04 TYCO DRY QR HSWSeries DS-1 Dry-Type Sprinklers 5.6K Pendent, Upright, and Horizontal Sidewall Quick Response, Standard Coverage Page 1 of 10 MARCH 2019 TFP510 IMPORTANT Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information. Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Worldwide Contacts www.tyco-fire.com authorities having jurisdiction. Failure to do so may impair the performance of these de vices. The owner is responsible for maintain­ ing their fire protection system and de vices in proper operating condi­ tion. Contact the installing contrac­ tor or product manufacturer with any questions. The Series DS­1 Dry­Type Sprinklers must only be installed in fittings that meet the requirements of the Design Criteria section. Sprinkler Identification Numbers (SINs) 3/4 in. NPT: TY3935 – Pendent TY3735 – Horizontal Sidewall 1 in. NPT: TY3235 – Pendent TY3135 – Upright TY3335 – Horizontal Sidewall Technical Data Approvals UL and C-UL Listed FM Approved NYC Approved under MEA 352-01-E Previous New York City Approval and MEA certification numbers apply to product as shown in this data sheet. In accordance with Section BC 3502 of the Construction Code, current NYC Approvals for use in the City of New York apply to all products that contain UL or FM Approvals and Listings; therefore, not all products currently Approved for use in the City of New York will carry an actual MEA Certifi- cation number. See Tables A and B. Maximum Working Pressure 175 psi (12,1 bar) Inlet Thread Connections 3/4 in. NPT 1 in. NPT or ISO 7-R 1 Discharge Coefficient K=5.6 gpm/psi½ (80,6 lpm/bar½) General Description TYCO Series DS-1 Dry-Type Sprinklers, 5.6K Pendent, Upright, and Horizontal Sidewall, Quick Response (3 mm bulb) and Standard Coverage are decora- tive glass bulb automatic sprinklers de signed for commercial use. Dry-type sprinklers are typically used where: • pendent sprinklers are re quired on dry pipe systems that are exposed to freezing temperatures (for example, sprinkler drops from unheated portions of buildings) • sprinklers and/or a portion of the connecting piping are exposed to freezing temperatures; for example, sprinkler drops from wet sys tems into freezers, sprinkler sprigs from wet systems into unheated attics, or horizontal piping extensions through a wall to protect an unheated areas such as loading docks, overhangs, and building exteriors • sprinklers are used on systems that are seasonally drained to avoid freezing (for example, vacation areas) NOTICE The Series DS­1 Dry­Type Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applica­ ble standards of the NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), in addition to the standards of any Temperature Ratings See Tables A and B Finishes Sprinkler: Natural Brass, Chrome Plated, or Signal White Escutcheon: Signal White, Chrome Plated, or Brass Plated Physical Characteristics Inlet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Copper Plug . . . . . . . . . . . . . . . . . . . . . . . . . . . . Copper Yoke .......................Stainless Steel Casing .............Galvanized Carbon Steel Insert . . . . . . . . . . . . . . . . . . . . . . . . . . . Bronze Bulb Seat . . . . . . . . . . . . . . . . . . . Stainless Steel Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Glass Compression Screw . . . . . . . . . . . . . . . . .Bronze Deflector . . . . . . . . . . . . . . . . . . . . . . . . . Bronze Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze Guide Tube . . . . . . . . . . . . . . . . . Stainless Steel Water Tube . . . . . . . . . . . . . . . . . Stainless Steel Spring .....................Stainless Steel Plug Spring* . . . . . . . . . . . . . . . . Stainless Steel Sealing Assembly . Beryllium Nickel w/TEFLON Escutcheon ....Carbon Steel or Stainless Steel * For 3/4 in. NPT only TFP510 Page 2 of 10 WATER TUBE VENT HOLE GUIDE TUBE SEALING PLUG WITH DEFLECTOR SPRING ASSEMBLY FRAME 3 mm BULB INSERT YOKE SCREW INLET CASING BULB COMPRESSION SEAT INLET BAND WATER TUBE VENT HOLE GUIDE TUBE 3 mm BULB INSERT SPRING SCREW INLET SEALING PLUG WITH CASING DEFLECTOR BULB YOKE COMPRESSION SEAT ASSEMBLY FRAME SPRING PLUG INLET BAND FIGURE 2 SERIES DS-1, 1 IN. NPT AND ISO 7-R 1 DRY-TYPE SPRINKLER ASSEMBLY FIGURE 1 SERIES DS-1, 3/4 IN. NPT, DRY-TYPE SPRINKLER ASSEMBLY Operation When the TYCO Series DS-1 Dry-Type Sprinklers, 5.6K Pendent, Upright, and Horizontal Sidewall, Quick Response (3 mm bulb) and Standard Coverage are in service, water is prevented from entering the assembly by the Plug with Sealing Assembly in the Inlet of the Sprinkler. See Figures 1 and 2. The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass Bulb, and the Bulb Seat is released. The compressed Spring is then able to expand and push the Water Tube as well as the Guide Tube outward. This action simultaneously pulls inward on the Yoke, withdrawing the Plug with Sealing Assembly from the Inlet and allowing the sprin kler to activate and flow water. Design Criteria The TYCO Series DS-1 Dry-Type Sprin- klers, 5.6K Pendent, Upright, and Hor- izontal Sidewall, Quick Response (3 mm bulb) and Standard Cover- age are intended for use in fire sprin- kler systems designed in accordance with the standard installation rules recognized by the applicable Listing or Approval agency; for example, UL Listing is based on NFPA 13 requirements. Sprinkler Fittings Install the 3/4 or 1 in. NPT Series DS-1 Dry-Type Sprinklers in the 3/4 or 1 in. NPT outlet or run of the follow- ing fittings: • malleable or ductile iron threaded tee fittings that meet the dimen- sional requirements of ANSI B16.3 (Class 150) • cast iron threaded tee fittings that meet the dimensional requirements of ANSI B16.4 (Class 125) Do not install the DS-1 Sprinklers into an elbow fittings. The Inlet of the sprinkler can contact the interior of the elbow, potentially damaging the Inlet seal. The unused outlet of the threaded tee is plugged as shown in Figure 13. You can also install the Series DS-1 Dry-Type Sprinklers in the 3/4 or 1 in. NPT outlet of a GRINNELL Figure 730 Mechanical Tee. However, the use of the Figure 730 Tee for this arrangement is limited to wet pipe systems. TFP510 Page 3 of 10 1 in. NPT (and ISO 7-R 1) TY3235 Pendent with Recessed Escutcheon (Figure 4) TY3235 Pendent with Standard Escutcheon (Figure 3) with Deep Escutcheon(Figure 5) without Escutcheon (Figure 6) TY3135 Upright without Escutcheon5 (Figure 7) TY3335 Horizontal Sidewall with Top of Deflector-to-Ceiling Distance of 4 to 12 in. (100 to 300 mm) with Standard Escutcheon (Figure 8) with Deep Escutcheon (Figure 9) without Escutcheon (Figure 10) Temperature Rating Bulb Color Code Finish Natural Brass Chrome Plated White Polyester Natural Brass Chrome Plated White Polyester Natural Brass Chrome Plated White Polyester 135°F (57°C)Orange 1, 2, 3, 4 1, 2, 4 1, 2, 3, 4 1, 2, 4 1*, 2*, 3**, 4 1*, 2*, 4 155°F (68°C)Red 175°F (79°C)Yellow 200°F (93°C)Green 286°F (141°C)Blue 1, 2, 4 Notes: 1. Listed by Underwriters Laboratories, Inc. (maximum order length of 48 in.) 2. Listed by Underwriters Laboratories for use in Canada (maximum order length of 48 in.) 3. Approved by Factory Mutual Research Corporation (maximum order length of 48 in.) 4. Approved by the City of New York under MEA 352-01-E 5. The Upright Sprinkler without an Escutcheon (TY3135) is available in 1 in. NPT only * Light and Ordinary Hazard occupancies only ** Light Hazard occupancies only 3/4 in. NPT TY3935 Pendent with Recessed Escutcheon (Figure 4) TY3935 Pendent with Standard Escutcheon (Figure 3) with Deep Escutcheon (Figure 5) without Escutcheon (Figure 6) TY3735 Horizontal Sidewall with Top of Deflector-to-Ceiling Distance of 4 to 12 in. (100 to 300 mm) with Standard Escutcheon (Figure 8) with Deep Escutcheon (Figure 9) without Escutcheon (Figure 10) Temperature Rating Bulb Color Code Finish Natural Brass Chrome Plated White Polyester Natural Brass Chrome Plated White Polyester Natural Brass Chrome Plated White Polyester 135°F (57°C)Orange 1, 2 1, 2 1*, 2* 155°F (68°C)Red 175°F (79°C)Yellow 200°F (93°C)Green 286°F (141°C)Blue Notes: 1. Listed by Underwriters Laboratories, Inc. (maximum order length of 48 in.) 2. Listed by Underwriters Laboratories for use in Canada (maximum order length of 48 in.) * Light and Ordinary Hazard occupancies only TABLE A 3/4 IN. NPT SERIES DS-1 QUICK RESPONSE, STANDARD COVERAGE DRY-TYPE SPRINKLERS LABORATORY LISTINGS AND APPROVALS TABLE B 1 IN. NPT (AND ISO 7-R 1) SERIES DS-1 QUICK RESPONSE, STANDARD COVERAGE DRY-TYPE SPRINKLERS LABORATORY LISTINGS AND APPROVALS TFP510 Page 4 of 10 2-1/4" DIA. (57,2 mm) 1-3/8" ± 1/8" (34,9 ± 3,2 mm) 2-7/8" DIA. (73,0 mm) IN 1/4" (6,4 mm) 3-3/4" to 48" INCREMENTS (95,3 to 1219,2 mm) ORDER LENGTHS: SPRINKLER FACE OF FITTING CEILING FACE OF CRITERIA SECTION) (REFER TO DESIGN SPRINKLER FITTING ORDER LENGTHS: INCREMENTS 4-1/4" ± 1/8" (108,0 ± 3,2 mm) IN 1/4" (6,4 mm) (12,7 to 1168,4 mm) 1/2" to 46" FACE OF CEILING (88,9 mm) 3-1/2" DIA. 2-1/2" DIA. (63,5 mm) FITTING FACE OF SPRINKLER CRITERIA SECTION) (REFER TO DESIGN SPRINKLER FITTING ORDER LENGTHS: (69,9 to 1219,2 mm) 2-3/4" to 48" IN 1/4" (6,4 mm) INCREMENTS FITTING FACE OF SPRINKLER SPRINKLER FITTING (REFER TO DESIGN CRITERIA SECTION) (76,2 mm) 3" DIA. 1-3/4" DIA. (44,5 mm) (55,6 ± 3,2 mm) 2-3/16" ± 1/8" CEILING FACE OF SPRINKLER FACE OF FITTING (127,0 to 1219,2 mm) INCREMENTS IN 1/4" (6,4 mm) ORDER LENGTHS: 5" to 48" DEFLECTOR TO CEILING 1-3/4" (44,5 mm) MINIMUM SPRINKLER FITTING (REFER TO DESIGN CRITERIA SECTION) TOP OF DEFLECTOR CRITERIA SECTION) (REFER TO DESIGN SPRINKLER FITTING SPRINKLER FITTING FACE OF IN 1/4" (6,4 mm) INCREMENTS (127,0 to 1219,2 mm) 5" to 48" ORDER LENGTHS: FIGURE 5 PENDENT TY3235 AND TY3935 WITH DEEP ESCUTCHEON FIGURE 6 PENDENT TY3235 AND TY3935 WITHOUT ESCUTCHEON FIGURE 3 PENDENT TY3235 AND TY3935 WITH STANDARD ESCUTCHEON FIGURE 4 PENDENT TY3235 AND TY3935 WITH RECESSED ESCUTCHEON FIGURE 7 UPRIGHT TY3135 WITHOUT ESCUTCHEON 1 IN. NPT ONLY TFP510 Page 5 of 10 3.5°5/16" (7,9 mm) CENTERLINE OF WATERWAY FITTING SPRINKLER FACE OF 2-1/4" (57,2 mm) DEFLECTOR TO 5-1/2" to 48" (139,7 to 1219,2 mm) IN 1/4" (6,4 mm) INCREMENTS ORDER LENGTHS: MINIMUM MOUNTING SURFACE SPRINKLER FITTING CRITERIA SECTION) (REFER TO DESIGN FACE OF SPRINKLER FITTING SPRINKLER FITTING (REFER TO DESIGN CRITERIA SECTION) CENTERLINE OF WATERWAY FACE OF MOUNTING SURFACE ORDER LENGTHS: 1/2" to 45-3/4" (12,7 to 1162,1 mm) IN 1/4" (6,4 mm) INCREMENTS 5/16" (7,9 mm) 3.5° 2-1/2" DIA. (63,5 mm) 4-1/4" ± 1/8" (108,0 ± 3,2 mm) 3-1/2" DIA. (88,9 mm) FACE OF SPRINKLER FITTING SPRINKLER FITTING (REFER TO DESIGN CRITERIA SECTION) CENTERLINE OF WATERWAY 1-3/4" DIA. (44,5 mm) FACE OF MOUNTING SURFACE ORDER LENGTHS: 2-3/4" to 48" (69,9 to 1219,2 mm) IN 1/4" (6,4 mm) INCREMENTS 3" DIA. (76,2 mm) 5/16" (7,9 mm) 2-3/8" ± 1/8" (60,3 ± 3,2 mm) 3.5° FIGURE 8 TY3335 AND TY3735 HORIZONAL SIDEWALL WITH STANDARD ESCUTCHEON FIGURE 9 TY3335 AND TY3735 HORIZONAL SIDEWALL WITH DEEP ESCUTCHEON FIGURE 10 TY3335 AND TY3735 HORIZONAL SIDEWALL WITHOUT ESCUTCHEON The configuration shown in Figure 12 is only applicable for wet pipe systems where the sprinkler fitting and water- filled pipe above the sprinkler fitting are not subject to freezing and where the length of the Dry-Type Sprinkler has the minimum exposure length depicted in Figure 11. See the Exposure Length section. For wet pipe system installations of the 1 in. NPT Series DS-1 Dry-Type Sprin- klers connected to CPVC piping, use only the following TYCO CPVC fittings: • 1 in. x 1 in. NPT Female Adapter (P/N 80145) • 1 in. x 1 in. x 1 in. NPT Sprinkler Head Adapter Tee (P/N 80249) For wet pipe system installations of the the 3/4 in. NPT Series DS-1 Sprinklers connected to CPVC piping, use in the 3/4 in. x 3/4 in. NPT Female Adapter (P/N 80142). For dry pipe system installa- tions, use only the side outlet of maximum 2-1/2-in. reducing tee when locating the Series DS-1 Sprinklers directly below the branch line. Other- wise, use the configuration shown in Figure 13 to assure complete water drainage from above the Series DS-1 Dry-Type Sprinklers and the branch line. Failure to do so may result in pipe freezing and water damage. NOTICE Do not install the Series DS­1 Dry­Type Sprinkler into any other type fitting without first consulting the Technical Services Department. Failure to use the appropriate fitting may result in one of the following: • failure of the sprinkler to operate properly due to formation of ice over the inlet Plug or binding of the Inlet Plug • insufficient engagement of the Inlet pipe threads with consequent leakage Drainage In accordance with the minimum requirements of the NATIONAL FIRE PROTECTION ASSOCIATION for dry pipe sprinkler systems, branch, cross, and feed-main piping connected to Dry Sprinklers and subject to freezing tem- peratures must be pitched for proper drainage. Exposure Length When using Dry Sprinklers in wet pipe sprinkler systems to protect areas subject to freezing temperatures, use TFP510 Page 6 of 10 RECESS WRENCH FLAT WRENCH WITH SPRINKLER ENGAGEMENT IN TO ENSURE WRENCHING AREA PUSH WRENCH SIDE OUTLET PLUGGED TO WET SYSTEM FITTING (SEE DESIGN CRITERIA SECTION) SPRINKLERDSB-2 INTENDED FOR FREEZER STRUCTURES HEATED AREA RUN OUTLET PLUGGED TO DRY SYSTEM DSB-2 INTENDED FOR FREEZER STRUCTURES FITTING (SEE DESIGN CRITERIA SECTION) SPRINKLER AREA SUBJECT TO FREEZING INSULATED FREEZER STRUCTURE STRAP TIES (ENDS ON OPPOSING SIDES OF BOOT) ADHESIVE DS-1 SHOWN WITH STANDARD ESCUTCHEON 1-3/4" DIA. (44,5 mm) CLEARANCE HOLE DSB-2 BOOT (SEE DESIGN CRITERIA SECTION) FACE OF SPRINKLER FITTING LENGTH EXPOSURE DSB-2 INTENDED FOR FREEZER STRUCTURES HEATED AREA INSULATED FREEZER STRUCTURE STRAP TIES (ENDS ON OPPOSING SIDES OF BOOT) ADHESIVE DS-1 SHOWN WITH STANDARD ESCUTCHEON 1-3/4" DIA. (44,5 mm) CLEARANCE HOLE DSB-2 BOOT FIGURE 16 W-TYPE 7 SPRINKLER WRENCH FIGURE 12 SPRINKLER FITTING HEATED AREA FIGURE 15 MODEL DSB-2 SPRINKLER BOOT WITH SIDEWALL SERIES DS-1 DRY SPRINKLER FIGURE 13 SPRINKLER FITTING UNHEATED AREA FIGURE 11 EXPOSURE LENGTH FIGURE 14 MODEL DSB-2 SPRINKLER BOOT WITH PENDENT SERIES DS-1 DRY SPRINKLER TFP510 Page 7 of 10 Ambient Temperature Exposed to Discharge End of Sprinkler Temperatures for Heated Area1 40°F (4°C) 50°F (10°C) 60°F (16°C) Minimum Exposed Barrel Length2 , in. (mm) 40°F (4°C)0 0 0 30°F (-1°C)0 0 0 20°F (-7°C) 4 (100)0 0 10°F (-12°C) 8 (200) 1 (25)0 0°F (-18°C) 12 (305) 3 (75)0 -10°F (-23°C) 14 (355) 4 (100) 1 (25) -20°F (-29°C) 14 (355) 6 (150) 3 (75) -30°F (-34°C) 16 (405) 8 (200) 4 (100) -40°F (-40°C) 18 (455) 8 (200) 4 (100) -50°F (-46°C) 20 (510) 10 (255) 6 (150) -60°F (-51°C) 20 (510) 10 (255) 6 (150) Notes: 1. For protected area temperatures that occur between values listed above, use the next cooler temperature. 2. These lengths are inclusive of wind velocities up to 30 mph (18,6 kph). TABLE C EXPOSED SPRINKLER BARRELS IN WET PIPE SYSTEMS MINIMUM RECOMMENDED LENGTHS meet the requirements of the Design Criteria section. See the Design Crite- ria section for other important require- ments regarding piping design and sealing of the clearance space around the Sprinkler Casing. Do not install any bulb-type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin- kler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 in. (1,6 mm) for the 135°F (57°C) rating to 1/8 in. (3,2 mm) for the 286°F (141°C) rating. • A leak-tight 3/4 in. NPT sprinkler joint should be obtained by applying a minimum-to-maximum torque of 10 to 20 lb-ft (13,4 to 26,8 N·m). • A leak-tight 1 in. NPT sprinkler joint should be obtained by applying a minimum-to-maximum torque of 20 to 30 lb-ft (26,8 to 40,2 N·m). Higher levels of torque can distort the sprinkler Inlet with consequent leakage or impairment of the sprinkler. Do not attempt to compensate for insufficient adjustment in an Escutch- eon Plate by under or over-tightening the sprinkler. Re-adjust the position of the sprinkler fitting to suit. Step 1. Install pendent sprinklers only in the pendent position, and install upright sprinklers only in the upright position. The deflector of a pendent or upright sprin kler must be parallel to the ceiling. Install horizontal sidewall sprinklers in the horizontal position with their cen- terline of waterway perpen dicular to the back wall and parallel to the ceiling. Ensure the word “TOP” on the De flector faces the ceiling. Step 2. With a non-hardening pipe- thread sealant such as TEFLON tape applied to the Inlet threads, hand- tighten the sprinkler into the sprinkler fitting. Step 3. Wrench-tighten the sprinkler using either: • a pipe wrench on the Inlet Band or the Casing (see Figures 1 and 2) • the W-Type 7 Sprinkler Wrench on the Wrench Flat (see Figure 16) Apply the Wrench Recess of the W-Type 7 Sprinkler Wrench to the Wrench Flat. build-up can occur that might damage the dry-type sprinkler and/or prevent proper operation in a fire situation. Use of the Model DSB-2 Dry Sprin- kler Boot, described in Technical Data Sheet TFP591 and shown in Figures 14 and 15, can provide the recommended seal. Installation The TYCO Series DS-1 Dry-Type Sprin- klers, 5.6K Pendent, Upright, and Hori- zontal Sidewall, Quick Response (3 mm bulb) and Standard Coverage must be installed in accordance with this section. General Instructions The Series DS-1 Dry-Type Sprinklers must only be installed in fittings that Table C to determine a sprinkler’s appropriate exposed barrel length to prevent water from freezing in the con- necting pipes due to conduction. The exposed barrel length measurement must be taken from the face of the sprinkler fitting to the surface of the structure or insulation that is exposed to the heated area. See Figure 11 for an example. Clearance Space In accordance with NFPA 13, when connecting an area subject to freez- ing and an area containing a wet pipe sprinkler system, the clearance space around the sprinkler barrel of Dry-Type Sprinklers must be sealed. Due to temperature differences between two areas, the potential for the formation of condensation in the sprinkler and sub- sequent ice build-up is increased. If this condensation is not controlled, ice TFP510 Page 8 of 10 have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprin- klers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. See the Installation Section. The owner is responsible for the in spection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the NATIONAL FIRE PROTEC TION ASSOCIATION, for example, NFPA 25, in addition to the standards of any other authorities having jurisdiction. Contact the installing contractor or product manufacturer with any questions. Automatic sprinkler systems are rec- ommended to be inspected, tested, and maintained by a qualified Inspec- tion Service in accordance with local requirements and/or national codes. Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. Note: If sprinkler removal becomes necessary, remove the sprinkler using the same wrenching method noted above. Sprinkler removal is easier when a non­hardening sealant was used and torque guidelines were followed. After removal, inspect the sprinkler for damage. Step 4. After installing the ceiling or wall and applying a ceiling finish, slide on the outer piece of the escutcheon until it comes in contact with the ceiling or wall. Do not lift the ceiling panel out of its normal position. When using the Deep Escutcheon, hold the outer piece in contact with the mounting surface (ceiling or wall). Then rotate the inner piece approximately 1/4 turn with respect to the outer piece, to hold the Deep Escutcheon firmly together. Care and Maintenance The TYCO Series DS-1 Dry-Type Sprin- klers, 5.6K Pendent, Upright, and Hori- zontal Sidewall, Quick Response (3 mm bulb) and Standard Coverage must be maintained and serviced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection systems from the proper authorities and notify all personnel who may be affected by this action. Absence of the outer piece of an es cutcheon, which is used to cover a clearance hole, can delay the time to sprinkler operation in a fire situation. A Vent Hole is provided in the Bulb Seat (see Figures 1 and 2) to indicate if the Dry-Type Sprinkler is remaining dry. Evi dence of leakage from the Vent Hole indicates potential leakage past the Inlet seal and the need to remove the sprinkler to determine the cause of leakage (for example, an improper installation or an ice plug). Close the fire protection system control valve and drain the system before removing the sprinkler. Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or other- wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but Ordering Procedure Contact your local distributor for avail- ability. When placing an order, indicate the full product name and Part Number (P/N). DS-1 Dry-Type Sprinklers When ordering TYCO Series DS-1 Dry-Type Sprinklers, 5.6K Pendent, Upright, and Horizontal Sidewall, Quick Response (3 mm bulb) and Stan- dard Coverage, specify the following information: • SIN: Pendent – TY3935 or TY3235 Sidewall – TY3735 or TY3335 Upright – TY3135 • 5.6 K-factor • Deflector Style: Upright, Pendent, or Horizontal Sidewall • Quick Response, Standard Cover- age, Dry-Type Sprinkler • Order Length: Dry-Type Sprinklers are furnished based upon Order Length as measured per Figures 3 through 10. After taking the measure- ment, round it to the nearest 1/4 in. increment. • Inlet Connections: 3/4 in. NPT, 1 in. NPT, or ISO 7-R 1 • Temperature Rating • Sprinkler Finish • Escutcheon Style and Finish, as applicable • Part Number (P/N) from Table D The Upright Sprinkler without an Escutcheon (TY3135) is available in 1 in. NPT only. Part Numbers are for 3/4 in. and 1 in. NPT standard order sprin- klers. Orders for all other sprinkler assemblies must be accompanied by a complete description. Refer to the Price List for a complete listing of Part Numbers. Sprinkler Wrench Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 Sprinkler Boot Specify: Model DSB-2 Dry Sprinkler Boot, P/N 63-000-0-002 This Part Number includes one (1) Boot, two (2) Strap Ties, and 1/3 oz of Adhesive (a sufficient quantity for installing one boot). TFP510 Page 9 of 10 SAMPLE ORDER LENGTHS2 055 5.50 in. 082 8.25 in. 180 18.00 in. 187 18.75 in. 372 37.25 in. 480 48.00 in. TEMPERATURE RATINGS 0 135°F (57°C) 1 155°F (68°C) 2 175°F (79°C) 3 200°F (93°C) 4 286°F (141°C) SPRINKLER FINISH ESCUTCHEON FINISH1 0 CHROME PLATED SIGNAL WHITE (RAL9003) 1 NATURAL BRASS SIGNAL WHITE (RAL9003) 2 NATURAL BRASS BRASS PLATED 4 SIGNAL WHITE (RAL9003) SIGNAL WHITE (RAL9003) 8 CHROME PLATED STAINLESS STEEL 9 CHROME PLATED CHROME PLATED SIN 01 Pendent with Standard Escutcheon (3/4 in. NPT) TY3935 (Figure 3) 02 Pendent with Deep Escutcheon (3/4 in. NPT) TY3935 (Figure 5) 03 Pendent with Recessed Escutcheon (3/4 in. NPT) TY3935 (Figure 4) 04 Pendent without Escutcheon (3/4 in. NPT) TY3935 (Figure 6) 05 Sidewall with Standard Escutcheon (3/4 in. NPT) TY3735 (Figure 8) 06 Sidewall with Deep Escutcheon (3/4 in. NPT) TY3735 (Figure 9) 07 Sidewall without Escutcheon (3/4 in. NPT) TY3735 (Figure 10) 36 Pendent with Standard Escutcheon (1 in. NPT) TY3235 (Figure 3 ) 33 Pendent with Deep Escutcheon (1 in. NPT) TY3235 (Figure 5 ) 37 Pendent with Recessed Escutcheon (1 in. NPT) TY3235 (Figure 4 ) 32 Pendent without Escutcheon (1 in. NPT) TY3235 (Figure 6 ) 34 Sidewall with Standard Escutcheon (1 in. NPT) TY3335 (Figure 8 ) 43 Sidewall with Deep Escutcheon (1 in. NPT) TY3335 (Figure 9 ) 44 Sidewall without Escutcheon (1 in. NPT) TY3335 (Figure 10 ) 38 Upright without Escutcheon (1 in. NPT) TY3135 (Figure 7) TABLE D SERIES DS-1 DRY-TYPE SPRINKLERS PART NUMBER SELECTION P/N* 60 – XXX – X – XXX Notes: 1. Escutcheon Finish applies to sprinklers provided with escutcheons. 2. Dry-Type Sprinklers are furnished based upon “Order Length” as measured per Figures 3 through 10, as applicable, and for each individual sprinkler where it is to be installed. After the measurement is taken, round it to the nearest 1/4 in. increment. * Use Prefix “I” for ISO 7-R 1 Connection (for example, I-60-360-4-055). TFP510 Page 10 of 10 NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association; TEFLON is a registered trademark of DuPont 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700 © 2019 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.