49 Federal St FP 6_11_20 (002)Notes:
0
1,547 .
Living
( 203 )
PROVIDE 21/2" SINGLE -INLET FIRE DEPARTMENT
CONNECTION (TYPE AND FINAL LOCATION TO BE
VERIFIED WITH BOSTON FIRE DEPARTMENT PRIOR
TO INSTALLATION). PROVIDE 2-1/2" CHECK VALVE
WITH BALL DRIP LOCATED IN COMMON AREA.
00B
MAIL STATI
2" COPPER SERVICE
(DESIGNED AND INSTALLED
PROVIDE NEW 1.511 PER NFPA 24 BY OTHERS)
BACKFLOW PREVENTER
AND STRAIGHT -PIPE RISER
(SEE DETAIL, THIS SHEET)
UNIT 2
1,529 SF
Living Room
( 207 )
Kitchell
210 )
DN'
n
First Floor Plan
SCALE: 1/4" = 1'-0"
G.1
L L. J .L
UNIT 1
Living Area
(103)
N
`$'.I,F. CO
ITH EXI
TAIR AB
LINE OF PORCH ABOVE
Bedroori
(105)
Basement Plan
SCALE: 1/4" = 1'-0"
Bedroom
(110)
JASON CATALFO
KAHAN
FIRE PROTECTION
, NO.483 a- -
�'ASTEV`
06/11/2020
DESCRIPTION:
STATUS.
CONSTRUCTION ISSUE
IPLS q0INC
/ CLIENT:
ENGINEER: PLS I N C
23 SAGAMORE LN
BOXFORD, MA
01921
SITE: 49 FEDERAL ST
SALEM, MA 01970
TITLE:
FIRE PROTECTION DETAILS
BASE -1ST
SCALE AT Al:
1 /4"= 1 '-0"
DATE:
6/11/20
DRAWN:
JK
CHECKED:
JK
PROJECT NO:
FP 1
DRAWING NO:
2020-FEDER
REVISION:
1
Notes:
Design Area 1
TOP FLOOR
Demand Calculations using Hazen -Williams Method
Occupancy Classification: LH
Design Area Density: 0.1
Additional Outside Hose: 100
Wet System
Design Area Size:
Notes:
0
edroom 4.9R
( 401) 7.0
4.9R
7.0
0} 1 LF
0
0.1
Bath
( 403 )
2
289.29
<044
-li
+8
I
I
0
o
i
(EX.;
Bedroo g
(408)
Bath
C 409
Bedroom
( 406
L
ALIGN
2E
Bedroom
407)
405
Third Floor Plan
SCALE. 1/4" = 1'-0"
1/2 Bath
itchen
303)
4III
P. 411
1
UNIT
856 SF
Living Roo
(302rI 18
Ilf\
LINE OF WALL
BELOW
®lh
( U?J
UNIT 3
890 SF
Living Room
( 305 )
Calculation results for Design Area 1 - TOP FLOOR
This system as shown on PLS INC company print no
for MULTI -UNIT at 49 FEDERAL ST
dated 6/11/20
contract no is designed to discharge at a rate of 0.1
a maximum area of 289.29 ft2 when supplied with water at a rate of 48 gpm
Hose stream allowance of
Occupancy classification: LH
Commodity classification:
Maximum storage height:
Storage arrangement:
is included in the above.
gpm/ft2 (L/min/m2) of floor area over
at 46.3 psi at the base of the riser.
Number of heads flowing: 3
System Type: Wet
Maximum velocity: 8.96 ft/s
Flow from In -Rack sprinklers:
Flow from Overhead sprinklers:
Flow from Inside Hoses:
Flow from Outside Hoses:
Other fixed flows:
Total flow in system piping:
Additional flow at/beyond source:
Total of all flows:
0 gpm
48 gpm
0 gpm
0 gpm
0gpm
48 gpm
100 gpm
148 gpm
INE OF WALL
BELOW
1
1)i\IIY
959 SF
C5)9Rig Room
OBI W/D
1
Ott
4417
UP
L I
Pressure Required at Source:
Pressure Available at Source:
Surplus Pressure at Source:
Bedroom
Kitchen
( 307 )
46.3 psi
79.9 psi
33.6 psi
Design Area 2
2ND FLOOR
Demand Calculations using Hazen -Williams Method
Occupancy Classification: LH
Design Area Density: 0.1
Additional Outside Hose: 100
Calculation results for Design Area 2 - 2ND FLOOR
This system as shown on PLS INC company print no
for MULTI -UNIT at 49 FEDERAL ST
dated 6/11/20
contract no is designed to discharge at a rate of 0.1
a maximum area of 282.66 ft2 when supplied with water at a rate of 59.5 gpm
Hose stream allowance of is included in the above.
Occupancy classification: LH
Commodity classification:
Maximum storage height:
Storage arrangement:
gpm/ft2 (L/min/m2) of floor area over
at 70.9 psi at the base of the riser.
Number of heads flowing: 4
System Type: Wet
Maximum velocity: 20.21 ft/s
Flow from In -Rack sprinklers:
Flow from Overhead sprinklers:
Flow from Inside Hoses:
Flow from Outside Hoses:
Other fixed flows:
Total flow in system piping:
Additional flow at/beyond source:
Total of all flows:
0 gpm
59.5 gpm
0 gpm
0 gpm
0 gpm
59.5 gpm
100 gpm
159.5 gpm
Wet System
Design Area Size:
Notes:
Second Floor Plan
SCALE: 1/4" = 1'-0"
282.66
Pressure Required at Source:
Pressure Available at Source:
Surplus Pressure at Source:
70.9 psi
79.9 psi
9 psi
JASON CATALFO
KAHAN
FIRE PROTECTION
NO. 483
06/11/2020
DESCRIPTION:
STATUS. CONSTRUCTION ISSUE
IPLS INC
/ CLIENT:
ENGINEER: PLS I N C
23 SAGAMORE LN
BOXFORD, MA
01921
SITE: 49 FEDERAL ST
SALEM, MA 01970
TITLE:
FIRE PROTECTION DETAILS
2ND-3RD
SCALE AT Al:
1 /4"= 1 '-0"
DATE:
6/11/20
DRAWN:
JK
CHECKED:
JK
PROJECT NO:
FP 2
DRAWING NO:
2020-FEDER
REVISION:
1
Notes:
1-
L - T
Tee with same
outlet size as
sprinkler thread
size.
See "Important
Installation
Information", later
in this document
2"Min. Dia.
Hole in Wall
Recessed
DRY-SIDEWALL DETAIL
SCALE: NOT TO SCALE
TABLE 8.10.7.1.3
POSITIONING OF SPRINKLER TO AVOID
OBSTRUCTION TO DISCHARGE
DISTANCE FROM SPRINKLERS TO
SIDE OF OBSTRUCTION
(A)
MAXIMUM ALLOWABLE DISTANCE OF
DEFLECTOR ABOVE BOTTOM OF
OBSTRUCTION (INCHES)
(B)
LESS THAN 8 FT
0
8'-0" TO LESS THAN 10'
0'-1"
10' TO LESS THAN 11'
0'-2"
11' TO LESS THAN 12'
0'-3"
12' TO LESS THAN 13'
0'-4"
13' TO LESS THAN 14'
0'-6"
14' TO LESS THAN 15'
0'-7"
15' TO LESS THAN 16'
0'-9"
16' TO LESS THAN 17'
0'-11"
17' OR GREATER
1'-2"
v
06 ea) 14 mm)
a;r: (ea ore)
Max Hole
2• {51 nlml
Mln. Hale
2's1°•
(5 owe
MAXIMUM EXTENSION
Typical cannel -Ile
Rnisbed Sodom
010
MAXIMUM RECESS
h" Adjustment
Recessed - V2732
prew/l7 tamfda &rile)
11Fpl°al Caeag Tin
(
Finiallad Surface
RESIDENTIAL PENDENT DETAIL
SCALE: NOT TO SCALE
FIGURE 8.10.7.1.3
POSITIONING OF SPRINKLERS TO AVOID OBSTRUCTION TO
DISCHARGE
NFPA 13 TABLE 8.10.7.1.3 + FIGURE 8.10.7.1.3
RESIDENTIAL SIDEWALL SPRINKLERS
TABLE 8.10.7.1.4
POSITIONING OF SPRINKLER TO AVOID OBSTRUCTION TO
DISCHARGE
DISTANCE FROM SPRINKLERS TO
SIDE OF OBSTRUCTION
(A)
MAXIMUM ALLOWABLE DISTANCE OF
DEFLECTOR ABOVE BOTTOM OF
OBSTRUCTION (INCHES)
(B)
LESS THAN 1'-6"
0'-0"
1'-6" TO LESS THAN 3'-0"
0'-1"
3' TO LESS THAN 4'
0'-3"
4' TO LESS THAN 4'-6"
0'-5"
4'-6" TO LESS THAN 6'
0'-7"
6' TO LESS THAN 6'-6"
0'-9"
6'-6" TO LESS THAN 7'
0'-11"
7' TO LESS THAN 7'-6"
1'-2"
OBSTRUCTION
A
FIGURE 8.10.7.1.4 (B)
POSITIONING OF SPRINKLERS TO AVOID OBSTRUCTION TO
DISCHARGE
NFPA 13 TABLE 8.10.7.1.4 + FIGURE 8.10.7.1.4 (B)
STANDARD SIDEWALL SPRINKLERS
TABLE 8.10.6.1.2
POSITIONING OF SPRINKLER TO AVOID OBSTRUCTION TO
DISCHARGE
SPRINKLERS TO
DISTANCE FROMDEFLECTOR
SIDE OF OBSTRUCTION
(A)
MAXIMUM ALLOWABLE DISTANCE OF
ABOVE BOTTOM OF
OBSTRUCTION (INCHES)
(B)
LESS THAN 1 FT
0
1'-0" TO LESS THAN 1'-6"
0'-0"
1'-6" TO LESS THAN 2'-0"
0'-1"
2'-0" TO LESS THAN 2'-6"
0'-1"
2'-6" TO LESS THAN 3'-0"
0'-1"
3'-0" TO LESS THAN 3'-6"
0'-3"
3'-6" TO LESS THAN 4'-0"
0'-3"
4'-0" TO LESS THAN 4'-6"
0'-5"
4'-6" TO LESS THAN 5'-0"
0'-7"
5'-0" TO LESS THAN 5'-6"
0'-7"
5'-6" TO LESS THAN 6'-0"
0'-7"
6'-0" TO LESS THAN 6'-6"
0'-9"
6'-6" TO LESS THAN 7'-0"
0'-11"
7'-0" AND GREATER
1'-2"
FIGURE 8.10.6.1.2(A)
POSITIONING OF SPRINKLERS TO AVOID OBSTRUCTION TO
DISCHARGE
NFPA 13 TABLE 8.10.6.1.2 + FIGURE 8.10.6.1.2(A)
RESIDENTIAL PENDENT AND UPRIGHT SPRAY SPRINKLERS
TABLE 8.3.2.5(c)
TEMPERATURE RATINGS OF SPRINKLERS IN SPECIFIED RESIDENTIAL AREAS
HEAT SOURCE
MINIMUM DISTANCE FROM EDGE OF
SOURCE TO ORDINARY TEMPERATURE
SPRINKLER (INCHES)
MINIMUM DISTANCE FROM EDGE
OF SOURCE TO INTERMEDIATE
TEMPERATURE SPRINKLER (INCHES)
SIDE OF OPEN OR RECESSED
FIREPLACE 36
12
FRONT OF RECESSED FIREPLACE
60
36
KITCHEN RANGE
18
9
WALL OVEN
18
9
SIDE OF CEILING OR WALL MOUNTED
DIFFUSER
HOT AIR 24
12
FRONT OF WALL MOUNTED HOT AIR DIFFUSER
36
18
HOT WATER HEATER OR FURNACE
6
3
LIGHT FIXTURE: OW-250W
6
3
LIGHT FIXTURE: 250W-499W
12
6
C)2 TEMPERATURE RATINGS OF SPRINKLERS IN SPECIFIED RESIDENTIAL AREAS
FP0.1 SCALE: NTS
Job: MULTI -UNIT
Address: 49 FEDERAL ST
City: SALEM
Contract #:
Contractor: PLS INC
State: MA
Date:
Designer:
Zip/Postal Code: 01970
6/11/20
JK
Address: 23 SAGAMORE LN
City: BOXFORD
State: MA
Zip/Postal Code: 01921
Phone: 617-633-3533 Fax:
Email:
Approving Authority:
Design Defaults
Default Sprig Size:
Default Sprig Material:
Default Sprig Elevation:
1
CPVC
0
Standards: NFPA13
Default Drop Size: 1
Default Drop Material: CPVC
Default Drop Elevation: 0
MAX. HANGER SPACING
PIPE
TYPE
NOMINAL PIPE SIZE (IN)
1
174"
1y"
2
2Y2 "
4
6
8
SCH 10,40 STEEL
12-0
12-0
15-0
15-0
15-0
15-0
15-0
15-0
UL LISTED CPVC
6-0
6-6
7-0
8-0
9-0
-{
r36" MAX. FOR 1 DIA.
)- 148" MAX. FOR 1 1/4" DIA. THEN
L60" MAX. FOR 1 1/2" DIA. OR LARGER
EXTEND HERE
O / 0/O/ 0/ 0 I
BETWEEN I
O/
0/3
DISTANCE OMIT HGR ON STARTER PIPES
SHALL NOT EXCEED 6' OR LESS, NO X-MAIN HGR
ABOVE TABLE OMISSIONS ALLOWED
IF GREATER THAN 36" MAX. FOR 1" DIA.3--
IF GREATER THAN 48" MAX. FOR 1 1/4" DIA.
IF GREATER THAN 60" FOR 1 1/2" DIA. OR LARGER
CLOSETS (TYPICAL)
EXCEPT WHERE SPECIFIED IN SECTION
6.6.4 (NFPA 13R, 2013 EDITION),
SPRINKLERS SHALL NOT BE REQUIRED
IN CLOTHES CLOSETS, LINEN CLOSETS,
AND PANTRIES THAT MEET ALL OF THE
FOLLOWING CONDITIONS:
1) THE AREA OF THE SPACE DOES NOT
EXCEED 24 SF
2) THE LEAST DIMENSION DOES NOT
EXCEED 3 FT
3) THE WALLS AND CEILINGS ARE
SURFACED WITH NONCOMBUSTIBLE
OR LIMITED -COMBUSTIBLE MATERIALS
AS DEFINED IN NFPA220.
NOTE: WHEN MECHANICAL EQUIPMENT
OR LAUNDRY MACHINES ARE PLACED
IN THE CLOSET, THE CLOSET IS NO
LONGER CONSIDERED A CLOTHES
CLOSET, LINEN CLOSET, OR PANTRY,
SO THE EXCEPTION OF 6.6.3 IS NO
LONGER VALID AND SPRINKLERS MUST
BE INSTALLED.
FIRE PROTECTION NOTES:
THE PURPOSE OF THIS FIRE PROTECTION DRAWING AND THE ASSOCIATED
FIRE PROTECTION DESIGN NARRATIVE IS TO INDICATE THE PROPOSED
COMMERCIAL SPRINKLER SYSTEM TO BE INSTALLED WITHIN THE
RENOVATED MULTI -UNIT BUILDING LOCATED AT 49 FEDERAL ST IN SALEM,
MASSACHUSETTS.
THIS BUILDING CONSISTS OF A BASEMENT LEVEL, 1ST LEVEL, 2ND LEVEL
AND 3RD LEVEL AS INDICATED ON THE ASSOCIATED ARCHITECTURAL
DRAWINGS.
THIS RESIDENTIAL SPRINKLER SYSTEM HAS BEEN DESIGNED IN
ACCORDANCE WITH THE REQUIREMENTS OF NFPA 13R (2013 EDITION) FOR A
RESIDENTIAL BUILDING UP TO 3 STORIES IN HEIGHT AND NOT EXCEEDING
12,000 GROSS SF WITH A SINGLE MEANS OF EGRESS.
THE SPRINKLER CONTRACTOR SHALL FOLLOW THE LATEST REQUIREMENTS
OF NFPA 13 AND 13R (2013 EDITION), MASSACHUSETTS STATE BUILDING
CODE (780 CMR, 9TH EDITION) AND SALEM FIRE DEPARTMENT
REQUIREMENTS.
THIS SYSTEM WILL BE SUPPLIED BY A NEW 2" COPPER SERVICE, TAPPED OFF
THE EXISTING WATER MAIN ON ATHENS STREET. THE 2" SERVICE SHALL BE
DESIGNED, INSTALLED, FLUSHED AND TESTED IN ACCORDANCE WITH THE
REQUIREMENTS OF NFPA 24 BY A LICENSED UNDERGROUND CONTRACTOR
AND WILL ENTER THE BASEMENT AS INDICATED ON THIS DRAWING.
THE SYSTEM HAS BEEN HYDRAULICALLY CALCULATED IN ACCORDANCE WITH
THE REQUIREMENTS OF NFPA 13R, INCLUDING THE FOUR HYDRAULICALLY
MOST DEMANDING HEADS IN A SINGLE COMPARTMENT BASED ON THE
REQUIREMENTS OF THE SPECIFIC SPRINKLER HEAD AND THE SPACING USED
IN THIS DESIGN (16'x16' REQUIRING A MINIMUM OF 13 GPM @ 7 PSI). REMOTE
AREAS, DENSITIES AND HOSE STREAM ALLOWANCES ARE INDICATED ON
THIS DRAWING ALONG WITH SYSTEM DEMANDS AT CONNECTION TO STREET
AND CALCULATION RESULTS HAVE BEEN COMPARED TO RECENT HYDRANT
FLOW TEST INFORMATION OBTAINED FROM THE BOSTON WATER & SEWER
DEPARTMENT. CALCULATIONS HAVE BEEN SUBMITTED WITH THIS DRAWING
TO THE SALEM FIRE DEPARTMENT FOR REVIEW.
SPRINKLER HEAD LOCATIONS HAVE NOT BEEN COORDINATED
WITH CEILING -MOUNTED FIXTURES. INSTALLING SPRINKLER
CONTRACTOR SHALL COORDINATE WITH ELECTRICIAN AND
LOCATE SPRINKLERS AT LEAST 36" FROM THE CENTER OF ANY
CEILING -MOUNTED FIXTURE, IN ACCORDANCE WITH THE
REQUIREMENTS OF NFPA 13R WHILE MAINTAINING THE MAXIMUM
DISTANCES FROM WALLS INDICATED ON THIS DESIGN (8-FT).
ADDITIONAL SPRINKLERS REQUIRED DUE TO INABILITY TO MEET
OBSTRUCTION CRITERIA SHALL BE AT THE OWNERS EXPENSE.
RESIDENTIAL
FLAT PLATE CONCEALED
PENDENT
SPRINKLER CONTRACTOR SHALL TAKE
PRECAUTIONS WHEN INSTALLING
SPRINKLER PIPING IN JOISTS ON TOP
FLOOR. GENERAL CONTRACTOR SHALL
BE REQUIRED TO INSTALL SUFFICIENT
INSULATION TO MAINTAIN 40-DEGREES
IN ALL AREAS WHERE SPRINKLER PIPING
AND HEADS ARE INSTALLED
SYM
CNT
POSITION
FINISH
TEMP
K
NPT
SIN
MFG.
MODEL#
62
PEND
BRASS
155
4.90
1/2"
TY2234
Tyco
LFII
UL LISTED CPVC SPRINKLER PIPING
FIDE ALA'
V1
SY
V130LS
TAMPER SWITCH
FLOW SWITCH
MONITOR MODULE
CONTROL MODULE
ISOLATOR MODULE
04 COMBINATION SPEAKER/STROBE, ADA APPROVED,
30 80" AFF; 15/75 CANDELLA, SET AT 15 cd U.O.N.
ON FLOOR PLANS.
DESIGNATES CANDELLA RATING;
WP
LF
FACP
ANN
RT
AD
O
200°
TPD
EXTERIOR WEATHERPROOF HORN/STROBE
EXACT LOCATION AND HEIGHT
PER FIRE DEPARTMENT.
LF MINIHORN (GENTEX GHLF 24 VDC SERIES)
FIRE ALARM CONTROL PANEL WITH BATTERY
BACKUP; NOTIFIER, FCI OR APPROVED EQUAL
REMOTE ANNUNCIATOR PANEL
ADDRESSABLE
MANUAL PULL STATION 48" AFF
ADDRESSABLE SYSTEM SMOKE DETECTOR
ADDRESSABLE SYSTEM CO2 DETECTOR
REMOTE TEST t FACP
AUTOMATIC DAMPER
HEAT DETECTOR 200 Deg. fixed temp.
DIGITAL UL DIALER
TRANSIENT PROTECTIVE DEVICE
KNOX BOX
ELECTRIC BELL
BEACON (OVER FDC)
NOTE: NOT ALL DEVICES USED IN THIS SYSTEM
PRODUCTS SHALL BE AS INDICATED OR EQUAL
INSTALLATION NOTES:
ALL WORK SHALL BE PERFORMED BY A MASSACHUSETTS LICENSED
SPRINKLER CONTRACTOR. THE SPRINKLER CONTRACTOR SHALL
FOLLOW THE LATEST REQUIREMENTS OF NFPA 13R (2013 EDITION),
MASSACHUSETTS STATE BUILDING CODE (9TH EDITION) AND THE SALEM
FIRE DEPARTMENTS.
THE ARCHITECTURAL BACKGROUND OF BUILDING MAY DIFFER
SLIGHTLY FROM ACTUAL LAYOUT. DRAWINGS ARE NOT INTENDED TO
SHOW ALL OFFSETS AND PIPING ELEVATION CHANGES. CONTRACTOR
SHALL FIELD VERIFY ALL MEASUREMENTS PRIOR TO FABRICATION.
CONTRACTOR SHALL HYDROSTATICALLY TEST ALL SPRINKLER PIPING
AT 200 PSI FOR 2 HOURS AND IS RESPONSIBLE FOR THE COMPLETION
OF ALL ABOVE GROUND TEST CERTIFICATES, SUPPLIED TO THE
OWNER.
ALL PIPING INSTALLED THROUGHOUT THE RESIDENTIAL AREAS OF THE
BUILDING SHALL BE UL LISTED CPVC SPRINKLER PIPING.ALL PIPING
SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF
NFPA 13 (2013 EDITION) AND ALL MANUFACTURERS INSTALLATION
RECOMMENDATIONS. ALL PIPING SHALL BE PITCHED TO DRAIN WITH
LOW -POINT DRAINS AT SECTIONS OF PIPING SUBJECT TO WATER
TRAPPING. SPRINKLER CONTRACTOR SHALL PROVIDE PROTECTIVE
PLATES WHERE CPVC PIPING IS RUN THROUGH STUDS TO PREVENT
PUNCTURING OF THE SPRINKLER PIPING DURING DRYWALL
INSTALLATION AS REQUIRED BY NFPA STANDARDS.
ALL SPRINKLER HEADS WITHIN RESIDENTIAL AREAS OF THE BUILDING
SHALL BE RESIDENTIAL PENDENT SPRINKLERS. SPRINKLERS WITHIN
THE BASEMENT LEVEL WILL BE QUICK -RESPONSE UPRIGHT HEADS. ALL
HEADS SHALL BE INSTALLED IN ACCORDANCE WITH THE
MANUFACTURER'S REQUIREMENTS AND THE REQUIREMENTS OF NFPA
13R (2013 EDITION).
THE BUILDING OWNER IS RESPONSIBLE FOR MAINTAINING THIS
SPRINKLER SYSTEM IN ACCORDANCE WITH THE REQUIREMENTS OF
NFPA 25, INCLUDING THE PROVISION OF HEAT IN ALL AREAS
CONTAINING SPRINKLER PIPING AND HEADS TO PREVENT PIPE FROM
FREEZING. JFP SOLUTIONS, INC. AND THE ENGINEER OF RECORD TAKE
NO RESPONSIBILITY FOR ANY DAMAGES CAUSED BY FREEZE UPS.
1 y" x 2'-0 GALVI (THD BY GROOVE) THROUGH
WALL
1.5" STRAIGHT -PIPE RISER
ASSEMBLY WITH VANE -TYPE
FLOW SWITCH, PRESSURE
GAUGE, TEST AND DRAIN
PROVIDE 1.5" AMES 2000B
BACKFLOW PREVENTER
WITH MONITORED
ISOLATION VALVES
°aeC1loN OF Nee
FINISHED FLOOR
2" FIRE SERVICE PER
NFPA 24 BY OTHERS)
ELECTRIC BELL WITH BACKED -BOX
BY OTHERS)
WOOD JOIST CONSTRUCTION
RESIDENTIAL
CONCEALED
SPRINKLER
HEAD (K=4.9)
TYPICAL
MAINTAIN
NFPA 13
OBSTRUCTION
CRITERIA
(TYPICAL) -\
CPVC MAIN LOCATED WITHIN
HVAC SOFFIT FEEDING
BRANCHLINES LOCATED WITHIN
JOIST CHANNELS (TYPICAL)
c
GYPSUM BOARD
CEILING ON WOOD
STRAPPING
TYPICAL RESIDENTIAL PENDENT SPRINKLER INSTALLATION
NOT TO SCALE
WIRED
SINGLE INLET 2y" FIRE DEPA-RTMENT
CONNECTION (COORDINATE NTTH
LOCAL FD PRIOR TO INSTALLATION)
1" DRAIN PIPED TO EXTERIOF
SUPPLY AND RISER DETAIL
NOT TO SCALE
FREEZE PROTECTION
THE BUILDING OWNER IS RESPONSIBLE FOR PROVIDING HEAT IN ALL
AREAS CONTAINING SPRINKLER PIPING AND HEADS TO PREVENT PIPE
FROM FREEZING. ANY AREAS THAT RAISE CONCERN WITH REGARD TO
FREEZING POTENTIAL SHALL BE BROUGHT TO THE ENGINEER'S
ATTENTION, IN WRITING, PRIOR TO INSTALLATION. JFP SOLUTIONS,
INC. AND THE ENGINEER OF RECORD TAKE NO RESPONSIBILITY FOR
DAMAGES CAUSED BY FREEZE -UPS OF THE SPRINKLER SYSTEM.
1.
FIRE ALARM \OTES
ALL FIRE ALARM SYSTEM WIRING SHALL COMPLY WITH THE
NATIONAL ELECTRICAL CODE, APPLICABLE STATE AND LOCAL
FIRE AND SAFETY CODES, AS WELL AS BEING COORDINATED
WITH THE LOCAL AUTHORITY HAVING JURISDICTION.
2. CAUTION: DO NOT CONNECT ANY POWER TO CONTROL
PANEL (BATTERIES OR 120VAC) UNTIL ALL OTHER FIELD
WIRING IS TESTED AND CONNECTED.
3. DO NOT INSTALL ANY A.C. CURRENT CARRYING CONDUCTORS
CLOSE TO OR IN THE SAME RACEWAY WITH FIRE ALARM
SYSTEM CONDUCTORS.
4. THE ENTIRE FIRE ALARM SYSTEMS SHALL BE A CLASS "A"
ADDRESSABLE SYSTEM.
5. THE RATING OF THE CONTROL MODULE (ES-200X) CONTACTS ARE:
20 WATTS AUDIO AT 25 OR 70 VOLTS
2.0 AMPS DC (BELLS, HORNS AND DC CONTROL CIRCUITS)
0.3 AMPS INDUCTIVE
6. ALL OUTPUT (SIGNAL) CIRCUITS ARE SHOWN IN ALARM CONDITION.
POLARITY IS REVERSED WHEN THE SYSTEM IS IN THE SUPERVISORY
CONDITION.
7. OWNER TO PROVIDE DESIGNATIONS FOR DEVICES PROGRAMMING LANGUAGE.
8. REFER TO FLOOR PLANS FOR EXACT LOCATIONS AND QUANTITY
OF ALL DEVICES.
9. FIRE ALARM CONTRACTOR SHALL FIELD VERIFY THE LENGTHS AND FEASIBILITY
OF ALL ROUTING BEFORE BEGINNING WORK.
10. ALL JUNCTION BOX COVERS IN THE FIRE ALARM SYSTEM SHALL BE PAINTED RED,
BY THE FIRE ALARM CONTRACTOR, BEFORE THEY ARE INSTALLED.
11. ALL EQUIPMENT SHALL BE UL LISTED AND/OR FM APPROVED.
12. ELECTRICAL SUBCONTRACTOR SHALL INSTALL ALL WIRING TO THE FIRE ALARM
CONTROL PANELS; TERMINATIONS TO FACP's SHALL BE MADE BY THE FIRE ALARM
SUPPLIER OR UNDER SUPERVISION OF A REPRESENTATIVE FROM THE FIRE ALARM
MANUFACTURER.
13. GROUND ALL EQUIPMENT PER N.E.C. REQUIREMENTS.
14. ALL PERMITS AND INSPECTION FEES SHALL BE OBTAINED AND PAID FOR BY THE
FOR BY THE FIRE ALARM CONTRACTOR.
15. ALL CUTTING, PATCHING, AND CORE DRILLING FOR FIRE ALARM SYSTEMS
SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR.
FIRE SEAL ALL NEW ELECTRICAL PENETRATIONS IN FLOORS AND WALLS.
16. THE LOCATIONS OF ALL SMOKE DETECTORS AND HEAT DETECTORS
SHOWN ARE CONSIDERED TO BE SCHEMATIC ONLY. THE ACTUAL
LOCATIONS (SPACING TO ADJACENT DETECTORS, WALLS ETC.) ARE
REQUIRED TO MEET NFPA 72.
Caution: Care should be taken to ovoid
compressing the insulation. This reduces its
R value. To prevent potential freeze -ups of
the sprinkler piping, the insulation should
be installed tight against the joists.
INSULATION PROTECTING SPRINKLER
PIPING ON UPPER FLOOR DETAIL
NOT TO SCALE
FIRE ALARM NOTES & NARRATIVE
THE FIRE ALARM SYSTEM FOR THIS BUILDING IS MADE UP OF THE
FOLLOWING:
INTERIOR FRAMING
(REFERENCE ONLY)
FINISHED CEILING
DRY-SIDEWALL FED
FROM TEE INSIDE
FINISHED UNIT
I><
OPTIONAL SOFFIT TO CONCEAL
EXPOSED PORTION OF DRY SIDEWALL
(COORDINATE WITH ARCHITECT AND
GENERAL CONTRACTOR).
NOTE: MAINTAIN SPRINKLER
COVERAGE WITHIN UNIT WITH
REGARD TO SOFFIT OBSTRUCTIONS
EXTERIOR DECK FRAMING
(REFERENCE ONLY)
DRY-SIDEWALL INSTALLED
WITH DEFLECTOR 4" TO 6"
BELOW UNDERSIDE OF WOOD
JOIST FRAMING OF DECK
INSULATED EXTERIOR WALL
(SPRINKLER CONTRACTOR TO
FOLLOW ALL RECOMMENDATIONS OF
MANUFACTURER WITH REGARD TO
INSTALLATION OF DRY-SIDEWALLS)
TYPICAL DRY-SIDEWALL INSTALLATION FOR EXTERIOR OVERHANGS
NOT TO SCALE
AMBIENT
TEMPERATURE OF
PROTECTED AREA
AT THE
DISCHARGE END
OF THE
SPRINKLER
EXPOSED BARREL AMBIENT
TEMPERATUTE
40°F (4°C)
50°F (10°C)
60°F (16°C)
EXPOSED MINIMUM BARREL LENGTH
DIMENSION "A"
(FACE OF TEE TO TOP OF CEILING OR INSIDE
WALL)
Inches (mm)
40'F
(4°C)
0
0
0
30°F
(-1°C)
0
0
0
20°F
(-7°C)
4 (102)
0
0
10°F
(-12°C)
8 (203)
1 (25)
0
0°F
(-18°C)
12 (305)
3 (76)
0
-10°F
(-23°C)
14 (356)
4 (102)
1 (25)
-20°F
(-29°C)
14 (356)
6 (152)
3 (76)
-30°F
(-34°C)
16 (406)
8 (203)
4 (102)
-40°F
(-40°C)
18 (457)
8 (203)
4 (102)
-50°F
(-46°C)
20 (508)
10 (254)
6 (152)
-60°F
(-51 °C)
20 (508)
10 (254)
6 (152)
1. FIRE ALARM CONTROL PANEL (ADDRESSABLE TYPE) LOCATED IN FRONT
ENTRANCE
2. PULL STATIONS AT MAIN EGRESS LOCATIONS
3. HORN STROBE LOCATED ON SECOND LEVEL COMMON AREA AND LOW
FREQUENCY SOUNDERS IN ALL APARTMENTS (70 dB MIN AT PILLOW OF
SLEEPING ROOMS).
4. LOCAL SMOKE DETECTORS IN ALL BEDROOMS AND COMBINATION
SMOKE AND CARBON MONOXIDE DETECTORS WITHIN 10-FT OF ALL
BEDROOM DOORS, INTERCONNECTED WITHIN UNIT.
5. SYSTEM SMOKE DETECTORS IN ALL COMMON AREAS
6. FLOW AND TAMPER SWITCHES FOR SPRINKLER SYSTEM. TAMPER
SWITCH SHALL BE TROUBLE ONLY ON THE FIRE ALARM PANEL AND
SIGNAL SENT VIA RADIO SIGNAL (WILL NOT TRIP MASTER BOX)
7. ELECTRIC BELL LOCATED ON OUTSIDE OF THE BUILDING NEAR FIRE
ALARM CONTROL PANEL AND FIRE DEPARTMENT CONNECTION
8. KNOX BOX AT MAIN ENTRANCE
9. CARBON MONOXIDE DETECTOR SHALL BE LOCATED IN ALL AREAS THAT
CONTAIN FOSSIL FUEL AND ADJACENT AREAS AND CONNECTED TO THE
FIRE ALARM SYSTEM. TROUBLE ONLY ON FIRE ALARM PANEL AND
SIGNAL SENT VIA RADIO SIGNAL (WILL NOT TRIP MASTER BOX).
SYSTEM OPERATION
THE ACTIVATION OF ANY MANUAL FIRE ALARM STATION OR THE AUTOMATIC
ACTUATION OF ANY SYSTEM SMOKE DETECTOR, SPRINKLER SYSTEM WATER
FLOW SWITCH OR ANY OTHER APPROVED ALARM INITIATION DEVICE SHALL
IMMEDIATELY RESULT IN THE FOLLOWING:
1. THE DEVICE IN ALARM SHALL BE LISTED ON A DISPLAY AT THE FIRE
ALARM PANEL AND REMOTE ANNUNCIATOR
2. THE AUDIBLE HORNS SHALL SOUND A TEMPORAL PATTERN AT ALL
LOCATIONS
3. ALL VISUAL ALARM SIGNALS SHALL FLASH AT A RATE OF 120 FLASHES
PER MINUTE.
4. IF ALARM SIGNALS ARE SILENCED FOR ANY REASON, THEY SHALL
AUTOMATICALLY RESOUND IF ANOTHER ADDRESS IS TRIPPED
5. OUTDOOR BEACON LIGHTS WILL ILLUMINATE
6. IN THE EVENT OF A COMMERCIAL POWER INTERRUPTION, THE SYSTEM
SHALL AUTOMATICALLY TRANSFER TO AN EMERGENCY BATTERY
SOURCE.
THIS TIER 1 DRAWING IS FOR DIAGRAMMATICAL USE ONLY. FIRE ALARM
CONTRACTOR TO SUBMIT TIER II SHOP DRAWINGS, BATTERY CALCULATIONS
AND PRODUCT CUTS TO BE REVIEWED BY JFP SOLUTIONS, INC. AND
REVIEWED AND APPROVED BY THE BOSTON FIRE DEPARTMENT AND
BUILDING DEPARTMENT.
r
L,
FACE OF
TEE
FITTING
MINIMUM
EXPOSED
at -
BARREL
LENGTH
I
\-TEE FITTING
ANSI B16.3 CLASS 150 OR
ANSI B16.4 CLASS 125
FIGURE 3: EXPOSED BARREL LENGTH
FACE OF
MOUNTING
SURFACE
TYPICAL
ESCUTCHEON
STAND-ALONE
AUDIBLE APPLIANCE
MANUAL FIRE
ALARM BOX
90" MINIMUM
48"
DOOR
FIRE
CEILING
STAND-ALONE
VISIBLE APPLIANCE
LENS
5'-0"
/ MAXIMUM
OPERATING
HANDLE
COMBINATION AUDIBLE/
VISIBLE APPLIANCE
80" 96"
LENS
FLOOR
TYPICAL MOUNTING HEIGHT DETAIL
FOR WALL MOUNTED DEVICES
Salem District Court 9
30-al St
1949 Federal Street
I�I1..,�a. IJr;II
DESCRIPTION:
STATUS. CONSTRUCTION ISSUE
/ PLS 1 INC
/ CLIENT:
ENGINEER: PLS I N C
23 SAGAMORE LN
BOXFORD, MA
01921
SITE: 49 FEDERAL ST
SALEM, MA 01970
TITLE:
FIRE PROTECTION DETAILS
INFO SHEET
SCALE AT Al:
1 /4"= 1 '-0"
DATE:
6/11/20
DRAWN:
JK
CHECKED:
JK
PROJECT NO:
FP 3
DRAWING NO:
2020-FEDER
REVISION:
1