E dwg'sa A/AM P AC ACU AF AFF AHU AIC ANN ANSI APPROX ATC ATS AVG AWG BSMT C C/B CLG CO COMP COND CP CU CUH MEPT ABBREVIATIONS 48" ABOVE FINISHED FLOOR AMPERE ALTERNATING CURRENT AIR CONDITIONING UNIT(S) ARC FAULT ABOVE FINISHED FLOOR AIR HANDLING UNIT AMPS INTERRUPTING CURRENT ANNUNCIATOR AMERICAN NATIONAL STANDARDS INSTITUTE APPROXIMATE AUTOMATIC TEMPERATURE CONTROL AUTOMATIC TRANSFER SWITCH AVERAGE AMERICAN WIRE GAUGE BASEMENT CONDUIT(S) CIRCUIT BREAKER CEILING CLEANOUT COMPRESSOR CONDENSER CONDENSATE PUMP CONDENSING UNIT CABINET UNIT HEATER D DATA DC DIRECT CURRENT DEG or ° DEGREE DIA or ODIAMETER DN DWG EF EFF ELEC ELEV EM EM/NL ER ETP EUH EVAP EXP FA GA GAL GF GND H HC HDCP HP HR HTR HUM HV HVAC IN JB KVA KW L LF MAX MD MECH MFR MIN N/A NEC NIC NTS P PE PH/0 PNL QTY R RAF RE REF RL RM RTU S SCP SD SE SPEC SQ STD SW SWBD TSTAT TAG TEL TEMP TR TX TYP UH V V V VA VFC VIF VOL W WEF WI WP WTR DOWN DRAWING EXHAUST FAN EFFICIENCY ELECTRICAL ELEVATOR EMERGENCY EMERGENCY/NIGHT LIGHT WALK-THRU EQUIPMENT ROOM ELECTRIC TRAP PRIMER ELECTRIC UNIT HEATER EVAPORATOR EXPANSION FIRE ALARM GAUGE GALLONS GROUND FAULT GROUND HEIGHT HORIZONTAL CROSS -CONNECT HANDICAP HORSEPOWER HOUR(S) HEATER HUMIDIFIER HEATINGNENTILATION UNIT HEATING, VENTILATION AND AIR CONDITIONING INCHES JUNCTION BOX KILOVOLT AMPERE KILOWATT LENGTH LINEAR FEET MAXIMUM MOTORIZED DAMPER MECHANICAL MANUFACTURER MINIMUM NOT APPLICABLE NATIONAL. ELECTRICAL CODE NOT IN CONTRACT NOT TO SCALE POLE PRIMARY ELECTRIC SERVICE PHASE PANELBOARD QUANTITY RELAY. RETURN AIR FAN EXISTING EQUIPMENT TO BE DISCONNECTED AND REMOVED ROOF EXHAUST FAN EXISTING EQUIPMENT TO BE DISCONNECTED, REMOVED AND RELOCATED ROOM ROOF TOP UNIT SLEEVE(S) STEAM CONDENSATE PUMP SMOKE DAMPER SECONDARY ELECTRIC SERVICE SPECIFICATION SQUARE STANDARD SWITCH SWITCHBOARD THERMOSTAT IDENTIFICATION OF EQUIPMENT TELECOMMUNICATIONS SERVICE TEMPERATURE TELECOMMUNICATIONS ROOM TRANSFORMER TYPICAL UNIT HEATER VENT VOICE VOLTAGE VOLT AMPERE VARIABLE FREQUENCY CONTROLLER VERIFY IN FIELD VOLUME WATT WALL EXHAUST FAN WIDTH WEATHERPROOF WATER ELECTRICAL GENERAL NOTES GENERAL 1. THE PROJECT DRAWINGS AND SPECIFICATIONS ARE BASED ON THE CONSTRUCTION SPECIFICATIONS INSTITUTE (CSI) DOCUMENTATION FORMAT. SPECIFICATION AND DRAWING CONTENTS ARE ARRANGED BY TOPIC AND CATEGORY AND ARE NOT INTENDED TO AWARD DIVISION OF WORK. 2. THE INTENT OF THESE DOCUMENTS IS FOR THE MEP TRADES TO FURNISH AND. INSTALL AS REQUIRED FOR THE RENOVATION FOR COMPLETE MECHANICAL AND ELECTRICAL SYSTEMS.. THE SPECIFIED FIRE PROTECTION, PLUMBING, HVAC, ELECTRICAL AND SPECIAL SYSTEMS SHALL BE COMPLETE IN ALL RESPECTS; OPERATIONAL, TESTED, ADJUSTED, CALIBRATED, APPROVED BY THE AUTHORITIES HAVING JURISDICTION AND READY FOR BENEFICIAL USE BY THE OWNER. 3. UTILIZING THE DESIGN INTENT MODEL: THE CONTRACT DOCUMENTS ARE SOLELY A TWO DIMENSIONAL SET OF DOCUMENTS, IF UTILIZED, THE DESIGN INTENT MODEL HAS BEEN DEVELOPED TO A LEVEL OF DEVELOPMENT LOD 200 AND LOD 300 MODEL CONTENT REQUIREMENTS AS DEFINED BY ALA G-202-2013. THE DESIGN INTENT MODEL IS A THREE DIMENSIONAL TOOL UTILIZED TO CREATE A TWO DIMENSIONAL CONTRACT DOCUMENT. A TWO DIMENSIONAL CONTRACT DOCUMENT REQUIRES, FOR REASON OF CLARITY AND OTHERWISE, THAT COMPONENTS OF THE DESIGN NOT BE MODELED IN THREE DIMENSIONS AND/OR THAT THE MODEL BE FORMED IN A WAY THAT CONSTRUCTION MEANS AND METHODS WILL DICTATE OTHER WAYS OF PERFORMING THE INSTALLATION. THE DESIGN INTENT MODEL IS NOT A SUBSTITUTE FOR THE CONTRACTORS' COORDINATION PROCESS AS OUTLINED IN THE CONTRACT DOCUMENTS; FULL COORDINATION REMAINS THE RESPONSIBILITY OF THIS CONTRACTOR AND THEIR SUB -CONTRACTORS. THE CONTENTS OF THE MODEL ARE NOT TO BE USED FOR THE BASIS OF DETAILED COST ESTIMATING, COORDINATING EQUIPMENT LOCATIONS AND SYSTEMS ROUTING WITH ALL OTHER TRADES. THE CONTRACTOR MAY USE THE DESIGN INTENT MODEL TO HELP ESTABLISH THE BACKGROUNDS AND/OR STARTING POINT FOR THE. COORDINATION DRAWINGS BASED ON THE STIPULATIONS OF THE RELEASE FORM THAT CAN BE PROVIDED IF AND WHEN THE MODEL IS REQUESTED. 4. THE TRADES SHALL OBTAIN AND REVIEW ALL CONTRACT DOCUMENTS BEFORE SUBMITTING A BID. INFORMATION IS PROVIDED ON THE VARIOUS DRAWINGS, SCHEDULES, SPECIFICATIONS AND ALL OF THE VARIOUS DOCUMENTS IN THE BIDDING PACKAGE. THE CONTRACT DOCUMENTS ARE COMPLEMENTARY AND FORM A TOTAL PROJECT DESIGN AND INFORMATION SOURCE FOR CONSTRUCTION PURPOSES. 5. THE DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS AND WORK INCLUDED IN THE CONTRACT. COORDINATE LOCATIONS OF EQUIPMENT WITH OTHER TRADES BEFORE AND DURING CONSTRUCTION. ANY MODIFICATION. TO THE EQUIPMENT LAYOUT, REQUIRED FOR INSTALLATION, IS TO BE PERFORMED UNDER THE CONTRACT AGREEMENT, AT NO ADDITIONAL COST. 6. PERFORM ALL WORK IN COMPLIANCE WITH THE SPECIFICATIONS, APPLICABLE CODES, ORDINANCES AND THE REGULATORY AGENCIES HAVING JURISDICTION. THE SPECIFICATIONS MAY EXCEED THE REQUIREMENTS OF THE CODE, IN WHICH CASE, THE SPECIFICATION MUST BE FOLLOWED. . 7. INSTALL ALL EQUIPMENT IN ACCESSIBLE LOCATIONS. WHERE EQUIPMENT MUST BE INSTALLED ABOVE AN INACCESSIBLE CEILING OR BEHIND A WALL, AN APPROPRIATE ACCESS DOOR SHALL BE PROVIDED AND THE LOCATION SHALL BE COORDINATED WITH THE ARCHITECT. 8. WHERE A CONFLICT OCCURS BETWEEN THE DOCUMENTS, IT SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT. CARRY AS PART OF THE BID THE LARGER QUANTITY AND/OR MORE EXPENSIVE ITEM(S). 9. PROVIDE THE REQUIRED/SPECIFIED SLEEVES AND SEALS FOR PIPES OR CONDUIT PENETRATING INTERIOR AND EXTERIOR WALLS OR FLOOR SLABS, 10. PROVIDE MEP COORDINATION DRAWINGS AS REQUIRED BY THE SPECIFICATIONS. 11. PROVIDE PIPING, DUCTWORK, CONDUIT AND ALL OTHER ACCESSORIES AS REQUIRED FOR PROPER AND PROFESSIONAL SYSTEMS INSTALLATION. 12. TEST AND BALANCE ELECTRICAL SYSTEMS. PROVIDE ADDITIONAL TESTS AS REQUIRED BY THE SPECIFICATIONS. 13. DO NOT INSTALL PIPING OR DUCTWORK OVER ELECTRICAL PANELS, TRANSFORMERS, SPECIAL EQUIPMENT, ELEVATOR MACHINE ROOMS OR SHAFTS. 14. DO NOT INSTALL ANY SYSTEMS IN OR THROUGH ELEVATOR MACHINE ROOMS THAT DO NOT SERVE THE ROOM. MAINTAIN A MINIMUM OF SEVEN (7) FOOT HEAD CLEARANCE IN THE ELEVATOR MACHINE ROOM. 15. DO NOT INSTALL IN STAIRWELL OR STAIRWELL WALLS, PIPING, DUCTWORK, CONDUIT OR OTHER DEVICES OR EQUIPMENT NOT ASSOCIATED WITH OR SERVING THE RESPECTIVE STAIR. 16. PROVIDE PIPE EXPANSION COMPENSATION FOR THE VARIOUS PIPING SYSTEMS. SUBMIT ENGINEERED DETAILS FOR APPROVAL AND VERIFY INSTALLATION IS IN ACCORDANCE WITH CODE. THE CONTRACTOR'S CONSULTING ENGINEER SHALL REVIEW THE INSTALLATION AND PROVIDE A REPORT OF THE FINDINGS. 17, PROVIDE ADDITIONAL TRANSITIONS AND OFFSETS IN ALL PIPING, DUCTWORK OR CONDUIT FOR COORDINATION WITH BUILDING STRUCTURE AND CONSTRUCTION. 18. NO MECHANICAL OR ELECTRICAL SYSTEM COMPONENTS MAY BE SUPPORTED FROM STRUCTURAL BRACED FRAMES. RENOVATION 1. THIS PROJECT INVOLVES THE RENOVATION OF AN EXISTING FACILITY; BEFORE SUBMITTING THE BID, CONTRACTORS SHALL VISIT THE SITE AND BECOME THOROUGHLY FAMILIAR WITH THE EXISTING CONDITIONS UNDER WHICH THE PROJECT IS TO BE COMPLETED. 2. CONTRACTORS SHALL BE HELD RESPONSIBLE FOR ASSUMPTIONS, OMISSIONS OR ERRORS MADE AS A RESULT OF FAILURE TO BECOME FULLY FAMILIAR WITH THE EXISTING CONDITIONS. 3. IT IS NOT THE INTENT OF THESE DOCUMENTS TO SHOW EVERY DEVICE, APPURTENANCE, PIPE, WIRE OR CONDUIT TO BE REMOVED. MEP EQUIPMENT, UNITS, AND SYSTEMS NOT BEING REUSED, SHALL BE REMOVED IN THEIR ENTIRETY INCLUDING ASSOCIATED HANGERS, SUPPORTS, BASES, PADS, PIPES, DUCTS, CONDUITS, WIRES, INSULATION, AND CONTROLS BACK TO THE POINT OF ORIGIN. 4. EQUIPMENT, PIPING, OR CONDUIT SHALL NOT BE ABANDONED IN -PLACE UNLESS SPECIFICALLY SO NOTED. 5. PROPERLY DISPOSE OF DEMOLISHED EQUIPMENT IN COMPLIANCE WITH CODES, REGULATIONS, AND DEEP STANDARDS. TURN OVER TO THE OWNER EQUIPMENT SO INDICATED. 6. RELOCATE EXISTING EQUIPMENT, DEVICES, PIPING, WIRING, AND RELATED SYSTEMS AS REQUIRED FOR CONSTRUCTION PURPOSES. ALL EXISTING SYSTEMS SHALL BE FULLY OPERATIONAL, INCLUDING RECONNECTION TO SERVICES AND UPGRADED SYSTEMS. ALL RELOCATED EQUIPMENT SHALL BE PROTECTED DURING CONSTRUCTION, 7, PROVIDE TEMPORARY CONNECTIONS AND SYSTEM MODIFICATIONS AS REQUIRED FOR CONSTRUCTION AND PHASING PURPOSES. 8. INCLUDE ALL WORK REQUIRED TO ALLOW PHASED CONSTRUCTION WHEN NECESSARY, COORDINATE WITH GENERAL CONTRACTORICONSTRUCTION MANAGER FOR PHASING REQUIREMENTS. 9. ALL EXISTING EQUIPMENT, FIXTURES, AND DEVICES TO BE REMOVED AND RELOCATED SHALL BE FIELD VERIFIED FOR EXACT QUANTITY AND CONDITION. KEEP AN ACCURATE RECORD OF STORED EQUIPMENT AND ITS CONDITION. 10, REBALANCE NEW AND EXISTING MECHANICAL AND ELECTRICAL SYSTEMS ASSOCIATED WITH THE RENOVATION, INCLUDING RENOVATED AREAS AND AREAS AFFECTED BY SYSTEM MODIFICATIONS. 11. SYSTEMS REQUIRING TO REMAIN IN OPERATION SHALL BE CAREFULLY PROTECTED FROM DAMAGE AND CONTAMINATION BY THE CONSTRUCTION PROCESS. ELECTRICAL 1. IT IS NOT THE INTENTION TO SHOW EVERY FITTING, WIRE, OR DEVICE. ALL SUCH ITEMS SHALL BE FURNISHED AND INSTALLED AS NECESSARY FOR A COMPLETE SYSTEM. 2. UNLESS OTHERWISE NOTED, CONCEAL RACEWAYS IN FINISHED AREAS. RACEWAYS WITHIN MECHANICAL AND ELECTRICAL ROOMS MAY BE SURFACE -MOUNTED. 3. PROVIDE POWER TO MECHANICAL EQUIPMENT SHOWN ON PLANS, RISERS, SCHEDULES, OR IN SPECIFICATIONS. MECHANICAL EQUIPMENT IS NOT NECESSARILY SHOWN ON ELECTRICAL PLANS. REFER TO MECHANICAL PLANS AND SCHEDULES ON MEP DRAWINGS FOR LOCATIONS AND SPECIFIC ELECTRICAL REQUIREMENTS. COORDINATE EXACT LOCATION AND ORIENTATION OF EQUIPMENT WITH. OTHER TRADES. 4. PROVIDE INTERFACE CONNECTIONS TO THE FIRE ALARM SYSTEM AND FIRE PROTECTION SYSTEM EQUIPMENT SHOWN ON PLANS, SCHEDULES, RISERS, OR IN SPECIFICATIONS. THIS EQUIPMENT IS NOT NECESSARILY SHOWN ON ELECTRICAL PLANS. COORDINATE EXACT LOCATION AND QUANTITY WITH THE FIRE PROTECTION CONTRACTOR. 5. PROVIDE BRANCH CIRCUITS FROM ELECTRICAL PANELS WITH SUFFICIENT CAPACITY AND SPACE FOR MISCELLANEOUS SYSTEMS. FURNISH AND INSTALL ALL BRANCH CIRCUIT WIRING AND CIRCUIT BREAKERS FOR THE EQUIPMENT SHOWN, CODES LISTED BELOW APPLY TO ALL DRAWINGS AND SPECIFICATIONS ON THIS PROJECT • MASSACHUSETTS STATE BUILDING CODE, 780 CMR - NINTH EDITION • THE FOLLOWING AS REFERENCED AND MODIFIED BY THE ABOVE CODE: 0 2015 INTERNATIONAL BUILDING CODE (IBC) WITH MASSACHUSETTS AMENDMENTS PER 780 CMR 0 780 CMR 9.00 - FIRE PROTECTION SYSTEMS • 527 CMR BOARD OF FIRE PREVENTION REGULATIONS • 2012 NFPA 1 - CURRENTLY ADOPTED MA STATE MODEL CODE • MASSACHUSETTS GENERAL LAW. CHAPTER 148 - FIRE PREVENTION - SECTION 26 0 780 CMR 13.00 - ENERGY EFFICIENCY AMENDMENTS • 2015 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) • 2013 ANSI/ASHRAE/IESNA STANDARD 90.1 - ENERGY STANDARD FOR BUILDINGS EXCEPT LOW-RISE RESIDENTIAL BUILDINGS 0 780 CMR CHAPTER 27.00 - ELECTRICAL • 527 CMR CHAPTER 12 - MASSACHUSETTS ELECTRICAL CODE (AMENDMENTS) • 527 CMR CHAPTER 27 - EMERGENCY AND STANDBY POWER SYSTEMS • 2017 NFPA 70 - NATIONAL ELECTRICAL CODE (NEC) • NFPA 110 - 2013 0 780 CMR 28,00 - MECHANICAL SYSTEMS 2015 INTERNATIONAL MECHANICAL CODE (IMC) • 271 CMR 6.00 - UNIFORM SHEET METAL INSTALLATION RULES 0 780 CMR 29.00 - PLUMBING SYSTEMS • 248 CMR CHAPTER 10 - MASSACHUSETTS UNIFORM STATE PLUMBING CODE 0 780 CMR 30.00 - ELEVATOR AND CONVEYING SYSTEMS • 524 CMR - BOARD OF ELEVATOR REGULATIONS • 2013 ASME A17.1 SAFETY CODE FOR ELEVATORS AND ESCALATORS 0 ACCESSIBILITY • 521 CMR - MASSACHUSETTS ARCHITECTURAL ACCESS BOARD REGULATIONS • MASSACHUSETTS GENERAL LAWS CHAPTER 22 • 2009 ICC/ANSI A117,1 - GUIDELINES FOR ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES * THE JOINT COMMISSION • THE AMERICANS WITH DISABILITY ACT, TITLE II, INCLUDING THE AMERICANS WITH DISABILITIES ACT ACCESSIBILITY GUIDELINES (ADAAG) AND ADA REGULATIONS • OCCUPATIONAL SAFETY AND HEALTH ACT, TITLE 29/LABOR • GENERAL LAWS OF MASSACHUSETTS GENERAL SYMBOLS THICK, DARKSOLID LINES INDICATE NEW OR RELOCATED ITEMS OR NEW RACEWAY AND WIRING THIN, LIGHT LINES INDICATE EXISTING ITEMS OR RACEWAY TO REMAIN IN PLACE AND BE REUSED THICK, DASHED LINES INDICATE EXISTING ITEMS TO BE REMOVED POINT OF NEW TO EXISTING CONNECTION, INCLUDING TRANSITIONS SUB LETTERS "EX" INDICATES EXISTING EQUIPMENT TO REMAIN INTACT SUB LETTER "RE" INDICATES EXISTING EQUIPMENT TO BE DISCONNECTED AND REMOVED SUB LETTER "RL" INDICATES EXISTING EQUIPMENT TO BE DISCONNECTED, REMOVED AND RELOCATED SUB LETTER."NL" INDICATES NEW LOCATION OF RELOCATED EQUIPMENT SUB LETTER "NR" INDICATES NEW EQUIPMENT TO REPLACE EXISTING SUB LETTER "RR" INDICATES REMOVE EQUIPMENT AND REPLACE ON NEW SURFACE * = a, b, clg, AF, GF IG OR TP. WHEN TAGGED IN THE ELECTRICAL SYMBOL LIST, REFER TO THE ABBREVIATION LIST - -�-� -- - EX RE RL NL NR RR * ELECTRICAL SYMBOLS LINEAR LIGHT FIXTURE RECESSED DOWNLIGHT FIXTURE CEILING OR WALL -MOUNTED EXIT LIGHT FIXTURE CEILING OR WALL -MOUNTED EMERGENCY LIGHT UNIT SINGLE -POLE SWITCH 3-WAY SWITCH 4-WAY SWITCH POWER WIRING - PANEL DESIGNATION 20A-1P HOME RUN (TYPICAL) 0 D 41 ® 1 S 3 S 4 S LV-1 a HOME RUN FEEDER TAG SURFACEPANEL, 480Y/277OR ELECTRICAL480 OLT V SURFACE208Y/120OR ELECTRICAL208 VOLT PANEL, FLUSH ELECTRICAL PANEL, 480Y/277 VOLT FLUSH ELECTRICAL PANEL, 208Y/120 VOLT ELECTRIC MOTOR JUNCTION BOX MASTER FIRE ALARM PULL BOX FIRE ALARM CONTROL PANEL FIRE ALARM REMOTE ANNUNCIATOR SMOKE DETECTOR COMBINATION SMOKE/CARBON MONOXIDE DETECTR HEAT DETECTOR REMOTE INDICATOR FIRE ALARM MANUAL PULL STATION FIRE ALARM SPEAKER / STROBE FIRE ALARM STROBE FIRE ALARM CEILING -MOUNTED SPEAKER MAGNETIC DOOR HOLD [Nj.G) ram,,..........__ i _...A_ >_.__itanm..._..............1 i i /CY Q u [ANNJ SjCO fl RI ��0F Ell El Q iI Office of Planning Design and Construction McCormack Building One Ashburton Place Boston MA 02108 617 727 4050 www.mass.govlcam Project Name: SALEM SUPERIOR COURT & COUNTY COMMISSIONER BUILDINGS WARM MOTHBALLING DCAMM Project Number DCP1726 FC1 Project Location 32-34 FEDERAL ST, SALEM, MA 01970 Project Archilecl PERRY DEAN ROGERS PARTNERS 177 MILK STREET BOSTON, MA 02109 T. 617-423-0100 F. 617-426-2274 www. perrydean.com Project Consultant A Iltsl. 12il li Wart 417 kvIll integrated services One Gateway Center, Suite 701 Newton, MA 02458 Tel: (617) 658-9008 www,bvhis.com Professional Stamp Site Number: CAMIS Number: Building Number: Secretariat: Original Issue Date 01/26/2018 BID DOCUMENTS Revisions Plan Name: ELECTRICAL NOTES, SYMBOLS AND ABBREVIATIONS Drawing Number: EOOO MAIN ELECTRICAL ROOM GENERAL NOTES 1. COORDINATE EXACT LOCATIONS OF NEW SMOKE DETECTORS WITH ARCHITECT AND FIRE DEPARTMENT PRIOR TO ROUGH -IN. VERIFY NEW SMOKE COVERAGE IS ADEQUATE WITH FIRE DEPARTMENT. DRAWING. NOTES EXACT LOCATION OF ELEV. AND WHEELCHAIR LIFT DISCONNECT SWITCHES SHALL BE VERIFIED INFIELD, SWITCHES SHALL BE PLACED IN THE OFF POSITION AND SECURED WITH PADLOCK. KEY SHALL BE LABELED AND HANDED OVER TO OWNER'S REPRESENTATIVE. 0 (7) EX DPB BOILER CONTROL PANEL PROVIDE 20A,120V, 2#12&1#12GND -3/4"C FEEDER FROM 20A/1P SPARE C/B IN NEAREST 208/120V PANELBOARD. NEW EXHAUST UNIT EX LB 7! V,14 V) ••; (T POWER -BASEMENT \71-09) 1/8" = 1.-0" ii ) 0 " H • ETT J EX ki EX III LB-1 PPM. EX 0 EX H f 1 EX / FOR INTRUSION / CONTROL PANEL. COORD. EXACT LOCATION WITH SECURITY VENDOR. EXISTING WHEELCHAIR DISCONNECT SWITCH IS MM. BELOW STAIRCASE. 1 EX ._i— 1 1 1 1 t _1 1 . 0 H \ EX__ E EX X AH EX APPROXIMATE PATHWAY OF NEW CONDUIT. COORDINATE IN FIELD WITH CONTRACTOR (TYPICAL). 111 NEW EXHAUST UNIT NEW EXHAUST UNIT iF II7 1.:,1 C.; NEW EXHAUST UNIT EX EX L 0 to x EX EX ELEVATOR DISCONNECT SWITCH I 0 1 EX I l!,/-1111-u EX EX EX EX 2. ALL NEW SMOKE DETECTORS SHALL BE COMPATIBLE WITH EXISTING BUILDING'S FIRE ALARM CONTROL PANEL, ALL NEW INITIATION DEVICES SHALL BE WIRED BACK TO EXISTING CONTROL PANEL. EXTEND EXISTING WIRING AS NECESSARY TO ACCOMMODATE RENOVATION. PANEL ZONING SHALL ALSO BE EXTENDED AS NEEDED TO PROVIDE CAPACITY FOR NEW DEVICES. COORDINATE WITH FIRE ALARM MANUFACTURER. 3, ALL CONDUIT PATHWAYS SHOWN ARE IN LOCATIONS WHERE ABATEMENT IS NECESSARY. COORDINATE NEW ELECTRICAL AND/OR FIRE ALARM CONDUIT ROUTING IN FIELD WITH ASBESTOS REMOVAL CONTRACTOR, UNLESS OTHERWISE INDICATED ON PLANS, CONDUIT SHALL BE MOUNTED ON WOOD STRAPPING. CONDUIT MOUNTING AND WOOD STRAPPING INSTALLATION SHALL BE COORDINATE WITH ARCHITECT/CONTRACTOR PRIOR TO INSTALLATION. IF CONDUIT ROUTING NOT INDICATEDON PLANS, EXTEND EXISTING CONDUIT TO SERVE NEW DEVICES. 4. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING LOCATION AND QUANTITY OF ALL EXISTING PANELBOARDS. 5. ELECTRICAL CONTRACTOR SHALL TRACE ALL BRANCH CIRCUITS IN ALL EXISTING PANELBOARDS. 6, CONTRACTOR SHALL PLACE IN THE OFF POSITION ALL EXITING C/B'S SERVING RECEPTACLES AND NON -ESSENTIAL LIGHTING (ANY CIRCUITS THAT DO NOT SERVE LIGHT FIXTURES IN THE MAIN CORRIDORS INDICATED ON FLOOR PLANS). 7. ELECTRICAL CONTRACTOR SHALL PLACE IN THE OFF POSITION ALL EXISTING C/B'S THAT SERVE HVAC EQUIPMENT NOT PART OF THE HEATING SYSTEM. VERIFY WITH MECHANICAL CONTRACTOR ALL HVAC EQUIPMENT THAT SHALL REMAIN IN USE. EX FX ELC-B LC-B DPC 0 EX rm • EX EX 1_1 EX EX EX \ EX [1 0 EX EX 00 EX F. L EXA ( 0 EF-1 I CONTROL PANEL NEW EXHAUST UNIT "EX FIRE ALARM NEW EXHAUST EX UNIT --lI - 0 ALL LIGHT FIXTURES, BATTERY LIGHT. UNITS, EXIT SIGNS, FIRE ALARM DEVICES, AND ASSOCIATED WIRING AND RACEWAY WITHIN THE AREA SHALL REMAIN AS. IS UNLESS OTHERWISE INIDICATED. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR TRACING CIRCUITS BACK TO SOURCE. CIRCUIT BREAKERS SERVING THE ABOVE ITEMS SHALL BE LEFT IN THE ON POSITION AND CLEARLY LABELED AS LIGHTING CIRCUIT. PROVIDE 30A-1P C/B IN NEAREST PANELBOARD. C/B SHALL SERVE NEW EXHAUST FAN VIA 2#10 & 1#10 GND IN 3/4" CONDUIT. PROVIDE 25A FUSED DISCONNECT SWITCH. ELEC. CONTRACTOR SHALL UTILIZE SPARE SPACE WITHIN THE PANELBOARD. IF NO SPACE AVAILABLE, DISCONNECT AND REMOVE ANY C/E3'S (SERVING EXISTING RECEPTACLES) THAT WERE PLACED IN THE OFF POSITION. PROVIDE MOTOR CONTROLLERSAND/OR COMBINATION DISCONNECT/MOTOR CONTROLLER AS REQUIRED (COORDINATE WITH MECH. CONTRACTOR AND MANUFACTURER). ALL CONDUIT PATHS SHALL BE COORDINATED WITH EXISTING CONDITIONS AND ABATEMENT CONSULTANT/CONTRACTOR PRIOR TO ROUGH -IN. PROVIDE 20A-1P C/B IN NEAREST PANELBOARD. C/B SHALL SERVE NEW MOTORIZED DAMPER VIA 2#12 & 1#12 GND - 3/4" CONDUIT. PROVIDE OVERCURRENT PROTECTION SWITCH. ELEC. CONTRACTOR SHALL UTILIZE SPARE SPACE WITHIN THE PANELBOARD. IF NO SPACE AVAILABLE, DISCONNECT AND UTILIZE A C/B(SERVING EXISTING RECEPTACLES) THAT WAS PLACED IN THE OFF POSITION. PROVIDE MOTOR. CONTROLLERS AS REQUIRED(COORDINATE WITH MECH. CONTRACTOR AND MANUFACTURER). ALL CONDUIT PATHS SHALL BE COORDINATED WITH. EXISTING CONDITIONS AND ABATEMENT CONSULTANT/CONTRACTOR PRIOR TO ROUGH -IN. NEW. SMOKE.DETECTOR TO REPLACE EXISTING DEVICE UTILIZE EXISTING JUNCTION BOX; CONDUIT, AND ASSOCIATED WIRING FOR NEW DETECTOR. EXTEND. EXISTING WIRING AS NECESSARY TO ACCOMMODATE • REPLACEMENT. • • • NEW LIGHT SWITCH(ES) TO CONTROL ALL EXISTING LIGHT FIXTURES AS INDICATED IN DESIGNATED PER FLOOR. SWITCH(ES) SHALL BE INSTALLED TO HAVE BASIC ON/OFF CONTROL TO ALLOW SERVICE, SECURITY, POLICE, AND/OR SFD PERSONNEL TO EASILY SWITCH ON/OFF BUILDING LIGHTS. COORDINATE EXACT LOCATION OF SWITCHES WITH ARCHITECT AND FIRE DEPARTMENT PRIOR TO INSTALLATION. EXTEND EXISTING BRANCH CIRCUIT WIRING AND CONDUIT AND DISCONNECT ALL OTHER. EXISTING CONTROLS AS NECESSARY TO ACCOMODATE NEW. SWITCHING SCHEME. CONTRACTOR SHALL FIELD VERIFY COUNT AND LOAD OF EXISTING BRANCH CIRCUITS FOR QUANTITY OF SWITCHES (SHOWN ON DWGS AS LOCATION REFERENCE ONLY). CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING WIRING AND CONDUIT TO ACCOMODATE ANY VOLTAGE DROP TO THE NEW SWITCH. ALL CONDUIT PATHS AND BACK BOXES SHALL BE COORDINATED WITH EXISTING CONDITIONS AND ABATEMENT CONSULTANT/CONTRACTOR PRIOR TO ROUGH -IN. (B.00.: CONTRACTOR TO CARRY COST FOR FOUR BRANCH CIRCUITS AND EACH CIRCUIT WITH (3)THREE WAY SWITCHES PER FLOOR). Office of Planning Design and Construction McCormack Building One Ashburton Place Boston MA 02108 617 727 4050 vvvvw.mass.govicam Project Name: SALEM SUPERIOR COURT & COUNTY COMMISSIONER BUILDINGS WARM MOTHBALLING DCAMM Project Number DCP1726 FC1 Project Location 32-34 FEDERAL ST, SALEM, MA 01970 Project Architect PERRY DEAN ROGERS PARTNERS 177. MILK STREET BOSTON, MA 02109 T. 617-423-0100 F. 617-426-2274 www.perrydean.com Project Consultant • ENHI integrated services One Gateway Center, Suite 701 Newton, MA 02458 Tel: (617) 658-9008 www.bvhis.com ( Professional Stamp Site Number: CAMIS Number: Building Number: Secretariat: Original Issue Date 01/26/2018 BID DOCUMENTS Revisions Plan Name: BASEMENT ELECTRICAL POWER PLAN Drawing Number: EPI -00 GENERAL NOTES DRAWING NOTES NEW EXHAUST UNIT APPROXIMATE PATHWAY OF NEW CONDUIT. COORDINATE IN FIELD WITH CONTRACTOR (TYPICAL). EXISTING TO REMAIN KNOX BOX __W. POWER -LEVEL 1 118" = 1'-0" 0 I-- 1 EX EX ALL CONDUIT WITHIN THIS CORRIDOR SHALL BE MOUNTED ON BRICK WALL NEW EXHAUST UNIT NEW EXHAUST UNIT NEW EXHAUST UNIT 1 COORDINATE EXACT LOCATIONS OF NEW SMOKE DETECTORS WITH ARCHITECT AND FIRE DEPARTMENT PRIOR TO ROUGH -IN. VERIFY NEW SMOKE COVERAGE IS ADEQUATE WITH FIRE DEPARTMENT, 2. ALL NEW SMOKE DETECTORS SHALL BE COMPATIBLE WITH EXISTING BUILDING'S FIRE ALARM CONTROL PANEL. ALL NEW INITIATION DEVICES SHALL BE WIRED BACK TO EXISTING CONTROL PANEL. EXTEND EXISTING WIRING AS NECESSARY TO ACCOMMODATE RENOVATION. PANEL ZONING SHALL ALSO BE EXTENDED AS NEEDED TO PROVIDE CAPACITY FOR NEW DEVICES. COORDINATE WITH FIRE ALARM MANUFACTURER. 3. ALL CONDUIT PATHWAYS SHOWN ARE IN LOCATIONS WHERE ABATEMENT IS NECESSARY. COORDINATE NEW ELECTRICAL AND/OR FIRE ALARM CONDUIT ROUTING IN FIELD WITH ASBESTOS REMOVAL CONTRACTOR. UNLESS OTHERWISE INDICATED ON PLANS, CONDUIT SHALL BE MOUNTED ON WOOD STRAPPING. CONDUIT MOUNTING AND WOOD STRAPPING INSTALLATION SHALL BE COORDINATE WITH ARCHITECT/CONTRACTOR PRIOR TO INSTALLATION, IF CONDUIT ROUTING NOT INDICATEDON PLANS, EXTEND EXISTING CONDUIT TO SERVE NEW DEVICES. . 4. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING LOCATION AND QUANTITY OF ALL EXISTING PANELBOARDS. 5. ELECTRICAL CONTRACTOR SHALL TRACE ALL BRANCH CIRCUITS IN ALL EXISTING PANELBOARDS. 6. CONTRACTOR SHALL PLACE IN THE OFF POSITION ALL EXITING C/B'S SERVING RECEPTACLES AND NON -ESSENTIAL LIGHTING (ANY CIRCUITS THAT DO NOT SERVE LIGHT FIXTURES IN THE MAIN CORRIDORS INDICATED ON FLOOR PLANS). 7. ELECTRICAL CONTRACTOR SHALL PLACE IN THE OFF POSITION ALL EXISTING C/B'S THAT SERVE HVAC EQUIPMENT NOT PART OF THE HEATING SYSTEM. VERIFY WITH MECHANICAL CONTRACTOR ALL HVAC EQUIPMENT THAT SHALL REMAIN IN USE. , NEW EXHAUST UNIT NEW EXHAUST UNIT EXACT LOCATION OF ELEV. AND WHEELCHAIR LIFT DISCONNECT SWITCHES SHALL BE VERIFIED IN FIELD. SWITCHES SHALL BE PLACED IN THE OFF POSITION AND SECURED WITH PADLOCK KEY SHALL BE LABELED AND HANDED OVER TO OWNERS REPRESENTATIVE. ALL LIGHT FIXTURES, BATTERY LIGHT UNITS, EXIT SIGNS, FIRE ALARM DEVICES, AND ASSOCIATED WIRING AND RACEWAY WITHIN THE AREA SHALL REMAIN AS IS UNLESS OTHERWISE INDICATED. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR TRACING CIRCUITS BACK TO SOURCE. CIRCUIT BREAKERS: SERVING THE ABOVE ITEMS SHALL BE LEFT IN THE ON POSITION AND CLEARLY LABELED AS LIGHTING CIRCUIT. PROVIDE 30A-1 P C/B IN. NEAREST PANELBOARD. C/B SHALL SERVE NEW EXHAUST FAN VIA 2#1O & 1#1O GND IN 3/4" CONDUIT. PROVIDE 25A FUSED DISCONNECT SWITCH.. ELEC. CONTRACTOR SHALL UTILIZE SPARE SPACE WITHIN THE PANELBOARD. IF NO SPACE AVAILABLE, DISCONNECT AND REMOVE ANY C/B'S (SERVING EXISTING RECEPTACLES) THAT WERE PLACED IN THE OFF POSITION. PROVIDE MOTOR CONTROLLERS AND/OR COMBINATION DISCONNECT/MOTOR CONTROLLER AS REQUIRED (COORDINATE WITH MECH. CONTRACTOR AND MANUFACTURER). ALL CONDUIT PATHS SHALL BE COORDINATED WITH EXISTING CONDITIONS AND ABATEMENT CONSULTANT/CONTRACTOR PRIOR TO ROUGH -IN. PROVIDE 20A-1P C/B IN NEAREST PANELBOARD. C/B SHALL SERVE NEW MOTORIZED DAMPER VIA 2#12 & 1#12 GND - 3/4" CONDUIT. PROVIDE OVERCURRENT PROTECTION SWITCH. ELEC. CONTRACTOR SHALL UTILIZE SPARE SPACE WITHIN THE PANELBOARD. IF NO SPACE AVAILABLE, DISCONNECT AND UTILIZE A C/B(SERVING EXISTING RECEPTACLES) THAT WAS PLACED IN THE OFF POSITION. PROVIDE MOTOR CONTROLLERS AS REQUIRED(COORDINATE WITH MECH. CONTRACTOR AND MANUFACTURER). ALL CONDUIT PATHS SHALL BE COORDINATED WITH EXISTING CONDITIONS AND ABATEMENT CONSULTANT/CONTRACTOR PRIOR TO ROUGH -IN. NEW SMOKE DETECTOR TO REPLACE EXISTING DEVICE. UTILIZE EXISTING JUNCTION BOX, CONDUIT, AND ASSOCIATED WIRING FOR NEW DETECTOR. EXTEND EXISTING WIRING AS NECESSARY TO ACCOMMODATE REPLACEMENT. NEW LIGHT SWITCH(ES) TO CONTROL ALL EXISTING LIGHT FIXTURES AS INDICATED IN DESIGNATED PER FLOOR. SWITCH(ES) SHALL BE INSTALLED TO HAVE BASIC ON/OFF CONTROL TO ALLOW. SERVICE, SECURITY, POLICE, AND/OR SFD PERSONNEL TO EASILY SWITCH ON/OFF BUILDING LIGHTS. COORDINATE EXACT LOCATION OF SWITCHES WITH ARCHITECT AND FIRE DEPARTMENT PRIOR TO INSTALLATION. EXTEND EXISTING BRANCH CIRCUIT WIRING AND CONDUIT AND DISCONNECT ALL OTHER EXISTING CONTROLS AS NECESSARY TO ACCOMODATE NEW SWITCHING SCHEME. CONTRACTOR SHALL FIELD VERIFY COUNT AND LOAD OF EXISTING BRANCH CIRCUITS FOR QUANTITY OF SWITCHES (SHOWN ON DWGS:AS LOCATION REFERENCE ONLY). CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING WIRING AND CONDUIT TO ACCOMODATE ANY VOLTAGE DROP TO THE NEW SWITCH. ALL CONDUIT PATHS AND BACK BOXES SHALL BE COORDINATED WITH EXISTING CONDITIONS AND ABATEMENT CONSULTANT/CONTRACTOR PRIOR TO ROUGH -IN, (B.O.D.: CONTRACTOR TO CARRY COST FOR FOUR BRANCH CIRCUITS AND EACH CIRCUIT WITH (3)THREE WAY SWITCHES PER FLOOR). Office of Planning Design and Construction McCormack Building One Ashburton Place Boston MA 02108 617 727 4050 wwvv.mass.gov/cam Project Name: SALEM SUPERIOR COURT & COUNTY COMMISSIONER BUILDINGS WARM MOTHBALLING DCAMM Project Number DCP1726 FC7 Project Location 32-34 FEDERAL ST, SALEM, MA 01970 Project Architect PERRY DEAN ROGERS PARTNERS 177 MILK STREET BOSTON, MA 02109 T. 617-423-0100 F. 617-426-2274 www.perrydean.com Project Consultant 17 ;II 1117 Elli1H1 integrated services One Gateway Center, Suite 701 Newton, MA 02458 Tel: (617) 658-9008 www.bvhis.Com Professional Stamp J Site Number: CAMIS Number: Building Number: Secretariat: Original Issue Date 01/26/2018 BID DOCUMENTS Revisions Plan Name: LEVEL 'l ELECTRICAL POWER PLAN Drawing Number: EPIOl GENERAL NOTES DRAWING. NOTES NEW EXHAUST UNIT POWER -LEVEL 2 -- 1/8" = 1 t-Or' -.. EX EF-1 NEW EXHAUST UNIT 4 L L- I o-t 1 4 EX APPROXIMATE PATHWAY OF NEW CONDUIT. COORDINATE IN FIELD (TYPICAL). NEW EXHAUST UNIT J EX EX Ho r --- EX EX'‘, EEC EX LC-2 AC-1 1. COORDINATE EXACT LOCATIONS OF NEW SMOKE DETECTORS WITH ARCHITECT AND. FIRE DEPARTMENT PRIOR TO ROUGH -IN. VERIFY NEW SMOKE COVERAGE IS ADEQUATE WITH FIRE DEPARTMENT. 2. ALL NEW SMOKE DETECTORS SHALL BE COMPATIBLE WITH EXISTING BUILDING'S FIRE ALARM CONTROL PANEL ALL NEW INITIATION DEVICES SHALL BE WIRED BACK TO EXISTING CONTROL PANEL. EXTEND EXISTING WIRING AS NECESSARY TO ACCOMMODATE RENOVATION. PANEL ZONING SHALL ALSO BE EXTENDED AS NEEDED TO PROVIDE CAPACITY FOR NEW DEVICES. COORDINATE WITH FIRE ALARM MANUFACTURER. 3. ALL CONDUIT PATHWAYS SHOWN ARE IN LOCATIONS WHERE ABATEMENT IS NECESSARY. COORDINATE NEW ELECTRICAL AND/OR FIRE ALARM CONDUIT ROUTING IN FIELD WITH ASBESTOS REMOVAL CONTRACTOR. UNLESS OTHERWISE INDICATED ON PLANS, CONDUIT SHALL BE MOUNTED ON. WOOD STRAPPING. CONDUIT MOUNTING AND WOOD STRAPPING INSTALLATION SHALL BE: COORDINATE WITH ARCHITECT/CONTRACTOR PRIOR TO INSTALLATION. IF CONDUIT ROUTING NOT INDICATEDON PLANS, EXTEND EXISTING CONDUIT TO SERVE NEW DEVICES. 4, ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING LOCATION AND QUANTITY OF ALL EXISTING PANELBOARDS. 5. ELECTRICAL CONTRACTOR SHALL TRACE ALL BRANCH CIRCUITS IN ALL EXISTING PANELBOARDS, 6. CONTRACTOR SHALL PLACE IN THE OFF POSITION ALL EXITING C/B'S SERVING RECEPTACLES AND NON -ESSENTIAL LIGHTING (ANY CIRCUITS THAT DO NOT SERVE LIGHT FIXTURES IN THE MAIN CORRIDORS INDICATED ON FLOOR PLANS). 7. ELECTRICAL CONTRACTOR SHALL PLACE IN THE OFF POSITION ALL EXISTING C/B'S THAT SERVE HVAC EQUIPMENT NOT PART OF THE HEATING SYSTEM, VERIFY WITH MECHANICAL CONTRACTOR ALL HVAC EQUIPMENT THAT SHALL REMAIN IN USE. l—, EX NEW EXHAUST UNIT NEW EXHAUST UNIT [[] EX 1 0 0 EXACT LOCATION OF ELEV. AND WHEELCHAIR LIFT DISCONNECT SWITCHES SHALL BE VERIFIED IN FIELD. SWITCHES SHALL BE PLACED IN THE OFF POSITION AND SECURED WITH PADLOCK.. KEY SHALL BE LABELED AND HANDED OVER TO OWNER'S REPRESENTATIVE: ALL LIGHT FIXTURES,BATTERY LIGHT UNITS, EXIT SIGNS, FIRE ALARM DEVICES, AND ASSOCIATED WIRING AND RACEWAY WITHIN THE AREA SHALL REMAIN AS IS UNLESS OTHERWISE: INDICATED. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE. FOR TRACING CIRCUITS BACK TO SOURCE. CIRCUIT BREAKERS SERVING THE ABOVE ITEMS SHALL BE LEFT IN THE ON POSITION AND CLEARLY LABELED AS LIGHTING CIRCUIT. PROVIDE 30A-1P C/B IN NEAREST PANELBOARD. C/B SHALL SERVE NEW EXHAUST FAN VIA 2#10 & 1#10 GND IN 3/4" CONDUIT. PROVIDE 25A FUSED DISCONNECT SWITCH. ELEC. CONTRACTOR SHALL UTILIZE SPARE SPACE WITHIN THE PANELBOARD, IF NO SPACE AVAILABLE, DISCONNECT AND REMOVE ANY C/B'S (SERVING EXISTING RECEPTACLES) THAT WERE PLACED IN THE OFF POSITION, PROVIDE MOTOR CONTROLLERS AND/OR COMBINATION DISCONNECT/MOTOR CONTROLLER AS REQUIRED (COORDINATE WITH MECH. CONTRACTOR AND MANUFACTURER). ALL CONDUIT PATHS SHALL BE. COORDINATED WITH EXISTING CONDITIONS AND ABATEMENT. CONSULTANT/CONTRACTOR PRIOR TO ROUGH -IN, PROVIDE 20A-1 P C/B IN NEAREST PANELBOAR. C/B SHALL SERVE NEW MOTORIZED DAMPER VIA 2#12 & 1#12 GND - 3/4" CONDUIT. PROVIDE OVERCURRENT PROTECTION SWITCH. ELEC, CONTRACTOR. SHALL UTILIZE SPARE SPACE WITHIN THE PANELBOARD. IF NO SPACE AVAILABLE, DISCONNECT AND UTILIZE A C/B(SERVING EXISTING RECEPTACLES) THAT WAS PLACED IN THE OFF POSITION. PROVIDE MOTOR. CONTROLLERS AS REQUIRED(COORDINATE WITH MECH. CONTRACTOR. AND MANUFACTURER). ALL CONDUIT PATHS SHALL BE COORDINATED WITH EXISTING CONDITIONS AND ABATEMENT CONSULTANT/CONTRACTOR PRIOR TO ROUGH -IN. NEW SMOKE DETECTOR TO REPLACE EXISTING DEVICE. UTILIZE EXISTING JUNCTION BOX, CONDUIT, AND ASSOCIATED WIRING FOR NEW DETECTOR. EXTEND EXISTING WIRING AS NECESSARY TO ACCOMMODATE REPLACEMENT. . NEW LIGHT SWITCH(ES) TO CONTROL ALL EXISTING LIGHT FIXTURES AS INDICATED IN DESIGNATED PER FLOOR. SWITCH(ES) SHALL BE INSTALLED TO HAVE BASIC ON/OFF CONTROL TO ALLOW SERVICE, SECURITY, POLICE, AND/OR SFD PERSONNEL TO EASILY SWITCH ON/OFF BUILDING LIGHTS. COORDINATE EXACT LOCATION. OF SWITCHES WITH ARCHITECT AND FIRE DEPARTMENT PRIOR TO INSTALLATION: EXTEND EXISTING BRANCH CIRCUIT WIRING AND CONDUIT AND DISCONNECT ALL OTHER EXISTING CONTROLS AS NECESSARY TO ACCOMODATENEW SWITCHING SCHEME. CONTRACTOR SHALL FIELD VERIFY COUNT AND LOAD OF EXISTING BRANCH CIRCUITS FOR QUANTITY OF SWITCHES (SHOWN ON DINGS AS LOCATION REFERENCE ONLY). CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING WIRING AND CONDUIT TO ACCOMODATE ANY VOLTAGE DROP TO THE NEW SWITCH. ALL CONDUIT PATHS AND BACK BOXES SHALL BE COORDINATED WITH EXISTING CONDITIONS AND ABATEMENT CONSULTANT/CONTRACTOR PRIOR TO ROUGH -IN, (B.O.D.: CONTRACTOR TO CARRY COST FOR FOUR BRANCH CIRCUITS AND EACH CIRCUIT WITH (3)THREE WAY SWITCHES PER FLOOR). Office of Planning Design and Construction McCormack Building One Ashburton Place Boston MA 02108 617 727 4050 www.mass.govlcam Project Name: SALEM SUPERIOR COURT & COUNTY COMMISSIONER BUILDINGS WARM MOTHBALLING DCAMM Project Number DCP1726 FC1 Project Location 32-34 FEDERAL ST, SALEM, MA 01970 Project Architect PERRY DEAN ROGERS PARTNERS 177 MILK STREET BOSTON, MA 02109 T. 617-423-0100 F. 617-426-2274 www.perrydean.com Project Consullan BVH integrated services One Gateway Center, Suite 701 Newton, MA 02458 Tel: (617) 658-9008 www.bvhis.com Professional Stamp Site. Number: CAM1S Number: Building Number: Secretariat: Original Issue Date 01/26/2018 BID DOCUMENTS Revisions Plan Name: LEVEL 2 ELECTRICAL POWER PLAN Drawing Number: EP1 -02 L POWER -LEVEL 3 1/8" = 1 t_O" NEW EXHAUST UNIT 0 APPROXIMATE LOCATION OF NEW CONDUIT. COORDINATE IN FIELD WITH CONTRACTOR (TYPICAL) EX EX r__ GENERAL NOTES 1. COORDINATE EXACT LOCATIONS OF NEW SMOKE DETECTORS WITH ARCHITECT AND FIFRE DEPARTMENT PRIOR TO ROUGH -IN. VERIFY NEW SMOKE COVERAGE IS ADEQUATE WITH FIRE DEPARTMENT: 2. ALL NEW SMOKE DETECTORS SHALL BE COMPATIBLE WITH EXISTING BUILDING'S FIRE ALARM CONTROL PANEL. ALL NEW INITIATION DEVICES SHALL BE. WIRED BACK TO EXISTING CONTROL PANEL. EXTEND EXISTING WIRING AS NECESSARY TO ACCOMMODATE RENOVATION. PANEL ZONING SHALL ALSO BE EXTENDED AS NEEDED TO PROVIDE CAPACITY FOR NEW DEVICES. COORDINATE WITH FIRE ALARM MANUFACTURER.. 3, ALL CONDUIT PATHWAYS SHOWN ARE IN LOCATIONS WHERE ABATEMENT IS NECESSARY. COORDINATE NEW ELECTRICAL AND/OR FIRE ALARM CONDUIT ROUTING IN FIELD.WITH ASBESTOS REMOVAL CONTRACTOR. UNLESS OTHERWISE INDICATED ON PLANS, CONDUIT SHALL BE MOUNTED.ON WOOD STRAPPING. CONDUIT MOUNTING AND WOOD STRAPPING INSTALLATION SHALL BE COORDINATE WITH ARCHITECT/CONTRACTOR PRIOR'TO INSTALLATION. IF CONDUIT ROUTING NOT INDICATEDON PLANS, EXTEND EXISTING CONDUIT TO SERVE NEW DEVICES. • 4. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING LOCATION AND QUANTITY OF ALL EXISTING PANELBOARDS. 5. ELECTRICAL CONTRACTOR SHALL TRACE ALL BRANCH CIRCUITS IN ALL EXISTING PANELBOARDS. 6. CONTRACTOR SHALL PLACE IN THE OFF POSITION ALL EXITING CIB'S SERVING RECEPTACLES AND NON -ESSENTIAL LIGHTING (ANY CIRCUITS THAT DO NOT SERVE LIGHT FIXTURES IN THE MAIN CORRIDORS INDICATED ON FLOOR PLANS). - 7. ELECTRICAL CONTRACTOR SHALL PLACE IN THE OFF POSITION ALL EXISTING CIB'S THAT SERVE HVAC EQUIPMENT NOT PART OF THE HEATING SYSTEM. VERIFY WITH MECHANICAL CONTRACTOR ALL HVAC EQUIPMENT THAT SHALL REMAIN IN USE, LJ 0 :WJ DRAWING NOTES EXACT LOCATION OF ELEV. AND WHEELCHAIR LIFT DISCONNECT. SWITCHES SHALL BE VERIFIED IN FIELD. SWITCHES SHALL BE PLACED IN THE OFF POSITION AND SECURED WITH PADLOCK. KEY SHALL BE LABELED AND HANDED OVER TO OWNER'S REPRESENTATIVE . ALL LIGHT FIXTURES,BATTERY LIGHT UNITS, EXIT, SIGNS, FIRE ALARM DEVICES, AND ASSOCIATED WIRING AND RACEWAY WITHIN THE AREA SHALL REMAIN AS IS UNLESS OTHERWISE INDICATED. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR TRACING CIRCUITS BACK TO SOURCE. CIRCUIT BREAKERS SERVING THE ABOVE ITEMS SHALL BE LEFT IN THE ON POSITION AND CLEARLY LABELED AS LIGHTING CIRCUIT. PROVIDE 30A-1 P C/B IN NEAREST PANELBOARD. C/B SHALL SERVE NEW EXHAUST FAN VIA 2#10 & 1#10 GND IN 3/4" CONDUIT. PROVIDE 25A FUSED DISCONNECT SWITCH. ELEC. CONTRACTOR SHALL UTILIZE SPARE SPACE WITHIN THE PANELBOARD. IF NO SPACE AVAILABLE, DISCONNECT AND REMOVE ANY GIB''S (SERVING EXISTING RECEPTACLES) THAT WERE PLACED IN THE OFF POSITION. PROVIDE MOTOR CONTROLLERS AND/OR COMBINATION DISCONNECT/MOTOR CONTROLLER AS REQUIRED (COORDINATE WITH MECH. CONTRACTOR AND MANUFACTURER). ALL CONDUIT PATHS SHALL BE COORDINATED WITH EXISTING CONDITIONS AND ABATEMENT CONSULTANT/CONTRACTOR PRIOR TO ROUGH -IN, PROVIDE 20A-1 P C/B IN NEAREST PANELBOARD. C/B SHALL SERVE NEW MOTORIZED DAMPER VIA 2#12 & 1#12 GND - 3/4" CONDUIT. PROVIDE OVERCURRENT PROTECTION SWITCH, ELEC. CONTRACTOR SHALL UTILIZE SPARE SPACE WITHIN THE PANELBOARD. IF NO SPACE AVAILABLE, DISCONNECT AND UTILIZE A C/B(SERVING EXISTING RECEPTACLES) THAT WAS PLACED IN THE OFF POSITION. PROVIDE MOTOR CONTROLLERS AS REQUIRED(COORDINATEWITH MECH. CONTRACTOR AND MANUFACTURER). ALL CONDUIT PATHS SHALL BE COORDINATED WITH EXISTING CONDITIONS AND ABATEMENT CONSULTANT/CONTRACTOR PRIOR TO ROUGH -IN. NEW SMOKE DETECTOR TO REPLACE EXISTING DEVICE: UTILIZE EXISTING JUNCTION BOX, CONDUIT, AND ASSOCIATED WIRING FOR NEW DETECTOR. EXTEND EXISTING WIRING AS NECESSARY TO ACCOMMODATE REPLACEMENT. NEW LIGHT SWITCHES) TO CONTROL ALL EXISTING LIGHT FIXTURES AS INDICATED IN DESIGNATED PER FLOOR. SWITCH(ES) SHALL BE INSTALLED TO HAVE BASIC ON/OFF CONTROL TO ALLOW SERVICE, SECURITY, POLICE, AND/OR SFD PERSONNEL TO EASILY SWITCH ON/OFF BUILDING LIGHTS.. COORDINATE EXACT LOCATION OF SWITCHES WITH ARCHITECT AND FIRE DEPARTMENT PRIOR TO INSTALLATION. EXTENDEXISTING BRANCH CIRCUIT WIRING AND CONDUIT AND DISCONNECT ALL OTHER EXISTING CONTROLS AS NECESSARY TO ACCOMODATE NEW SWITCHING SCHEME. CONTRACTOR SHALL FIELD VERIFY COUNT AND LOAD OF EXISTING BRANCH CIRCUITS FOR QUANTITY OF SWITCHES (SHOWN ON DINGS AS LOCATION REFERENCE ONLY). CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING WIRING AND CONDUIT TO ACCOMODATE ANY VOLTAGE DROP TO THE NEW SWITCH, ALL CONDUIT PATHS AND BACK BOXES SHALL BE COORDINATED WITH EXISTING CONDITIONS AND ABATEMENT CONSULTANT/CONTRACTOR PRIOR TO ROUGH -IN. (B.O.D.: CONTRACTOR TO CARRY COST FOR FOUR BRANCH CIRCUITS AND EACH CIRCUIT WITH (3)THREE WAY SWITCHES PER FLOOR). Office of Planning Design and Construction McCormack Building One Ashburton Place Boston MA 02108 617 727 4050 www.mass.govlcam Project Name: SALEM SUPERIOR COURT & COUNTY COMMISSIONER BUILDINGS WARM MOTHBALLING DCAMM Project Number DCP1726 FCI Project Location 32-34 FEDERAL ST, SALEM, MA 01970 Project Architect PERRY DEAN ROGERS PARTNERS 177 MILK STREET BOSTON, MA 02109 T. 617-423-0100 F. 617-426-2274 www.perrydean.com Project G.hint all 11 .t► '141.11- 131/11 integrated services One Gateway Center, Suite 701 Newton, MA 02458 Tel: (617) 658-9008 www.bvhis.com 1 Professional Stamp Site Number: CAMIS Number: Building Number: Secretariat: Original Issue Date 01/26/2018 BIDDOCUMENTS Revisions Plan Name: LEVEL 3 ELECTRICAL POWER PLAN Drawing Number: E-!Pi-03 ii 711.€ ii; l: Ili � Vr[ I Ifj I H If i I'1 1 �_1`l fl.l_ tl�t�ll,It.- 1 LI.II.i',_•I I1 1 � I 1 ., � `3 1.L.Lil 1 I I i f l €Ii E 1 111 L 1 "T.`i T 1—r� i L i h t 1_,_:_ 1 LI 1-,11 11 L.L�__l.Lf�.! j J. 11f 1 ?tI t11 11J LL1"1t1 Ii rTfEtiI.;Ii T i i1_I €1Li_I 1 ' Ll 1 I i! L l T 1 L - —L-T T 1 13 1 1: I I I,' I_ €1 11 I i - 1 1_: 1 1 1, Li IT: 1. 1 1 1 _.il _.� :=�111 i'ill,_:l_iII1 11 t i 1, 1_LI1 .-111-Ft`11 ]tiJ__Tj_ Ii_1_Et €l T-1T1 €I l 1 1_ITL L 1 t_ €IiII1T JI 11I' �1....L_I. 1.1 1 �T= t [ ICI, 1 1,1 1.1. L. LI.1"Li 1.1 (1 IJ_11 H. T=`_1 1 .I..1 RE• - LI#° 1_ I.i1_ DISCONNECT AND REMOVE OVERCURRENT-, PROTECTION DEVICE AND POWER FEED TO —EXISTING TO BE REMOVED CONDENSER UNITS. REMOVE FEEDER'S ASSOCIATED WIRING AND -__RACEWAY BACK TO SOURCE. PLACE BREAKER IN OFF POSITION AND LABEL AS SPARE. 1I J1€IiL I. 1.. IiJT[ 1 111J..1_.f _- III 1'1I [I<Iii-f�l)Ilil 1 1 I°1 i 111 1=i�1I.� ,.11i :li{1,I.lt. i 0) POWER DEMO -ROOF 1/8" = 1'-0" ;_! < <<;.ii._..1 i__ . n..i. .l E I•I L I �I 1i,il< i';11 < Iiii;i I;I. f IlrllaL lI; ti�.._�=l ll€`_ •1�. 1T`IIIITI r��I T 11 1 1_ fl 3 1 t�l 1`1 1 I '" f j ! ili li; I E) i iiE it l 11_i I .11lll I!i i �I .I. - J J_l ! 1 ; 1 I Li_ 1.. J. I . __ t `. I . .t t l .l ' i j"j"' I. 1 i i" I. i, I I I J f-_I ` € 1 I I;L-,'< 1 s i° 1 1 l 1 .1 "I i 1_ i "l € I �i 1 [ I I 11 I I 1-111 1 I I I1 1 1 j i [i , i , , F_{ I I I t 1 , ' ; , 1. 1. € ? .L 1 ' -1 i RE .. ;. 1 JI 1;11TT -Ell 11 I J 1-r 1 I d3._L_I1. l f ? 1�iff T Z;m u ILLLLl.. T l LTT 1.1 '. 1.� i L� ii`f"lit€ELT_. 1 .1 l..I i1 I.11 L1T1T i LI 11• SElimT 1 ; 11 i i_ L E I .. I I T._ 1 r. €I LLIi1._:1 .il.i .lIT+11 i 1 1E .1. I. L_i, t -1.1 1. ;— _I__i _I,l..11 it 1i13_`i -} Li. ': 1 T T I i .. l 1 I11 1 } _L Office of Planning Design and Construction McCormack Building One Ashburton Place Boston MA 02108 617 727 4050 Project Name: SALEM SUPERIOR COURT & COUNTY COMMISSIONER BUILDINGS WARM MOTHBALLING DCAMM Project Number Project Location 32 34 FEDERAL ST, SALEM, MA 01970 Project Architect PERRY DEAN ROGERS PARTNERS 177 MILK STREET BOSTON, MA 02109 T. 617-423-0100 F. 617-426-2274 Project Co-nsultarl 17111 FIr 131/11 integated services One Gateway Center, Suite 701 Newton, MA 02458 Tel: (617) 658-9008 www.bvhis.com Professional Stamp Site Number: CAMIS Number: Building Number: Secretariat: Original Issue Date 01/26/2018 BID DOCUMENTS Revisions Plan Name: ROOF ELECTRICAL POWER DEMOLITION PLAN Drawing Number: EPD 04 TYPICAL EXISTING FIRE ALARM SPEAKER STROBE UNIT TYPICAL EXISTING FIRE ALARM STROBE UNIT EX EX EXISTING WRING. EXTEND WIRING AS NECESSARY TO ACCOMODATE RENOVATION. EX NEW BATTERIES SHALL BE PROVIDED FOR EXISTING TO REMAIN SYSTEM. REFER TO SPECIFICATIONS FOR FURTHER INFORMATION. EX EXISTING FCI 7200 FACP BATTERIES EX FIRE ALARM RISER NOT TO SCALE C EX TYPICAL EXISITNG SMOKE DETECTOR TYPICAL EXISTING MANUAL PULL STATION TYPICAL NEW SMOKE DETECTOR. / NEW DEVICE SHALL BE COMPATIBLE WITH EXISTING SYSTEM. FIRE ALARM RISER GENERAL NOTES 1. SEE SECTION 260001 SPECIFICATION FOR ADDITIONAL INFORMATION. 2. DEVICES AND CIRCUITS ARE ILLUSTRATED FOR TYPICAL ARRANGEMENT ONLY. REFER TO PLANS AND DETAILS FOR QUANTITIES AND TYPES OF DEVICES. 3. PROVIDE ADDRESSABLE INTERFACE DEVICES AS REQUIRED. DEVICES ARE NOT SPECIFICALLY INDICATED ON PLANS OR RISER. 4, PROVIDE WIRING PER APPROVED MANUFACTURER'S DIRECTION. 5. ALL WIRING IS IN RACEWAY. 6. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING EXISTING BATTERY CAPACITY FOR ENTIRE SYSTEM AND PROVIDING NEW BATTERIES AS REQUIRED TO MAINTAIN CODE COMPLAINT SYSTEM. 7. CONTRACTOR SHALL PROVIDE ALL CARDS, CONNECTIONS, BATTERIES, ACCESSORIES, PROGRAMMING, AND TESTING TO ALLOW FOR NEW SMOKE DETECTOR DEVICES. 8. CONTRACTOR SHALL BE RESPONSIBLE FOR REPLACING ANY EXISTING EQUIPMENT, CONNECTIONS, OR ASSOCIATED PARTS THAT ARE DEEMED DEFECTIVE DURING THE PROGRAMMING AND TESTING OF THE UPDATED SYSTEM. FIRE ALARM MATRIX. GENERAL NOTES 1. DETECTORS ON ALARM VERIFICATION SHOULD "SNIFF" THE AIR, THEN CHECK AGAIN. IF THE SMOKE IS STILL THERE, THEN A GENERAL ALARM SHOULD SOUND TO EVACUATE. THESE ARE THE ALARMS THAT DO NOT HAVE CROSS -ZONE CAPABILITY. EX EX EXISTING WIRING. EXTEND WIRING AS NECESSARY TO ACCOMODATE RENOVATION. SYSTEM OUTPUTS CONTROL. UNIT ANNUNCIATION 1 EXISTING MANUAL FIRE ALARM BOXES I I I I I I 1 2 EXISTING CO DETECTORS I I I I I I 2 3 EXISTING SMOKE DETECTORS I 3 4 NEW SMOKE DETECTORS I I I I I I 4 5 EXISTING NOTIFICATION APPLIANCE CIRCUIT SHORT I I I I 5 6 EXISTING HEAT DETECTORS - MECH AREA I I I I I I 6 7 EXISTING DUCT SMOKE DETECTORS I I I I 1 I 7 8 FIRE ALARM SYSTEM LOW BATT I I I I 8 9 OPEN CIRCUIT I I I I 9 10 GROUND FAULT I I I I 10 A F G FIRE ALARM MATRIX NOT TO SCALE NOTIFICATION EQUIPMENT MOTOR --- (NOT SPECIFICALLY INDICATED ON FLOOR PLANS) EQUIPMENT TAG -■ A NON -FUSED ENCLOSED SWITCH PER SECTION 260001 SPECIFICATIONS WITH AUXILIARY CONTACTS. MOUNT IN SIGHT OF EQUIPMENT. MOTOR. PROVIDE SWITCH ONLY WHENEVER CONTROLLER AND SWITCH CANNOT BE MOUNTED WITHIN SIGHT OF EQUIPMENT X BRANCH CIRCUIT BY SECTION 260001 SPEC. CONTRACTOR. SEE SECTION 260001 SPEC. AND FLOOR PLANS FOR BRANCH CIRCUIT REQUIREMENTS AND SECTION 230001 SPECIFICATION AND EQUIPMENT SCHEDULES FOR SIZING. EQUIPMENT TAG REFERENCES MEP AND OWNER SCHEDULES TERMINAL BOX BRANCH CIRCUIT WIRING BY SECTION 260001 CONTRACTOR PER SECTION 260001 SPECIFICATION. PROVIDE ADDITIONAL WIRING AS. REQUIRED TO MATCH CONTROLLER. COORDINATE WITH SECTION 230001 SPECIFICATION CONTRACTOR. FOR EQUIPMENT REQUIRING A COMBINATION MOTOR CONTROLLER/DISCONNECT SWITCH, FURNISH AND INSTALL CONTROLLER/SWITCH PER SECTION 260001 SPECIFICATION, UNLESS OTHERWISE PROVIDED BY MANUFACTURER. MOUNT ADJACENT TO EQUIPMENT: SWITCH. TO BE FUSED. SECTION 230001 AND SECTION 260001 CONTRACTORS SHALL COORDINATE MOTOR AND CONTROLLER REQUIREMENTS AND INSTALLATION. NOTE: THIS DETAIL IS. FOR ALL EQUIPMENT MOTORS. SECTION 260001 SPECIFICATION CONTRACTOR TO PROVIDE WIRING BETWEEN REMOTE COMBINATION MOTOR CONTROLLER/ DISC SWITCH AND MOTORS. REFER TO SECTION 260001 AND 230001 SPECIFICATIONS, AND MEP EQUIPMENT SCHEDULES AND/OR FLOOR PLANS . IF NOT NOTED OTHERWISE IN EQUIPMENT SCHEDULES, SECTION 260001 SPECIFICATION CONTRACTOR SHALL PROVIDE A COMBINATION MOTOR CONTROLLER/DISC: SWITCH. SECTION 230001 AND SECTION 260001 SPECIFICATION CONTRACTORS SHALL BE RESPONSIBLE FOR COORDINATING EXACT SIZE AND REQUIREMENTS OF COMBINATION DEVICE AND THE SEQUENCE OF INSTALLATION,. NON -FUSED ENCLOSED SWITCH PER SECTION 260001 SPECIFICATIONS WITH AUXILIARY CONTACTS. MOUNT IN SIGHT OF EQUIPMENT MOTOR. COORDINATE WITH SECTION 230001 SPECIFICATION CONTRACTOR. EQUIPMENT TAG REFERENCES MEP SCHEDULES/FLOOR PLANS TERMINAL BOX BRANCH CIRCUIT WIRING BY SECTION 260001 CONTRACTOR PER SECTION 260001 SPECIFICATION. PROVIDE ADDITIONAL WIRING AS REQUIRED TO MATCH CONTROLLER. COORDINATE WITH SECTION 230001 SPECIFICATION CONTRACTOR. --- BRANCH CIRCUIT BY SECTION 260001 SPEC: CONTRACTOR. SEE SECTION 260001 SPEC. AND FLOOR PLANS FOR BRANCH CIRCUIT REQUIREMENTS AND SECTION 230001 SPECIFICATION AND EQUIPMENT SCHEDULES FOR SIZING. NOTE: THIS DETAIL IS FOR ALL EQUIPMENT WHERE EQUIPMENT REQUIRES POWER AND WHERE THERE ARE NO MOTORS INVOLVED OR WHERE SPECIFICATIONS OR SCHEDULES FOR MULTIPLE MOTOR EQUIPMENT SPECIFICALLY INDICATE. ONE POINT POWER CONNECTION. SECTION 260001 SPECIFICATION CONTRACTOR TO. PROVIDE WIRING BETWEEN REMOTE DISCONNECTS, STARTERS AND MOTORS. SEE SECTION 230001 EQUIPMENT SCHEDULES AND SECTION 260001 SPECIFICATIONS, EXISTING UNDERGROUND UTILITY PRIMARY FEEDER TO REMAIN. EXISTING UNDERGROUND SECONDARY FEEDER INTO MAIN ELEC. RM WITHIN SUPERIOR COURT BLDG. EXISTING UTILITY OWNED, CONCRETE PAD MTD, EXTERIOR TRANSFORMER 1600AF 1600AT EXISTING DPB, 1600A MCB, 208/120V, 3PH, 4W 100A EX 60A TO ALL EXISTING COURTROOM PANELBOARDS. FIELD VERIFY EXACT LOCATION IN FIELD. ) 100A ) 100A LB-2 EX LB-3 EX I 1100A LB-4 EX ) 150A LB-5 EX 100A LB-6 EXISTING 40HP ELEVATOR EXISTING ELECTRICAL ONE -LINE DIAGRAM NOT TO SCALE EXISTING ELEV. CONTROL ) 400A ) 400A J 1. GENERAL NOTES ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING LOCATION AND QUANTITY OF ALL EXISTING PANELBOARDS, NOT ALL PANELBOARDS ARE INDICATED ON THIS ONE -LINE DIAGRAM OR FLOOR PLANS. 2. ELECTRICAL CONTRACTOR SHALL TRACE ALL BRANCH CIRCUITS IN ALL EXISTING PANELBOARDS. 3. CONTRACTOR SHALL PLACE IN THE OFF POSITION ALL EXISTING C/B'S SERVING RECEPTACLES AND NON- ESSTIONAL LIGHTING (ANY CIRCUITS THAT DO NOT SERVE LIGHT FIXTURES IN THE MAIN CORRIDORS INDICATED ON FLOOR PLANS). 4. ELECTRICAL CONTRACTOR SHALL PLACE IN THE OFF POSITION ALL EXISTING C/B'S THAT SERVE HVAC EQUIPMENT NOT PART OF THE HEATING SYSTEM. VERIFY WITH MECHANICAL CONTRACTOR ALL HVAC EQUIPMENT THAT SHALL REMAIN IN USE. PANELBOARD AND SWITCHBOARD LEGEND INDICATES MAINS TYPE j (CIRCUIT BREAKER). �, 7, NI 225AF "" 225AT �_.__ XXXXX INDICATES MAINS TYPE -'A (MAIN LUG ONLY) INDICATES PANEL INDICATES PANEL I XXXXX DESIGNATION. DESIGNATION. INDICATES FRAME SIZE INDICATES TRIP SETTING INDICATES FEED THROUGH LUGS. EXISTING DPC, 400A MCB, 208/120V, 3PH, 4W EX ELC-B ) 150A LC-2 100A V^ TO EXISTING PANELBOARD. FIELD VERIFY EXACT LOCATION IN FIELD. ) 100A W- TO EXISTING PANELBOARD. FIELD VERIFY EXACT LOCATION IN FIELD. ) 100A TO EXISTING PANELBOARD. FIELD VERIFY EXACT LOCATION IN FIELD. 4- ) 100A A TO EXISTING PANELBOARD. FIELD VERIFY EXACT LOCATION IN FIELD. POWER RISER DIAGRAM FEEDER SIZING CHART (SEE FEEDER LEGEND FOR APPLICATION OF THIS CHART) AMPERAGE NUMBER OF PARALLEL SETS PHASE CONDUCTOR(S) NEUTRAL CONDUCTOR(S) GROUNDING CONDUCTOR(S) RACEWAY SIZE AMPERAGE NUMBER OF PARALLEL SETS PHASE CONDUCTOR(S) NEUTRAL CONDUCTOR(S) GROUNDING CONDUCTOR(S) RACEWAY SIZE STANDARD OVERSIZED EQUIPMENT ISOLATED OVERSIZED STANDARD OVERSIZED EQUIPMENT ISOLATED OVERSIZED 20or30 1 (3)#10 (1)#10 (1)#8 (1)#10 (1)#10 8 1" 400 1 (3)#500 (1)#500 (2)#350 (1)#3 (1)#3 3/0 4" 40 or 50 1 (3) # 8 (1) # 8 NA (1) # 10 NA 8 1" 420 1 (3) # 600 (1) # 600 (2) # 350 (1) # 2 (1) # 2 3/0 4" 60 1 (3)#6 (1)#6 (1)#3 (1)#10 (1)#10 8 11/4" 450 2 (3)#4/0 (1)#4/0 (2)#2/0 (1)#2 (1)#2 3/0 3" 70 1 (3)#4 (1)#4 NA (1)#8 NA 8 11/4" 500 2 (3)#250 (1)#250 (2)#3/0 (1)#2 (1)#2 3/0 3" 80 1 (3)#4 (1)#4 NA (1)# 8 NA 6 1 1/4" 600 2 (3)#350 (1)#350 (2)#4/0 (1)# 1 (1)#1 4/0 4" 90 1 (3) # 3 (1) # 3 NA (1) # 8 NA 6 1 1/2" 700 2 (3) # 500 (1) # 500 (2) # 300 (1) # 1/0 (1) # 1/0 4/0 4" 100 1 (3)#2 (1)#2 (1)#1/0 (1)#8 (1)#8 4 11/2" 800 2 (3)#500 (1)#500 (2)#350 (1)#1/0 (1)#1/0 250 4" 840 2 (3) # 600 (1) # 600 (1) # 350 (1) # 2 (1) # 2 3/0 4" 110 1 (3) # 2 (1) # 2 (1) # 2/0 (1) # 6 (1) # 6 3 2" 1000 3 (3) # 500 (1) # 500 (2) # 500 (1) # 2/0 N.A. 500 4" 125 1 (3)# 1 (1)# 1 (1)#3/0 (1)#6 (1)#6 2 2" 1200 4 (3)#500 (1)#500 (2)#500 (1)#3/0 N.A. 500 4" 150 1 (3) # 1/0 (1) # 1/0 (1) # 4/0 (1) # 6 (1) # 6 2 2" 1600 5 (3) # 500 (1) # 500 (2) # 500 (1) # 4/0 N.A. 500 4" 175 1 (3) # 2/0 (1) # 2/0 (1) # 300 (1) # 6 (1) # 6 1 2 1/2" 2000 6 (3) # 500 (1) # 500 N.A. (1) # 250 N.A. 500 4" 200 1 (3) # 3/0 (1) # 3/0 (2) # 1/0 (1) # 6 (1) # 6 1 2.1/2" 2500 7 (3) # 500 (1) # 500 N.A. (1) # 350 N.A. 500 4" 225 1 (3) # 4/0 (1) #4/0 (2) ## 2/0 (1) # 4 (1) # 4 1/0 3" 3000 8 (3) # 500 (1) # 500 N.A, (1) ## 400 N.A. 500 4,, 250 1 (3) # 250 (1) # 250 (2) # 3/0 (1) # 4 (1) # 4 2/0 3" 3200 9 (3) # 500 (1) # 500 N.A. (1) # 500 N.A. 500 4" 300 1 (3) # 350 (1). # 350 (2) # 4/0 (1) ## 4 (1) # 4 2/0 4" 3600 10 (3) # 500 (1) # 500 N.A, (1) ## 500 N.A. . 5.00 4" 350 1 (3) # 400 (1) # 400 (2) # 300 (1) # 3 (1) # 3 3/0 4" 4000 11 (3) # 500 (1) # 500 N.A. (1) # 500 N,A. 500 4" NOTES: CONDUCTORS LISTED ABOVE ARE THHN/THWN, COPPER. MAY ELECT TO INCREASE SIZE OF CONDUCTORS LISTED ABOVE IF THERE IS NO INCREASE IN COST. INCREASE SIZE OF RACEWAY PER CODE AS REQUIRED. AUXILIARY LUGS AND OVERSIZED GUTTERS IN DISTRIBUTION EQUIPMENT TO ACCOMMODATE OVERSIZED CONDUTORS. 1. • ALL 2. CONTRACTOR 3. PROVIDE Office of Planning Design and Construction McCormack Building One Ashburton Place Boston MA 02108 617 727 4050 www.mass.gov/cam Project Name: SALEM SUPERIOR COURT & COUNTY COMMISSIONER BUILDINGS WARM MOTHBALLING DCAMM Project Number DCP1726 FC1 Project Location 3234 FEDERAL ST, SALEM, MA 01970 Project Architect PERRY DEAN ROGERS PARTNERS 177 MILK STREET BOSTON, MA 02109 T. 617-423-0100 F. 617-426-2274 www.perrydean.com Project COnsutnt /A �, all !Mil II ilk 1111111407 integrated services One Gateway Center, Suite 701 Newton, MA 02458 Tel: (617) 658-9008 www.bvhis,com Professional Stamp N. Site Number: CAM'S Number: Building Number: Secretariat: Original Issue Date 01/26/2018 BID DOCUMENTS Revisions Plan Name: ELECTRICAL ONE -LINE DIAGRAM, FIRE ALARM RISER, AND DETAILS Drawing Number: TYPICAL. COMBINATION MOTOR CONTROLLER/DISC SWITCH DETAIL NOT TO SCALE TYPICAL EQUIPMENT CONNECTION DETAIL NOT TO SCALE E3-01