03 TYCO DRY CONC PEND QRSeries DS-C Dry Type Sprinklers 5.6K Concealed Pendent Standard and Quick Response, Standard Coverage Page 1 of 8 AUGUST 2018 TFP515 IMPORTANT Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information. Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Worldwide Contacts www.tyco-fire.com General Description TYCO Series DS-C Dry Type Sprinklers, 5.6K Concealed Pendent, Standard (5 mm Bulb) and Quick Response (3 mm Bulb) and Standard Coverage, are dec- orative sprinklers featuring a flat cover plate designed to conceal the sprinkler. This type of sprinkler is typically used to provide a sprinkler drop from an unheated attic into an area where aes- thetics is a concern, such as nursing homes, restaurants, and schools. Each unit includes a Cover Plate Assembly that conceals the sprinkler operating components above the ceiling. The separable two-piece design of the Cover Plate and Support Cup Assemblies allows installation of the sprinklers and pressure testing of the fire protection system prior to installation of a suspended ceiling or application of the finish coating to a fixed ceiling. They also permit removal of suspended ceiling panels for access to building service equipment without having to first shut down the fire pro- tection system and remove sprinklers. Also, the separable two-piece design of the Sprinkler provides for 1/2 inch (12,7 mm) of vertical adjustment. Series DS-C Sprinklers are shipped with a Disposable Protective Cap. The Pro- tective Cap is temporarily removed for installation, and then it can be replaced to help protect the sprinkler while the ceiling is installed or finished. The tip of the Protective Cap can also be used to mark the center of the ceiling hole into plaster board and ceiling tiles by gently pushing the ceiling product against the Protective Cap. When the ceiling instal- lation is complete the Protective Cap is removed and the Cover Plate Assembly installed. NOTICE Series DS-C Dry Type Concealed Pendent Sprinklers described herein must be installed and maintained in compliance with this document and the applicable standards of the NATIONAL FIRE PROTECTION ASSOCIATION, in addition to the standards of any author- ities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for main- taining their fire protection system and devices in proper operating con- dition. Contact the installing contrac- tor or product manufacturer with any questions. Series DS-C Dry Type Concealed Pendent Sprinklers must only be installed in fittings that meet the requirements of the Design Criteria section. Sprinkler Identification Numbers (SINs) TY3535 - 3 mm Bulb TY3555 - 5 mm Bulb Technical Data Approvals UL and C-UL Listed NYC Approved under MEA 352-01-E-2 Maximum Working Pressure 175 psi (12,1 bar) Inlet Thread Connections 1 inch NPT (Standard Order) ISO 7-R1 Discharge Coefficient K=5.6 GPM/psi1/2 (80,6 LPM/bar1/2) Temperature Ratings 155°F (68°C) Sprinkler with 139°F (59°C) Cover Plate 200°F (93°C) Sprinkler with 165°F (74°C) Cover Plate Adjustment 1/2 inch (12,7 mm) Finishes Refer to Ordering Procedure section Physical Characteristics Inlet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Copper Plug . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Copper Yoke .......................Stainless Steel Casing .............Galvanized Carbon Steel Insert . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze Bulb Seat . . . . . . . . . . . . . . . . . . . Stainless Steel Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Glass Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze Guide Tube . . . . . . . . . . . . . . . . . Stainless Steel Water Tube . . . . . . . . . . . . . . . . . Stainless Steel Spring .......Stainless Steel Gasketed Spring Plate Seal ........Beryllium Nickel w/TEFLON Support Cup ............Chrome Plated Steel Guide Pins . . . . . . . . . . . . . . . . . . Stainless Steel Compression Screw . . . . . . . . . . . . . . . . . Brass Cover Plate . . . . . . . . . . . . . . . . . . . . . . . . .Brass Retainer . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass Ejection Spring . . . . . . . . . . . . . . Stainless Steel TFP515 Page 2 of 8 Operation When TYCO Series DS-C Dry Type Concealed Pendent Sprinklers is in service, water is prevented from enter- ing the assembly by the Plug with Gas- keted Spring Plate Seal (Ref. Figure 1) in the Inlet of the Sprinkler. When exposed to heat from a fire, the Cover Plate, which is normally soldered to the Retainer at three points, falls away to expose the Sprinkler Assembly. At this point the Deflector supported by the Guide Pins drops down to its opera- tional position. The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, and the Bulb Seat is released. The compressed Spring is then able to expand and push the Water Tube as well as the Guide Tube outward. This action simultaneously pulls inward on the Yoke, withdrawing the Plug with Gasketed Spring Plate Seal, from the Inlet, allowing the sprinkler to activate and flow water. INSERT FRAME BULB DEFLECTOR GUIDE PIN VENT HOLE CASING GUIDE TUBE SPRING INLET YOKE INLET BAND WATER TUBE BULB SEAT COMPRESSION SCREW EJECTION SPRING COVER PLATE SOLDER TAB RETAINER WITH THREAD DIMPLES DEFLECTOR (DROPPED POSITION) PLUG WITH GASKETED SPRING PLATE SEAL SUPPORT CUP WITH ROLL FORMED THREADS THREAD INTO SUPPORT CUP UNTIL MOUNTING SURFACE IS FLUSH WITH CEILING COVER PLATE RETAINER ASSEMBLY SPRINKLER SUPPORT CUP ASSEMBLY FIGURE 1 SERIES DS-C STANDARD COVERAGE DRY-TYPE CONCEALED PENDENT SPRINKLER ASSEMBLY TFP515 Page 3 of 8 COVER PLATE RETAINER ASSEMBLY SPRINKLER FITTING (REFER TO DESIGN CRITERIA SECTION) FACE OF SPRINKLER FITTING 2-1/2" DIA. (63,5 mm) SPRINKLER SUPPORT CUP ASSEMBLY 1/2" (12,7 mm) THREADED ADJUSTMENT ORDER LENGTHS: 5" (127,0 mm) to 48" (1219,2 mm) IN 1/4" (6,4 mm) INCREMENTS FACE OF CEILING, RETAINING RING MOUNTING SURFACE 3/16" to 11/16" (4,8 to 17,5 mm) REFERENCE 3/16" (4,8 mm)FACTORY PRESET GAP 3/32" (2,4 mm) DEFLECTOR IN DROPPED POSITION 3-1/4" DIA. (82,6 mm) 2-1/2" DIA. (63,5 mm) CLEARANCE HOLE ACCEPTS 1/2" SOCKET DRIVE ALIGN ARROWS WITH FRAME ARMS 7/8" (23 mm) SQUARE SUPPORT CUP FRAME ARM FIGURE 2 SERIES DS-C STANDARD COVERAGE DRY-TYPE CONCEALED PENDENT SPRINKLER INSTALLATION DIMENSIONS FIGURE 3 DISPOSABLE PROTECTIVE CAP FIGURE 4 RFII SPRINKLER WRENCH TFP515 Page 4 of 8 Design Criteria TYCO Series DS-C 3 mm bulb-type Dry Type Concealed Pendent Sprin- klers (TY3535) are UL and C-UL Listed as quick response, standard spray sprinklers for use in accordance with the current NFPA standard. Series DS-C 5 mm bulb-type Dry Type Concealed Pendent Sprinklers (TY3555) are UL and C-UL Listed as standard response, standard spray sprinklers for use in accordance with the current NFPA standard. Series DS-C Dry Type Sprinklers are only listed when installed with Series RFII Concealed Cover Plates having a factory-applied painted or metallic finish. Series DS-C Dry Type Sprinklers must not be used in applications where the air pressure above the ceiling is greater than that below. Down drafts through the Support Cup could delay sprinkler operation in a fire situation. Sprinkler Fittings Install 1 inch NPT Series DS-C Dry Type Concealed Pendent Sprinklers in the 1 inch NPT outlet or run of the following fittings: • malleable or ductile iron threaded tee fittings that meet the dimensional requirements of ANSI B16.3 (Class 150) • cast iron threaded tee fittings that meet the dimensional requirements of ANSI B16.4 (Class 125) Do not install Series DS-C Dry Type Concealed Pendent Sprinklers into elbow fittings. The Inlet of the sprinkler can contact the interior of the elbow. The unused outlet of the threaded tee is plugged as shown in Figures 5 and 6. Install Series DS-C Dry-Type Sprinklers in the tee run or branch outlet. The configuration shown in Figure 5 is only applicable for wet pipe systems where the sprinkler fitting and water- filled pipe above the sprinkler fitting are not subject to freezing and where the length of the Dry Type Sprinkler has the minimum exposure length depicted in Figure 7. Refer to the Exposure Length section. For wet pipe system installations of 1 inch NPT Series DS-C Dry Type Sprin- klers connected to CPVC piping, use only the following TYCO CPVC fittings: • 1 in. x 1 in. NPT Female Adapter (P/N 80145) • 1 in. x 1 in. x 1 in. NPT Sprinkler Head Adapter Tee (P/N 80249) For dry pipe system installations, use only the side outlet of maximum 2-1/2 inch reducing tee when locating Series DS-C Dry Type Sprinklers directly below the branch line. Otherwise, use the configuration shown in Figure 6 to assure complete water drainage from above Series DS-C Dry Type Sprinklers and the branch line. Failure to do so may result in pipe freezing and water damage. NOTICE Do not install Series DS-C Dry Type Sprinklers into any other type fitting without first consulting the Technical Services Department. Failure to use the appropriate fitting may result in one of the following: • failure of the sprinkler to operate properly due to formation of ice over the Inlet Plug or binding of the Inlet Plug • insufficient engagement of the Inlet pipe-threads with consequent leakage Drainage In accordance with the minimum requirements of the NATIONAL FIRE PROTECTION ASSOCIATION for dry pipe sprinkler systems, branch, cross, and feed-main piping connected to Dry Sprinklers and subject to freezing tem- peratures must be pitched for proper drainage. Exposure Length When using Dry Type Sprinklers in wet pipe sprinkler systems to protect areas subject to freezing temperatures, use Table A to determine a sprinkler’s appropriate exposed barrel length to prevent water from freezing in the con- necting pipes due to conduction. The exposed barrel length measurement must be taken from the face of the sprinkler fitting to the surface of the structure or insulation that is exposed to the heated area. Refer to Figure 7 for an example. For protected area temperatures between those given above, the minimum recommended length from the face of the fitting to the outside of the protected area may be determined by interpolating between the indicated values. Do not attempt to add additional insula- tion around the barrel in the heated area as a method to minimize condensation. This will reduce the calculated “Expo- sure Length”. Clearance Space In accordance with NFPA 13, where dry sprinklers are connected to wet pipe sprinkler systems protecting insulated freezer structures, the clearance space around the sprinkler barrel of Dry Type Sprinklers must be sealed. Due to tem- perature differences between two areas, the potential for the formation of con- densation in the sprinkler and subse- quent ice build-up is increased. If this condensation is not controlled, ice build-up can occur that might damage the dry type sprinkler and/or prevent proper operation in a fire situation. Use of the Model DSB-2 Dry Sprinkler Boot, described in technical data sheet TFP591 and shown in Figure 8, will provide the recommended seal. NOTICE For applications where a bore greater than 1-3/4 inches in diameter has been cut through the entire height of an insu- lated freezer ceiling creating a cavity above the sprinkler support cup (Ref. Figure 8), the cavity must not be filled. TFP515 Page 5 of 8 Installation TYCO Series DS-C Dry Concealed Pendent Sprinklers must be installed in accordance with this section. Series DS-C Dry Type Concealed Pendent Sprinklers must only be installed in fittings that meet the requirements of the Design Criteria section. Refer to the Design Criteria section for other important require- ments regarding piping design and sealing of the clearance space around the Sprinkler Casing. Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin- kler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 inch (1,6 mm). A leak-tight 1 inch NPT sprinkler joint should be obtained by applying a min- imum-to-maximum torque of 20 to 30 lb-ft (26,8 to 40,2 N·m). Higher levels of torque may distort the sprinkler Inlet with consequent leakage or impairment of the sprinkler. Do not attempt to compensate for insufficient adjustment in the Sprinkler Assembly by under or over-tightening the Sprinkler/Support Cup Assembly. Re-adjust the position of the sprinkler fitting to suit. Step 1. Install the sprinkler in the pendent position with the centerline of the sprinkler perpendicular to the mounting surface. Step 2. With a non-hardening pipe- thread sealant such as TEFLON pipe- thread sealant applied to the Inlet threads, hand-tighten the sprinkler into the sprinkler fitting. Step 3. Wrench-tighten the sprinkler using either: • a pipe wrench on the Inlet Band or the Casing (Ref. Figure 1). • the RFII Sprinkler Wrench on the wrench flat (Ref. Figure 4). Apply the wrench recess of the RFII Sprinkler Wrench to the wrench flat. Note: If sprinkler removal becomes necessary, remove the sprinkler using the same wrenching method noted above. Sprinkler removal is easier when a non-hardening sealant was used and torque guidelines were followed. After removal, inspect the sprinkler for damage. When using the RFII Sprinkler Wrench, temporarily remove the Protective Cap. Replace the Protec- tive Cap (Ref. Figure 4) by pushing it upwards until it bottoms out against the Support Cup. The Protective Cap helps prevent damage to the Deflector and Arms during ceiling installation and/or during application of the finish coating of the ceiling. It may also be used to locate the center of the clearance hole by gently pushing the ceiling material up against the center point of the Pro- tective Cap. As long as the Protective Cap remains in place, the system is considered to be “Out of Service”. Step 4. After installing the ceiling and applying a ceiling finish, with the 2-1/2 inch (63,5 mm) diameter hole and in preparation for installing the Cover Plate Assembly, remove and discard the Protective Cap, and verify that the Deflector moves up and down freely. If the Sprinkler has been damaged and the Deflector does not move up and down freely, replace the entire Sprinkler assembly. Do not attempt to modify or repair a damaged sprinkler. Step 5. Screw on the Cover Plate/ Retainer Assembly until the Retainer (Ref. Figure 2) contacts the ceiling. Do not continue to screw on the Cover Plate/Retainer Assembly such that it lifts a ceiling panel out of its normal position. If the Cover Plate/Retainer Assembly cannot be engaged with the Support Cup or the Cover Plate/ Retainer Assembly cannot be engaged sufficiently to contact the ceiling, repo- sition the Sprinkler Fitting. Ambient TemperatureExposed to Discharge End of Sprinkler Temperatures for Heated Areaa 40°F (4°C)50°F (10°C)60°F (16°C) Minimum Exposed Barrel Length, Inches (mm)b 40°F (4°C)0 0 0 30°F (-1°C)0 0 0 20°F (-7°C)4 (100)0 0 10°F (-12°C)8 (200)1 (25)0 0°F (-18°C)12 (305)3 (75)0 -10°F (-23°C)14 (355)4 (100)1 (25) -20°F (-29°C)14 (355)6 (150)3 (75) -30°F (-34°C)16 (405)8 (200)4 (100) -40°F (-40°C)18 (455)8 (200)4 (100) -50°F (-46°C)20 (510)10 (255)6 (150) -60°F (-51°C)20 (510)10 (255)6 (150) NOTES: a. For protected area temperatures that occur between values listed above, use the next cooler temperature b. These lengths are inclusive of wind velocities up to 30 mph (18,6 kph) TABLE A EXPOSED SPRINKLER BARRELS IN WET PIPE SYSTEMS MINIMUM RECOMMENDED LENGTHS TFP515 Page 6 of 8 Care and Maintenance TYCO Series DS-C Dry Type Concealed Pendent Sprinklers must be maintained and serviced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection systems from the proper authorities and notify all personnel who may be affected by this action. Absence of the Cover Plate Assembly may delay sprinkler operation in a fire situation. A Vent Hole is provided in the Bulb Seat (Ref. Figure 1) to indicate if the Dry Sprinkler is remaining dry. Evi- dence of leakage from the Vent Hole indicate potential leakage past the Inlet seal and the need to remove the sprin- kler to determine the cause of leakage; for example, an improper installation or an ice plug. Close the fire protection system control valve and the system drain before removing the sprinkler. When properly installed, there is a nominal 3/16 in. (4,8 mm) air gap between the lip of the Cover Plate and the ceiling, as shown in Figure 2. This air gap is necessary for proper oper- ation of the sprinkler. If the ceiling is to be repainted after the installation of the Sprinkler, care must be exercised to ensure that the new paint does NOT seal off any of the air gap. Do not pull the Cover Plate relative to the Enclosure. Separation may result. Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or other- wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid damage to the sprinklers - before, during, and after installation. Sprin- klers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprin- kler that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installa- tion Section.) If a sprinkler must be removed, do not reinstall it or a replacement without reinstalling the Cover Plate Assembly. If a Cover Plate Assembly becomes dislodged during service, replace it immediately. The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the NATIONAL FIRE PROTECTION ASSOCIATION (for example, NFPA 25), in addition to the standards of any other authorities having jurisdiction. Contact the installing contractor or product manufacturer with any questions. Automatic sprinkler systems are rec- ommended to be inspected, tested, and maintained by a qualified Inspec- tion Service in accordance with local requirements and/or national codes. SIDE OUTLET PLUGGED TO WET SYSTEM FITTING (SEE DESIGN CRITERIA SECTION) SPRINKLERDSB-2 INTENDED FOR FREEZER STRUCTURES HEATED AREA RUN OUTLET PLUGGED TO DRY SYSTEM DSB-2 INTENDED FOR FREEZER STRUCTURES FITTING (SEE DESIGN CRITERIA SECTION) SPRINKLER AREA SUBJECT TO FREEZING (SEE DESIGN CRITERIA SECTION) FACE OF SPRINKLER FITTING LENGTH EXPOSURE DSB-2 INTENDED FOR FREEZER STRUCTURES HEATED AREA INSULATED FREEZER STRUCTURE STRAP TIES (ENDS ON OPPOSING SIDES OF BOOT) ADHESIVE 2-1/2" DIA. (63,5 mm) CLEARANCE HOLE DSB-2 BOOT DS-C DRY PENDENT CONCEALED SPRINKLER FIGURE 5 SPRINKLER FITTING HEATED AREA FIGURE 6 SPRINKLER FITTING UNHEATED AREA FIGURE 7 EXPOSURE LENGTH FIGURE 8 MODEL DSB-2 DRY SPRINKLER BOOT WITH DRY-TYPE SPRINKLER TFP515 Page 7 of 8 Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. Ordering Procedure Contact your local distributor for avail- ability. When placing an order, indi- cate the full product name, including description and Part Number (P/N). Dry Type Sprinkler Assemblies When ordering 5.6 K-Factor Series DS-C Standard Coverage Dry Type Concealed Pendent Sprinklers, specify the following information: • SIN Quick Response TY3535 or Standard Response TY3555 • Temperature Rating • Order Length Dry Type Sprinklers are furnished based upon Order Length as measured from the face of the ceiling to the face of the sprinkler fitting (Ref. Figure 2). After the measure- ment is taken, round it to the nearest 1/4 inch increment. • Inlet Thread Connection 1 inch NPT or ISO 7-R1 • Part Number from Table B P/N * 60 – XXX – 1 – XXX Note * Use Prefix “I” for ISO 7-R1 Connection (for example, I-60-461-1-180). ** Dry-Type Sprinklers are furnished based upon “Order Length” as measured per Figure 2, for each individual sprinkler where it is to be installed. After the measurement is taken, round it to the near- est 1/4 inch increment. Separately Ordered Cover Plate Specify: Series RFII Concealed Cover Plate with (specify) temperature rating, (specify) finish, P/N (specify): 139°F (59°C) Cover Plate for use with 155°F (68°C) Sprinkler Grey White (RAL9002). . . . . . . . . . 56-792-0-135 Brass . . . . . . . . . . . . . . . . . . . . . . . .56-792-1-135 Pure White (RAL9010)*. . . . . . . . . .56-792-3-135 Signal White (RAL9003). . . . . . . . .56-792-4-135 Jet Black (RAL9005). . . . . . . . . . . 56-792-6-135 Chrome . . . . . . . . . . . . . . . . . . . . . 56-792-9-135 Custom . . . . . . . . . . . . . . . . . . . . . 56-792-X-135 165°F (74°C) Cover Plate for use with 200°F (93°C) Sprinkler Grey White (RAL9002). . . . . . . . . . 56-792-0-165 Brass . . . . . . . . . . . . . . . . . . . . . . . .56-792-1-165 Pure White (RAL9010)*. . . . . . . . . .56-792-3-165 Signal White (RAL9003). . . . . . . . .56-792-4-165 Jet Black (RAL9005). . . . . . . . . . . 56-792-6-165 Chrome . . . . . . . . . . . . . . . . . . . . . 56-792-9-165 Custom . . . . . . . . . . . . . . . . . . . . . 56-792-X-165 * Eastern Hemisphere Sales Only Sprinkler Wrench Specify: RFII Sprinkler Wrench, P/N 56-000-1-075 Sprinkler Boot Specify: Model DSB-2 Dry Sprinkler Boot, P/N 63-000-0-002 This Part Number includes one Boot, two Strap Ties, and 1/3 oz. of Adhe- sive (a sufficient quantity for installing one boot), refer to Technical Data Sheet TFP591 for complete information. SIN 46 Quick Response (3 mm Bulb)TY3535 86 Standard Response (5 mm Bulb)TY3555 TEMPERATURE RATING 1 155°F (68°C) 3 200°F (93°C) ORDER LENGTH** 055 5.50 in. 082 8.25 in. 180 18.00 in. 187 18.75 in. 372 37.25 in. 480 48.00 in. TABLE B SERIES DS-C STANDARD COVERAGE DRY-TYPE CONCEALED PENDENT SPRINKLER PART NUMBER SELECTION TFP515 Page 8 of 8 NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association; TEFLON is a registered trademark of DuPont 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700 © 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.