95cd 110cd 135cd 185cd Temporal High 83 107 156 177 198 234 287 Temporal Low 68 91 145 165 185 223 271 Non-Temporal High 111 135 185 207 230 264 316 Non-Temportal Low 79 104 157 175 197 235 283 3.1K Temporal High 81 105 155 177 196 234 284 3.1K Temporal Low 68 90 145 166 186 222 276 3.1K Non-Temporal High 104 131 177 204 230 264 326 3.1K Non-Temporal Low 77 102 156 177 199 234 291 UL Max. Horn Current Draw (mA RMS) Sound Pattern dB 8–17.5 Volts 16–33 Volts DC DC FWR Temporal High 39 44 54 Temporal Low 28 32 54 Non-Temporal High 43 47 54 Non-Temporal Low 29 32 54 3.1 KHz Temporal High 39 41 54 3.1 KHz Temporal Low 29 32 54 3.1 KHz Non-Temporal High 42 43 54 3.1 KHz Non-Temporal Low 28 29 54 Coded High 43 47 54 3.1 KHz Coded High 42 43 54 UL Current Draw Data Horn Tones and Sound Output Data 41 3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 www.systemsensor.com ©2017 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. AVDS86503 • 03/17 L-Series Dimensions Model Description Wall Horn Strobes P2RL 2-Wire, Horn Strobe, Red P2WL 2-Wire, Horn Strobe, White P2GRL 2-Wire, Compact Horn Strobe, Red P2GWL 2-Wire, Compact Horn Strobe, White P2RL-P 2-Wire, Horn Strobe, Red, Plain P2WL-P 2-Wire, Horn Strobe, White, Plain P2RL-SP 2-Wire, Horn Strobe, Red, FUEGO P2WL-SP 2-Wire, Horn Strobe, White, FUEGO Wall Strobes SRL Strobe, Red SWL Strobe, White SGRL Compact Strobe, Red SGWL Compact Strobe, White SRL-P Strobe, Red, Plain SWL-P Strobe, White, Plain SRL-SP Strobe, Red, FUEGO SWL-CLR-ALERT Strobe, White, ALERT L-Series Ordering Information Notes: All -P models have a plain housing (no “FIRE” marking on cover) All -SP models have “FUEGO” marking on cover All -ALERT models have “ALERT” marking on cover Compact Strobe / Horn Strobe Strobe / Horn Strobe Compact Horn Horn Model Description Horns HRL Horn, Red HWL Horn, White HGRL Compact Horn, Red HGWL Compact Horn, White Accessories TR-2 Universal Wall Trim Ring Red TR-2W Universal Wall Trim Ring White SBBRL Wall Surface Mount Back Box, Red SBBWL Wall Surface Mount Back Box, White SBBGRL Compact Wall Surface Mount Back Box, Red SBBGWL Compact Wall Surface Mount Back Box, White 42 Agency Listings Features • Plug-in design with minimal intrusion into the back box • Tamper-resistant construction • Automatic selection of 12- or 24-volt operation at 15 and 15/75 candela • Field-selectable candela settings on ceiling units: 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185 • Horn rated at 88+ dBA at 16 volts • Rotary switch for horn tone and three volume selections • Universal mounting plate for ceiling units • Mounting plate shorting spring feature checks wiring continuity before device installation • Electrically Compatible with legacy SpectrAlert devices • Compatible with MDL3 sync module • Listed for ceiling or wall mounting The SpectrAlert Advance series offers the most versatile and easy-to-use line of horns, strobes, and horn strobes in the industry. With white and red plastic housings, wall and ceiling mounting options, and plain and FIRE-printed devices, SpectrAlert Advance can meet virtually any application requirement. Like the entire SpectrAlert Advance product line, ceiling-mount strobes and horn strobes include a variety of features that increase their application versatility while simplifying installation. All devices feature a plug-in design with minimal intrusion into the back box, making installations fast and foolproof while virtually eliminating costly and time-consuming ground faults. To further simplify installation, SpectrAlert Advance utilizes a universal mounting plate so you can mount them to a wide array of back boxes. With an onboard shorting spring, installers can test wiring continuity before the device is installed. Installers can also easily adapt devices to a suit a wide range of application requirements using field-selectable candela settings, automatic selection of 12- or 24-volt operation, and a rotary switch for horn tones with three volume selections. Indoor Selectable- Output Strobes and Horn Strobes for Ceiling Applications SpectrAlert® Advance audible visible notification products are rich with features guaranteed to cut installation times and maximize profits. MEA452-05-E3023572 7125-1653:0186 (indoor strobes) 7125-1653:0188 (horn strobes, chime strobes) 7135-1653:0189 (horns, chimes) S4011 (chimes, horn strobes, horns) S5512 (strobes) 43 AVDS10101 SpectrAlert Advance Specifications Architect/Engineer Specifications General SpectrAlert Advance strobes and horn strobes shall mount to a standard 4 × 4 × 1½-inch back box, 4-inch octagon back box, or double- gang back box. Two-wire products shall also mount to a single-gang 2 × 4 × 17⁄8-inch back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185. Strobe The strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have three audibility options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. On four-wire products, the strobe shall be powered independently of the sounder. The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns on horn strobe models over a single pair of wires. The module shall mount to a 4 11 ⁄16 × 4 11 ⁄16 × 2 1⁄8-inch back box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F (0°C to 49°C) Humidity Range 10 to 93% non-condensing Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR1 Operating Voltage Range2 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Operating Voltage Range (MDL3)8.5 to 17.5V (12 V nominal) or 16.5 to 33 V (24V nominal) Input Terminal Wire Gauge 12 to 18 AWG Ceiling-Mount Dimensions (including lens)6.8" diameter × 2.5" high (173 mm diameter × 64 mm high) Ceiling-Mount Surface Mount Back Box Skirt Dimensions (SBBCR, SBBCW) 6.9" diameter x 3.4" high (175 mm diameter x 86 mm high) Notes: 1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs. 2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 15/75 cd. 44 AVDS10101 Horn Strobe Output (dBA) Switch Position Sound Pattern dB 8–17.5 Volts 16–33 Volts 24-Volt Nominal Reverberant Anechoic DC FWR DC FWR DC FWR DC FWR 1 Temporal High 78 78 84 84 88 88 99 98 2 Temporal Medium 74 74 80 80 86 86 96 96 3 Temporal Low 71 73 76 76 83 80 94 89 4 Non-Temporal High 82 82 88 88 93 92 100 100 5 Non-Temporal Medium 78 78 85 85 90 90 98 98 6 Non-Temporal Low 75 75 81 81 88 84 96 92 7†Coded High 82 82 88 88 93 92 101 101 8†Coded Medium 78 78 85 85 90 90 97 98 9†Coded Low 75 75 81 81 88 85 96 92 †Settings 7, 8, and 9 are not available on 2-wire horn strobes. UL Max. Strobe Current Draw (mA RMS) Candela 8–17.5 Volts 16–33 Volts DC FWR DC FWR Standard Candela Range 15 123 128 66 71 15/75 142 148 77 81 30 NA NA 94 96 75 NA NA 158 153 95 NA NA 181 176 110 NA NA 202 195 115 NA NA 210 205 High Candela Range 135 NA NA 228 207 150 NA NA 246 220 177 NA NA 281 251 185 NA NA 286 258 UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, Standard Candela Range (15–115 cd) DC Input 8–17.5 Volts 16–33 Volts 15 15/75 15 15/75 30 75 95 110 115 Temporal High 137 147 79 90 107 176 194 212 218 Temporal Medium 132 144 69 80 97 157 182 201 210 Temporal Low 132 143 66 77 93 154 179 198 207 Non-Temporal High 141 152 91 100 116 176 201 221 229 Non-Temporal Medium 133 145 75 85 102 163 187 207 216 Non-Temporal Low 131 144 68 79 96 156 182 201 210 FWR Input Temporal High 136 155 88 97 112 168 190 210 218 Temporal Medium 129 152 78 88 103 160 184 202 206 Temporal Low 129 151 76 86 101 160 184 194 201 Non-Temporal High 142 161 103 112 126 181 203 221 229 Non-Temporal Medium 134 155 85 95 110 166 189 208 216 Non-Temporal Low 132 154 80 90 105 161 184 202 211 UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, High Candela Range (135–185 cd) DC Input 16–33 Volts FWR Input 16–33 Volts 135 150 177 185 135 150 177 185 Temporal High 245 259 290 297 Temporal High 215 231 258 265 Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258 Temporal Low 232 251 282 292 Temporal Low 207 221 248 256 Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281 Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267 Non-Temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262 UL Current Draw Data Horn Strobe Tones and Sound Output Data 45 3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 ©2015 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. AVDS10102 • 03/15 SpectrAlert Advance Dimensions Model Description Ceiling Horn Strobes PC2R 2-Wire Horn Strobe, Standard cd, Red PC2R-P 2-Wire Horn Strobe, Standard cd, Red, Plain (no “FIRE”) marking PC2RH 2-Wire Horn Strobe, High cd, Red PC2W 2-Wire Horn Strobe, Standard cd, White PC2W-P 2-Wire Horn Strobe, Standard cd, White, Plain (no “FIRE”) marking PC2W-SP 2-Wire Horn Strobe, Standard cd, White, “Fuego” marking PC2WH 2-Wire Horn Strobe, High cd, White PC2WH-P 2-Wire Horn Strobe, High cd, White, Plain (no “FIRE”) marking PC2WH-SP 2-Wire Horn Strobe, High cd, White, “Fuego” PC4R 4-Wire Horn Strobe, Standard cd, Red PC4RH 4-Wire Horn Strobe, High cd, Red PC4W 4-Wire Horn Strobe, Standard cd, White SpectrAlert Advance Ordering Information Notes: All -P models have a plain housing (no “FIRE” marking on cover) All -SP models have “FUEGO” marking on cover “Standard cd” refers to strobes that include 15, 15/75, 30, 75, 95, 110, and 115 candela settings. “High cd” refers to strobes that include 135, 150, 177, and 185 candela settings. 4.7" 5.6" 6.8"Dia. 2.5" 2.5" 5.703" 1.85"4.8" 6.922" dia.2.5" Ceiling-mount horn strobes Ceiling back box surface mount back box Model Description Ceiling Strobes SCR Strobe, Standard cd, Red SCRH Strobe, High cd, Red SCW Strobe, Standard cd, White SCW-P Strobe, Standard cd, White, Plain (no “Fire”) marking SCWH Strobe, High cd, White Accessories SBBCR Surface Mount Back Box, Ceiling, Red SBBCW Surface Mount Back Box, Ceiling, White 46 Agency Listings Features • 520 Hz ± 10% square wave tone • Plug-in design with minimal intrusion into the back box • Tamper-resistant construction • Field-selectable candela settings on wall units: 135, 150, 177, and 185 • Rotary switch for low frequency sounder tone • Universal mounting plate for wall units • Mounting plate shorting spring checks wiring continuity before device installation • Electrically compatible with legacy SpectrAlert devices • Compatible with MDL3 sync module • Listed for ceiling or wall mounting The SpectrAlert Advance series offers the most versatile and easy-to-use line of low frequency sounder and low frequency sounder strobes in the industry. With white and red plastic housings, dual listed for wall and ceiling mounting, SpectrAlert Advance can meet virtually any application requirement. The wall-mount low frequency sounder, and low frequency sounder strobes were designed to address the NFPA 72 sleeping space requirements that require a low frequency notification appliance that operates within frequency range of 520 Hz ± 10% and is of a square wave tone. Like the entire SpectrAlert Advance product line they include a variety of features that increase their application versatility while simplifying installation. All devices feature plug-in designs with minimal intrusion into the back box, making installations fast and foolproof while virtually eliminating costly and time-consuming ground faults. To further simplify installation and protect devices from construction damage, SpectrAlert Advance utilizes a universal mounting plate with an onboard shorting spring, so installers can test wiring continuity before the device is installed. Installers can also easily adapt devices to a suit a wide range of application requirements using field-selectable candela settings, automatic selection of 12- or 24-volt operation, and a rotary switch for 520 Hz low frequency sounder tones. Selectable-Output Low Frequency Sounder and Low Frequency Sounder Strobes for Wall Applications SpectrAlert® Advance audible visible notification products are rich with features guaranteed to cut installation times and maximize profits. 3047563 7135-1653:0223 7125-1653:0224 S4011 (sounder) S5512 (strobes) MEA452-05-E 47 SpectrAlert Advance Specifications Architect/Engineer Specifications General SpectrAlert Advance low frequency sounder and low frequency sounder strobes shall mount to a standard 4 × 4 × 1½-inch back box, 4-inch octagon back box, or double-gang back box. Two-wire products shall also mount to a single-gang 2 × 4 × 17⁄8-inch back box. A universal mounting plate shall be used for mounting products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full- wave rectified unfiltered power supply. Low Frequency Sounder strobes shall have field-selectable candela settings including 135, 150, 177, and 185. The field selectable tones will sound within the frequency range of 520 Hz ±10% square wave tone and have a permanent marking on the housing that reads “low frequency sounder”. Low Frequency Sounder The low frequency sounder shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 464 and shall be approved for fire protective service. The low frequency sounder and the Sync•Circuit™ MDL3 Module accessory, if used, shall be powered from a notification appliance circuit output and shall operate on a nominal 12 or 24 volts (includes fire alarm panels with built in sync). When used with the Sync•Circuit Module MDL3, 12-volt rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt rated notification appliance circuit outputs shall operate between 16.5 to 33 volts. If the notification appliances are not UL 9th edition listed with the corresponding panel or power supply being used, then refer to the compatibility listing of the panel to determine maximum devices on a circuit. The low frequency sounder has an option to switch between temporal three pattern, non-temporal (continuous) pattern and coded supply within the frequency range of 520Hz ± 10% square wave tone. The low frequency sounder shall operate on a coded or non-coded power supply. Low Frequency Sounder Strobe Combination The low frequency sounder strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and UL 464 and shall be approved for fire protective service. The low frequency sounder strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The sounder shall have an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. The low frequency sounder on low frequency sounder strobe models shall operate on a non-coded power supply. The field selectable tones will sound within the frequency range of 520 Hz ±10% square wave tone. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz and low frequency sounder at temporal three. Also, while operating the strobes, the module shall silence the low frequency sounder on low frequency sounder strobe models over a single pair of wires. The module shall mount to a 411 ⁄16 × 411 ⁄16 × 21⁄8-inch back box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F (0°C to 49°C) Humidity Range 10 to 93% non-condensing Frequency Range 520 Hz ± 10% Strobe Flash Rate 1 flash per second Nominal Voltage Low Frequency Sounder Regulated 12 DC/FWR or regulated 24 DC/FWR1 Nominal Voltage Range Low Frequency Sounder Strobe Regulated 24 VDC/FWR1 Operating Voltage Range 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Operating Voltage Range MDL3 Sync Module 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Wall-Mount Dimensions (including lens)6.4 inches L x 4.7 inches W x 2.5 inches D (162 mm L x 119 mm W x 64 mm D) Sounder Dimensions 5.6 inches L × 4.7 inches W × 1.3 inches D (142 mm L × 119 mm W × 33 mm D) Low Frequency Sounder/Strobe with Surface Mount Back Box Dimensions (SBBR, SBBW) 6.4 inches L x 4.7 inches W x 4.3 inches D (162 mm L x 120 mm W x 108 mm D) Low Frequency Sounder with Surface Mount Back Box Dimensions (SBBR, SBBW) 5.7 inches L x 4.8 inches W x 3 inches D (145 mm L x 120 mm W x 76 mm D) Notes: 1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs. 48 Low Frequency Sounder and Low Frequency Sounder Strobe Output (dBA) Switch Position Sound Pattern 8–17.5 Volts 16–33 Volts 24-Volt Nominal Reverberant Anechoic DC FWR DC FWR DC FWR DC FWR 1 Temporal 3 76 76 76 76 76 76 86 86 2 Continuous 80 80 80 80 80 80 90 90 3†Coded 80 80 80 80 80 80 90 90 UL Max. Low Frequency Sounder Current Draw (mA RMS) Sound Pattern dB 8–17.5 Volts 16–33 Volts DC FWR DC FWR Temporal 3 High 191 262 138 166 Continuous High 292 384 138 208 Coded High 292 388 153 205 UL Max. Current Draw (mA RMS), 2-Wire Low Frequency Sounder Strobe, High Candela Range DC Input 16–33 Volts FWR Input 16–33 Volts 135 150 177 185 135 150 177 185 Temporal 3 277 292 325 344 Temporal 3 296 309 343 351 Continuous 337 362 387 417 Continuous 393 395 432 433 UL Current Draw Data Low Frequency Sounder Tones and Sound Output Data † Sounder ratings provided are for continuous voltage as provided by the NAC 49 3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 www.systemsensor.com ©2015 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. AVDS16404 • 1/15 SpectrAlert Advance Dimensions Model Description Wall Low Frequency Sounder Strobes P2RH-LF 2-Wire Low Frequency Sounder Strobe, High cd, Red P2WH-LF 2-Wire Low Frequency Sounder Strobe, High cd, White Low Frequency Sounders HR-LF Low Frequency Sounder, Red HW-LF Low Frequency Sounder, White Accessories SBBR Surface Mount Back Box, Wall, Red SBBW Surface Mount Back Box, Wall, White TR-HS Trim Ring, Wall, Red SpectrAlert Advance Ordering Information Notes: “High cd” refers to strobes that include 135, 150, 177, and 185 candela settings. 4.7 in. 6.4 in. 2.5 in. 4.7 in. 5.6 in. 1.3 in. Wall-mount low frequency sounder strobes Wall-mount low frequency sounder 50 490S/1280 Micro IVStrobe 10/6/16 Mammoth Fire Alarms Incorporated “Servicing the installer before and after the installation.” Sales 978-934-9130 · 1-800-995-9808 · Fax 978-934-9131 176 Walker Street Lowell, MA 01854 www.mammothfire.com MICRO IV STROBE 490S/1280 The MICRO IV strobe family is an enhanced version of the MICROSTROBE featuring a power supply that operates over a wide input voltage range of 12–80VDC or 16–24VAC. The supply has a regulated output so that the lamp brightness and flash remain constant when operated over the rated input voltage range. The power supply is potted in polyurethane for the ultimate in protection from moisture, vibration and exposure to high voltage. The enclosure is all Lexan®, and the plug-in lamp is field replaceable. All units are polarity protected and have built-in filters to protect against radio interference and spike voltages. FEATURES Wide input voltage range Universal mounting Built-in RFI filters 10,000 hour strobe lamp Available in five lens colors Lens has hermetic o-ring seal NEMA 4X SPECIFICATIONS Lamp Type - 5001 Xenon Strobe Lamp Lens Type - 470S-L-xxx (Please Specify Color) Voltage and Amperage - 12-80VDC Draws 0.4A avg. @ 12VDC tapering to 0.05A avg. @ 80VDC Power Supply Output 2.7Watts - 1.9 Joules per Flash Flash Rate - 60 to 80 Flashes per Minute Light Output - Clear 50 Candela eff. Amber 40 Candela eff. Blue 20 Candela eff. Green 20 Candela eff. Red 10 Candela eff. Size and Weight - 5” Tall x 3” Dia. 0.6 lbs. (127 mm) (76 mm) (0.27 kg) ORDERING INFORMATION Strobe - 490S/1280X X= color lens (clear, amber, blue, green, red) Mounting Kit - FMSL/4RA (optional) Shown with optional Mounting Kit 51 Mammoth Fire Alarms JOB NAME:CANAL STREET REALTY Incorporated NORTH BUILDING-SALEM, MA. CONTRACTOR:BRUNELLE BROS. ELECTRIC,INC. 176 Walker St., Lowell, MA 01854-3126 DATE:7/10/2019 12:50 Tel. (978) 934-9130 Sales 1-800-995-9808 Fax (978) 934-9131 LOOP #2 ADDRESS MODULE # OF DEVICES LOCATION/DEVICES TYPE LOGIC OUTPUTS L2S1 5251AP HEAT DETECTOR TOP OF ELEV HOISTWAY HEAT GENERAL ALARM L2S2 2251AP SMOKE DETECTOR 1ST FLOOR UNIT 01 SMK GENERAL ALARM L2S3 2251AP SMOKE DETECTOR 1ST FLOOR UNIT 01 SMK GENERAL ALARM L2S4 2251AP SMOKE DETECTOR 1ST FLOOR STAIR 2 SMK GENERAL ALARM L2S5 2251AP SMOKE DETECTOR 1ST FLOOR UNIT 02 SMK GENERAL ALARM L2S6 2251AP SMOKE DETECTOR 1ST FLOOR UNIT 02 SMK GENERAL ALARM L2S7 2251AP SMOKE DETECTOR 1ST FLOOR ELEC RM SMK GENERAL ALARM L2S8 2251AP SMOKE DET 1ST FLOOR UNIT 03 REAR ENTRY SMK GENERAL ALARM L2S9 2251AP SMOKE DET 1ST FLOOR SPRINKLER ROOM SMK GENERAL ALARM L2S10 2251AP SMOKE DETECTOR 1ST FLOOR UNIT 03 SMK GENERAL ALARM L2S11 2251AP SMOKE DETECTOR 1ST FLOOR UNIT 03 SMK GENERAL ALARM L2S12 2251AP SMOKE DETECTOR 1ST FLOOR UNIT 04 SMK GENERAL ALARM L2S13 2251AP SMOKE DETECTOR 1ST FLOOR UNIT 04 SMK GENERAL ALARM L2S14 2251AP SMOKE DETECTOR 1ST FLOOR STAIR 1 SMK GENERAL ALARM L2S15 2251AP SMOKE DETECTOR 1ST FLOOR ELEV LOBBY SMK GENERAL ALARM L2S16 2251AP SMOKE DETECTOR 1ST FL ELEV MACH RM SMK GENERAL ALARM & RA100Z L2S17 2251AP SMOKE DETECTOR 1ST FLOOR UNIT 05 SMK GENERAL ALARM L2S18 2251AP SMOKE DETECTOR 1ST FLOOR UNIT 05 SMK GENERAL ALARM L2S19 2251AP SMOKE DETECTOR 2ND FLOOR STAIR 1 SMK GENERAL ALARM L2S20 2251AP SMOKE DETECTOR 2ND FLOOR ELEV LOBBY SMK GENERAL ALARM L2S21 2251AP SMOKE DETECTOR 2ND FLOOR CORRIDOR SMK GENERAL ALARM L2S22 2251AP SMOKE DETECTOR 2ND FLOOR CORRIDOR SMK GENERAL ALARM L2S23 2251AP SMOKE DETECTOR 2ND FLOOR CORRIDOR SMK GENERAL ALARM L2S24 2251AP SMOKE DETECTOR 2ND FLOOR ELEC ROOM SMK GENERAL ALARM & RA100Z L2S25 2251AP SMOKE DETECTOR 2ND FLOOR UTILITY RM SMK GENERAL ALARM & RA100Z L2S26 2251AP SMOKE DETECTOR STAIR 2 SMK GENERAL ALARM L2S27 2251AP SMOKE DETECTOR 3RD FLOOR STAIR 1 SMK GENERAL ALARM L2S28 2251AP SMOKE DETECTOR 3RD FLOOR ELEV LOBBY SMK GENERAL ALARM L2S29 2251AP SMOKE DETECTOR 3RD FLOOR CORIDOR SMK GENERAL ALARM L2S30 2251AP SMOKE DETECTOR 3RD FLOOR CORIDOR SMK GENERAL ALARM L2S31 2251AP SMOKE DETECTOR 3RD FLOOR CORIDOR SMK GENERAL ALARM L2S32 2251AP SMOKE DETECTOR 3RD FLOOR ELEC ROOM SMK GENERAL ALARM & RA100Z52 Mammoth Fire Alarms JOB NAME:CANAL STREET REALTY Incorporated NORTH BUILDING-SALEM, MA. CONTRACTOR:BRUNELLE BROS. ELECTRIC,INC. 176 Walker St., Lowell, MA 01854-3126 DATE:7/10/2019 12:50 Tel. (978) 934-9130 Sales 1-800-995-9808 Fax (978) 934-9131 LOOP #2 ADDRESS MODULE # OF DEVICES LOCATION/DEVICES TYPE LOGIC OUTPUTS L2S33 2251AP SMOKE DETECTOR 3RD FLOOR UTILITY RM SMK GENERAL ALARM & RA100Z L2S34 2251AP SMOKE DETECTOR 3RD FLOOR STAIR 2 SMK GENERAL ALARM L2S35 2251/BR DUCT SMOKE DETECTOR 1ST FLOOR UNIT 01 DUCT GENERAL ALARM & L2M L2S36 2251/BR DUCT SMOKE DETECTOR 1ST FLOOR UNIT 01 DUCT GENERAL ALARM & L2M L2M1 M500DM 1 WATERFLOW MAIN VALE FLOW GENERAL ALARM L2M2 "1 TAMPER MAIN VALVE TAMP SUPERVISORY ALARM L2M3 M500DM 1 WATERFLOW 1ST FLOOR FLOW GENERAL ALARM L2M4 "1 TAMPER 1ST FLOOR TAMP SUPERVISORY ALARM L2M5 M500DM 1 WATERFLOW 2ND FLOOR FLOW GENERAL ALARM L2M6 "1 TAMPER 2ND FLOOR TAMP SUPERVISORY ALARM L2M7 M500DM 1 WATERFLOW 3RD FLOOR FLOW GENERAL ALARM L2M8 "1 TAMPER 3RD FLOOR TAMP SUPERVISORY ALARM L2M9 M500DM 1 TAMPER BACKFLOW SYSTEM SIDE TAMP SUPERVISORY ALARM L2M10 "1 TAMPER BACKFLOW CITY SIDE TAMP SUPERVISORY ALARM L2M11 M500MAP 1 PRESSURE SWITCH FLOW GENERAL ALARM L2M12 M500MAP 1 TAMPER SWITCH TAMP SUPERVISORY ALARM L2M13 MS710APU PULL 1ST FLOOR UNIT 01 FRONT PULL GENERAL ALARM L2M14 MS710APU PULL 1ST FLOOR UNIT 01 REAR PULL GENERAL ALARM L2M15 MS710APU PULL 1ST FLOOR UNIT 02 FRONT PULL GENERAL ALARM L2M16 MS710APU PULL 1ST FLOOR UNIT 02 REAR PULL GENERAL ALARM L2M17 MS710APU PULL 1ST FLOOR UNIT 03 FRONT PULL GENERAL ALARM L2M18 MS710APU PULL 1ST FLOOR UNIT 03 REAR PULL GENERAL ALARM L2M19 MS710APU PULL 1ST FLOOR UNIT 04 FRONT PULL GENERAL ALARM L2M20 MS710APU PULL 1ST FLOOR UNIT 04 REAR PULL GENERAL ALARM L2M21 MS710APU PULL 1ST FLOOR UNIT 05 FRONT PULL GENERAL ALARM L2M22 MS710APU PULL 1ST FLOOR UNIT 05 REAR PULL GENERAL ALARM L2M23 MS710APU PULL 1ST FLOOR ELEV LOBBY EXIT PULL GENERAL ALARM L2M24 MS710APU PULL 2ND FLOOR STAIR 1 PULL GENERAL ALARM L2M25 MS710APU PULL 2ND FLOOR STAIR 2 PULL GENERAL ALARM L2M26 MS710APU PULL 3RD FLOOR STAIR 1 PULL GENERAL ALARM L2M27 MS710APU PULL 3RD FLOOR STAIR 2 PULL GENERAL ALARM L2M28 M501MAP 1 CO DETECTOR 1ST FLOOR LAUNDRY RM CO SUPERVISORY ALARM53 Mammoth Fire Alarms JOB NAME:CANAL STREET REALTY Incorporated NORTH BUILDING-SALEM, MA. CONTRACTOR:BRUNELLE BROS. ELECTRIC,INC. 176 Walker St., Lowell, MA 01854-3126 DATE:7/10/2019 12:50 Tel. (978) 934-9130 Sales 1-800-995-9808 Fax (978) 934-9131 LOOP #2 ADDRESS MODULE # OF DEVICES LOCATION/DEVICES TYPE LOGIC OUTPUTS L2M29 M501MAP 1 ELEV HOISTWAY SMOKE DAMPER POWER TRBL TROUBLE INPUT ONLY L2M30 M500DM BDA ANTENNA FAILURE BDA SUPERVISORY ALARM L2M31 "BDA TROUBLE BDA SUPERVISORY ALARM L2M32 M500DM BDA POWER LOSS BDA SUPERVISORY ALARM L2M33 "BDA CHARGER TROUBLE BDA SUPERVISORY ALARM L2M34 M500MAP BDA LOW BATTERY BDA SUPERVISORY ALARM L2M66 M500RAP ELEV CAR RECALL TO 1ST FL RELAY TO BE DETERMINED L2M67 M500RAP ELEV CAR RECALL TO 2ND FL RELAY TO BE DETERMINED L2M68 M500RAP ELEV CAR FIREMAN'S HAT LIGHT RELAY TO BE DETERMINED L2M69 M500SAP 1 ELEV HOISTWAY SMOKE DAMPER OPEN RELAY TO BE DETERMINED L2M70 M500RAP HVAC SHUTDOWN 1ST FLOOR UNIT 01 RELAY ACTIVATED BY L2S L2M71 M500RAP HVAC SHUTDOWN 1ST FLOOR UNIT 01 RELAY ACTIVATED BY L2S L2M72 M500RAP CARD ACCESS SYSTEM OVERRIDE RELAY GENERAL ALARM INPUTS L2M73 M500SAP 1 UNIT 01 WP STROBE NAC NAC ONLY UNIT 01 INPUTS L2M74 M500SAP 1 UNIT 02 WP STROBE NAC NAC ONLY UNIT 02 INPUTS L2M75 M500SAP 1 UNIT 03 WP STROBE NAC NAC ONLY UNIT 03 INPUTS L2M76 M500SAP 1 UNIT 04 WP STROBE NAC NAC ONLY UNIT 04 INPUTS L2M77 M500SAP 1 UNIT 05 WP STROBE NAC NAC ONLY UNIT 05 INPUTS L2M78 M500SAP 1 SMOKE DAMPER ACTIVATION RELAY TO BE DETERMINED L2M79 M500SAP 1 SMOKE DAMPER ACTIVATION RELAY TO BE DETERMINED L2M80 INPUT INX#1 COMMON TROUBLE TRBL TROUBLE INPUT ONLY L2M81 RELAY INX#1 SILENCE RELAY CORRELATE TO SIGNAL SILENCE L2M82 INPUT INX#1 AC FAILURE TROUBLE TRBL TROUBLE INPUT ONLY L2M83 INPUT INX#1 BATTERY TROUBLE TRBL TROUBLE INPUT ONLY L2M84 INPUT INX#1 GROUND FAULT TROUBLE TRBL TROUBLE INPUT ONLY L2M85 NAC INX#1 CKT 1 CONTROL/STATUS - 1ST FLR NAC GENERAL ALARM L2M86 NAC INX#1 CKT 2 CONTROL/STATUS - 1ST FLR NAC GENERAL ALARM L2M87 NAC INX#1 CKT 3 CONTROL/STATUS - 1ST FLR NAC GENERAL ALARM L2M88 NAC INX#1 CKT 4 CONTROL/STATUS - 2ND FLR NAC GENERAL ALARM L2M89 NAC INX#1 CKT 5 CONTROL/STATUS - 2ND FLR NAC GENERAL ALARM L2M90 INPUT INX#2 COMMON TROUBLE TRBL TROUBLE INPUT ONLY L2M91 RELAY INX#2 SILENCE RELAY CORRELATE TO SIGNAL SILENCE54 Mammoth Fire Alarms JOB NAME:CANAL STREET REALTY Incorporated NORTH BUILDING-SALEM, MA. CONTRACTOR:BRUNELLE BROS. ELECTRIC,INC. 176 Walker St., Lowell, MA 01854-3126 DATE:7/10/2019 12:50 Tel. (978) 934-9130 Sales 1-800-995-9808 Fax (978) 934-9131 LOOP #2 ADDRESS MODULE # OF DEVICES LOCATION/DEVICES TYPE LOGIC OUTPUTS L2M92 INPUT INX#2 AC FAILURE TROUBLE TRBL TROUBLE INPUT ONLY L2M93 INPUT INX#2 BATTERY TROUBLE TRBL TROUBLE INPUT ONLY L2M94 INPUT INX#2 GROUND FAULT TROUBLE TRBL TROUBLE INPUT ONLY L2M95 NAC INX#2 CKT 1 CONTROL/STATUS - 2ND FLR NAC GENERAL ALARM L2M96 NAC INX#2 CKT 2 CONTROL/STATUS - 2ND FLR NAC GENERAL ALARM L2M97 NAC INX#2 CKT 3 CONTROL/STATUS - 3RD FLR NAC GENERAL ALARM L2M98 NAC INX#2 CKT 4 CONTROL/STATUS - 3RD FLR NAC GENERAL ALARM L2M99 NAC INX#2 CKT 5 CONTROL/STATUS - SPARE NAC GENERAL ALARM 55 Fire Alarm System Operation Matrix System Outputactivate FACP common alarm indicationactivate FACP common supervisory indicationactivate FACP common trouble indicationactivate alarm notification appliancesactivate retail unit exterior red strobesactivate general alarm exterior red strobetransmit alarm signals to supervising stationinitiate elevator recall sequenceactivate elevator car fireman's hat lightopen elevator hoistway smoke dampershutdown HVAC unit operationoverride card access systemoperate common area smoke dampersSystem Input manual fire alarm stations X X X X X heat detector X X X X X smoke detectors X X X X X elevator lobby smoke detectors X X X X X X X elevator machine room smoke detector X X X X X X X corridor smoke detectors X X X X X X retail unit alarm devices X X X X X X duct smoke detectors X X X X X X carbon monoxide detectors X X sprinkler waterflow devices X X X X X sprinkler supervisory devices X X fire alarm AC power failure X X fire alarm system battery trouble X X fire alarm open circuit X X fire alarm ground fault X X SLC short X X NAC short X X 56 Mammoth Fire Alarms Incorporated 176 Walker Street, Lowell, MA 01854-3126 To determine the required wire size for each notification appliance circuit, use the above chart and the following steps. ♦Compute the notification appliance current. (Number of devices multiplied by the device current = amperes) ♦Compute the distance in feet from the panel to the last notification appliance. ♦Locate total appliance load (amperes) on the vertical axis of the chart; locate wire distance (in feet) on the horizontal axis; find the point where they intersect. ♦Read wire size in AWG on the curved line to the right of the point of intersection. Notification Appliance Circuit Wiring Estimator “Servicing the installer before and after the installation” SALES (978) 934-9130 * 1-800-995-9808 * FAX (978) 934-9131 57 Mammoth Fire Alarms Incorporated 176 Walker Street Lowell, MA 01854 WARRANTY: Mammoth Fire Alarms, Inc. warranties all equipment supplied by it to be free from defects for one (1) year from the date of shipment. Mammoth Fire Alarms, Inc. will repair or replace, at its option, any equipment that it determines to be defective. Said equipment will be returned to the purchaser. Mammoth Fire Alarms, Inc. shall not be obligated to repair or replace equipment that has been repaired by others, abused, improperly installed, altered or otherwise misused or damaged in any way, including damage caused by any Acts of God. Mammoth Fire Alarms, Inc. will not be responsible for any on-site dismantling, reassembling or reinstallation charges or costs. TROUBLESHOOTING/SERVICE: All field troubleshooting/service performed by Mammoth Fire Alarms, Inc. personnel will be billed per hour portal to portal, plus all costs for parts. All defective equipment that is under warranty will be replaced or repaired, at the option of Mammoth Fire Alarms, Inc. provided the equipment was not damaged during installation, damaged because of poor or improper installation, or damaged by any Acts of God. No troubleshooting will be performed, either over the telephone or in the field, if the customer’s account is not current. RETURNS FOR CREDIT: Authorizations for merchandise to be returned for credit must be previously authorized and cannot exceed 60 days from the date of original Mammoth Fire Alarms, Inc. invoice. Merchandise authorized for return must be sent PREPAID and insured within 30 days of the date of the authorization. When merchandise is returned for credit and is returned for other than a Mammoth Fire Alarms, Inc. shipping error, a 20% charge will be made to cover handling, inspection and testing. Non-stock items will be assessed a 50% restocking charge. For credit to be issued, the item(s) must be in the original factory packaging. Custom and special ordered items will not be accepted for credit. Items damaged in transit will be deducted from the credit. Acceptance of goods returned for credit shall be at the sole discretion of Mammoth Fire Alarms, Inc. Receiving an RMA number from Mammoth Fire Alarms, Inc. is not a guarantee of issuance of credit. RETURNS FOR REPAIR OR REPLACEMENT: Mammoth Fire Alarms, Inc. requires prior approval before return of equipment for repair. The information required for equipment to be returned for repair is the product model number and the problem that existing with the unit. Confirmation will be faxed/emailed to you and then the return may be made. If the item(s) is under warranty (one year from the date of shipment) it will be repaired or replaced at our option. All items shipped to Mammoth Fire Alarms, Inc. must be shipped PREPAID. If the item(s) is out of warranty, but repairable, it will be repaired at a cost not to exceed 50% of the cost of a new unit. MATERIALS DAMAGED UPON RECEIPT: Any material physically damaged upon receipt must remain at the original place of delivery and in the original packaging. If the packaging is visibly damaged, the delivery driver should be instructed to make note of it prior to signing for the delivery. Mammoth Fire Alarms, Inc. Shipping Manager must then be contacted to arrange a replacement and an on-site evaluation of the damaged equipment. Mammoth Fire Alarms, Inc. cannot warranty any damaged equipment that has been removed from its original delivery location or does not contain the original packaging. “Servicing the installer before and after the installation” www.mammothfire.com Policies 02/02/15 POLICIES 58 PPM call us 3/14/19 Property Protection Monitoring Incorporated SALES (978) 459-3344 ● (877) 794-3344 ● FAX (978) 459-6655 176 Walker Street propertyprotectionmonitoring.com Lowell, MA. 01854 To Connect your Dialer/Radio/ Communicator to our UL Listed Central Station Today Call! 978-459-3344 Protect Your Investment! Attention! We make it very easy to connect and have off premises protection now! Thank You PPM/Sales Listed Central Station Listed Central Station 59