65 Federal St Narrative-calc 5.22.20Fire Protection Construction Documents Five Unit Dwelling 65 Federal St. Salem, Ma. 01970 Narrative Report Fire Sprinkler Installation By: Diablo Fire Protection, LLC 17 Libby St. Goffstown, NH 03045 Tel: (603) 820-2593 JASON CATALFO KAHAN FIRE PROTECTION NO. 483'.:.. TERM 05/22/2020 P2 FIRE PROTECTION FIRE SYSTEMS NARRATIVE REPORTS 903. 1.1 BASIS (METHODOLOGY) OF DESIGN Section 1.1 (1.a) Existing Building Description The existing building at 65 Federal St. is a five unit/family, three story, plus basement structure. The use group of this facility, as defined in 780 CMR is R1 Residential, constructed with combustible materials. Basement will also be used for residential occupancy. The existing building's total area is approximately 5,150 sq. ft., including basement. SECTION 2 — Applicable Laws, Regulations and Standards a) The Massachusetts State Building Code 9th Edition, 780 CMR Chapter 9, "Fire Protection System Requirements" b) NFPA Standards and Editions used for the design of each fire protection system: NFPA 13R, Installation of Sprinkler Systems in Residential multifamily dwellings, 2013 Edition NFPA 13, Installation of Sprinkler Systems, 2013 Edition. NFPA 25, Inspection, Testing and Maintenance of Sprinkler Systems, 2007 Edition. c) M.G.L. Chapter 146 and Chapter 148. SECTION 3 — Design Responsibility for Fire Protection Systems a) This project is developed under the following design responsibility: The Design Build Sprinkler Contractor (Diablo Fire Protection LLC) and the Fire Protection Professional Engineer (Jason C. Kahan, MA Registration # 48388) fully designs (complete layout and calculations) and specify through construction management collaboration, the fire protection system or systems to be installed. The Design Build Professional Engineer reviews and approves the completed shop drawings for code compliance. The Design Build Professional Engineer is considered the engineer of record and certifies system installation for code compliance at completion. (continue) P3 SECTION 4 — Fire Protection Systems to be installed SPRINKLER SYSTEM DESCRIPTION The new sprinkler system will be as follows: a) Mech Rm.; blk. steel pipe with CI Trd. fittings and commercial sprinklers. b) All residential areas; CPVC piping with CPVC glued type fittings and residential style sprinklers. A flow switch will be installed and wired to local smoke detectors, outdoors electric bell as well to a dialer alerting the Fire Dept. WATER SUPPLY New 1 1/2" or larger, fire protection underground copper pipe will be installed from the city water main into the basement. FIRE ALARM SYSTEMS AND COMPONENTS The flow switch and tamper switches will be connected, by others, to the house fire alarm and/or smoke detection system. For further description please see the "Fire Alarm Narrative" SECTION 5 — Fire Protection Systems Design Methodology This building will be protected with a NFPA 13R wet sprinkler system installed in accordance with 780 CMR TAB 903.2, as modified and permitted for 4 family dwellings. 903. 1.1 (1.b) SEQUENCE OF OPERATION Section 1 WET SPRINKLER SYSTEM System operates automatically upon the fusing of a single fire sprinkler. (continue) P4 1. Activation of a single sprinkler will drop the pressure in the system, activating a low pressure switch, which in turn will start-up the fire pump. 2. A water will discharge from the open sprinkler(s) activating the system flow switch. 3. Activation of this flow switch will "set off' a local horn and strobe and/or smoke detectors, and send an alarm to the Fire Dept. Station . 903. 1.1 (1.c) TESTING CRITERIA Section 1 Upon completion of the sprinkler system, the system shall be tested hydrostatically for 2 hours at 200 PSI by Arkon fire Protection Co. Inc. and witnessed by the General Contractor, the owner's Representative and, if desired, the Salem Fire Department. Upon final completion of the sprinkler, the sprinkler foreman and /or contractor will arrange final sprinkler inspection with the Fire Department. Section 2 The sprinkler system shall be tested and inspected thereafter by -annually, by a licensed sprinkler company Section 3 Upon final testing completion, all sprinkler closeout documents such as as -built drawings, Operation & Maintenance Manuals, and copies of the Material Letter of Compliance and Test Certificates will be forwarded to the Fire Department and building owner. The building owner's facility personnel will be trained (as necessary) on system operations immediately thereafter, prior to occupancy. Narrative prepared by HJS, licensed Sprinkler Contractor, On 05/07/20 HYDRAULIC CALCULATIONS COVER SHEET 5UNIT HOUSE 65 FEDERAL ST 05/07/20 D1-20 B NFPA 13R CALL 2ND FL 2 SPRS FLOWI WATER SUPPLY STATIC PRESSURE (psi) 80 RESIDUAL PRESSURE (psi) 77 RESIDUAL FLOW (gpm) 1190 BOOSTER PUMPS NUMBER OF BOOSTER PUMPS 0 SPRINKLERS MINIMUM FLOW PER SPRINKLER (gpm) 14 MINIMUM PRESSURE PER SPRINKLER (psi) 10.00 THIS SYSTEM OPERATES AT A FLOW OF 29.50 gpm AT A PRESSURE OF 47.81 psi AT THE BASE OF THE RISER (REF. PT. 3) PIPES USED FOR THIS SYSTEM 111 DUCTILE IRON (350) 019 COPPER TYPE 'M' 009 BLAZEMASTER CPVC 001 SCHEDULE 40 �� tN OF SS90 4 JASON CATALFO m O KAHAN-1i 0 FIRE PROTECTION en NO. 483 O -\�R'•�`. TERM -- �� ioNAL„ 05/ 020 5UNIT HOUSE 65 FEDERAL ST 05/07/20 D1-20 B NFPA 13R CALC 2ND FL 2 SPRS FLOWI PAGE 1 SYSTEM ANALYSIS TO SHOW MAXIMUM FLOW WITH ZERO PRESSURE REMAINING NNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNN [ ] TEST AREA 1 REF. PT. THE FOLLOWING SPRINKLERS ARE OPERATING IN:, / [ ] TEST AREA 2 [ ] TEST AREA 3 [ ] REMOTE AREA Elevation of sprinklers = Elevation above water test. K ELEV. FLOW PRESSURE ft gpm psi 30 4.90 34.00 31 4.40 34.00 THE SPRINKLER SYSTEM FLOW IS 23.66 23.32 21.37 23.59 THE OUTSIDE HOSE FLOW AT REFERENCE POINT NO. 1 IS [ ] THE INSIDE HOSE [ ] RACK SPKLR'S. [ ] YARD HYDT. FLOW IS STATIC PRESSURE RESIDUAL PRESSURE TOTAL SYSTEM FLOW AVAILABLE PRESSURE OPERATING PRESSURE PRESSURE REMAINING THE FOLLOWING PRESSURES & FLOWS OCCUR ---> AT REF. PT. 1 <--- 80.00 psi 77.00 psi 145.03 gpm 80.81 psi 80.81 psi 0.00 psi AT 1190.00 gpm AT 145.03 gpm AT 145.03 gpm 45.03 gpm 100.00 gpm 0.00 gpm THEABOVE RESULTS INCLUDE 4.00 psi FRICTION LOSS AT REF. PT. # 6 FOR A [VJ E BACKFLOW PREVENTER [ ] METER [ ] DETECTOR CHECK VALVE [ ] OTHER DEVICE 5UNIT HOUSE 65 FEDERAL ST 05/07/20 D1-20 B NFPA 13R CALC 2ND FL 2 SPRS FLOWI PAGE 2 HYDRAULIC CALCULATIONS AT SPECIFIED FLOW THE FOLLOWING SPRINKLERS ARE OPERATING IN: [ ] TEST AREA 1 [ ] TEST AREA 2 [ ] TEST AREA 3 [ EMOTE AREA Elevation of sprinklers = Elevation above water test. REF. PT. K ELEV. FLOW PRESSURE ft gpm psi 30 4.90 34.00 15.50 10.00 31 4.40 34.00 14.00 10.12 THE SPRINKLER SYSTEM FLOW IS THE OUTSIDE HOSE FLOW AT REFERENCE POINT NO. 1 IS [ ] THE INSIDE HOSE [ ] RACK SPKLR'S. [ ] YARD HYDT. FLOW IS THE FOLLOWING PRESSURES & FLOWS OCCUR ---> AT REF. PT. 1 <--- STATIC PRESSURE RESIDUAL PRESSURE TOTAL SYSTEM FLOW AVAILABLE PRESSURE OPEtRATING PRESSURE PRESSURE REMAINING THE ABOVE RESULTS INCLUDE 80.00 psi 77.00 psi 129.50 gpm 80.82 psi 46.43 psi 34.39 psi AT 1190.00 gpm AT 129.50 gpm AT 129.50 gpm 29.50 gpm 100.00 gpm 0.00 gpm 4.00 psi FRICTION LOSS AT REF. PT. # 6 FOR A [� BACKFLOW PREVENTER [ ] METER [ ] DETECTOR CHECK VALVE [ ] OTHER DEVICE 5UNIT HOUSE 65 FEDERAL ST 05/07/20 D1-20 B NFPA 13R CALC 2ND FL 2 SPRS FLOWI PAGE 3 FITTING Equivalent Length per NFPA 13 1994, 6'=4.3 '-' Indicates Equivalent Length. 'T' Indicates Threaded Fitting 1=45 Elbow, 2=90 Elbow, 3='T'/Cross, 4=Butterfly Valve, 5=Gate Valve, 6=Swing Check Valve FROM TO FLOW PIPE FITS EQV. H-W PIPE DIA. FRIC. ELEV. FROM TO DIFF ---------- (gpm) --- (ft) --------- (ft) C ------NTYPEN-- (in) ---- (psi) ..,- (psi) --- (psi) --- (psi) ".,.ti (psi) 1 2 29.501000.00 322 113.44 140 111 8.550 2 3 29.50 40.00 35 6.00 150 19 2.009 3 4 29.50 21.00 22 18.04 150 9 1.602 4 5 29.50 3.00 2 9.02 150 9 1.602 5 6 29.50 2.00 222 6.60 120 1 1.380 6 7 29.50 4.00 2 8.01 150 9 1.400 7 8 29.50 31.00 2223 30.04 150 9 1.400 8 16 29.50 15.00 222 21.04 150 9 1.109 16 17 29.50 30.00 2 7.01 150 9 1.109 17 18 29.50 5.00 23 12.02 150 9 1.109 18 30 15.50 3.00 3 5.01 150 9 1.109 18 31 14.00 6.00 0 0.00 150 9 1.109 0.000 0.007 0.022 0.022 0.070 0.043 0.043 0.134 0.134 0.134 0.041 0.034 0.000 -1.733 3.467 1.300 0.000 -1.300 0.000 0.000 13.000 0.000 0.000 0.000 A MAX. VELOCITY OF 9.79 ft./sec. OCCURS BETWEEN REF. PT. 17 AND 18 Sprinkler-CALC Release 7.2 Win By Walsh Engineering Inc. North Kingstown R.I. U.S.A. 46.43 46.42 0.01 46.42 47.81 0.34 47.81 43.47 0.88 43.47 41.90 0.27 41.90 41.30 0.60 41.30 38.08 4.52 38.08 35.44 2.64 35.44 30.59 4.85 30.59 12.62 4.98 12.62 10.33 2.29 10.33 10.00 0.33 10.33 10.12 0.20 P R E S s U R E 150.00 140.00 130.00 120.00 110.00 100.00 90.00 80.00 70.00 60.00 50.00 40.00 30.00 20.00 10.00 0.00 0 WATER SUPPLY/DEMAND GRAPH 5UNIT HOUSE 65 FEDERAL ST 05/07/20 D1-20 B NFP413R CALC 2ND FL 2 SPAS FLOW! 500 1000 1500 2000 FLOW Sprinkler-CALC 7.2 Win HYDRAULIC CALCULATIONS COVER SHEET SUNIT HOUSE 65 FEDERAL ST 05/07/20 D1-20 A NFPA 13R CALC 2ND FL 3 SPRS FLOWI WATER SUPPLY STATIC PRESSURE (psi) 80 RESIDUAL PRESSURE (psi) 77 RESIDUAL FLOW (gpm) 1190 BOOSTER PUMPS NUMBER OF BOOSTER PUMPS 0 SPRINKLERS MINIMUM FLOW PER SPRINKLER (gpm) 18 MINIMUM PRESSURE PER SPRINKLER (psi) 16.72 THIS SYSTEM OPERATES AT A FLOW OF 56.79 gpm AT A PRESSURE OF 55.02 psi AT THE BASE OF THE RISER (REF. PT. 3) PIPES USED FOR THIS SYSTEM 111 DUCTILE IRON (350) 019 COPPER TYPE 'M' 009 BLAZEMASTER CPVC 001 SCHEDULE 40 JASON CATALFO KAHAN FIRE PROTECTION NO. 483 05/22/2020 5UNIT HOUSE 65 FEDERAL ST 05/07/20 D1-20 A NFPA 13R CALC 2ND FL 3 SPRS FLOWI PAGE 1 SYSTEM ANALYSIS TO SHOW MAXIMUM FLOW WITH ZERO PRESSURE REMAINING THE FOLLOWING SPRINKLERS ARE OPERATING IN: [ ] TEST AREA 1 [ ] TEST AREA 2 [ ] TEST AREA 3 [ /REMOTE AREA Elevation of sprinklers = Elevation above water test. REF. PT. K ELEV. FLOW PRESSURE ft gpm psi 20 4.90 24.00 27.05 30.47 21 4.40 24.00 23.45 28.40 22 4.40 24.00 23.44 28.37 THE SPRINKLER SYSTEM FLOW IS THE OUTSIDE HOSE FLOW AT REFERENCE POINT NO. 1 IS [ ] THE INSIDE HOSE [ ] RACK SPKLR'S. [ ] YARD HYDT. FLOW IS STATIC PRESSURE RESIDUAL PRESSURE TOTAL SYSTEM FLOW AVAILABLE PRESSURE OPERATING PRESSURE PRESSURE REMAINING THE FOLLOWING PRESSURES & FLOWS OCCUR ---> AT REF. PT. 1 <--- 80.00 psi 77.00 psi 173.94 gpm 80.78 psi 80.78 psi 0.00 psi AT 1190.00 gpm AT 173.94 gpm AT 173.94 gpm 73.94 gpm 100.00 gpm 0.00 gpm THE , BOVE RESULTS INCLUDE 4:00 psi FRICTION LOSS AT REF. PT. # 6 FOR A BACKFLOW PREVENTER [ ] METER [ ] DETECTOR CHECK VALVE [ ] OTHER DEVICE 5UNIT HOUSE 65 FEDERAL ST 05/07/20 D1-20 A NFPA 13R CALC 2ND FL 3 SPAS FLOWI ------------------------------------------------------------------------------------PAGE----- [ ] TEST AREA 1 HYDRAULIC CALCULATIONS AT SPECIFIED FLOW THE FOLLOWING SPRINKLERS ARE OPERATING IN:, / [ ] TEST AREA 2 [ ] TEST AREA 3 [ (((///] REMOTE AREA Elevation of sprinklers = Elevation above water test. REF. PT. K ELEV. FLOW PRESSURE ft gpm psi 20 4.90 24.00 20.80 18.01 21 4.40 24.00 17.99 16.72 22 4.40 24.00 18.00 16.73 THE SPRINKLER SYSTEM FLOW IS THE OUTSIDE HOSE FLOW AT REFERENCE POINT NO. 1 IS [ ] THE INSIDE HOSE [ ] RACK SPKLR'S. [ ] YARD HYDT. FLOW IS THE FOLLOWING PRESSURES & FLOWS OCCUR ---> AT REF. PT. 1 <--- STATIC PRESSURE 80.00 psi RESIDUAL PRESSURE 77.00 psi AT 1190.00 gpm TOTAL SYSTEM FLOW 156.79 gpm AVAILABLE PRESSURE 80.80 psi AT 156.79 gpm OPERATING PRESSURE 54.46 psi AT 156.79 gpm PRESSURE REMAINING 26.33 psi 56.79 gpm 100.00 gpm 0.00 gpm THE ABOVE RESULTS INCLUDE 4.00 psi FRICTION LOSS Al REF. PT. # 6 FOR A [(1 BACKFLOW PREVENTER [ ] METER [ ] DETECTOR CHECK VALVE [ ] OTHER DEVICE 5UNIT HOUSE 65 FEDERAL ST 05/07/20 D1-20 A NFPA 13R CALC 2ND FL 3 SPRS FLOWI PAGE 3 FITTING Equivalent Length per NFPA 13 1994, 6-4.3 '-' Indicates Equivalent Length. 'T' Indicates Threaded Fitting 1=45 Elbow, 2=90 Elbow, 3='T'/Cross, 4=Butterfly Valve, 5=Gate Valve, 6=Swing Check Valve FROM TO FLOW PIPE FITS EQV. H-W PIPE DIA. (gpm) (ft) (ft) C TYPE (in) 1 2 56.791000.00 2 3 56.79 40.00 3 4 56.79 21.00 4 5 56.79 3.00 5 6 56.79 2.00 6 7 56.79 4.00 7 8 56.79 31.00 8 10 20.80 2.00 10 11 20.80 20.00 11 20 20.80 14.00 8 12 35.99 7.00 12 13 35.99 10.00 13 14 35.99 10.00 14 15 35.99 10.00 15 21 17.99 1.00 15 22 18.00 6.00 322 113.44 140 111 8.550 35 6.00 150 19 2.009 22 18.04 150 9 1.602 2 9.02 150 9 1.602 222 6.60 120 1 1.380 2 8.01 150 9 1.400 2223 30.04 150 9 1..400 3 5.01 150 9 1.109 2 7.01 150 9 1.109 22 14.03 150 9 1.109 3 6.01 150 9 1.400 2 8.01 150 9 1.400 33 12.02 150 9 1.400 223 22.03 150 9 1.400 3 5.01 150 9 1.109 0 0.00 150 9 1.109 FRIC. ELEV. FROM TO DIFF (psi) (psi) (psi) (psi) (psi) 0.000 0.000 0.025 -1.733 0.075 3.467 0.075 1.300 0.236 0.000 0.145 -1.300 0.145 0.000 0.070 0.000 0.070 8.667 0.070 0.000 0.063 0.000 0.063 4.333 0.063 0.000 0.063 4.333 0.054 0.000 0.054 0.000 A MAX. VELOCITY OF 12.18 ft./sec. OCCURS BETWEEN REF. PT. Sprinkler-CALC Release 7.2 Win By Walsh Engineering Inc. North Kingstown R.I. U.S.A. 5 AND 6 54.46 54.43 0.03 54.43 55.02 1.15 55.02 48.60 2.95 48.60 46.40 0.91 46.40 44.37 2.03 44.37 39.93 5.74 39.93 31,05 8.88 31.05 30.56 0.49 30.56 19.99 1.90 19.99 18.01 1.97 31.05 30.24 0.81 30.24 24.76 1.15 24.76 23.38 1.38 23.38 17.04 2.00 17.04 16.72 0.32 17.04 16.73 0.31 WATER SUPPLY/DEMAND GRAPH EUNIT HOUSE 65 FEDERAL ST 05/07/20 D1-20A NFPA 13R CALC 2ND FL 3 SPRS FLOW! P R E S S U R E 150.00 140.00 130.00 120.00 110.00 100.00 90.00 80.00 70.00 60.00 50.00 40.00 30.00 20.00 10.00 0.00 0 500 1000 0 Supply: 77.00 psi @ 1190.00 gpm FLOW 1500 Demand: 54.46 psi 156.79 gpm 2000 Sprinkler-CALC 7.2 Win