Webb Salem Fire Alarm Submittals 5.2.19
FW WEBB SALEM SUBMITTED TO: GREEN LEAF CONSTRUCTION 98 ADAMS ST. SUITE 105 LEOMINSTER, MA 01453 SUBMITTED BY: D&D ELECTRICAL CONTRACTORS, INC. 10 EVERBERG RD WOBURN, MA 01801 FIRE ALARM SUBMITTALS TABLE OF CONTENTS FIRE ALARM Quantity Part Number Description 1 IFP-300 Intelligent Fire Alarm Control Panel 6 IDP-MINIMON Addressable Mini-Monitor Module 4 IDP-MONITOR-2 Addressable Dual Monitor Module 6 IDP-PHOTO-W Intelligent Addressable Photoelectric Detector, White 6 B300-6 6" Mounting Base, White 5 IDP-PULL-DA Addressable Manual Dual Action Pull Station 6 PS-DA Dual Action Pull Station with Key Lock 2 PS12180 12 Volt, 18AH Battery 2 PS1270 12 Volt, 7AH Battery 1 FF8 8 Ampere UL Fire System Power Supply 1 HPP31076 8 Ampere UL Fire System Power Supply Class A Module 1 125STRNR1248D Red Exterior Beacon/Strobe 1 SSM24-6 6" Red Exterior Sprinkler Bell with Back Box 1 E120V-GT 120VAC Surge Arrestor Kit 1 IFP-300-BC Intelligent Fire Alarm Control Panel Battery Calculation 1 FF8-BC 8 Ampere UL Fire System Power Supply Battery Calculation FW Webb Salem, MA Bill of Materials • Network support for up to 32 Sites • Built-in support for up to 159 IDP/SK detectors and 159 IDP/SK modules or 127 SD SLC devices • Four line LCD display with 40 characters per line • Available in a red or black cabinet •$an be surface or flush mounted • Built-in USB interface for convenient and quick programming • Firmware can be upgraded in the field • Network card allows copper network connection with a multi-mode or single- mode fiber connection option • Built-in dual phone line, digital alarm communicator/ transmitter (DACT) XJUIIP BOE optional cellular technologies • JumpStartk Buto Qrogrammingfeature for easy programming • Supports up to four SWIFTk wireless gateways. Each gateway can have up to 49 wireless devices • Supports Class B (Style 4) and Class A (Style 6 or Style 7 configuration for SLC, and SBUS • Builtin/"$ synchronization for EFWJDFT from AMSECOk, GenteYk, System Sensork, and Wheelockk *'1# Farenhyt™ Series IFP-300 / IFP-300B Intelligent Fire Alarm Control Panel The IFP-300 (red) and IFP-300B (black) are intelligent analog/addressable fire alarm control panels (FACP)BOEBSFEJSFDUSFQMBDFNFOUTGPSUIF *'1'"$1. The IFP-300 panel contains one builtin signaling line circuit (SLC), which can support 159 (IDP/SK) System Sensor® sensors and 159 IDP/SK modules or 127 (SD) Hochiki® devices per loop. Additional SLC loops can be added using the model 6815 SLC expander for SK/IDP devices to increase the overall point capacity to a maximum of 300 points per panel, or model 5815XL for SD devices to increase the overall point capacity to a maximum of 254 points per panel. 5IFIFP-300 has the interconnection capability for up to 32 panels. The system has two modes of operation, multiple panels covering one larger building, or multiple independent buildings. 5IF4,/*$/FUXPSL*OUFSGBDF $BSEJTVTFEUPnetwork panels together Copper wire or fiber optic cable panel connectivity can be used within the same networked system. IFP-300 has a built-in dual phone line, digital alarm communicator/ transmitter (DACT)XJUIIPBOE optional cellular technologies, GormC trouble relay, and two programmable GormC relays. 5IFIFP-300 has powerful features such as detector sensitivity, day/night thresholds, drift compensation, pre-trouble maintenance alert, and calibration trouble alert. The IFP-300 supports a variety of devices, including RA-2000, RA-1000 or RA-100 remote annunciatorT, 5824 serial/parallel printer interface moduleT (for printing system reports), RPS-1000 power moduleT, and IDP, SK or SD devices. '&"563&4#&/&'*54 'MFYQVUk +VNQ4UBSUk )POFZXFMMk 4ZTUFN 4FOTPSk BOE48*'5kBSF SFHJTUFSFEUSBEFNBSLTPG BOE'BSFOIZUƇJTB USBEFNBSLPG)POFZXFMM *OUFSOBUJPOBM *OD "NTFDPkJTBSFHJTUFSFE USBEFNBSLPG1PUUFS&MFDUSJD 4JHOBM$PNQBOZ --$ (FOUFYkJTBSFHJTUFSFE USBEFNBSLPG(FOUFY $PSQPSBUJPO)PDIJLJkJTB SFHJTUFSFEUSBEFNBSLPG )PDIJLJ$PSQPSBUJPO 8IFFMPDLkJTBUSBEFNBSL PG$PPQFS5FDIOPMPHJFT $PNQBOZ This document is not intended to be used for installation purposes. We try to keep our product information up-to date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For Technical Support, Please call 800-446-6444. *'1 Technical Specifications PHYSICAL: Overall Dimensions: 26.4”H x 16.4"W x 4.11”D Weight: 45 lbs. Color: Red or Black ENVIRONMENTAL Operating Temperature: 32°F to 120°F (0°C to 49°C) Humidity: 0 to 93% relative humidity (non- condensing) ELECTRICAL: IFP-300 Primary AC: 120VAC @ 60 Hz, 3.3A Total Accessory Load: 6A @ 24VDC power-limited Standby Current: 190mA Alarm Current: 250mA Battery Charging Capacity: 17 to 55AH Battery Size: 18AH max. allowed in control panel cabinet. Larger capacity batteries can be housed in RBB accessory cabinet. AGENCY LISTINGS AND APPROVALS NFPA 13, NFPA 15, NFPA 16, NFPA 70, & NFPA 72: Central Station; Remote Signaling; Local Protective SignalJng Systems; Auxiliary Protected Premises Unit; & Water Deluge Releasing Service UL Listed4 CSFM: 7165-0559:0504 FDNY: COA#6245 FMBQQSPWFE APPROVED RELEASING SOLENOIDS Asco T8210A107 24 VDC 3 A max 0 Hz Asco 8210G207 24 VDC 3 A max 0 Hz ORDERING INFORMATION IFP-300: Intelligent Fire Alarm Control Panel. Red Cabniet. IFP-300B: Intelligent Fire Alarm Control Panel Black Cabinet. SBUS ACCESSORIES RA-2000, RA-1000, RA-1000R, RA-100, RA-2000GRAY: Remote annunciators 6815: Signal Line Circuit (SLC) Expander for IDP or SK devices 5815XL: Signal Line Circuit (SLC) Expander for SD devices RPS-1000: Power Supply 5496: NAC Expander 5824: Serial/Parallel Module 5880: LED I/O Module 5865-3 or 5865-4: LED Annunciator 5883: Relay Interface MISCELLANEOUS ACCESSORIES HFSS: Software Suite. Provides programming, upload/download and event reporting RBB: Remote Battery Box Cabinet. Use for backup batteries up to 35 AH. Dimensions: 16" W x 10" H x 6" D SK-SCK: Seismic Compliance Kit SK-NIC: Network Interface Card SK-NIC-KIT: Installation Accessory Kit SK-FML: Fiber-Optic Multi Mode, transmitter and receiver SK-FSL: Fiber-Optic Single Mode CELL-MOD: Cellular Communicator in Plastic Enclosure CELL-CAB-SK: Cellular Communicator in Metal Enclosure with lock and key 351603 |# | © 201 Honeywell International Inc. COMPATIBLE DEVICES See the data sheets listed below for a complete listing of the IDP, SK, SWIFT or SD devices. 350361: IDP Device Protocol data sheet 53623: SK Device Protocol data sheet350360: SD Device Protocol data sheet350615 & 350617: SWIFT devices data sheet Honeywell Farenhyt 12 Clintonville Road Northford, CT 06472 800-328-0103 XXXGBSFOIZUDPN FEATURES & BENEFITS The IDP-Minimon compatible with the following Farenhyt SeriesFACPs: • IFP-2100 / IFP-2100ECS / RFP-2100 • IFP-2000 / IFP-2000ECS / RPS-2000 • IFP-1000 / IFP-1000ECS • IFP-300 / IFP-300ECS • IFP-100 / IFP-100ECS • IFP-75 • IFP-50 • Single contact monitor • Small and lightweight size allows for fl exible mounting options • Support for Class B wiring • Fully supervised • Rotary address switches for fast installation • Analog communications • UL Approved • CSFM Listed • MEA Listed 457-99-E Vol. V Addressable Monitor Module IDP-Minimon The IDP-Minimon is a compact and light weight addressable monitor module for use with Silent Knight IFP-series fi re alarm control panels (FACPs). The IDP-Minimon acts as an interface to contact devices, such as waterfl ow switches and pull stations. The IDP-Minimon supports Class B supervised wiring to the load device. Conventional 4-wire smoke detectors can be monitored for alarm and trouble conditions. Installation The IDP-Minimon can be mounted in a single gang junction box directly behind the monitored device. Its small size and light weight allow it to be installed without rigid mounting requirements. IDP-MINIMON For a complete listing of all compliance approvals and certifications, please visit www.farenhyt.com. Microsoft, Windows, and the Windows Logo are registered trademarks or trademarks of Microsoft Corporation. Honeywell® and System Sensor® are registered trademark of and Farenhyt™ is a trademark of Honeywell International, Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For Technical Support, Please call 800-446-6444. IDP-Minimon Technical Specifications SPECIFICATIONS Physical: 1.3" H x 2.8" W x .5" D (3.3 x 7x 1.3 cm) Shipping Weight: 1.2oz (37 g) ENVIRONMENTAL Operating Temperature: 32°F - 120 °F (0°C - 49°C) Humidity: 10 to 93% non-condensing) ELECTRICAL RATINGS Operating Voltage: 15 – 32VDC SLC Standby and Alarm Current: 350μ A End-of-Line Resistance: 47K W Initiating Device Circuit Wiring Resistance: 1,500W max SLC Loop Resistance: 40W max. Wire Length: 6” min. ORDERING INFORMATION IDP-Minimon: Minature Monitoring Module Doc 350279 | Rev H| 08/17 © 2017 Honeywell International Inc. For more information Learn more about Honeywell’s Farenhyt Series and other products available by visiting www.farenhyt.com Honeywell Security & Fire 12 Clintonville Road Northford, CT 06472 800-328-0103 FEATURES & BENEFITS • Monitor two circuits, with unique addresses, simultaneously • Support for Class B wiring • Fully supervised • Panel controlled status LED that fl ashes green in normal state and is solid red in alarm • Attractive ivory cover plate • Rotary address switches for fast installation • SEMS screws for easy wiring • UL Listed • CSFM Listed • MEA Listed 457-99-E Vol. V Addressable Dual Monitor Module IDP-Monitor-2 The IDP-Monitor-2 is an addressable monitor module with two initiating circuits for use with Honeywell Farenhyt Series fi re alarm control panels (FACPs). The IDP-Monitor-2 acts as an interface to contact devices, such as waterfl ow switches and pull stations. The IDP-Monitor-2 supports Class B supervised wiring to the load device. Conventional 4-wire smoke detectors can be monitored for alarm and trouble conditions. Because the IDP-Monitor-2 is capable of monitoring two separate Class B circuits, it is ideal for waterfl ow tamper switch and fl ow switch monitoring. Installation The IDP-Monitor-2 mounts directly into a 4” square electrical box. The box must have a minimum depth of 2-1/8”. A surface mount electrical box (System Sensor® PN SMB500) is available from Honeywell. IDP-MONITOR-2 Compatibility The IDP-Monitor-2 is compatible with the following Farenhyt Series FACPs: • IFP-2100 / IFP-2100ECS / RFP-2100 • IFP-2000 / IFP-2000ECS / RPS-2000 • IFP-1000 / IFP-1000ECS • IFP-300 / IFP-300ECS • IFP-100 / IFP-100ECS • IFP-75 • IFP-50 For a complete listing of all compliance approvals and certifications, please visit www.farenhyt.com. Microsoft, Windows, and the Windows Logo are registered trademarks or trademarks of Microsoft Corporation. Honeywell® and System Sensor® are registered trademarks of and Farenhyt™ is a trademark of Honeywell International, Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For Technical Support, Please call 800-446-6444. IDP-Monitor-2 Technical Specifications SPECIFICATIONS* Physical: 4.5" H x 4" W x 1.3 D ( 11.4 x 10.2 x 3.2cm) Shipping Weight: 6.3oz (196g) ELECTRICAL RATINGS Operating Voltage: 15 – 32VDC Maximum Current Draw: 6.4mA (LED on) SLC Standby & Alarm Current: 750 μ A max @ 24 VDC (one communication every sec with 47k EOL) End of Line Resistance: 47k W ENVIRONMENTAL Operating Temperature: 32º-120ºF (0ºC – 49ºC) Humidity: 10 to 93% non-condensing) ORDERING INFORMATION IDP-Monitor-2: Dual Monitoring Module ACCESSORIES SMB500: 4” Square Surface Mount Electrical Box Doc 350289 | Rev G| 09/17 © 2017 Honeywell International Inc. For more information Learn more about Honeywell’s Farenhyt Series and other products available by visiting www.farenhyt.com Honeywell Security & Fire 12 Clintonville Road Northford, CT 06472 800-328-0103 Typical Wiring for IDP-Monior-2 Module, NFPA Style B Agency Listings S2522 3034401 7300-1653:0212 7300-1653:0211 7135-1653:0196 9080301 Duct Smoke Detector Accessories Expand the versatility of the InnovairFlex™ line of duct smoke detectors with System Sensor notification and test accessories. Available Accessories APA151 Piezo Annunciator MHR Mini-Horn, Red MHW Mini-Horn, White RA100Z/RA100ZA Remote Annunciator RTS151 Remote Test Station RTS151KEY Remote Test Station with Key RTS2 Multi-Signaling Accessory AOS Add-On Strobe RTS2-AOS Multi-Signaling Accessory Duct smoke detector accessories add functionality to the duct smoke detection system by allowing quick, convenient inspections at eye level and effective audible and visible notification options. All System Sensor duct smoke detectors and accessories are UL listed. The APA151 piezo annunciator, which replaces the APA451 with a new, improved look, provides an audible alarm signal, a red LED to indicate alarm status, and a green LED to indicate power status. It is intended for use with System Sensor 4-wire conventional duct smoke detector applications without a system control panel, to comply with NFPA 90A. The MHR and MHW SpectrAlert® Advance mini-horns feature temporal or continuous tones at high and low volume settings. Their small footprint allows mounting to single-gang back boxes for applications where a small device is desired. The RA100Z and RA100ZA remote annunciators are designed for both conventional and intelligent applications. Their red LED provides visual indication of an alarm condition. The RTS151 and RTS151KEY remote test stations are automatic fire detector accessories designed to test duct smoke detectors from a convenient location. For 4-wire detectors, the RTS151KEY test station features a multi-colored LED that alternates between steady green and red. For 2-wire detectors, the LED illuminates red for alarm. The RTS2 and RTS2-AOS multi-signaling accessories are designed to work with InnovairFlex 4-wire conventional duct smoke detectors. These accessories include a key switch that can be used to select one of two connected sensors to be tested, reset, or both by a push button switch. They also enable sensitivity measurements using the SENS-RDR sensitivity reader (sold separately). The AOS (Add-On Strobe) is an optional accessory included with the RTS2- AOS model. 3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 www.systemsensor.com ©2013 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. HVDS20202 • 8/13 APA151 Piezo Annunciator Voltage Regulated 24 VDC Operating Voltage 16 to 33 VDC Maximum Alarm Current 30 mA Temperature Range 0°C to 49°C (32°F to 120°F) Relative Humidity 10 to 93% non-condensing Wire Gauge 12 to 18 AWG Dimensions 4.6˝ H × 2.9˝ W × .45˝ D MHR/MHW SpectrAlert® Advance Mini-Horns Voltage Regulated 12 DC or FWR (Full Wave Rectified) or Regulated 24 VDC or FWR Sounder Current Draw 22 mA RMS max. at 8 to 17.5 Volts DC 29 mA RMS max. at 16 to 33 Volts DC Temperature Range 0°C to 49°C (32°F to 120°F) Humidity Range 10 to 93% non-condensing Nominal Sounder Frequency 3 kHz Wire Gauge 12 to 18 AWG Dimensions 4.6˝ H × 2.9˝ W × 0.45˝ D RA100Z/RA100ZA Remote Annunciator Voltage Range Conventional System: 3.1 to 32 VDC Intelligent System: 18 to 32 VDC Maximum Alarm Current 10 mA Dimensions 4.6 ˝ H × 2.8˝ W × 1.3˝ D Specifications, Duct Smoke Detector Accessories RTS151 Remote Test Station Power Requirements Alarm LED: 2.8 to 32 VDC, 12 mA max. Total Current: 105 mA max. Test Switch 10 VA @ 32 VDC Reset Switch 10 VA @ 32 VDC Alarm Response Time 40 seconds max. Temperature Range –10°C to 60°C (14°F to 140°F) Relative Humidity 95% non-condensing Wire Gauge 14 to 18 AWG Dimensions 4.8˝ H x 2.90˝ W x 1.4˝ D RTS151KEY Remote Test Station with Key Power Requirements Power LED (Green): 14 to 35 VDC, 12 mA max. Alarm LED (Red): 2.8 to 32 VDC, 12 mA max. Total Current: 105 mA max. Alarm Response Time 40 seconds max. Temperature Range –10°C to 60°C (14°F to 140°F) Relative Humidity 95% non-condensing Wire Gauge 14 to 18 AWG Dimensions 4.6˝ H × 2.75˝ W × 1.8˝ D RTS2 and RTS2-AOS Multi-signaling Accessory Voltage 20 to 29 VDC Power Requirements Standby: 3.0 mA max. Trouble: 16.0 mA max. Alarm without strobe: 30 mA max. Alarm with strobe: 55 mA max. Sounder 85 dBA at ten feet Temperature Range –10°C to 60°C (14°F to 140°F) Relative Humidity 95% non-condensing Wire Gauge 14 to 22 AWG Dimensions 4.8˝ W x 5.3˝ H x 1.6˝ D For the very latest product specifications and listing information, please visit the System Sensor Web site at www.systemsensor.com. RTS151 UL S4011 RA100Z UL S2522 RTS151KEY UL S2522 MHW UL S4011 MHR UL S4011 APA151 UL S4011 RTS2-AOS UL S2522 AOS FEATURES & BENEFITS • New modern profile for improved aesthetics • Stable communication technique with noise immunity • Low standby current • Two-wire SLC connection • Optional remote, single- gang LED accessory • Dual LED design provides 360° viewing angle • Remote test feature from the panel • Built-in functional test switch activated by external magnet • Built-in tamper- resistant feature • Sealed against back pressure • Expanded color options • SEMS screws for wiring of the separate base • Optional relay, isolator, and sounder bases • Plugs into separate base for ease of installation and maintenance Farenhyt IDP-PHOTO-W Series Intelligent Plug-in Photoelectric Smoke Detectors Honeywell’s IDP-PHOTO-W Series intelligent plug-in smoke detectors are designed for both performance and aesthetics. A new modern, sleek, contemporary design and enhanced optical sensing chamber is engineered to sense smoke produced by a wide range of combustion sources in accordance with more stringent code standards. The IDP-PHOTO-W Series detector sensitivity can be programmed in the control panel software. Sensitivity is continuously monitored and reported to the panel. Point ID capability allows each detector’s address to be set with rotary, decimal address switches, providing exact detector location for selective maintenance when chamber contamination reaches an unacceptable level. Dual electronic thermistors add 135°F (57°C) fixed temperature thermal sensing on the IDP-PHOTO-T. The IDP-PHOTO-R is a remote test capable detector for use with DNR Series duct detector housings IDP-PHOTO-W in B300-6 base DETECTOR SPACING AND APPLICATIONS Honeywell recommends spacing detectors in compliance with NFPA 72. In low airflow applications with smooth ceiling, space detectors 30 feet (9m). For specific information regarding detector spacing, placement, and special applications refer to NFPA 72. System Smoke Detector Application Guide, document A05-1003, is available at systemsensor.com INSTALLATION The IDP-PHOTO-W Series plug-in detectors use a separate base to simplify installation, service, and maintenance. Installation instructions are shipped with each detector. Mount base (all base types) on an electrical backbox which is at least 1.5" (3.81 cm) deep. NOTE: • Because of the inherent supervision provided by the SLC loop, end-of-line resistors are not required. Wiring “T-taps” or branches are permitted for Style 4 (Class “B”) wiring. • When using relay or sounder bases, consult the installation sheet for device limitations between isolator modules and isolator bases. ORDERING INFORMATION NOTE: Detectors must be mounted to one of the Intelligent Bases listed below IDP-PHOTO-W: White, low-profile intelligent photoelectric sensor. IDP-PHOTO-IV: Ivory, low-profile intelligent photoelectric sensor. IDP-PHOTO-T-W: White, same as the IDP-PHOTO-W, but includes a built-in 135°F (57°C) fixed-temperature thermal device. IDP-PHOTO-T-IV: Same as IDP- PHOTO-T but in Ivory. IDP-PHOTO-R-W: White, low-profile intelligent photoelectric sensor, remote test capable. For use with DNR/DNRW.. IDP-PHOTO-R-IV: Ivory, low-profile intelligent photoelectric sensor, remote test capable. For use with DNR/DNRW. INTELLIGENT BASES B300-6: White, standard flanged low-profile mounting base. B300-6-BP: Bulk pack of B300-6, package contains 10. B300-6-IV: Ivory, standard flanged low-profile mounting base. B501-WHITE: White, standard European flangeless mounting base. UL listed. B501-BL: Black, standard European flangeless mounting base. UL listed. B501-IV: Ivory, standard European flangeless mounting base. UL listed. B200S-WH: White, Intelligent, programmable sounder base. B200S-IV: Ivory, Intelligent, programmable sounder base. B200SR-WH: White, Intelligent sounder base for retrofit applications. B200SR-IV: Ivory, Intelligent sounder base for retrofit applications. B200S-LF-WH: White, Low Frequency Intelligent, programmable sounder base. B200S-LF-IV: Ivory, Low Frequency Intelligent, programmable sounder base. B200SR-LF: White, Low Frequency Intelligent sounder base for retrofit applications. B200SR-LF-IV: Ivory, Low Frequency Intelligent sounder base for retrofit applications. B224RB-WH: White, plug-in System Sensor relay base. B224RB-IV: Ivory, plug-in System Sensor relay base. B224BI-WH: White, plug-in System Sensor isolator detector base. B224BI-IV: Ivory, plug-in System Sensor isolator detector base. ACCESSORIES TR300: White, replacement flange for B210LP and B300-6 bases. TR300-IV: Ivory, replacement flange for B210LP and B300-6 bases. RA100Z: Remote LED annunciator. 3 – 32 VDC. Mounts to a U.S. single-gang electrical box. For use with B501 and B300(A)-6 bases only. M02-04-00: Test magnet. M02-09-00: Test magnet with telescoping handle. CK300: White, detector color kit. Pack of 10. CK300-IV: Ivory, detector color kit. Pack of 10. CK300-BL: Black, detector color kit. Pack of 10. For a complete listing of all compliance approvals and certifications, please visit www.farenhyt.com. Microsoft, Windows, and the Windows Logo are registered trademarks or trademarks of Microsoft Corporation. Honeywell® and System Sensor® are registered trademark of and Farenhyt™ is a trademark of Honeywell International, Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For Technical Support, Please call 800-446-6444. Farenhyt IDP-PHOTO-W Series Technical Specifications PHYSICAL Height: 2.0" (51mm) installed in B300-6 base Diameter: 6.2" (156mm) installed in B300-6 base 4.1" (104 mm) installed in B501 base Weight: 3.4 oz (95 g) ENVIRONMENTAL Operating Temperature range: Photo: 32°F to 122°F (0°C to 50°C) Photo with Thermal: 32°F to 100°F (0°C to 38°C) Thermal Ratings: Fixed Temperature Set point: 135°F (57°C) Sensitivity: UL Applications: 0.5% to 4.0% per foot obscuration. ELECTRICAL RATINGS Voltage Range: 15 to 32VDC peak Operating Current @ 24VDC : 200 µA (one communication every 5 seconds with green LED blink on communication) Maximum Current: 4.5mA @ 24VDC (one communication every 5 seconds with amber LED solid on). COMPATIBILITY The IDP-PHOTO-W series detectors are compatible with the following Farenhyt Series FACPs: • IFP-2100 / IFP-2100ECS / RFP-2100 • IFP-2000 / IFP-2000ECS / RPS-2000 • IFP-1000 / IFP-1000ECS • IFP-300 / IFP-300ECS • IFP-100 / IFP-100ECS • IFP-75 • IFP-50 AGENCY LISTINGS AND APPROVALS For exact certification listings for each model, please reference the respective agency Web site. UL listed: S6173 FM approved CSFM: 7272-0559:0512 Doc 351629 | Rev A| 04/18 © 2018 Honeywell International Inc. For more information Learn more about Honeywell’s Farenhyt Series and other products available by visiting www.farenhyt.com Honeywell Farenhyt 12 Clintonville Road Northford, CT 06472 800-328-0103 FEATURES & BENEFITS • Installer can open station without causing an alarm condition • Dual-color LED is visible through handle of station blinks green to indicate normal operation and remains steady red in an alarm condition • Key operated test and reset lock using lock plate actuator • Key matches compatible FACP locks • Meets ADA requirement for 5 lbs maximum pull force to active • Meets the Americans with Disabilities Act Accessibility Guidelines (ADAAG) controls and operating mechanisms guidelines (Section 4.1.3[13]) • Shell, door, and handle molded from durable LEXAN® • Reliable analog communications for trouble-free operation • Braille text on station handle • Rotary address switches for fast installation • Handle latches in down position and the word Activated appears, clearly indicating the station has been pulled • UL Listed, including UL 38, Standard of Manually Actuated Signaling System • CSFM Listed • MEA Listed Addressable Single Action and Dual Action Pull Stations IDP-Pull-SA & IDP-Pull-DA The IDP-Pull-SA is a single action pull station requiring only one motion to activate the station. The IDP-Pull-DA is a dual action pull station requiring two motions to active the station. Both pull stations are designed to work with Honeywell Farenhyt series fi re alarm control panels (FACPs). Installation The IDP-Pull-SA and IDP-Pull-DA can be surface mounted to an SB-I/O surface back box or semi-fl ush mounted on a standard single-gang with a minimum depth of 2.13”(5.40 cm) or double gang or 4” (10.61 cm) square electrical box. You can also use the optional (System Sensor® PN BG-TR) trim ring if the station is being semi-fl ush mounted. Compatibility The IDP-Pull-SA and IDP-Pull-DA are compatible with the following Farenhyt Series FACPs: • IFP-2100 / IFP-2100ECS / RFP-2100 • IFP-2000 / IFP-2000ECS / RPS-2000 • IFP-1000 / IFP-1000ECS • IFP-300 / IFP-300ECS • IFP-100 / IFP-100ECS • IFP-75 • IFP-50 IDP-PULL-SA IDP-PULL-DA For a complete listing of all compliance approvals and certifications, please visit www.farenhyt.com. Microsoft, Windows, and the Windows Logo are registered trademarks or trademarks of Microsoft Corporation. Honeywell® and System Sensor® are registered trademarks of and Farenhyt™ is a trademark of Honeywell International, Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For Technical Support, Please call 800-446-6444. IDP-Pull-SA and IDP-PUll-DA Technical Specifications SPECIFICATIONS* Physical: 5.5" H x 4" D ( 14cm x 10.2cm) Shipping Weight: 5.4oz Housing Material: LEXAN polycarbonate resin Bi-Colored LED: Blinking Green: Normal Steady Red: Alarm Switch: Single pole, single throw (SPST) normally open (N/O) switch which closes upon activation of the pull station ELECTRICAL RATINGS Operating Voltage: 15 – 32VDC SLC Standby and Alarm Current: 350μ A Wire Gauge: Up to 12AWG (3.1 mm2) ENVIRONMENTAL Operating Temperature: 32º-120ºF (0ºC – 49ºC) Humidity: 10 to 93% non-condensing) ORDERING INFORMATION IDP-Pull-SA: Single Action Pull Station IDP-Pull-DA: Dual Action Pull Station ACCESSORIES BG-TR: Optional trim ring. SB-I/O: Surface backbox, indoor/outdoor. * Unless otherwise noted, specifications apply to IDP-Pull-SA and IDP-Pull-DA Doc 350286 | Rev H | 08/17 © 2017 Honeywell International Inc. For more information Learn more about Honeywell’s Farenhyt Series and other products available by visiting www.farenhyt.com Honeywell Security & Fire 12 Clintonville Road Northford, CT 06472 800-328-0103 Conventional Pull Stations PS-SA and PS-DAThe PS-DA and PS-SA Pull Stations are manual pull stationswhich provide a Fire Alarm Control Panel (FACP) with a singlealarm initiating input signal. The PS-DA is a dual-action model.The PS-SA is a single-action model. Both the PS-DA and the PS-SA are equipped with key lock / reset. Both are designed to meetmultiple applications with the installer and end-user in mind. Itsinnovative design, durable construction, and multiple mountingoptions make the PS-DA and PS-SA simple to install, maintain,and operate.The single-action pull-station is activated by a single pull-down ofthe alarm handle. The dual-action versions require pushing in thehandle, then pulling the handle down for activation. The PS-DAand PS-SA manual pull stations are UL listed and meet the ADArequirement of a 5-lbs. maximum pull force to activate. Operatinginstructions are molded into the handle along with Braille text.Molded terminal numbers can be found adjacent to the wiringterminals.Models:PS-SA–Single action with ‘pigtail’ connections and a key lockreset. Pigtail wires are provided for connection to the Fire AlarmControl Panel’s (FACP) initiation circuit.PS-DA –Dual action model with screw terminal connections andakey lock reset.PS-DAH -Same as PS-DA except with hex lock reset.PS-DALOB-Same as PS-DA except with “outdoor use” listing. Includes SB-I/O backbox with sealing gasket.PS-DASP –Same as PS-DA except with both English andSpanish operating instructions.Features:• UL Listed• CSFM Listed• Meets ADA requirements• Operating instructions are molded into the handle along withBraille text.•Made of durable Lexan• Available in Spanish•Key resettable• Easy to Install, maintain and operate•Single or dual action• Surface mount box available P/N 350250 Rev DCopyright © 2011 Honeywell International Inc. Specification:Dimensions:Height: 5-1/2” (13.97 cm)Width: 4” (10.16 cm)Depth: 1-7/16” (3.65 cm)Operatingtemperature:32°F to 120°F (0°C to 49°C)Electrical:Switch ContactRating: 0.25 A @ 30 VAC or VDC Accessories:SB-I/0 Surface Mount Back-boxBG-TR Trim Ring Agency Listings PS-DA PS-DASP PS-SA PS-DA PS-SA Rear PS-DA Rear Made in the U.S.A. This document is not intended to be used for installation purposes. We try to keep ourproduct information up-to-date and accurate. We cannot cover all specific applicationsor anticipate all requirements. All specifications are subject to change without notice.For more information, contact Silent Knight 12 Clintonville Road Northford, CT06472-1610 Phone: (800) 328-0103, Fax: (203) 484-7118. www.farenhyt.com Warning: Risk of fire, explosion, or burns. Do not disassemble,heat above 60 C , or incinerate. R echargeable Sealed Lead-Acid BatteryDC power, constant voltage chargeCycle use: 14.4 - 15.0V(20 C ) Standby use: 13.5 - 13.8V(20 C) Initial current: 5.4A MAX 831334001054 MO DE L P S -12180 NB 12 Volt 18.0 Amp. Hr. S ealed R echargeable B attery 120180400208 L HT H W Tolerances are +/- 0.04 in. (+/- 1mm) and +/- 0.08 in. (+/- 2mm) for height dimensions. All data subject to change without notice. Physical Dimensions: in (mm) Features • Absorbent Glass Mat (AGM) technology for superior performance • Valve regulated, spill proof construction allows safe operation in any position • Power/volume ratio yielding unrivaled energy density • Rugged impact resistant ABS case and cover (UL94-HB) • Approved for transport by air. D.O.T., I.A.T.A., F.A.A. and C.A.B. certified • U.L. recognized under file number MH 20845 Performance Specifications Nominal Voltage .......................................................12 volts (6 cells) Nominal Capacity 20-hr. (900mA to 10.50 volts) .......................................... 18.0 AH 10-hr. (1.7A to 10.50 volts) ............................................. 17.0 AH 5-hr. (3.2A to 10.20 volts) ............................................. 16.0 AH 1-hr. (11.1A to 9.00 volts) ............................................. 11.1 AH 15-min. (34.3A to 9.00 volts) ...............................................8.58 AH Approximate Weight ....................................... 12.60 lbs. (5.72 kg) Energy Density (20-hr. rate) ............... 1.53 W-h/in3 (93.51 W-h/l) Specific Energy (20-hr. rate) ............ 17.14 W-h/lb (37.79 W-h/kg) Internal Resistance (approx.) ..................................... 14 milliohms Max Discharge Current (7 Min.) ............................... 54.0 amperes Max Short-Duration Discharge Current (10 Sec.) .. 180.0 amperes Shelf Life (% of nominal capacity at 68°F (20°C) 1 Month ................................................................................. 97% 3 Months ................................................................................ 91% 6 Months ............................................................................... 83% Operating Temperature Range Charge ................................................-4°F (-20°C) to 122°F (50°C) Discharge ............................................-40°F (-40°C) to 140°F (60°C) Case ..................................................................................ABS Plastic Power-Sonic Chargers ...............................PSC-122000A, 124000A, .................................................................122000A-C, 124000A-C PS-12180 www.power-sonic.comTo ensure safe and efficient operation always refer to the latest edition of our Technical Manual, as published on our website. All data subject to change without notice. Terminals: (mm) 12 Volt 18.0 AH L: 7.13 (181) W: 3.00 (76) H: 6.59 (167) HT: 6.59 (167) • F2 - Quick disconnect tabs, 0.250” x 0.032” - Mate with AMP. INC FASTON “250” series • NB2: Tin plated brass post with nut & bolt connectors • T12 - Threaded insert with 5mm stud 14 4.5126 2 7.95 6.35 3.4 0.8 12mm F2 T12 NB 6mm M5 CORPORATE OFFICE • 7550 Panasonic Way • San Diego, CA 92154 • USA • Tel: +1-619-661-2020 • Fax: +1-619-661-3650 CUSTOMER SERVICE Tel: +1-619-661-2030 Fax: +1-619-661-3648 customer-service@power-sonic.com INTERNATIONAL SALES Tel: +1-650-364-5001 Fax: +1-650-366-3662 international-sales@power-sonic.com DOMESTIC SALES Tel: +1-619-661-2020 Fax: +1-619-661-3650 national-sales@power-sonic.com TECHNICAL SUPPORT Tel: +1-619-661-2020 Fax: +1-619-661-3648 support@power-sonic.com Contact Information www.power-sonic.com 0816 1M © 2016. Power-Sonic Corporation. All rights reserved. All trademarks are the property of their respective owners. Charging Cycle Applications: Limit initial current to 5.4A. Charge until battery voltage (under charge) reaches 14.4 to 14.7 volts at 68°F (20°C). Hold at 14.4 to 14.7 volts until current drops to under 180mA. Battery is fully charged under these conditions, and charger should be disconnected or switched to “float” voltage. “Float” or “Stand-By” Service: Hold battery across constant voltage source of 13.5 to 13.8 volts continuously. When held at this voltage, the battery will seek its own current level and maintain itself in a fully charged condition. Note: Due to the self-discharge characteristics of this type of battery, it is imperative that they be charged within 6 months of storage, otherwise permanent loss of capacity might occur as a result of sulfation. Chargers Power-Sonic offers a wide range of chargers suitable for batteries up to 100AH. Please refer to the Charger Selection Guide in our specification sheets for “C-Series Switch Mode Chargers” and “Transformer Type A and F Series”. Please contact our Technical department for advice if you have difficulty in locating suitable models.Capacity Retention Ratio (%)Standing Period (Months) 100 80 60 40 00 2 4 6 8 10 12 14 16 18 20 40oC (104oF) 30oC (86oF)20oC (68oF) 5oC (41oF) Charging is not necessary unless 100% of capacity is required. Charging beforeuse is necessaryto help recoverfull capacity. Charge may failto restore fullcapacity. Do notlet batteries reachthis state. 100 80 60 40 20 0 0 1 2 3 4 Ambient Temperature 20˚C (68˚F) Float Charging Voltage 2.25 - 2.30 V/Cell Retention Capacity (%)Years 120 100 80 60 40 20 0 0 200 400 600 800 1000 1200 Number of Cycles 1. Discharge Current 0.2C (Final Voltage 1.7V/Cell) 2. Charge Current: 0.1C 3. Ambient Temperature: 20oC to 25oC (68oF to 77oF)Retention Capacity (%)Discharge Depth 30% Discharge Depth 100% Discharge Depth 50% Discharge Characteristics Discharge Time vs. Discharge Current Shelf Life & Storage Life Characteristics in Stand-By Use Life Characteristics in Cyclic Use PS-12180 12 Volt 18.0 AH ® Further Information Please refer to our website www.power-sonic.com for a complete range of useful downloads, such as product catalogs, material safety data sheets (MSDS), ISO certification, etc.. 13.0 12.0 11.0 10.0 9.0 8.0 14.0 Terminal Voltage (V)Ambient Temperature 20oC (68oF) 1.2 2.4 6 12 24 36 48 1 2 4 6 8 10 20 4 0 Discharge Time FinalVoltage min h 0.901.83.6 9.0 18 36 0.90 1.8 3.6 9.0 18 36 Discharge Current (A) 20 15 10 5 2 1 30 10 5Discharge Time40oC (104oF) 20oC (68oF) 0oC (32 oF)minh10.2V 9.6V 9.0V 8.1V Final Voltage 10.5V MOD E L P S -1270 F 1 12 Volt 7.0 Amp. Hr. Warning: R isk of fire, explosion, or burns.Do not disassemble, heat above 60 C , or incinerate. R echargeable Sealed Lead-Acid BatteryDC power, constant voltage chargeCycle use: 14.4 - 15.0V(20 C) S tandby use: 13.5 - 13.8V(20 C) Initial current: 2.1A MAX 801334001000S ealed R echargeable B attery 120070260211 L HT H W 6.35 4.75 3.2 F1 F2 0.8 7.95 6.35 3.4 0.8 Tolerances are +/- 0.04 in. (+/- 1mm) and +/- 0.08 in. (+/- 2mm) for height dimensions. All data subject to change without notice. Physical Dimensions: in (mm) Features • Absorbent Glass Mat (AGM) technology for superior performance • Valve regulated, spill proof construction allows safe operation in any position • Power/volume ratio yielding unrivaled energy density • Rugged impact resistant ABS case and cover (UL94-HB) • Approved for transport by air. D.O.T., I.A.T.A., F.A.A. and C.A.B. certified • U.L. recognized under file number MH 20845 Performance Specifications Nominal Voltage .......................................................12 volts (6 cells) Nominal Capacity 20-hr. (350mA to 10.50 volts) .......................................... 7.00 AH 10-hr. (650mA to 10.50 volts) .......................................... 6.50 AH 5-hr. (1.2A to 10.20 volts) ............................................. 6.00 AH 1-hr. (4.5A to 9.00 volts) ............................................... 4.50 AH 15-min. (14A to 9.00 volts) ..................................................3.50 AH Approximate Weight ......................................... 4.80 lbs. (2.18 kg) Energy Density (20-hr. rate) ............... 1.49 W-h/in3 (90.95 W-h/l) Specific Energy (20-hr. rate) ............ 17.50 W-h/lb (38.58 W-h/kg) Internal Resistance (approx.) ..................................... 23 milliohms Max Discharge Current (7 Min.) ............................... 21.0 amperes Max Short-Duration Discharge Current (10 Sec.) .... 70.0 amperes Shelf Life (% of nominal capacity at 68°F (20°C) 1 Month ................................................................................. 97% 3 Months ................................................................................ 91% 6 Months ............................................................................... 83% Operating Temperature Range Charge ................................................-4°F (-20°C) to 122°F (50°C) Discharge ............................................-40°F (-40°C) to 140°F (60°C) Case ..................................................................................ABS Plastic Power-Sonic Chargers .................................PSC-12800A, 12800A-C PS-1270 www.power-sonic.com To ensure safe and efficient operation always refer to the latest edition of our Technical Manual, as published on our website. All data subject to change without notice. Terminals: (mm) 12 Volt 7.0 AH L: 5.95 (151) W: 2.56 (65) H: 3.70 (94) HT: 3.86 (98) • F1 - Quick disconnect tabs, 0.187” x 0.032”- Mate with AMP. INC. FASTON “187” series • F2 - Quick disconnect tabs, 0.250” x 0.032” - Mate with AMP. INC FASTON “250” series OR CORPORATE OFFICE • 7550 Panasonic Way • San Diego, CA 92154 • USA • Tel: +1-619-661-2020 • Fax: +1-619-661-3650 CUSTOMER SERVICE Tel: +1-619-661-2030 Fax: +1-619-661-3648 customer-service@power-sonic.com INTERNATIONAL SALES Tel: +1-650-364-5001 Fax: +1-650-366-3662 international-sales@power-sonic.com DOMESTIC SALES Tel: +1-619-661-2020 Fax: +1-619-661-3650 national-sales@power-sonic.com TECHNICAL SUPPORT Tel: +1-619-661-2020 Fax: +1-619-661-3648 support@power-sonic.com Contact Information www.power-sonic.com 0816 1M © 2016. Power-Sonic Corporation. All rights reserved. All trademarks are the property of their respective owners. Charging Cycle Applications: Limit initial current to 2.1A. Charge until battery voltage (under charge) reaches 14.4 to 14.7 volts at 68°F (20°C). Hold at 14.4 to 14.7 volts until current drops to under 70mA. Battery is fully charged under these conditions, and charger should be disconnected or switched to “float” voltage. “Float” or “Stand-By” Service: Hold battery across constant voltage source of 13.5 to 13.8 volts continuously. When held at this voltage, the battery will seek its own current level and maintain itself in a fully charged condition. Note: Due to the self-discharge characteristics of this type of battery, it is imperative that they be charged within 6 months of storage, otherwise permanent loss of capacity might occur as a result of sulfation. Chargers Power-Sonic offers a wide range of chargers suitable for batteries up to 100AH. Please refer to the Charger Selection Guide in our specification sheets for “C-Series Switch Mode Chargers” and “Transformer Type A and F Series”. Please contact our Technical department for advice if you have difficulty in locating suitable models.Capacity Retention Ratio (%)Standing Period (Months) 100 80 60 40 00 2 4 6 8 10 12 14 16 18 20 40oC (104oF) 30oC (86oF)20oC (68oF) 5oC (41oF) Charging is not necessary unless 100% of capacity is required. Charging beforeuse is necessaryto help recoverfull capacity. Charge may failto restore fullcapacity. Do notlet batteries reachthis state. 100 80 60 40 20 0 0 1 2 3 4 Ambient Temperature 20˚C (68˚F) Float Charging Voltage 2.25 - 2.30 V/Cell Retention Capacity (%)Years 120 100 80 60 40 20 0 0 200 400 600 800 1000 1200 Number of Cycles 1. Discharge Current 0.2C (Final Voltage 1.7V/Cell) 2. Charge Current: 0.1C 3. Ambient Temperature: 20oC to 25oC (68oF to 77oF)Retention Capacity (%)Discharge Depth 30% Discharge Depth 100% Discharge Depth 50% Discharge Characteristics Discharge Time vs. Discharge Current Shelf Life & Storage Life Characteristics in Stand-By Use Life Characteristics in Cyclic Use PS-1270 12 Volt 7.0 AH ® Further Information Please refer to our website www.power-sonic.com for a complete range of useful downloads, such as product catalogs, material safety data sheets (MSDS), ISO certification, etc.. 13.0 12.0 11.0 10.0 9.0 8.0 14.0 Terminal Voltage (V)Ambient Temperature 20oC (68oF) 1.2 2.4 6 12 24 36 48 1 2 4 6 8 10 20 4 0 Discharge Time FinalVoltage min h 0.350.701.4 3.5 7.0 14 0.35 0.70 1.4 3.5 7.0 14 Discharge Current (A) 20 15 10 5 2 1 30 10 5Discharge Time40oC (104oF) 20oC (68oF) 0oC (32 oF)minh10.2V 9.6V 9.0V 8.1V Final Voltage 10.5V FireForce 8 (FF8) Notification Appliance Circuit Power Supply ff8int.jpgDescription The FireForce 8 (FF8) is a Notification Appliance Circuit (NAC) extender panel designed to extend the power capabilities of existing NACs and provide power for other ancillary devices. The FF8 will connect to any brand of UL-Listed Fire Alarm Control Panel (FACP) to provide Notification Appliance Circuit expansion. Designed with advanced switch-mode power-supply technology, the FireForce 8 provides filtered and electronically regulated power distributed to four NACs. Each NAC is rated at 3.0 A maximum, auxiliary power rated 1.5 A, with a total output capacity of 8.0 A. The outputs may be configured as: four Class B (Style W, X, Y); or two Class A (Style Z); or two Class B and one Class A; or four Class A (Style Z) with the optional Class A adaptor installed. The FF8 includes an internal battery charger. The FF8 provides independent output circuit supervision; so in the event of a NAC fault, the FF8 can notify the FACP. The FF8 has field-selectable, built-in strobe and horn sync protocols that support Faraday, Gentex, System Sensor, Amseco, and Wheelock devices; and a pass-through feature that passes a pre-generated sync protocol from another synchronization source. Independent horn silencing via sync protocol allows synchronized horns and strobes to operate on a single circuit. For enhanced notification appliance circuit survivability, the FF8 can utilize its dual-activation inputs for redundant trip operation. One of the most challenging aspects of a retrofit application is locating the existing EOL resistor. In retrofit applications that have EOL values other than the 3.9K ohm EOL resistor normally used with the FF8, a single resistor matching the existing EOL can be used as a reference EOL for all outputs. This feature speeds installation and system checkout. The reference resistor must be within a range of 2K to 25K ohms. Benefits • Extends and supplies power for additional fire alarm devices. • Instantaneous switchover to standby battery (if equipped) when AC fails, maintaining power to all attached devices without intervention. • Reference resistor feature eliminates need to locate EOL in retrofit applications. • Strobe signal "passes through" allowing syncing of large systems. • Redundant trip functionality that allows multiple activation inputs. Features • Provides two fully-supervised input/control circuits. • Redundant activation option for survivability. • Pass-through and generated sync protocols, compatible with the following appliances: Wheelock, Faraday, System Sensor, Amseco, and Gentex — as field-selectable options. • Four configurable supervised NAC outputs. • 8.0 A, 24 VDC, fully regulated full-load output (power limited). • Output fault notification to FACP. • Eight trouble and status LEDs. • Common trouble Form-C relay. • Isolated AC Fail Form-C relay, immediate or delayed six hours. • Ground fault detection. • 26 AH battery charger capability. • Selectable temporal coding. • Facilitates multiple NAC synchronization for large areas. • Optional multipack for up to four FF8s in a single lockable enclosure. • Optional Class A adaptor (HPP31076). Specifications • Primary input power: 120 VAC, 60 Hz, 3.0 A; or 220 V, 1.5 A; jumper selectable. • Secondary power: 24-volt operation, two 7 – 26 AH batteries. • Battery charging capacity: up to 26 AH batteries; 12 AH batteries to fit in cabinet. • Battery space: up to two 12 AH batteries maximum inside FF8 cabinet. Larger batteries require a separate battery cabinet. • Standby current: 0.040 A. • Auxiliary power output: 0.15 A under all conditions. 1.5 A, if load is removed during operation (external relay or AC Fail relay use required). • NAC output ratings: 24 VDC fully regulated, 3.0 A maximum per circuit (8.0 A total). • End-of-line resistor range: 2K to 25K, 1/2 watt. • Common trouble relay, AC Fail relay: 2.0 A/28 VDC or 120 VAC. • Input control circuit: 16 – 30 VDC @ 5 mA minimum. • Temperature rating: 32°F to 120°F (0°C to 49°C). • Relative humidity: 10 – 93%, non-condensing. • Dimensions: FF8 cabinet: 18.0" H x 12.5" W x 4.5" D (cm: 45.72 H x 31.75 W x 11.43 D). FF8-MP cabinet: 37.2" H x 24.0" W x 6.0" D (cm: 94.49 H x 60.96 W x 15.24 D). Automation and Control Solutions Honeywell 12 Clintonville Road 1(877) HPP-POWR Northford, CT 06472-1610 hpp_techserv@honeywell.com www.honeywellpower.com This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. ©2010 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. DH-1010:B May 2010 Made in the U.S.A. ® U.S. Registered Trademark © 2010 Honeywell International Inc. Page 2 of 2 Listings Listings and approvals below apply to the basic FireForce 8 panel. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. • UL Listed: file S6677 • MEA: 206-01-E Vol II • CSFM: 7300-1637:100 • FM Approved Ordering Information FF8: 24 VDC, 8.0 A, fire alarm NAC expander/power supply with integral battery charger. FF8-MP: Multipack cabinet with one FF8 and space for up to three additional FF8-CMs or 31085s in a single lockable enclosure. UL approved. FF8-CM: Chassis assembly version of FF8, for mounting in FF8-MP spaces. HPP31076: Class A adaptor, converts signal circuits to Class A wiring. 31081: SCE-95 mounting plate provides a means to install two SCE-95 modules. The addition of SCE-95s provides a means to run on FF8 outputs via a panel command on an SLC. Mounts over the main PCB, hinged for access to FF8 terminal. 31085: Mounting plate for XP95 devices into the FF8-MP; includes standoffs for eight devices. BAT-1270: Battery, 12 VDC, 7 AH (two required for 24 V operation). BAT-12120: Battery, 12 VDC, 12 AH (two required for 24 V operation). Data Sheet ES001-0108 Issue 1 Not to be used for installation purposes. Page 1 of 2 The Edwards 125 Class Strobe beacons are UL and cUL listed signaling devices, available in two versions, normal light output and high light output. Both versions feature a corrosion resistant Type 4X enclosure and can be panel or conduit mounted. The base is manufactured from a 33% glass filled nylon, providing high resistance to heat and high chemical resistivity. The lens is made of shatter resistant polycarbonate. Both the normal light output and high light output beacons are available with either a black or gray base, and amber, blue, clear, green or red lens. The 125 Class Strobe beacons can be mounted on 1/2" or 3/4" NPT conduit using a 1/2" internal or 3/4" external conduit hub that comes with the unit. It can also be panel-mounted using the mounting gasket provided with the unit. When panel- mounting the 125 Class Strobe, the surface and construction details of the panel must be taken into consideration to ensure the integrity of the outdoor, NEMA 4X rating is fully maintained. 125 Class Strobe Features • High Light Output available in 120V AC • Normal Light Output available in 12-48V DC, 120V AC or 240V AC • Available with gray or black base • Option for panel or conduit mounting • Available in High Light Output or Normal Light Output versions • Available with amber, blue, clear, green or red lens • -31°F to 150°F (-35°C to 66°C) operating temperature • Protective wire guard available, Cat. No. 125GRD 125 Class Strobe Beacons for NEMA 4X Applications 125 Class Strobe Beacons Description Strobe Output Cat. No.Base Color Lens Colors Operating Voltage Current Replacement Lens Replacement Strobe Tube Strobe Beacons in NEMA 4X Enclosure High Output 300,000 peak candlepower** 125STRH*120A Gray Amber, Blue, Clear, Green, Red 120V AC 50/60 Hz 0.120 A 125L*91B-ST 125STRH*120AB Black Amber, Blue, Clear, Green, Red 120V AC 50/60 Hz 0.120 A 125L*91B-ST Normal Output 175,000 peak candlepower 125STRN*1248D Gray Amber, Blue, Clear, Green, Red 12-48V DC 0.350 A 125L*114-ST 125STRN*120A Gray Amber, Blue, Clear, Green, Red 120V AC 50/60 Hz 0.100 A 125L*91B-ST 125STRN*240A Gray Amber, Blue, Clear, Green, Red 240V AC 50/60 Hz 0.050 A 125L*91B-ST 125STRN*1248DB Black Amber, Blue, Clear, Green, Red 12-48V DC 0.350 A 125L*114-ST 125STRN*120AB Black Amber, Blue, Clear, Green, Red 120V AC 50/60 Hz 0.100 A 125L*91B-ST 125STRN*240AB Black Amber, Blue, Clear, Green, Red 240V AC 50/60 Hz 0.050 A 125L*91B-ST Data Sheet ES001-0108 Issue 1 Not to be used for installation purposes. Page 2 of 2 41 Woodford Avenue Plainville, CT 06062 1.800.336.4206 www.edwardssignaling.com © Copyright 2010 Edwards Signaling *Letter in this position designates lens color: A - amber, B - blue, C - clear, G - green, or R - red **Maximum capacitor operating temperature (Tc) is 185°F (85°C). Dimensional Drawings Agency Approvals Gasket (provided for use when direct panel mounting) Locknut - 1.3625" O.D. (provided for use when direct panel mounting) 3.25"(82.6mm) 3.875"(98.4mm) Double threaded forpanel mounting or1/2" internal or 3/4" externalconduit mounting 1638 Listed Listed NEMA 4X Enclosure Listed Agency Listings SSM/SSV Series Alarm Bells System Sensor’s SSM and SSV series alarm bells are low current, high decibel notification appliances for use in fire and burglary systems or other signaling applications. Features • Approved for indoor and outdoor use • Low current draw • High dB output • Available in six-inch, eight-inch, and ten-inch sizes • AC and DC models • DC models polarized for use with supervision circuitry • Mount directly to standard four-inch square electrical box indoors • SSM and SSV series come pre-wired Reliable Performance. The SSM and SSV series provide loud resonant tones. The SSM series operates on 24VDC and are motor driven, while the SSV series operates on 120VAC utilizing a vibrating mechanism. Simplified Installation. For indoor use, the SSM and SSV series mount to a standard four-inch square electrical box. For outdoor applications, weatherproof back box, model number WBB, is used. The SSM and SSV series come pre-wired, to reduce installation time. The SSM series incorporates a polarized electrical design for use with supervision circuitry. S4011 7135-1653:0125CS5493005255 3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 www.systemsensor.com ©2012 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. WFDS74501 • 3/12 Ordering Information UL/FM Model No.ULC/Canadian Model No.Description SSM24-6 SSM24-6A Bell, 6˝, 24VDC, Polarized, 82dBA SSM24-8 SSM24-8A Bell, 8˝, 24VDC, Polarized, 80dBA SSM24-10 SSM24-10A Bell, 10˝, 24VDC, Polarized, 81dBA SSV120-6 SSV120-6A Bell, 6˝, 120VAC, 85dBA SSV120-8 SSV120-8A Bell, 8˝, 120VAC, 82dBA SSV120-10 SSV120-10A Bell, 10˝, 120VAC, 82dBA WBB Weatherproof back box for SSM and SSV series, when installed outdoors SSM/SSV Specifications Architectural/Engineering Specifications Model shall be a SSM or SSV Series alarm bell. Bells shall have underdome strikers and operating mechanisms. Gongs on said bells shall be no smaller than nominal 6˝/8˝/10˝ (specify size) with an operating voltage of 24VDC or 120VAC (specify by part number). Bells shall be suitable for surface or semi-flush mounting. Outdoor surface mounted installations shall be weatherproof (using optional WBB weatherproof electrical box). Otherwise bells shall mount to a standard 4˝ square electrical box having a maximum projection of 2½˝. Bells shall be located as shown on the drawings or as determined by the Authority Having Jurisdiction. Bells shall be listed for indoor/outdoor use by Underwriters Laboratories and the California State Fire Marshal, and approved by Factory Mutual and MEA. Physical/Operating Specifications Operating Temperature Range –31°F to 140°F Operating Voltage SSM series: 24 VDC SSV series: 120 VAC Termination Provided with 2 sets of leads for in/out wiring Service Use Fire Alarm, General Signaling, Burglar Alarm Warranty 3 years Electrical Specifications Model Gong Diameter (inches) Nominal Voltage Operating Voltage Limit Maximum Current Sound Output (dBA) SSM24-6 6 Regulated 24VDC 16 to 33VDC DC-31.1mA/ FWR-53.5mA 82 SSM24-8 8 Regulated 24VDC 16 to 33VDC DC-31.1mA/ FWR-53.5mA 80 SSM24-10 10 Regulated 24VDC 16 to 33VDC DC-31.1mA/ FWR-53.5mA 81 SSV120-6 6 Regulated 120VAC 96 to 132VAC 53mA 85 SSV120-8 8 Regulated 120VAC 96 to 132VAC 53mA 82 SSV120-10 10 Regulated 120VAC 96 to 132VAC 53mA 82 * Sound output measured at Underwriter Laboratories, as specified in UL464 E120V-GT Hybrid Surge Protection Device Features • 120 VAC • 10KA Short Circuit Current Rating • ANSI/UL Listed 1449 4th Edition, Type 2 • CSA C22.2 No. 269.2-17 2nd edition, Type 2 • Acerbox ELOCK Circuit Lockout Kit included per NFPA 72 2013 10.6.5.2 • Surface or conduit mounting • Diagnostic indicator light • Self restoring • 3 Wire device (18” length) An ideal choice for your 120VAC applications, the E120V-GT maintains system integrity and protects against transients introduced into electrical lines via poor atmospheric and utility conditions as well as internally generated inductive loads. Not only is the E-120V-GT robust enough to absorb a spike, but to also clamp long enough to trip the branch circuit breaker and still be functional for additional surges. Reduce downtime associated with power surges and lightning strikes, prevent interruption of recurring monthly revenue based systems, and eliminate non-billable service calls and expensive repairs by protecting your equipment with this invaluable device. Applications • Fire alarm control panels • Mass notification systems • Dedicated branch circuits • Amplifiers, motors, pumps, and power boosters Specifications All 120 VAC equipment will have Transient Voltage Surge Suppression (TVSS) protection manu factured by Space Age Electronics, Inc., part number E120V-GT. The unit shall be ANSI/ UL listed to standard 1449, 4th edition and will be labeled clearly with indelible ink. Can be attached via the ¾” rigid coupling, or surface mounted via the 2 external mounting holes. The unit shall have thermal fuses to protect against fire in short circuit conditions and will have 18” long, 14 gauge wires (3x) with a green ground wire. The enclosure will be a non dielectric material UL94 QMFZ2/8 grade material providing UV protection. The unit shall provide visual indication (LED) that unit is protecting and functioning. Pg. 1/2 Ordering Information P/N# E120V-GT 120V Hybrid Surge Protection Device (ELOCK Circuit Lockout Kit included) P/N# ELOCK-FA Acerbox ELOCK Circuit Lockout Kit www.1sae.com | toll free 1.800.486.1723 | fax 508.485.4740 © Copyright 2018 Space Age Electronics, Inc. | This document subject to change without notice | LT10629 | Rev. A Pg. 2/2 Performance Specifications Short Circuit Current Rating (SCCR): 10kA Enclosure Material: UL94 QMFZ2/8 (green) VPR=700 (L-N) 700 (L-G) 600 (N-G) Capacitance: < 2,000 pf Clamping Response Time: < 5 nanoseconds Current: Non-Load Bearing Max Operating Voltage (MCOV): 140VAC, 50/60 Hz Design: Thermally Fused Hybrid Operation Indicators: LED Max Surge Current: 25kA Energy Dissipation: 500J Clamping Voltage: 230V RMS Operating Specifications Service Voltage: 120VAC Single Phase Circuits Protected: L-N L-G N-G Connection Type: Hardwired Installation Configuration: Parallel Compliance Specifications UL Listed: 1449 4th Edition - VZCA File Number: E319370 Vol. 1 Sec. 1 Dimensions Wiring Diagram Device Type Qty Total Qty Total IFP-300 Control Panel 1 x 0.190000 =0.190000 1 x 0.250000 =0.250000 IDP-PHOTO 0 x 0.000300 =0 x 0.000300 = IDP-PHOTO-T 0 x 0.000300 =0 x 0.000300 = IDP-PHOTOR 0 x 0.000300 =0 x 0.000300 = IDP-ION 0 x 0.000300 =0 x 0.000300 = IDP-HEAT 0 x 0.000300 =0 x 0.000300 = IDP-HEAT-HT 0 x 0.000300 =0 x 0.000300 = IDP-HEAT-ROR 0 x 0.000300 =0 x 0.000300 = IDP-BEAM 0 x 0.002000 =0 x 0.002000 = IDP-BEAM-T 0 x 0.002000 =0 x 0.002000 = IDP-FIRE-CO 0 x 0.030000 =0 x 0.007200 = IDP-ACCLIMATE 0 x 0.000300 =0 x 0.000300 = IDP-CONTROL 0 x 0.000375 =0 x 0.000375 = IDP-MONITOR 0 x 0.000375 =0 x 0.000375 = IDP-MINIMON 6 x 0.000375 =0.002250 6 x 0.000375 =0.002250 IDP-PULL-SA 0 x 0.000375 =0 x 0.000375 = IDP-PULL-DA 5 x 0.000375 =0.001875 5 x 0.000375 =0.001875 IDP-MONITOR-2 4 x 0.000750 =0.003000 4 x 0.000750 =0.003000 IDP-MONITOR-10 0 x 0.003500 =0 x 0.003500 = IDP-RELAY-6 0 x 0.001450 =0 x 0.001450 = IDP-CONTROL-6 0 x 0.002250 =0 x 0.002250 = IDP-RELAY 0 x 0.000255 =0 x 0.000255 = IDP-RELAYMON-2 0 x 0.001300 =0 x 0.024000 = IDP-ZONE 0 x 0.002000 =0 x 0.002000 = IDP-ZONE-6 0 x 0.002000 =0 x 0.002000 = B200S 0 x 0.000300 =0 x 0.000300 = B200S-LF 0 x 0.003000 =0 x 0.000300 = B200SR 0 x 0.000300 =0 x 0.000300 = B200SR-LF 0 x 0.001000 =0 x 0.125000 = B224RB 0 x 0.000500 =0 x 0.000500 = RTS151KEY 0 x 0.000000 =0 x 0.007500 = RA100Z 0 x 0.000000 =0 x 0.010000 = IDP-CONTROL (Aux. Power)0 x 0.001700 =0 x 0.007000 = IDP-CONTROL-6 (Aux. Power)0 x 0.008000 =0 x 0.020000 = IDP-ZONE (Aux. Power)0 x 0.012000 =0 x 0.090000 = IDP-ZONE-6 (Aux. Power)0 x 0.050000 =0 x 0.270000 = B200S (Aux. Power)0 x 0.000500 =0 x 0.035000 = B200S-LF (Aux. Power)0 x 0.000550 =0 x 0.140000 = B200SR (Aux. Power)0 x 0.000500 =0 x 0.035000 = B200SR-LF (Aux. Power)0 x 0.001000 =0 x 0.125000 = IDP-ISO 0 x 0.000450 =0 x 0.000450 = B224BI 0 x 0.000500 =0 x 0.000500 = RA-2000 0 x 0.025000 =0 x 0.050000 = RA-2000GRAY 0 x 0.025000 =0 x 0.050000 = 6815 0 x 0.078000 =0 x 0.078000 = RA-100 0 x 0.020000 =0 x 0.025000 = RA-1000 0 x 0.020000 =0 x 0.025000 = RA-1000R 0 x 0.020000 =0 x 0.025000 = 5824 0 x 0.045000 =0 x 0.045000 = 5496 0 x 0.010000 =0 x 0.010000 = 7. Accessory Modules 1. Control Panel 2. Addressable SLC Devices 3. Addressable SLC Detectors 4. SLC Accessories 5. Auxiliary Power Draw - SLC Devices 6. SLC Isolator Devices IFP-300 Battery Calculation Secondary Power Source Requirements Standby Current (amps)Secondary Alarm Current (amps) Current Draw Current Draw Silent Knight by Honeywell Page 1 5/1/2019 RPS-1000 0 x 0.010000 =0 x 0.010000 = 5865-4 0 x 0.035000 =0 x 0.145000 = 5865-3 0 x 0.035000 =0 x 0.145000 = 5880 0 x 0.035000 =0 x 0.200000 = 5883 0 x 0.000000 =0 x 0.220000 = SK-NIC 0 x 0.021000 =0 x 0.021000 = SK-FML 0 x 0.053000 =0 x 0.053000 = SK-FSL 0 x 0.079000 =0 x 0.079000 = IPDACT-2 0 x 0.093000 =0 x 0.136000 = IPDACT-2UD 0 x 0.098000 =0 x 0.155000 = CELL-MOD 0 x 0.055000 =0 x 0.100000 = CELL-CAB-SK 0 x 0.055000 =0 x 0.100000 = Conventional Detectors 0 x 0.000000 =0 x 0.000000 = IDP-PHOTO-W 6 x 0.000300 =0.001800 6 x 0.000000 =0.000000 Miscellaneous Device 2 0 x 0.000000 =0 x 0.000000 = Miscellaneous Device 3 0 x 0.000000 =0 x 0.000000 = Miscellaneous Device 4 0 x 0.000000 =0 x 0.000000 = Miscellaneous Device 5 0 x 0.000000 =0 x 0.000000 = NAC 1 0.000000 =0.000000 = NAC 2 0.000000 =0.000000 = NAC 3 0.000000 =0.000000 = Constant-Power 1 0.000000 =0.000000 = 0.198925 0.257125 8. Network Cards 9. Auxiliary Devices 10. Miscellaneous Devices 11. Output Circuits Total Standby Load Total Alarm Load Silent Knight by Honeywell Page 2 5/1/2019 Note 2: Use the dropdowns in the yellow cells to enter values. x =4.774 AH x =0.022 AH 4.796 AH =x 1.20 5.75 AH Circuit#4 current is within the limitations of the circuit. IFP-300 Control Panel: The output current is within the panel's limitations. The batteries can be housed in the IFP-300 Cabinet. Current Draw Check Circuit#1 current is within the limitations of the circuit. Circuit#2 current is within the limitations of the circuit. Circuit#3 current is within the limitations of the circuit. Total Ampere Hours Required Recommended Batteries:BAT-1270 - 7AH Batteries Battery Check The batteries can be charged by the IFP-300 Charger. Alarm Load Current (Amps)0.25713 Amps 0.084 Total Current Load Multiply by the Derating Factor 1.2 Standby Load Current 0.19893 Amps 24 Required Alarm Time in Minutes 5 Minutes IFP-300 Battery Calculation Note 1: You are fully responsible for verifying these calculations. Calculation in Total Sheet Required Standby Time in Hours 24 Hours Silent Knight by Honeywell Page 3 5/1/2019 Device Qty Total Qty Total 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0.000000 0.000000 Device Qty Total Qty Total 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0.000000 0.000000 Device Qty Total Qty Total 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0.000000 0.000000 Device Qty Total Qty Total 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0 x 0.000000 =0 x 0.000000 = 0.000000 0.000000 Non-Alarm Draw Alarm Draw Total Standby Load Total Alarm Load NAC 3 Non-Alarm Draw Alarm Draw Total Standby Load Total Alarm Load Constant-Power 1 Total Standby Load Total Alarm Load NAC 2 Non-Alarm Draw Alarm Draw Total Standby Load Total Alarm Load IFP-300 Circuit Detail NAC 1 Non-Alarm Draw Alarm Draw Silent Knight by Honeywell Page 4 5/1/2019 Silent Knight by Honeywell Page 5 5/1/2019 Standby 0.075 A Alarm 4.696 A Qty Draw Non-Alarm Qty Draw Alarm 1 x 0.07500 0.07500 1 x 0.20600 0.20600 4 x 0.00000 0.00000 4 x 0.14700 0.58800 3 x 0.00000 0.00000 3 x 0.13900 0.41700 1 x 0.00000 0.00000 1 x 0.09400 0.09400 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0.00000 1.09900 4 x 0.00000 0.00000 4 x 0.14700 0.58800 3 x 0.00000 0.00000 3 x 0.13900 0.41700 1 x 0.00000 0.00000 1 x 0.09400 0.09400 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0.00000 1.09900 4 x 0.00000 0.00000 4 x 0.14700 0.58800 3 x 0.00000 0.00000 3 x 0.13900 0.41700 1 x 0.00000 0.00000 1 x 0.09400 0.09400 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0.00000 1.09900 4 x 0.00000 0.00000 4 x 0.14700 0.58800 3 x 0.00000 0.00000 3 x 0.13900 0.41700 2 x 0.00000 0.00000 2 x 0.09400 0.18800 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0.00000 1.19300 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0.00000 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAC #3 Totals (Max 3 Amps): 5. NAC #4 PC2RL75 P2RL75 SPSWV30 P2RL75 SPSWV30 NAC #2 Totals (Max 3 Amps): Device PC2RL75 SPSWV30 4.696 System Current Draw - HPFF8 Total Current P2RL75 Secondary Alarm CurrentSecondary Non-Alarm Current 1. System Modules 2. NAC #1 HPFF8 Main Circuit Board Other compatible devices Other compatible devices Total Non-Alarm Load: 3. NAC #2 NAC #1 Totals (Max 3 Amps): P2RL75 SPSWV30 NAC #4 Totals (Max 3 Amps): 4. NAC #3 PC2RL75 TB4 Totals (Max 2 Amps): PC2RL75 Other compatible devices 7. Compatible Devices not listed 0.075 6. Auxiliary Power Auxiliary Device Auxiliary Device Auxiliary Device Auxiliary Device Auxiliary Device Total Alarm Load: Protected Premises:Date:5/1/2019 Address: City:State:MA Zip: Prepared By:Phone: Address:Email: City:State:MA Zip:02359 Secondary Load Requirements 2.63 Amp Hours Total (AH) 1.80 0.39 2.19 x 1.2 2.63 AH 7 Amp Hours TRUE Current Draw Secondary Standby Load Select batteries from the list below. Battery Selection 7.0 AH BAT-1270 Battery (12 volt) Derating factor Secondary Load Requirements Total Secondary Load Secondary Alarm Load x4.696 A Required Alarm Time (hours) 0.084 hours Time (hours) Required Standby Time 24 hoursx Total Secondary Load from the calculation table below. 0.075 A 70 CORPORATE PARK #1215 GARYE@FIRETECHNOLOGIESLLC.COM PEMBROKE Secondary Power Requirements FW WEBB SALEM GARY J. EMOND SET HPFF8 Power Supply Two Four (two 12VDC sets in parallel) Page 1 of 2 Battery Distribution Chart Comments 4.37 2.16 0.47 3. The selected batteries (7AH) are within the charger range of this power supply (7-26AH). Spare Battery Capacity Secondary Standby Load 2. Selected battery size meets secondary load requirements. Battery Selection (AH) - Secondary Load Requirements (AH) Secondary Standby Load (AH) * Derating Factor 1. Batteries will fit in the FACP cabinet. Secondary Alarm Load (AH) * Derating FactorSecondary Alarm Load Shows amp-hour distribution of your selections. Spare Battery Capacity 62% Secondary Standby Load 31% Secondary Alarm Load 7%Spare Battery Capacity Secondary Standby Load Secondary Alarm Load Page 2 of 2