02 TYCO CC3 COIN SPKR
Model CC3 — 4.2 and 5.6 K-factor Combustible Concealed Space Sprinklers Specific Application, Upright Page 1 of 8 DECEMBER 2018 TFP633 IMPORTANT Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information. Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Worldwide Contacts www.tyco-fire.com General Description The Model CC3 Combustible Con- cealed Sprinklers are quick response, upright, specific application sprinklers designed to provide protection of spe- cific light hazard combustible, as well as non-combustible, con cealed spaces requiring sprinkler protection. The Model CC3 Sprinklers comply with the criteria for the protection of combus- tible concealed spaces as described in NFPA 13. The Model CC3 Sprinklers are designed for installation on BLAZE- MASTER CPVC wet pipe systems, other UL Listed CPVC pipe products, and steel wet pipe or dry pipe sprinkler systems (refer to the respective Design Criteria sections). The Model CC3 Sprinklers are designed to be installed in the following arrangements for both wet CPVC and steel: • 4.2K 14 ft (4,3 m) maximum between sprinklers 196 ft² (18,2 m²) maximum cover-age area • 5.6K 16 ft (4,9 m) maximum between sprinklers 256 ft² (23,8 m²) maximum cover- age area • 6 in. (152,4 mm) minimum height for joist with steel pipe or CPVC when insulation filled. 12 in. (305 mm) min- imum height for all other arrange- ments and sizes • 60 in. (1524 mm) maximum height from joist to joist and 84 in. (2134 mm) from floor to ceiling • 60 in. (1524 mm) maximum height for truss and bar joist NOTICE The Model CC3 Combustible Con- cealed Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applicable standards of the NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), in addition to the standards of any other authorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for main- taining their fire protection system and devices in proper operating con- dition. Contact the installing contrac- tor or product manufacturer with any questions. Sprinkler Identification Number TY2199 – Upright, 4.2K TY3199 – Upright, 5.6K Technical Data Approvals UL Listed (Listings and approvals only apply to the service conditions indicated in the Design Criteria sections.) Maximum Working Pressure 175 psi (12,1 bar) Pipe Thread Connection 1/2 in. NPT Discharge Coefficient K = 4.2 GPM/psi½ (60,5 LPM/bar½) K = 5.6 GPM/psi½ (80,6 LPM/bar½) Temperature Rating 200°F (93°C) Finish Natural Brass Physical Characteristics Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass Button . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze Sealing Assembly ..Beryllium Nickel w/TEFLON Bulb .........................Glass (3 mm) Compression Screw . . . . . . . . . . . . . . . . . .Brass Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze Operation The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb allowing the sprinkler to acti- vate and flow water. Design Criteria Design criteria is provided as follows: • 200°F (93°C), Model CC3 Combusti- ble Concealed Sprinklers with CPVC pipe and horizontal slope above sprinklers not exceeding 2:12 (Refer to Page 2). • 200°F (93°C), Model CC3 Combus- tible Concealed Sprinklers with steel pipe and horizontal slope above sprinklers not exceeding 2:12 (Refer to Page 4). TFP633 Page 2 of 8 Design Criteria, CPVC Pipe Area of Use (CPVC Pipe) Horizontal (slope not exceeding 2:12) combustible concealed spaces of: • Unobstructed wood truss construc- tion or unobstructed bar joist con- struction (Ref. Figure 2). • Non-combustible, insulation-filled solid wood or composite wood joist construction (Ref. Figure 3). NOTE: In order to be considered “non-combustible insulation-filled solid wood or composite wood joist construction,” the insulation (includ- ing insulation provided with a combus- tible vapor barrier), must completely fill the pockets between the joists to the bottom of the joists, and the insulation must be secured in place with metal wire netting. The metal wire netting is intended to hold the insulation in place should the insulation become wetted by the operation of the Model CC3 Sprinklers in the event of a fire. Concealed Space Area (CPVC Pipe) The area of the concealed space is not limited; however, for both Figure 2 and Figure 3, where CPVC pipe is being uti- lized, draft curtains or full height walls must be provided at 1000 ft² (93 m²) areas. This draft curtain shall be at least 1/3 the depth of the concealed space or 8 in. (200 mm), whichever is greater, and be constructed using a material that will not allow heat to escape through or above the draft curtain. Concealed Space Size (CPVC Pipe) The depth of the concealed space is 60 in. (1524 mm) maximum to 6 in. (152 mm) minimum. System Type (CPVC Pipe) Light hazard, wet pipe system Maximum Distance Between Model CC3 Sprinklers (CPVC Pipe) TY2199 4.2K . . . . . . . . . . . . . . 14 ft (4,3 m) TY3199 5.6K . . . . . . . . . . . . . . 16 ft (4,9 m) Maximum Coverage Area (CPVC Pipe) TY2199 4.2K . . . . . . . . . . . 196 ft² (18,2 m²) TY3199 5.6K . . . . . . . . . . .256 ft² (23,8 m²) Minimum Distance Between Model CC3 Sprinklers (CPVC Pipe) Minimum sprinkler spacing is 7 ft (2,1 m) NOTE: Minimum spacing does not apply to any additional sprinklers required for protection of CPVC pipe that is offset over an obstruction. Deflector Position (CPVC Pipe) • 1-1/2 in. to 4 in. (40 to 100 mm) below upper deck for wood truss construc- tion or bar joist construction (Ref. Figure 2) • 1-1/2 in. to 4 in. (40 to 100 mm) below solid wood or composite wood joists (Ref. Figure 3) Minimum Distance Away From Trusses (CPVC Pipe) 4-1/2 in. (114 mm) Remote Area (CPVC Pipe) The remote area is 1000 ft² (93 m²) NOTE: The remote area does not include any additional sprinklers required for protection of CPVC pipe that is offset over an obstruction. Required Minimum Density (CPVC Pipe) 0.10 gpm/ft² (4,1 mm/min) Minimum Operating Pressure (CPVC Pipe) 7 psi (0,48 bar) Obstructions (CPVC Pipe) See Figure 8 in this data sheet for obstructions rules. Use of UL Listed BLAZEMASTER CPVC Pipe with Model CC3 Sprinklers BLAZEMASTER CPVC product may be used in concealed spaces requir- ing automatic sprinklers, when used in conjunction with Model CC3 Sprinklers. In order to use the BLAZEMASTER CPVC product for wood truss or bar joist construction, the horizontal run of pipe must be a maximum of 6 in. (150 mm) above the ceiling or noncombus- tible ceiling insulation, or 1/3 the depth of concealed space (as measured from the top surface of the ceiling to the bottom of the deck above), which- ever is smaller (Ref. Figure 2). For insu- lation-filled solid wood or composite wood joist construction, the horizon- tal run of pipe must be a maximum of 6 in. (150 mm) above ceiling or non- combustible ceiling insulation, or 1/3 the depth of concealed space (as measured from the top surface of the ceiling to the bottom surface of the joist insulation above), whichever is smaller (Ref. Figure 3). The CPVC pipe can then be used to supply the Model CC3 Sprinklers, as well as the sprin- klers below the ceiling. Unless modified by this technical data sheet, all other guidelines of the “BLAZEMASTER — Installation Instructions & Technical Manual” must be met. When using 1 in. (DN25) or larger pipe, a hanger must be located at the truss nearest a sprig for purposes of restraint. If using 3/4 in. (DN19) piping, all sprigs over 12 inches (305 mm) must be laterally braced using methods described in the NFPA standards. Where the CPVC must be offset up and over an obstruction and the pipe exceeds the allowed horizontal posi- tioning requirements specified above as well as shown in Figure 2 and 3, additional Model CC3 Sprinklers are to be installed as shown in Figures 2 and 3 to protect the BLAZEMASTER CPVC product. A minimum lateral distance of 18 in. (460 mm) must be maintained between the CPVC pipe and heat pumps, fan motors, and heat lamps. - - - - - - - 2 7 4 6 5 3 1 Frame Button Sealing Assembly Deector Bulb Compression Screw 2 1 3 4 Components: 5 6 WRENCH FLATS 7/16" (11,1 mm) NOMINAL MAKE-IN SPRINKLER FRAME ARMS 1-11/16" (42,9 mm) 2-1/4" (57,2 mm) 1/2" NPT 7 Ejection Spring FIGURE 1 MODEL CC3 SPRINKLER TFP633 Page 3 of 8 MODEL CC3 SPRINKLER 6" (152 mm) MINIMUM 60" (1524 mm) MAXIMUM 1-1/2" (40 mm) MINIMUM 4" (102 mm) MAXIMUM 6" (152 mm) MAXIMUM FOR CPVC PIPE FRAME ARMS OF SPRINKLER MUST BE INSTALLED IN-LINE WITH PIPE RUN WHEN OFFSETTING CPVC PIPE OVER AN OBSTRUCTION, A MODEL CC3 SPRINKLER MUST BE INSTALLED DIRECTLY ON THE CPVC PIPE OVER THE OBSTRUCTION 6" (152 mm) MAXIMUM ABOVE CEILING TO BOTTOM OF PIPE OR NON-COMBUSTIBLE CEILING INSULATION, OR 1/3 THE DEPTH OF CONCEALED SPACE (AS MEASURED FROM TOP SURFACE OF CEILING TO BOTTOM OF DECK ABOVE), WHICHEVER IS SMALLER BOTTOM OF PIPE TOP CHORD 4" (102 mm) OR LESS CEILING OBSTRUCTION UPPER DECK TOP OF CHORD 4-1/2" (114 mm) MINIMUM FROM FACE OF WOOD TRUSS OR TOP CHORD OF BAR JOIST MODEL CC3 SPRINKLER UPPER DECK NON-COMBUSTIBLE INSULATION 6" (152 mm) MINIMUM 60" (1524 mm) MAXIMUM 1-1/2" (40 mm) MINIMUM 4" (102 mm) MAXIMUM 6" (152 mm) MAXIMUM FOR CPVC PIPE COMPOSITE WOOD JOISTS SOLID WOOD JOISTS FRAME ARMS OF SPRINKLER MUST BE INSTALLED IN-LINE WITH PIPE RUN WHEN OFFSETTING CPVC PIPE OVER AN OBSTRUCTION, A MODEL CC3 SPRINKLER MUST BE INSTALLED DIRECTLY ON THE CPVC PIPE OVER THE OBSTRUCTION 6" (152 mm) MAXIMUM ABOVE CEILING TO BOTTOM OF PIPE OR NON-COMBUSTIBLE CEILING INSULATION, OR 1/3 THE DEPTH OF CONCEALED SPACE (AS MEASURED FROM TOP SURFACE OF CEILING TO BOTTOM SURFACE OF JOIST INSULATION ABOVE), WHICHEVER IS SMALLER BOTTOM OF PIPE TOP OF CHORD OBSTRUCTION CEILING 72" (1829 mm) MAXIMUM FIGURE 3 NON-COMBUSTIBLE INSULATION-FILLED UPPER DECK SOLID WOOD OR COMPOSITE WOOD JOIST CONSTRUCTION CROSS SECTION ELEVATION VIEW CPVC PIPE FIGURE 2 UNOBSTRUCTED WOOD TRUSS CONSTRUCTION OR UNOBSTRUCTED BAR JOIST CONSTRUCTION CROSS SECTION ELEVATION VIEW CPVC PIPE TFP633 Page 4 of 8 Design Criteria, Steel Pipe Area of Use (Steel Pipe) Horizontal (slope not exceeding 2:12) combustible concealed spaces of: • Unobstructed wood truss construc- tion or unobstructed bar joist con- struction (Ref. Figure 4) • Solid wood joist construction (Ref. Figure 5) where the upper deck and ceiling joists may have a maximum depth of 12 inches (300 mm) and typical on center joist spacing of minimum 16 inches (400 mm) • Non-combustible insulation-filled solid wood joist or wood composite joist construction (Ref. Figure 6) • Obstructed wood truss construction (Ref. Figure 7) NOTE: In order to be considered “non- combustible insulation-filled solid wood joist or composite wood joist construction”, the insulation (includ- ing insulation provided with a combus- tible vapor barrier), must completely fill the pockets between the joists to the bottom of the joists, and the insulation must be secured in place with metal wire netting. The metal wire netting is intended to hold the insulation in place should the insulation become wetted by the operation of the Model CC3 Sprinklers in the event of a fire. Concealed Space Area (Steel Pipe) The area of the concealed space is not limited; however, • For unobstructed wood truss con- struction or concealed spaces of non-combustible, unobstructed bar joist construction (Ref. Figure 4) draft curtains or full height walls must be provided at 1000 ft² (93 m²) areas. This draft curtain shall be at least 1/3 the depth of the concealed space or 8 in. (200 mm), whichever is greater, and be constructed using a mate- rial that will not allow heat to escape through or above the draft curtain. • For solid wood joist construction (Ref. Figure 5) and obstructed wood truss construction (Ref. Figure 7): Blocking must be provided in each upper deck and ceiling joist channel at a maximum 32 ft (9,75 m) inter- vals. This blocking shall be installed to the full depth of the joists and be installed so as to not allow heat to escape through or above the block- ing. The blocking must be con- structed using a non-combustible material or the joist construction material. Draft curtains must protrude below the joist a minimum of 6 inches (150 mm) or 1/3 the depth of the con-cealed space, whichever is greater, and run parallel with the joist spaced at 31 ft (9,4 m) width maxi- mum to limit the area to a maximum of 1000 ft² (93 m²). The draft cur- tains are to be constructed using a material that will not allow heat to escape through or above the draft curtain. • For non-combustible, insulation-filled solid wood joist or composite wood joist construction (Ref. Figure 6), the requirement for draft curtains and blocking does not apply. Concealed Space Size (Steel Pipe) The minimum and maximum concealed space depth is as follows: For unobstructed wood truss construc- tion or concealed spaces of unob- structed bar joist construction (Ref. Figure 4) the maximum depth of the concealed space is 60 in. (1524 mm) from bottom of upper deck to top of ceiling, and the minimum depth is 6 in. (152 mm) from the bottom of the upper chords to the top of the lower chords. For solid wood joist construction (Ref. Figure 5) and solid wood or com- posite wood joist construction the maximum depth of the concealed space is 84 in. (2134 mm) from bottom of upper deck to top of ceiling, and the minimum depth is 6 in. (152 mm) from the bottom of the upper deck joists to the top of the ceiling joists. If joist con- struction is filled with non-combustible insulation the maximum height of the space is 84 in. (2134 mm) (Ref. Figure 6). For obstructed wood truss construc- tion (Ref. Figure 7), the maximum depth of the concealed space is 84 in. (2134 mm) from bottom of upper deck to top of ceiling, and the minimum depth is 6 in. (152 mm) from the bottom of the upper chord to the top of the lower chord. System Type (Steel Pipe) Light hazard, wet or dry pipe system NOTES: Use of the 4.2K sprinklers in dry pipe systems is permitted by section 8.3.4.4 of NFPA 13 (2013 edition) where piping is corrosion resistant or internally galvanized. Maximum Distance Between Model CC3 Sprinklers (Steel Pipe) TY2199 4.2K . . . . . . . . . . . . . . 14 ft (4,3 m) TY3199 5.6K . . . . . . . . . . . . . . 16 ft (4,9 m) Maximum Coverage Area (Steel Pipe) TY2199 4.2K . . . . . . . . . . . 196 ft² (18,2 m²) TY3199 5.6K . . . . . . . . . . .256 ft² (23,8 m²) Minimum Distance Between Model CC3 Sprinklers (Steel Pipe) Minimum sprinkler spacing is 7 ft (2,1 m) Deflector Position (Steel Pipe) 1-1/2 in. to 4 in.s (40 mm to 100 mm) below upper deck for wood truss con- struction or concealed spaces of non- combustible bar joist construction (Ref. Figure 4) 1-1/2 in. to 2 in. (40 to 50 mm) below solid wood joist (Ref. Figure 5) or top chord of a wood truss that has a depth greater than 4 in. (Ref. Figure 7) 1-1/2 in. to 4 in. (40 to 100 mm) below non-combustible insulation-filled solid wood joists or composite wood joists (Ref. Figure 6) Remote Area (Steel Pipe) The remote area for wood truss con- struction or bar joist construction (Ref. Figure 4), solid wood joist con- struction (Ref. Figure 5), or obstructed wood truss construction (Ref. Figure 7) is 1000 ft² (93 m²) for wet pipe or dry pipe systems. The remote area for non-combusti- ble insulation-filled solid wood joist or wood composite joist construction (Ref. Figure 6) without draft curtains is to be calculated per the requirements of NFPA 13. Required Minimum Density (Steel Pipe) 0.10 gpm/ft² (4,1 mm/min) Minimum Operating Pressure (Steel Pipe) 7 psi (0,48 bar) Obstructions (Steel Pipe) See Figure 8 in this data sheet for obstructions rules. TFP633 Page 5 of 8 MODEL CC3 SPRINKLER 60" (1524 mm) MAXIMUMFRAME ARMS OF SPRINKLER MUST BE INSTALLED IN-LINE WITH PIPE RUN 4-1/2" (114 mm) MINIMUM FROM FACE OF WOOD TRUSS OR TOP CHORD OF BAR JOIST TOP CHORD 4" (102 mm) OR LESS 6" (152 mm) MINIMUM 1-1/2" (40 mm) MINIMUM 4" (102 mm) MAXIMUM CEILING UPPER DECK FRAME ARMS OF SPRINKLER MUST BE INSTALLED IN-LINE WITH PIPE RUN UPPER DECK CEILING FRAMING 84" (2134 mm) MAXIMUM 2x FLOOR SOLID WOOD JOISTS 6" (152 mm) MINIMUM 60" (1524 mm) MAXIMUM MODEL CC3 SPRINKLER 1-1/2" (38 mm) MINIMUM 2" (51 mm) MAXIMUM CEILING FIGURE 4 UNOBSTRUCTED WOOD TRUSS CONSTRUCTION OR UNOBSTRUCTED BAR JOIST CONSTRUCTION CROSS SECTION ELEVATION VIEW STEEL PIPE FIGURE 5 SOLID WOOD JOIST CONSTRUCTION CROSS SECTION ELEVATION VIEW STEEL PIPE TFP633 Page 6 of 8 UPPER DECK MODEL CC3 SPRINKLER CEILING FRAMING 84" (2134 mm) MAXIMUM CEILING TOP CHORD GREATER THAN 4" (102 mm) IN DEPTH 6" (152 mm) MINIMUM 60" (1524 mm) MAXIMUM FRAME ARMS OF SPRINKLER MUST BE INSTALLED IN-LINE WITH PIPE RUN 1-1/2" (38 mm) MINIMUM 2" (51 mm) MAXIMUM 4" (102 mm) MAXIMUM FRAME ARMS OF SPRINKLER MUST BE INSTALLED IN-LINE WITH PIPE RUN UPPER DECK MODEL CC3 SPRINKLER CEILING FRAMING 2x FLOOR SOLID WOOD JOISTS NON-COMBUSTIBLE INSULATION COMPOSITE WOOD JOISTS 1-1/2" (38 mm) MINIMUM CEILING 6" (152 mm) MINIMUM 60" (1524 mm) MAXIMUM 84" (2134 mm) MAXIMUM FIGURE 6 NON-COMBUSTIBLE INSULATION-FILLED UPPER DECK SOLID WOOD OR COMPOSITE WOOD JOIST CONSTRUCTION CROSS SECTION ELEVATION VIEW STEEL PIPE FIGURE 7 OBSTRUCTED WOOD TRUSS CONSTRUCTION CROSS SECTION ELEVATION VIEW STEEL PIPE TFP633 Page 7 of 8 Installation The Model CC3 Sprinklers must be installed in accordance with this section. General Instructions The Model CC3 Sprinklers are to be installed upright and with their frame arms (Ref. Figure 1) in-line with the pipe run (Ref. Figures 2 through 7, as applicable). Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin- kler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 in. (1,6 mm) for the 200°F (93°C) tempera- ture rating. A leak-tight 1/2 in. NPT sprinkler joint should be obtained with a torque of 7 to 14 lb-ft (9,5 to 19,0 N∙m). Higher levels of torque may distort the sprinkler inlet with consequent leakage or impairment of the sprinkler. The Model CC3 Sprinklers must only be installed in the upright position with the deflector parallel to the upper deck. With pipe thread sealant applied to the pipe threads, use only the W-Type 6 (End A) Sprinkler Wrench (Ref. Figure 9) for installation of the Model CC3 Sprinklers by applying the wrench to the sprinkler wrench flats only. WRENCH RECESS (USE END "A" ONLY)0" 2-1/2" (63,5 mm) 3-1/2" (88,9 mm) 5-1/2" (139,7 mm) 7-1/2" (190,5 mm) 9-1/2" (241,3 mm) 12" (304,8 mm) 14" (355,6 mm) 16-1/2" (419,1 mm) (0 mm) Maximum Allowable Distance of Deector Above Bottom of Obstruction (B) Distance from Centerline of Sprinkler to Side of Obstruction (A) A3C or 3D A24" (609,6 mm) (Use dimension C or D, whichever is greater) <12" <(304,8 mm) 12" to <18" (304,8 mm to <457,2 mm) 18" to <24" (457,2 mm to <609,6 mm) 24" to <30" (609,6 mm to <762,0 mm) 30" to <36" (762,0 mm to <914,4 mm) 36" to <42" (914,4 mm to <1066,8 mm) 42" to <48" (1066,8 mm to <1219,2 mm) 48" to <54" (1219,2 mm to <1371,6 mm) 54" to <60" (1371,6 mm to <1524,0 mm) NOTE: WEB MEMBERS AND GUSSETS SHALL NOT BE CONSIDERED OBSTRUCTIONS PROVIDED THE MINIMUM 4-1/2 INCH LATERAL DISTANCE (FIG. 2) REQUIRED BY THE SPECIFIC APPLICATION LISTING IS MAINTAINED. OBSTRUCTION MODEL CC3 SPRINKLERC D A OBSTRUCTION UPPER DECK LOWER DECK A MODEL CC3 SPRINKLER MODEL CC3 SPRINKLER A UPPER DECK OR BOTTOM OF NON-COMUSTIBLE INSULATION B ELEVATION VIEW PLAN VIEW C D OBSTRUCTION FIGURE 9 W-TYPE 6 SPRINKLER WRENCH FIGURE 8 NFPA 13 OBSTRUCTION TO WATER DISTRIBUTION CRITERIA (REFERENCE) TFP633 Page 8 of 8 NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association; TEFLON is a registered trademark of DuPont; BLAZEMASTER is a registered trademark of The Lubrizol Corporation 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700 © 2019 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. Care and Maintenance The Model CC3 Sprinklers must be maintained and serviced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, permission to shut down the affected fire protection systems must be obtained from the proper authorities and all personnel who may be affected by this action must be notified. Sprinklers that are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or other- wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprin- klers damaged by dropping, striking, wrench twist/slippage, or the like, must be re placed. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. Refer to the Instal- lation section. The owner is responsible for the inspec- tion, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the NATIONAL FIRE PROTECTION ASSO- CIATION (e.g., NFPA 25), in addition to the standards of any other authorities having jurisdiction. Contact the install- ing contractor or product manufacturer with any questions. It is recommended that automatic sprinkler systems be inspected , tested, and maintained by a qualified Inspec- tion Service in accordance with local requirements and/or national codes. Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. Ordering Procedure Contact your local distributor for avail- ability. When placing an order, indicate the full product name and Part Number (P/N). Sprinkler Assemblies with NPT Thread Connections Specify: SIN (specify), K-factor (specify), Model CC3 Combustible Concealed Space Sprinkler, Specific Application, Upright, 200°F (93°C), P/N (specify): TY2199, 4.2K .................51-311-1-200 TY3199, 5.6K .................51-301-1-200 Sprinkler Wrench: Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387