200611 EBSB Salem MA - Stamped and Signed Fire Alarm Permit Plans Rev 3 2001170FIRE ALARM NOTES: (F1) FIRE ALARM INSTALLATION CONTRACTOR SHALL OBTAIN A COPY OF THE FIRE ALARM REGULATIONS FROM THE LOCAL FIRE PREVENTION DEPARTMENT, BUREAU OF FIRE PREVENTION. THESE REGULATIONS ARE PART OF THE PROJECT'S CONSTRUCTION DOCUMENTS AND THE CONTRACTOR SHALL REVIEW ALL LOCAL REGULATIONS PRIOR TO SUBMITTING BID. IF THERE IS ANY CONFLICT BETWEEN WHAT IS SHOWN ON THE DRAWINGS AND LOCAL REGULATIONS THEN LOCAL REGULATIONS SHALL TAKE PRIORITY. CONTRACTOR SHALL INFORM ENGINEER IF ANY CONFLICTS ARISE PRIOR TO SUBMITTING BID. CONTRACTOR SHALL PROVIDE FINAL "AS —BUILT" DRAWINGS AT THE END OF THIS PROJECT. (F2) (F3) (F4) (F5) (F6) (F7) (F8) (F9) NEW AUDIO/STROBES SHALL BE ADA AND NFPA 72 APPROVED. CANDELA RATING AS NOTED. NEW AUDIO/STROBES SHALL HAVE A 1 WATT AUDIO OUTPUT. AUDIO/STROBES SHALL BE MTD. 80" A.F.F. OR 6" BELOW CEILING HEIGHT WHICHEVER IS LESS. SMOKE DETECTORS SHALL BE PHOTOELECTRIC TYPE. THE TESTING OF THE FIRE ALARM SYSTEM SHALL BE INCLUDED IN THE CONTRACT OF THE EC. EC SHALL CONFIRM THAT THE CURRENT DRAW ON THE AUDIO RISER IS NOT EXCEEDED DUE TO THE CURRENT DRAW OF EACH NEW AUDIO/STROBE. ALL WIRING SHALL TERMINATE ON TERMINAL BOARDS IN SPACE FATC. EC SHALL FURNISH, INSTALL, AND WIRE REMOTE ALARM INDICATORS (RAI) AND REMOTE ALARM INDICATORS WITH TEST SWITCHES (RAITS) AS INDICATED ON THE PLANS. EC SHALL FURNISH AND INSTALL ENGRAVED NAMEPLATES FOR EACH RAI AND RAITS. EACH ENGRAVED NAMEPLATE SHALL HAVE THE UNIQUE NAME FOR EACH ROOM OR DEVICE IT IS MONITORING. (F10) EC SHALL CONFIRM THAT THERE ARE NO OPEN OR SHORTED FIRE ALARM CIRCUITS PRIOR TO FACP TIE IN AND TEST. (F1 1) ALL WIRING FOR FIRE ALARM DEVICES SHALL BE TWISTED SHIELDED TYPE, #16 AWG SOLID COPPER IN 1/2" IMC OR METAL CLAD CABLE PAINTED RED. (F12) ALL AUDIO/STROBES SHALL BE SYNCHRONIZED. (F13) CONTRACTOR SHALL PERFORM ALL BATTERY CALCULATIONS FOR THE FIRE ALARM SYSTEM TO MEET ALL NFPA 72 REQUIREMENTS. ANY BATTERY UPGRADES, ADDITIONS OR MODIFICATIONS TO MEET ALL STATE AND LOCAL REQUIREMENTS. (F14) CONTRACTOR SHALL PERFORM A SITE SURVEY BEFORE SUBMITTING BID. (F15) FINAL FIRE DEPARTMENT ACCEPTANCE TESTING OF THE FIRE ALARM SYSTEM SHALL BE INCLUDED IN THE CONTRACT OF THE CONTRACTOR. TESTING SHALL INCLUDE ALL AUXILIARY INITIATING, CONTROL, AND INDICATING FUNCTIONS AS REQUIRED BY THE AUTHORITY HAVING JURISDICTION. (F16) THE CONTRACTOR SHALL PREPARE A CERTIFICATION OF COMPLETION PRIOR TO FIRE DEPARTMENT ACCEPTANCE TEST. (F17) DOOR CONTROL: THE FIRE ALARM SYSTEM SHALL OVERRIDE ALL SECURITY SYSTEM ELECTRIC DOOR LOCKS WHICH EMERGENCY DOORS OR, ARE PRIMARY PATHS OF EGRESS. ALL MAGNETIC DOOR HOLDERS IN THE PREMISES SHALL BE RELEASED. (F18) OUTSIDE BEACON & MUNICIPAL FIRE DEPARTMENT CONNECTION: A. PROVIDE 200 Cd WP BEACON FOR EACH PROJECT SPACE. B. PROVIDE TIE AND PROGRAMMING OF INTO EXISTING FACP. (F19) ZONE WIRING: A. MATCH EXISTING FOR INITIATING DEVICES. B. SHALL MATCH EXISTING FOR NOTIFICATION APPLIANCES. (F20) FINAL "AS —BUILT" DRAWINGS AND DOCUMENTATION — THE CONTRACTOR SHALL PROVIDE REPRODUCIBLE DRAWINGS DETAILING THE FOLLOWING: SCHEMATICS OF ALL COMPONENT INTERCONNECTIONS ASSEMBLY DRAWINGS OF ALL CONTROL PANELS CONNECTION DIAGRAMS OF TERMINAL OR MODULE CABINETS LOCATION OF END OF THE LINE COMPONENTS MANUALS FOR ALL CONTROL PANELS CUT SHEETS FOR EACH DEVICE BATTERY CALCULATIONS SYSTEMWIDE RISER DIAGRAM WITH INITIATING, INDICATING AND CONTROL DEVICES (F21) MINIMUM BATTERY AND WIRING REQUIREMENTS: A. BOX AND CONDUIT MARKINGS: BOXES, CABINETS OR ENCLOSURES CONTAINING FIRE ALARM COMPONENTS OR TERMINATIONS SHALL BE RED AND CLEARLY MARKED "FIRE ALARM". CONDUIT SHALL BE MARKED WITH A 2" WIDE RED STRIPE EVERY 10' AND WITHIN 3' OF EACH BOX. B. TERMINATION'S: CABLE TERMINATION'S SHALL BE MADE ON TERMINAL STRIPS WITH EACH WIRE LABELED IN THE FOLLOWING WAY: INPUT OR OUTPUT ZONE ZONE NUMBER LINE VOLTAGE POLARITY C. BATTERY CALCULATIONS THE CONTRACTOR SHALL SIZE THE AMPERE —HOUR OF THE BATTERIES BASED ON THE FOLLOWING: MANUFACTURERS DATA SHEETS FOR ALL INDICATING AND INITIATING COMPONENTS. MANUFACTURERS DATA SHEETS ON ALL FIRE ALARM SYSTEM ELECTRIC POWER CONSUMING COMPONENTS. A. B. THE BATTERIES SHALL BE SIZED TO HANDLE BOTH STANDBY AND ALARM MODES WITH 25% SPARE CAPACITY: 24 HOURS IN THE STANDBY MODE 45 MINUTES IN FULL LOAD ALARM MODE D. FIRE ALARM TERMINAL CABINETS CONTRACTOR SHALL PROVIDE. A NEMA 4, RED CABINET APPROXIMATELY 24"X 18" X 6" DEEP IN EACH OF THE FOLLOWING LOCATIONS: BACK EXITS (F22) GUARANTEE: A. THE FIRE ALARM SYSTEM SHALL BE FREE FROM DEFECTS IN WORKMANSHIP AND MATERIALS UNDER NORMAL USE AND SERVICE FOR A PERIOD OF ONE YEAR FROM THE DATE OF ACCEPTANCE. ANY EQUIPMENT SHOWN TO BE DEFECTIVE IN WORKMANSHIP OR MATERIAL SHALL BE REPAIRED, REPLACED OR ADJUSTED FREE OF CHARGE. THE DATE OF ACCEPTANCE SHALL BE THE DATE OF FINAL APPROVAL OF THE FIRE DEPARTMENT. (F23) TIE INTO EXISTING FACP AND PROVIDE ALL PROGRAMMING, WIRING AND TESTING. (F24) CONFIRM ALL DEVICE QUANTITIES WITH FLOOR PLANS. ACTUAL FIRE ALARM DEVICE COUNTS SHALL BE DONE WITH FIRE ALARM FLOOR PLANS. PROVIDE AS PART OF THE DOCUMENTATION AN "AS —BUILT" RISER DIAGRAM AT THE END OF THE PROJECT. (F25) CONTRACTOR SHALL PROVIDE AND INSTALL WITH MECHANICAL CONTRACTOR DUCT SMOKE DETECTORS (DSD) WITH MONITOR MODULES AT THE COMMON ROOFTOP UNIT DUCTED RETURN AIR RISER. THE DUCT SMOKE DETECTORS WHEN ACTIVATED SHALL ALARM AT THE FIRE ALARM CONTROL PANEL AND SHUT DOWN THE ASSOCIATED HVAC EQUIPMENT. DSD SHALL BE FURNISHED WITH REMOTE ALARM INDICATORS AND TEST SWITCHES THAT ARE PERMANENTLY AND PROPERLY LABELED IN THE OCCUPIED SPACE. (F26) CARBON MONOXIDE DETECTORS SHALL BE PROVIDED AND INSTALLED THAT SEND A TROUBLE ALARM IF THE 9 PPM CARBON MONOXIDE LEVEL IS REACHED TO THE CENTRAL STATION SERVICE FOR CORRECTIVE ACTION TO BE INITIATED. SCHEDULE OF FIRE ALARM DRAWINGS DWG. # DESCRIPTION FIRE ALARM FA0.0 FIRE ALARM — SYMBOLS, NOTES, & DETAILS FA1.0 FIRE ALARM — FIRE ALARM PLAN DURING CONSTRUCTION FA1.1 FIRE ALARM — NEW FLOOR PLAN BLACK #16AWG THHN SOLID CLEAR PLASTIC WRAPPING ARMORED CABLE PAINTED RED FIRELITE MS-10UD F—SSD F—SSD 1SD F—SSD PULL STATION F—SSD DUCT SMOKE DETECTORS EA-S EA-S DSD R A T 135F F—dil° SD LOUNGE DSD R A T F—SSD SMOKE/HEAT DETECTORS E,FACP LOCATED ON 2ND FLOOR INSIDE BUILDING MANAGEMENT OFFICE AT 201-201 WASHINGTON STREET ARAIREMOTE NNUNCIATOR 1-o 1-o AUDIO/VISUAL STROBE FIRE ALARM - RISER DIAGRAM SCALE: NTS FIRE ALARM RISER DIAGRAM NOTES (F1) CONFIRM ALL DEVICE QUANTITIES WITH FLOOR PLANS. FIRE ALARM RISER DIAGRAM SHALL BE USED AS A SYSTEM INTEGRATION DIAGRAM ONLY. ACTUAL FIRE ALARM DEVICE COUNTS SHALL BE DONE WITH FIRE ALARM FLOOR PLANS. PROVIDE AS PART OF THE DOCUMENTATION AN "AS —BUILT" RISER DIAGRAM AT THE END OF THE PROJECT THAT SHOWS ALL WIRING, DEVICE ADDRESSES (ZONING), BATTERY AMPERE —HOUR AND VOLTAGE DROP CALCULATIONS. (F2) GROUNDING CONDUCTOR NOT SHOWN IN FIRE ALARM RISER DIAGRAM FOR REASONS OF CLARITY. ALUMINUM —BARE CONTINUOUS BOND STRIP WHITE #16AWG THHN SOLID LUMINUM FOIL SHIELD NOTES: ZONE WIRING: (PROVIDE ADDRESSABLE FIRE ALARM SYSTEM) A. INITIATING DEVICE CIRCUITS (IDC) SHALL BE SUPERVISED CLASS A. B. NOTIFICATION APPLIANCE CIRCUITS (NAC) SHALL BE CLASS A. C. SIGNALING LINE CIRCUITS (SLC) SHALL BE CLASS A. D. 2#16—Cu, SOLID, WITH GROUND FPLP METAL —CLAD CABLE PAINTED RED AS THE MINIMUM STANDARD FOR FIRE ALARM SYSTEM WIRING. 1) ON PARALLEL RUNS EC SHALL MAINTAIN A 1' CLEARANCE MINIMUM FROM POWER & TEL/DATA CONDUCTORS. MFR PART #: AFC CABLE SYSTEMS 16-2/1 TSP PRODUCT CODE 1860 DESCRIPTION: FIRE ALARM FPLP CONTROL CABLE AVAILABLE THROUGH: AFC CABLE SYSTEMS 800-757-6996 2 TYP FPLP, 16/2 TSP, ARMORED CABLE PAINTED RED SCALE: NTS 7'-6" 6'-8" 4'-0" Ct I1 FIRE FINISHED FLOOR • REMOTE ALARM INDICATOR FIRE ALARM AUDIO/VISUAL DEVICES WALL TELEPHONES/FIRE TELEPHONE JACK PULL STATION NOTES: 1. DEVICES SHALL BE INSTALLED ON A COMMON VERTICAL CENTERLINE WHEREVER POSSIBLE. 2. ALL DEVICES SHALL BE INSTALLED AT MOUNTING HEIGHTS AS INDICATED ON THIS DETAIL, UNO. SYSTEM I\PUTS FIRE ALARM AC POWER FAILURE 2. FIRE ALARM SYSTEM LOW BATTERY 3. OPEN CIRCUIT 4. GROUND FAULT 5. SHORT CIRCUIT 6. MANUAL PULL STATION AREA SMOKE DETECTOR(S) 8. HVAC AIR DUCT SMOKE DETECTORS 9. — 10. — 11. — 12. — 13. — 14. — WIRING DEVICE, STANDARD MOUNTING HEIGHTS FOR TYPICAL DEVICES SCALE: NTS VISUAL STROBE DSD IDlD 200 CANDELA EXTERIOR STROBE ❑K F—SSD FIRE DEPARTMENT KEY VAULT AND KEYS PER LOCAL FIRE DEPARTMENT REQUIREMENTS SYSTE V OUTPUTS —SS D ANNUNCIATION NOTIFICATION LIFE SAFETY CONTROLS cp F. G' J �J ' Q PP'PJ,`x-J1,e1cjs S c F. 4.4, 4. F. 4, & -1 ABCDEFGHI JKLMNOPQRS 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ABCDEFGHI JKLMNOPQRS FIRE ALARM - INPUT/OUTPUT MATRIX SCALE: NTS SUBSCRIPTS & ABBREVIATIONS AFF ACT Cd CO CP DACT EMT E EC ER F FA FACP FARA FATC FBO FMC FUAC MC MTD N NP SPE TBD UNO WP ABOVE FINISHED FLOOR ABOVE COUNTER TOP INDICATES THE CANDELA RATING OF THE CARBON MONOXIDE CONTROL PANEL DIGITAL ALARM RECIEVER/TRANSMITTER ELECTRICAL METALLIC TUBING EXISTING ELECTRICAL CONTRACTOR EXISTING, RELOCATED FUTURE FIRE ALARM FIRE ALARM CONTROL PANEL FIRE ALARM REMOTE ANNUNCIATOR FIRE ALARM TERMINAL CABINET FURNISHED BY OTHERS FLEXIBLE METAL CONDUIT FURNISHED UNDER ANOTHER CONTRACT MECHANICAL CONTRACTOR MOUNTED NEW DEVICE NORMAL POWER SIGNAL POWER EXPANDER TO BE DETERMINED UNLESS NOTED OTHERWISE WEATHER PROOF STROBE 2. 3. 4. 5. 6 7. 8. 9. 10. 11 12. 13. 14. SYMBOLS PsH — S SD 135F 75 Cd —1Q DBA IMI PSD PULL STATION SMOKE DETECTOR, PHOTOELECTRIC TYPE HEAT DETECTOR, FIXED TEMPERATURE AS INDICATED AUDIO —STROBE W/CANDELLA & AUDIO LEVEL MASTERBOX PLENUM SMOKE DETECTOR ❑K — FIRE DEPARTMENT KEY VAULT — REMOTE ALARM INDICATOR IRAITSI— — REMOTE ALARM INDICATOR WITH TEST INDICATOR SWITCH SYNC SPE DSD IFARA 1 - 200 CANDELA EXTERIOR STROBE SYNCHRONIZATION MODULE AUDIO/STROBE SIGNAL POWER EXPANDER DUCT SMOKE DETECTOR — RADIO MASTERBOX MM — FIRE ALARM REMOTE ANNUNCIATOR MONITOR MODULE 1111114 O'SULLIVAN ARCHITECTS, I\C. ARCHITECTURE (DESIGN I PLANNING 580 READING, MAIN MASSACHUSETTS STREET, SUITE 204 01867 Tel: www.osullivanarchitects.com (781) 439-6166 Fax (781) 439-6170 These for use use is Reuse or in permission © 2019 drawings at the location expressly limited or reproduction part, is prohibited of O'Sullivan O'Sullivan and specifications indicated. to the by without Architects, Architects were prepared Publication identified location. any method, in the written Inc. Inc. and whole airim New England =__. Engineering Building Massachusetts 30 Turnpike Tel: (508) Systems Road, 485-4633 & Commissioning Suite #1, Southborough, Fax: (508) Engineers MA 01772 485-1830 East New Boston Savgs Branch Bak 193 Salem, Washington VA 01970 St ABBREVIATIONS FIRE NOTES, SYMBOLS, ALARM AND yg4'� ppyy { NN y:.�1.E�.r t �47{��AL Vv. °'`.064 � i• fs SCALE: AS NOTED ISSUED / DRAWN BY © O'Sullivan Architects Inc. REVISED / REVISED BY Issued for Permit 3-05-20 Revision 1 4-17-20 Revision 2 4-23-20 Revision 3 6-10-20 . JOB NO: 20011 70 SHEET NUMBER FAO.O FIRE ALARM DURING CONSTRUCTION NOTES: (F1) CONTRACTOR SHALL PERFORM PRIOR TO SUBMITTING BID. (F2) ALL FIRE ALARM DEVICES AND (F3) CONTRACTOR SHALL REPLACE DURING DEMOLITION AND NEW A DETAILED FIELD INVESTIGATION FOR EXACT WORK SCOPE COMPONENTS ARE NEW, UNLESS NOTED OTHERWISE. ALL EXISTING SMOKE DETECTORS WITH HEAT DETECTORS CONSTRUCTION. PULL STATION AUDIO/VISUAL STROBE 75 Cd 85 dBA 135F 135F 135F 135F 135F 135F AUDIO/VISUAL STROBE 75 Cd 85 dBA 135F 135F 135F AUDIO/VISUAL STROBE 75 Cd 85 dBA 135F PULL STATION 135F FIRE ALARM - FIRE ALARM BASEMENT PLAN DURING SCALE: 1 /4"=1'-0" 135F 135F CONSTRUCTION (II 1111111114 O'SULLIVAN ARCHITECTS, I\C. ARCHITECTURE (DESIGN I PLANNING 580 MAIN READING, STREET, MASSACHUSETTS SUITE 204 01867 Tel: (781) www.osullivanarchitects.com 439-6166 Fax (781) 439-6170 These drawings for use at the use is expressly Reuse or reproduction or in part, is permission of © 2019 O'Sullivan and location limited prohibited O'Sullivan specifications were prepared indicated. Publication and to the identified location. by any method, in whole without the written Architects, Inc. Architects Inc. =_`- New England =---- Engineering Building Massachusetts 30 Turnpike Tel: (508) Systems Road, 485-4633 Suite & #1, Fax: Commissioning Engineers Southborough, MA 01772 (508) 485-1830 East New Boston Samos Branch Bank 193 Salem, Washington VA 01970 St FIRE DURING CONSTRUCTION PLAN ALARM - s me ELEC , *E. No. 4064E5 SCALE: AS NOTED ISSUED / DRAWN BY © O'Sullivan Architects Inc. REVISED / REVISED BY Issued for Permit 3-05-20 Revision 1 4-17-20 Revision 2 4-23-20 JOB NO: 20011 70 SHEET NUMBER FA1.O FIRE ALARM NOTES (F1) NEW AUDIO/STROBES SHALL BE ADA APPROVED. (F2) AUDIO/STROBES SHALL BE MTD. 80" A.F.F. OR 6" BELOW CEILING HEIGHT WHICHEVER IS LESS. (F3) WHERE SHOWN ON PLANS, SMOKE DETECTORS SHALL BE PHOTOELECTRIC TYPE. (F4) THE TESTING OF THE FIRE ALARM SYSTEM SHALL BE INCLUDED IN THE CONTRACT OF THE EC. (F5) EC SHALL FURNISH, INSTALL, AND WIRE REMOTE ALARM INDICATORS (RAI) AND REMOTE ALARM INDICATORS WITH TEST SWITCHES (RAITS) AS INDICATED ON THE PLANS. EC SHALL FURNISH AND INSTALL ENGRAVED NAMEPLATES FOR EACH RAI AND RAITS. EACH ENGRAVED NAMEPLATE SHALL HAVE THE UNIQUE NAME FOR EACH ROOM OR DEVICE IT IS MONITORING. (F6) EC SHALL CONFIRM THAT THERE ARE NO OPEN OR SHORTED FIRE ALARM CIRCUITS PRIOR TO FACP TIE IN AND TEST. (F7) ALL WIRING FOR FIRE ALARM DEVICES SHALL BE TWISTED SHIELDED TYPE, AWG SIZED FOR VOLTAGE DROP BY FACP SYSTEM PROVIDER. USE SOLID COPPER IN 1/2" IMC OR METAL CLAD CABLE OR ARMORED CLAD CABLE PAINTED RED. (F8) ALL AUDIO/STROBES AND STROBES SHALL BE SYNCHRONIZED. (F9) CONTRACTOR SHALL PERFORM CALCULATIONS FOR THE FIRE ALL NFPA 72 REQUIREMENTS. ADDITIONS OR MODIFICATIONS LOCAL REQUIREMENTS. (F10) CONTRACTOR SHALL PERFORM SUBMITTING BID. ALL BATTERY ALARM SYSTEM TO MEET ANY BATTERY UPGRADES, TO MEET ALL STATE AND A SITE SURVEY BEFORE (F1 1) THE CONTRACTOR SHALL PREPARE A CERTIFICATION OF COMPLETION PRIOR TO FIRE DEPARTMENT ACCEPTANCE TEST. (F12) FIRESTOP ALL FIRE RATED ASSEMBLY PENETRATIONS AS REQUIRED BY STATE FIRE AND BUILDING CODES. OFFICE /4> -F CE -LICE FIRE ALARM SEQUENCE (SEQ) OF OPERATION: UPON ACTIVATION OF ANY DOUBLE ACTION PULL STATION, SMOKE DETECTOR, OR HEAT DETECTOR: SEQ1— UPON ACTIVATION OF FIRE ALARM THE FACP SHALL NOTIFY THE MUNICIPAL FIRE DEPARTMENT THROUGH THE MASTERBOX OR CENTRAL STATION THRU DACT. SEQ2— ACTIVATE THE HORN/STROBE AND STROBE EVACUATION SYSTEM. SEQ3— INDICATE THE ZONE OR DEVICE OF ACTIVATION ON THE FACP AND REMOTE ANNUNCIATOR(S). SEQ4— RELEASE ALL FIRE DOORS (MAGNETIC HOLD) CONNECTED TO THE FIRE ALARM SYSTEM. SEQ5— RELEASE ALL PATH OF EGRESS ELECTRIC/MAGNETIC SECURITY LOCKS CONNECTED TO THE FIRE ALARM SYSTEM. FIRE DEPARTMENT KEY VAULT AND KEYS PER LOCAL FIRE DEPARTMENT REQUIJ€Mad-T-- AUDIO/VISUAL STROB 5 Cd 85 tl'BA_ LOBBY VISUAL ROBE 75 Cd derb t t i WORK ROOM FIRE ALARM - NEW GROUND FLOOR PLAN SCALE: 1 /4"=1'-0" FIRE ALARM METHODOLOGY, SEQUENCE OF OPERATION & TESTING THE FIRE ALARM SYSTEM IS DESIGNED TO MEET THE FIRE ALARM SYSTEM REQUIREMENTS OF THE STATE BUILDING CODE. NOTIFICATION APPLIANCE (AUDIO/STROBE) AND SMOKE DETECTOR ADDITIONS TO THE AUTOMATIC FIRE ALARM AND SUPERVISION REQUIREMENTS PERFORMED BY THE CONSTRUCTION WORK ARE AS FOLLOWS: 1. FIRE ALARM SYSTEM INITIATING MANUAL PULL STATIONS ARE PROVIDED NOT MORE THAN FIVE FEET AWAY FROM AT ALL FLOOR EXITS AND MOUNTED 48" ABOVE THE FINISHED FLOOR. INITIATING AUTOMATIC SMOKE DETECTORS AND DUCT SMOKE DETECTORS SHALL ACTIVATE THE FIRE ALARM AND DUCT SMOKE DETECTORS SHALL ALSO SHUT DOWN THE CORRESPONDING HVAC EQUIPMENT. CARBON MONOXIDE DETECTORS SHALL BE MONITORED FOR TROUBLE CONDITIONS SUCH AS HIGH CARBON MONOXIDE LEVELS. 2. FIRE ALARM SYSTEM NOTIFYING AUDIO STROBE AND STROBE COVERAGE HAS BEEN ADDED PER 2013 NFPA 72 PUBLIC MODE, THE AMERICAN WITH DISABILITIES ACT (ADA), AND STATE BUILDING CODE REQUIREMENTS FOR SPACING, CANDELA AND AUDIO ALARM AMPLITUDE. 3. WHEN THE FIRE ALARM SYSTEM IS ACTIVATED, ALL AUDIO STROBES SHALL IN SYNCHRONIZED MANNER ALARM FOR BUILDING EVACUATION AS DESCRIBED PER THE 2013 NFPA 72. 4. TESTING OF ALL FIRE ALARM SYSTEM FUNCTIONS THAT CONSTITUTE THE WORK UNDER THIS PROJECT SHALL BE COORDINATED WITH THE FIRE DEPARTMENT. ALL 2013 NFPA 72 REQUIREMENTS, ALONG WITH THOSE OF THE AUTHORITY HAVING JURISDICTION SHALL BE MET. CONTRACTOR SHALL COORDINATE FIRE ALARM TESTING WITH ALL OTHER PROJECT CONTRACTORS TO CONFIRM ALL FIRE ALARM FUNCTIONS AS DEFINED IN THIS NARRATIVE REPORT FOR THE AFFECTED SPACE. AUDIO/VISUAL STROBE Cd 85 .BA HP2FCU1 L STROBE LL STATION STAFF UNCE • STROBE 75( \ OMEN ANITO TOR/LAC PROJECT SPACE E,FACP ON 2ND FLOOR OF 201 -203 WAS H I N GTO N ST FIRE ALARM - KEY MAP OF BUILDING SCALE: 1 /16"=l'-0" APPROXIMATE SCALE (i 4111 O'SULLIVAN ARCHITECTS, I\C. ARCHITECTURE I DESIGN I PLANNING 580 MAIN READING, STREET, SUITE MASSACHUSETTS 204 01867 Tel: (781) 439-6166 www.osullivanarchitects.conn Fax: (781) 439-6170 These drawings for use at the location use is expressly Reuse or reproduction or in part, is prohibited permission of O'Sullivan © 2019 O'Sullivan and specifications were indicated. Publication limited to the identified location. by any method, in without the written Architects, Inc. Architects Inc. prepared and whole New England ___ Engineering .:::::: Building Massachusetts 30 Turnpike Tel: (508) Systems Road, 485-4633 & Commissioning Suite #1, Southborough, MA Fax: (508) 485-1830 Engineers 01772 East New Boston Savgs Branch Bn 193 Salem, Washington IVA 01970 St FIRE NEW PLAN ALARM FLOOR - KITSA „IS. ELECTRICAL No. 40646 +,7 SCALE: AS NOTED ISSUED / DRAWN BY © O'Sullivan Architects Inc. REVISED / REVISED BY Issued for Permit 3-05-20 Revision 1 4-17-20 Revision 2 4-23-20 Revision 3 6-10-20 JOB No: 2001 170 SHEET NUMBER Al ■