E dwg'sa
A/AM P
AC
ACU
AF
AFF
AHU
AIC
ANN
ANSI
APPROX
ATC
ATS
AVG
AWG
BSMT
C
C/B
CLG
CO
COMP
COND
CP
CU
CUH
MEPT ABBREVIATIONS
48" ABOVE FINISHED FLOOR
AMPERE
ALTERNATING CURRENT
AIR CONDITIONING UNIT(S)
ARC FAULT
ABOVE FINISHED FLOOR
AIR HANDLING UNIT
AMPS INTERRUPTING CURRENT
ANNUNCIATOR
AMERICAN NATIONAL STANDARDS INSTITUTE
APPROXIMATE
AUTOMATIC TEMPERATURE CONTROL
AUTOMATIC TRANSFER SWITCH
AVERAGE
AMERICAN WIRE GAUGE
BASEMENT
CONDUIT(S)
CIRCUIT BREAKER
CEILING
CLEANOUT
COMPRESSOR
CONDENSER
CONDENSATE PUMP
CONDENSING UNIT
CABINET UNIT HEATER
D DATA
DC DIRECT CURRENT
DEG or ° DEGREE
DIA or ODIAMETER
DN
DWG
EF
EFF
ELEC
ELEV
EM
EM/NL
ER
ETP
EUH
EVAP
EXP
FA
GA
GAL
GF
GND
H
HC
HDCP
HP
HR
HTR
HUM
HV
HVAC
IN
JB
KVA
KW
L
LF
MAX
MD
MECH
MFR
MIN
N/A
NEC
NIC
NTS
P
PE
PH/0
PNL
QTY
R
RAF
RE
REF
RL
RM
RTU
S
SCP
SD
SE
SPEC
SQ
STD
SW
SWBD
TSTAT
TAG
TEL
TEMP
TR
TX
TYP
UH
V
V
V
VA
VFC
VIF
VOL
W
WEF
WI
WP
WTR
DOWN
DRAWING
EXHAUST FAN
EFFICIENCY
ELECTRICAL
ELEVATOR
EMERGENCY
EMERGENCY/NIGHT LIGHT WALK-THRU
EQUIPMENT ROOM
ELECTRIC TRAP PRIMER
ELECTRIC UNIT HEATER
EVAPORATOR
EXPANSION
FIRE ALARM
GAUGE
GALLONS
GROUND FAULT
GROUND
HEIGHT
HORIZONTAL CROSS -CONNECT
HANDICAP
HORSEPOWER
HOUR(S)
HEATER
HUMIDIFIER
HEATINGNENTILATION UNIT
HEATING, VENTILATION AND AIR CONDITIONING
INCHES
JUNCTION BOX
KILOVOLT AMPERE
KILOWATT
LENGTH
LINEAR FEET
MAXIMUM
MOTORIZED DAMPER
MECHANICAL
MANUFACTURER
MINIMUM
NOT APPLICABLE
NATIONAL. ELECTRICAL CODE
NOT IN CONTRACT
NOT TO SCALE
POLE
PRIMARY ELECTRIC SERVICE
PHASE
PANELBOARD
QUANTITY
RELAY.
RETURN AIR FAN
EXISTING EQUIPMENT TO BE DISCONNECTED
AND REMOVED
ROOF EXHAUST FAN
EXISTING EQUIPMENT TO BE DISCONNECTED,
REMOVED AND RELOCATED
ROOM
ROOF TOP UNIT
SLEEVE(S)
STEAM CONDENSATE PUMP
SMOKE DAMPER
SECONDARY ELECTRIC SERVICE
SPECIFICATION
SQUARE
STANDARD
SWITCH
SWITCHBOARD
THERMOSTAT
IDENTIFICATION OF EQUIPMENT
TELECOMMUNICATIONS SERVICE
TEMPERATURE
TELECOMMUNICATIONS ROOM
TRANSFORMER
TYPICAL
UNIT HEATER
VENT
VOICE
VOLTAGE
VOLT AMPERE
VARIABLE FREQUENCY CONTROLLER
VERIFY IN FIELD
VOLUME
WATT
WALL EXHAUST FAN
WIDTH
WEATHERPROOF
WATER
ELECTRICAL GENERAL NOTES
GENERAL
1. THE PROJECT DRAWINGS AND SPECIFICATIONS ARE BASED ON THE CONSTRUCTION SPECIFICATIONS
INSTITUTE (CSI) DOCUMENTATION FORMAT. SPECIFICATION AND DRAWING CONTENTS ARE ARRANGED BY
TOPIC AND CATEGORY AND ARE NOT INTENDED TO AWARD DIVISION OF WORK.
2. THE INTENT OF THESE DOCUMENTS IS FOR THE MEP TRADES TO FURNISH AND. INSTALL AS REQUIRED FOR THE
RENOVATION FOR COMPLETE MECHANICAL AND ELECTRICAL SYSTEMS.. THE SPECIFIED FIRE PROTECTION,
PLUMBING, HVAC, ELECTRICAL AND SPECIAL SYSTEMS SHALL BE COMPLETE IN ALL RESPECTS; OPERATIONAL,
TESTED, ADJUSTED, CALIBRATED, APPROVED BY THE AUTHORITIES HAVING JURISDICTION AND READY FOR
BENEFICIAL USE BY THE OWNER.
3. UTILIZING THE DESIGN INTENT MODEL: THE CONTRACT DOCUMENTS ARE SOLELY A TWO DIMENSIONAL SET OF
DOCUMENTS, IF UTILIZED, THE DESIGN INTENT MODEL HAS BEEN DEVELOPED TO A LEVEL OF DEVELOPMENT
LOD 200 AND LOD 300 MODEL CONTENT REQUIREMENTS AS DEFINED BY ALA G-202-2013. THE DESIGN INTENT
MODEL IS A THREE DIMENSIONAL TOOL UTILIZED TO CREATE A TWO DIMENSIONAL CONTRACT DOCUMENT. A
TWO DIMENSIONAL CONTRACT DOCUMENT REQUIRES, FOR REASON OF CLARITY AND OTHERWISE, THAT
COMPONENTS OF THE DESIGN NOT BE MODELED IN THREE DIMENSIONS AND/OR THAT THE MODEL BE FORMED
IN A WAY THAT CONSTRUCTION MEANS AND METHODS WILL DICTATE OTHER WAYS OF PERFORMING THE
INSTALLATION. THE DESIGN INTENT MODEL IS NOT A SUBSTITUTE FOR THE CONTRACTORS' COORDINATION
PROCESS AS OUTLINED IN THE CONTRACT DOCUMENTS; FULL COORDINATION REMAINS THE RESPONSIBILITY
OF THIS CONTRACTOR AND THEIR SUB -CONTRACTORS. THE CONTENTS OF THE MODEL ARE NOT TO BE USED
FOR THE BASIS OF DETAILED COST ESTIMATING, COORDINATING EQUIPMENT LOCATIONS AND SYSTEMS
ROUTING WITH ALL OTHER TRADES. THE CONTRACTOR MAY USE THE DESIGN INTENT MODEL TO HELP
ESTABLISH THE BACKGROUNDS AND/OR STARTING POINT FOR THE. COORDINATION DRAWINGS BASED ON THE
STIPULATIONS OF THE RELEASE FORM THAT CAN BE PROVIDED IF AND WHEN THE MODEL IS REQUESTED.
4. THE TRADES SHALL OBTAIN AND REVIEW ALL CONTRACT DOCUMENTS BEFORE SUBMITTING A BID.
INFORMATION IS PROVIDED ON THE VARIOUS DRAWINGS, SCHEDULES, SPECIFICATIONS AND ALL OF THE
VARIOUS DOCUMENTS IN THE BIDDING PACKAGE. THE CONTRACT DOCUMENTS ARE COMPLEMENTARY AND
FORM A TOTAL PROJECT DESIGN AND INFORMATION SOURCE FOR CONSTRUCTION PURPOSES.
5. THE DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS AND WORK
INCLUDED IN THE CONTRACT. COORDINATE LOCATIONS OF EQUIPMENT WITH OTHER TRADES BEFORE AND
DURING CONSTRUCTION. ANY MODIFICATION. TO THE EQUIPMENT LAYOUT, REQUIRED FOR INSTALLATION, IS TO
BE PERFORMED UNDER THE CONTRACT AGREEMENT, AT NO ADDITIONAL COST.
6. PERFORM ALL WORK IN COMPLIANCE WITH THE SPECIFICATIONS, APPLICABLE CODES, ORDINANCES AND THE
REGULATORY AGENCIES HAVING JURISDICTION. THE SPECIFICATIONS MAY EXCEED THE REQUIREMENTS OF
THE CODE, IN WHICH CASE, THE SPECIFICATION MUST BE FOLLOWED. .
7. INSTALL ALL EQUIPMENT IN ACCESSIBLE LOCATIONS. WHERE EQUIPMENT MUST BE INSTALLED ABOVE AN
INACCESSIBLE CEILING OR BEHIND A WALL, AN APPROPRIATE ACCESS DOOR SHALL BE PROVIDED AND THE
LOCATION SHALL BE COORDINATED WITH THE ARCHITECT.
8. WHERE A CONFLICT OCCURS BETWEEN THE DOCUMENTS, IT SHALL BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT. CARRY AS PART OF THE BID THE LARGER QUANTITY AND/OR MORE EXPENSIVE ITEM(S).
9. PROVIDE THE REQUIRED/SPECIFIED SLEEVES AND SEALS FOR PIPES OR CONDUIT PENETRATING INTERIOR AND
EXTERIOR WALLS OR FLOOR SLABS,
10. PROVIDE MEP COORDINATION DRAWINGS AS REQUIRED BY THE SPECIFICATIONS.
11. PROVIDE PIPING, DUCTWORK, CONDUIT AND ALL OTHER ACCESSORIES AS REQUIRED FOR PROPER AND
PROFESSIONAL SYSTEMS INSTALLATION.
12. TEST AND BALANCE ELECTRICAL SYSTEMS. PROVIDE ADDITIONAL TESTS AS REQUIRED BY THE
SPECIFICATIONS.
13. DO NOT INSTALL PIPING OR DUCTWORK OVER ELECTRICAL PANELS, TRANSFORMERS, SPECIAL EQUIPMENT,
ELEVATOR MACHINE ROOMS OR SHAFTS.
14. DO NOT INSTALL ANY SYSTEMS IN OR THROUGH ELEVATOR MACHINE ROOMS THAT DO NOT SERVE THE ROOM.
MAINTAIN A MINIMUM OF SEVEN (7) FOOT HEAD CLEARANCE IN THE ELEVATOR MACHINE ROOM.
15. DO NOT INSTALL IN STAIRWELL OR STAIRWELL WALLS, PIPING, DUCTWORK, CONDUIT OR OTHER DEVICES OR
EQUIPMENT NOT ASSOCIATED WITH OR SERVING THE RESPECTIVE STAIR.
16. PROVIDE PIPE EXPANSION COMPENSATION FOR THE VARIOUS PIPING SYSTEMS. SUBMIT ENGINEERED DETAILS
FOR APPROVAL AND VERIFY INSTALLATION IS IN ACCORDANCE WITH CODE. THE CONTRACTOR'S CONSULTING
ENGINEER SHALL REVIEW THE INSTALLATION AND PROVIDE A REPORT OF THE FINDINGS.
17, PROVIDE ADDITIONAL TRANSITIONS AND OFFSETS IN ALL PIPING, DUCTWORK OR CONDUIT FOR COORDINATION
WITH BUILDING STRUCTURE AND CONSTRUCTION.
18. NO MECHANICAL OR ELECTRICAL SYSTEM COMPONENTS MAY BE SUPPORTED FROM STRUCTURAL BRACED
FRAMES.
RENOVATION
1. THIS PROJECT INVOLVES THE RENOVATION OF AN EXISTING FACILITY; BEFORE SUBMITTING THE BID,
CONTRACTORS SHALL VISIT THE SITE AND BECOME THOROUGHLY FAMILIAR WITH THE EXISTING CONDITIONS
UNDER WHICH THE PROJECT IS TO BE COMPLETED.
2. CONTRACTORS SHALL BE HELD RESPONSIBLE FOR ASSUMPTIONS, OMISSIONS OR ERRORS MADE AS A RESULT
OF FAILURE TO BECOME FULLY FAMILIAR WITH THE EXISTING CONDITIONS.
3. IT IS NOT THE INTENT OF THESE DOCUMENTS TO SHOW EVERY DEVICE, APPURTENANCE, PIPE, WIRE OR
CONDUIT TO BE REMOVED. MEP EQUIPMENT, UNITS, AND SYSTEMS NOT BEING REUSED, SHALL BE REMOVED IN
THEIR ENTIRETY INCLUDING ASSOCIATED HANGERS, SUPPORTS, BASES, PADS, PIPES, DUCTS, CONDUITS,
WIRES, INSULATION, AND CONTROLS BACK TO THE POINT OF ORIGIN.
4. EQUIPMENT, PIPING, OR CONDUIT SHALL NOT BE ABANDONED IN -PLACE UNLESS SPECIFICALLY SO NOTED.
5. PROPERLY DISPOSE OF DEMOLISHED EQUIPMENT IN COMPLIANCE WITH CODES, REGULATIONS, AND DEEP
STANDARDS. TURN OVER TO THE OWNER EQUIPMENT SO INDICATED.
6. RELOCATE EXISTING EQUIPMENT, DEVICES, PIPING, WIRING, AND RELATED SYSTEMS AS REQUIRED FOR
CONSTRUCTION PURPOSES. ALL EXISTING SYSTEMS SHALL BE FULLY OPERATIONAL, INCLUDING
RECONNECTION TO SERVICES AND UPGRADED SYSTEMS. ALL RELOCATED EQUIPMENT SHALL BE PROTECTED
DURING CONSTRUCTION,
7, PROVIDE TEMPORARY CONNECTIONS AND SYSTEM MODIFICATIONS AS REQUIRED FOR CONSTRUCTION AND
PHASING PURPOSES.
8. INCLUDE ALL WORK REQUIRED TO ALLOW PHASED CONSTRUCTION WHEN NECESSARY, COORDINATE WITH
GENERAL CONTRACTORICONSTRUCTION MANAGER FOR PHASING REQUIREMENTS.
9. ALL EXISTING EQUIPMENT, FIXTURES, AND DEVICES TO BE REMOVED AND RELOCATED SHALL BE FIELD VERIFIED
FOR EXACT QUANTITY AND CONDITION. KEEP AN ACCURATE RECORD OF STORED EQUIPMENT AND ITS
CONDITION.
10, REBALANCE NEW AND EXISTING MECHANICAL AND ELECTRICAL SYSTEMS ASSOCIATED WITH THE RENOVATION,
INCLUDING RENOVATED AREAS AND AREAS AFFECTED BY SYSTEM MODIFICATIONS.
11. SYSTEMS REQUIRING TO REMAIN IN OPERATION SHALL BE CAREFULLY PROTECTED FROM DAMAGE AND
CONTAMINATION BY THE CONSTRUCTION PROCESS.
ELECTRICAL
1. IT IS NOT THE INTENTION TO SHOW EVERY FITTING, WIRE, OR DEVICE. ALL SUCH ITEMS SHALL BE FURNISHED
AND INSTALLED AS NECESSARY FOR A COMPLETE SYSTEM.
2. UNLESS OTHERWISE NOTED, CONCEAL RACEWAYS IN FINISHED AREAS. RACEWAYS WITHIN MECHANICAL AND
ELECTRICAL ROOMS MAY BE SURFACE -MOUNTED.
3. PROVIDE POWER TO MECHANICAL EQUIPMENT SHOWN ON PLANS, RISERS, SCHEDULES, OR IN SPECIFICATIONS.
MECHANICAL EQUIPMENT IS NOT NECESSARILY SHOWN ON ELECTRICAL PLANS. REFER TO MECHANICAL PLANS
AND SCHEDULES ON MEP DRAWINGS FOR LOCATIONS AND SPECIFIC ELECTRICAL REQUIREMENTS.
COORDINATE EXACT LOCATION AND ORIENTATION OF EQUIPMENT WITH. OTHER TRADES.
4. PROVIDE INTERFACE CONNECTIONS TO THE FIRE ALARM SYSTEM AND FIRE PROTECTION SYSTEM EQUIPMENT
SHOWN ON PLANS, SCHEDULES, RISERS, OR IN SPECIFICATIONS. THIS EQUIPMENT IS NOT NECESSARILY
SHOWN ON ELECTRICAL PLANS. COORDINATE EXACT LOCATION AND QUANTITY WITH THE FIRE PROTECTION
CONTRACTOR.
5. PROVIDE BRANCH CIRCUITS FROM ELECTRICAL PANELS WITH SUFFICIENT CAPACITY AND SPACE FOR
MISCELLANEOUS SYSTEMS. FURNISH AND INSTALL ALL BRANCH CIRCUIT WIRING AND CIRCUIT BREAKERS FOR
THE EQUIPMENT SHOWN,
CODES LISTED BELOW APPLY TO ALL DRAWINGS AND SPECIFICATIONS ON THIS PROJECT
• MASSACHUSETTS STATE BUILDING CODE, 780 CMR - NINTH EDITION
• THE FOLLOWING AS REFERENCED AND MODIFIED BY THE ABOVE CODE:
0 2015 INTERNATIONAL BUILDING CODE (IBC) WITH MASSACHUSETTS AMENDMENTS PER 780 CMR
0 780 CMR 9.00 - FIRE PROTECTION SYSTEMS
• 527 CMR BOARD OF FIRE PREVENTION REGULATIONS
• 2012 NFPA 1 - CURRENTLY ADOPTED MA STATE MODEL CODE
• MASSACHUSETTS GENERAL LAW. CHAPTER 148 - FIRE PREVENTION - SECTION 26
0 780 CMR 13.00 - ENERGY EFFICIENCY AMENDMENTS
• 2015 INTERNATIONAL ENERGY CONSERVATION CODE (IECC)
• 2013 ANSI/ASHRAE/IESNA STANDARD 90.1 - ENERGY STANDARD FOR BUILDINGS EXCEPT
LOW-RISE RESIDENTIAL BUILDINGS
0 780 CMR CHAPTER 27.00 - ELECTRICAL
• 527 CMR CHAPTER 12 - MASSACHUSETTS ELECTRICAL CODE (AMENDMENTS)
• 527 CMR CHAPTER 27 - EMERGENCY AND STANDBY POWER SYSTEMS
• 2017 NFPA 70 - NATIONAL ELECTRICAL CODE (NEC)
• NFPA 110 - 2013
0 780 CMR 28,00 - MECHANICAL SYSTEMS
2015 INTERNATIONAL MECHANICAL CODE (IMC)
• 271 CMR 6.00 - UNIFORM SHEET METAL INSTALLATION RULES
0 780 CMR 29.00 - PLUMBING SYSTEMS
• 248 CMR CHAPTER 10 - MASSACHUSETTS UNIFORM STATE PLUMBING CODE
0 780 CMR 30.00 - ELEVATOR AND CONVEYING SYSTEMS
• 524 CMR - BOARD OF ELEVATOR REGULATIONS
• 2013 ASME A17.1 SAFETY CODE FOR ELEVATORS AND ESCALATORS
0 ACCESSIBILITY
• 521 CMR - MASSACHUSETTS ARCHITECTURAL ACCESS BOARD REGULATIONS
• MASSACHUSETTS GENERAL LAWS CHAPTER 22
• 2009 ICC/ANSI A117,1 - GUIDELINES FOR ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES
* THE JOINT COMMISSION
• THE AMERICANS WITH DISABILITY ACT, TITLE II, INCLUDING THE AMERICANS WITH DISABILITIES ACT
ACCESSIBILITY GUIDELINES (ADAAG) AND ADA REGULATIONS
• OCCUPATIONAL SAFETY AND HEALTH ACT, TITLE 29/LABOR
• GENERAL LAWS OF MASSACHUSETTS
GENERAL SYMBOLS
THICK, DARKSOLID LINES INDICATE NEW
OR RELOCATED ITEMS OR NEW RACEWAY
AND WIRING
THIN, LIGHT LINES INDICATE EXISTING ITEMS
OR RACEWAY TO REMAIN IN PLACE AND BE
REUSED
THICK, DASHED LINES INDICATE EXISTING
ITEMS TO BE REMOVED
POINT OF NEW TO EXISTING CONNECTION,
INCLUDING TRANSITIONS
SUB LETTERS "EX" INDICATES EXISTING
EQUIPMENT TO REMAIN INTACT
SUB LETTER "RE" INDICATES EXISTING
EQUIPMENT TO BE DISCONNECTED AND
REMOVED
SUB LETTER "RL" INDICATES EXISTING
EQUIPMENT TO BE DISCONNECTED,
REMOVED AND RELOCATED
SUB LETTER."NL" INDICATES NEW
LOCATION OF RELOCATED EQUIPMENT
SUB LETTER "NR" INDICATES NEW
EQUIPMENT TO REPLACE EXISTING
SUB LETTER "RR" INDICATES REMOVE
EQUIPMENT AND REPLACE ON NEW
SURFACE
* = a, b, clg, AF, GF IG OR TP. WHEN
TAGGED IN THE ELECTRICAL SYMBOL LIST,
REFER TO THE ABBREVIATION LIST
- -�-� -- -
EX
RE
RL
NL
NR
RR
*
ELECTRICAL SYMBOLS
LINEAR LIGHT FIXTURE
RECESSED DOWNLIGHT FIXTURE
CEILING OR WALL -MOUNTED EXIT LIGHT
FIXTURE
CEILING OR WALL -MOUNTED EMERGENCY
LIGHT UNIT
SINGLE -POLE SWITCH
3-WAY SWITCH
4-WAY SWITCH
POWER WIRING
- PANEL DESIGNATION
20A-1P HOME RUN (TYPICAL)
0
D
41
® 1
S
3
S
4
S
LV-1
a
HOME RUN
FEEDER TAG
SURFACEPANEL,
480Y/277OR ELECTRICAL480 OLT
V
SURFACE208Y/120OR ELECTRICAL208 VOLT PANEL,
FLUSH ELECTRICAL PANEL, 480Y/277 VOLT
FLUSH ELECTRICAL PANEL, 208Y/120 VOLT
ELECTRIC MOTOR
JUNCTION BOX
MASTER FIRE ALARM PULL BOX
FIRE ALARM CONTROL PANEL
FIRE ALARM REMOTE ANNUNCIATOR
SMOKE DETECTOR
COMBINATION SMOKE/CARBON MONOXIDE
DETECTR
HEAT DETECTOR
REMOTE INDICATOR
FIRE ALARM MANUAL PULL STATION
FIRE ALARM SPEAKER / STROBE
FIRE ALARM STROBE
FIRE ALARM CEILING -MOUNTED SPEAKER
MAGNETIC DOOR HOLD
[Nj.G)
ram,,..........__ i
_...A_
>_.__itanm..._..............1
i i
/CY
Q
u
[ANNJ
SjCO
fl
RI
��0F
Ell
El
Q
iI
Office of Planning
Design and Construction
McCormack Building
One Ashburton Place
Boston MA 02108
617 727 4050
www.mass.govlcam
Project Name:
SALEM SUPERIOR
COURT & COUNTY
COMMISSIONER
BUILDINGS WARM
MOTHBALLING
DCAMM Project Number
DCP1726 FC1
Project Location
32-34 FEDERAL ST,
SALEM, MA
01970
Project Archilecl
PERRY DEAN ROGERS PARTNERS
177 MILK STREET
BOSTON, MA 02109
T. 617-423-0100
F. 617-426-2274
www. perrydean.com
Project Consultant
A Iltsl. 12il li
Wart 417
kvIll
integrated
services
One Gateway Center, Suite 701
Newton, MA 02458
Tel: (617) 658-9008 www,bvhis.com
Professional Stamp
Site Number:
CAMIS Number:
Building Number:
Secretariat:
Original Issue Date
01/26/2018 BID DOCUMENTS
Revisions
Plan Name:
ELECTRICAL NOTES,
SYMBOLS AND
ABBREVIATIONS
Drawing Number:
EOOO
MAIN ELECTRICAL ROOM
GENERAL NOTES
1. COORDINATE EXACT LOCATIONS OF NEW SMOKE DETECTORS WITH
ARCHITECT AND FIRE DEPARTMENT PRIOR TO ROUGH -IN. VERIFY NEW
SMOKE COVERAGE IS ADEQUATE WITH FIRE DEPARTMENT.
DRAWING. NOTES
EXACT LOCATION OF ELEV. AND WHEELCHAIR LIFT DISCONNECT SWITCHES
SHALL BE VERIFIED INFIELD, SWITCHES SHALL BE PLACED IN THE OFF
POSITION AND SECURED WITH PADLOCK. KEY SHALL BE LABELED AND
HANDED OVER TO OWNER'S REPRESENTATIVE.
0
(7)
EX
DPB
BOILER CONTROL
PANEL
PROVIDE 20A,120V, 2#12&1#12GND -3/4"C
FEEDER FROM 20A/1P SPARE C/B IN
NEAREST 208/120V PANELBOARD.
NEW
EXHAUST
UNIT
EX
LB
7! V,14
V) ••;
(T POWER -BASEMENT
\71-09) 1/8" = 1.-0"
ii )
0
"
H
•
ETT
J
EX
ki EX
III LB-1
PPM.
EX
0
EX
H
f
1 EX
/ FOR INTRUSION
/ CONTROL PANEL.
COORD. EXACT
LOCATION WITH
SECURITY VENDOR.
EXISTING WHEELCHAIR
DISCONNECT SWITCH IS
MM. BELOW STAIRCASE.
1
EX
._i— 1 1 1
1 t _1
1 . 0 H \
EX__
E
EX X
AH EX
APPROXIMATE PATHWAY OF
NEW CONDUIT.
COORDINATE IN FIELD WITH
CONTRACTOR (TYPICAL).
111
NEW
EXHAUST
UNIT
NEW
EXHAUST
UNIT
iF
II7
1.:,1
C.;
NEW
EXHAUST
UNIT
EX
EX
L
0
to x
EX EX
ELEVATOR
DISCONNECT
SWITCH
I 0 1
EX
I
l!,/-1111-u EX EX EX
EX
2. ALL NEW SMOKE DETECTORS SHALL BE COMPATIBLE WITH EXISTING
BUILDING'S FIRE ALARM CONTROL PANEL, ALL NEW INITIATION DEVICES
SHALL BE WIRED BACK TO EXISTING CONTROL PANEL. EXTEND EXISTING
WIRING AS NECESSARY TO ACCOMMODATE RENOVATION. PANEL ZONING
SHALL ALSO BE EXTENDED AS NEEDED TO PROVIDE CAPACITY FOR NEW
DEVICES. COORDINATE WITH FIRE ALARM MANUFACTURER.
3, ALL CONDUIT PATHWAYS SHOWN ARE IN LOCATIONS WHERE
ABATEMENT IS NECESSARY. COORDINATE NEW ELECTRICAL AND/OR FIRE
ALARM CONDUIT ROUTING IN FIELD WITH ASBESTOS REMOVAL
CONTRACTOR, UNLESS OTHERWISE INDICATED ON PLANS, CONDUIT SHALL
BE MOUNTED ON WOOD STRAPPING. CONDUIT MOUNTING AND WOOD
STRAPPING INSTALLATION SHALL BE COORDINATE WITH
ARCHITECT/CONTRACTOR PRIOR TO INSTALLATION. IF CONDUIT ROUTING
NOT INDICATEDON PLANS, EXTEND EXISTING CONDUIT TO SERVE NEW
DEVICES.
4. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING
LOCATION AND QUANTITY OF ALL EXISTING PANELBOARDS.
5. ELECTRICAL CONTRACTOR SHALL TRACE ALL BRANCH CIRCUITS IN ALL
EXISTING PANELBOARDS.
6, CONTRACTOR SHALL PLACE IN THE OFF POSITION ALL EXITING C/B'S
SERVING RECEPTACLES AND NON -ESSENTIAL LIGHTING (ANY CIRCUITS
THAT DO NOT SERVE LIGHT FIXTURES IN THE MAIN CORRIDORS INDICATED
ON FLOOR PLANS).
7. ELECTRICAL CONTRACTOR SHALL PLACE IN THE OFF POSITION ALL
EXISTING C/B'S THAT SERVE HVAC EQUIPMENT NOT PART OF THE HEATING
SYSTEM. VERIFY WITH MECHANICAL CONTRACTOR ALL HVAC EQUIPMENT
THAT SHALL REMAIN IN USE.
EX
FX
ELC-B LC-B DPC
0
EX
rm •
EX
EX
1_1 EX
EX
EX \
EX [1
0
EX
EX
00
EX
F.
L
EXA
(
0
EF-1 I CONTROL PANEL
NEW
EXHAUST
UNIT
"EX
FIRE ALARM
NEW
EXHAUST EX
UNIT
--lI
-
0
ALL LIGHT FIXTURES, BATTERY LIGHT. UNITS, EXIT SIGNS, FIRE ALARM
DEVICES, AND ASSOCIATED WIRING AND RACEWAY WITHIN THE AREA SHALL
REMAIN AS. IS UNLESS OTHERWISE INIDICATED. ELECTRICAL CONTRACTOR
SHALL BE RESPONSIBLE FOR TRACING CIRCUITS BACK TO SOURCE. CIRCUIT
BREAKERS SERVING THE ABOVE ITEMS SHALL BE LEFT IN THE ON POSITION
AND CLEARLY LABELED AS LIGHTING CIRCUIT.
PROVIDE 30A-1P C/B IN NEAREST PANELBOARD. C/B SHALL SERVE NEW
EXHAUST FAN VIA 2#10 & 1#10 GND IN 3/4" CONDUIT. PROVIDE 25A FUSED
DISCONNECT SWITCH. ELEC. CONTRACTOR SHALL UTILIZE SPARE SPACE
WITHIN THE PANELBOARD. IF NO SPACE AVAILABLE, DISCONNECT AND
REMOVE ANY C/E3'S (SERVING EXISTING RECEPTACLES) THAT WERE PLACED
IN THE OFF POSITION. PROVIDE MOTOR CONTROLLERSAND/OR
COMBINATION DISCONNECT/MOTOR CONTROLLER AS REQUIRED
(COORDINATE WITH MECH. CONTRACTOR AND MANUFACTURER). ALL
CONDUIT PATHS SHALL BE COORDINATED WITH EXISTING CONDITIONS AND
ABATEMENT CONSULTANT/CONTRACTOR PRIOR TO ROUGH -IN.
PROVIDE 20A-1P C/B IN NEAREST PANELBOARD. C/B SHALL SERVE NEW
MOTORIZED DAMPER VIA 2#12 & 1#12 GND - 3/4" CONDUIT. PROVIDE
OVERCURRENT PROTECTION SWITCH. ELEC. CONTRACTOR SHALL UTILIZE
SPARE SPACE WITHIN THE PANELBOARD. IF NO SPACE AVAILABLE,
DISCONNECT AND UTILIZE A C/B(SERVING EXISTING RECEPTACLES) THAT
WAS PLACED IN THE OFF POSITION. PROVIDE MOTOR. CONTROLLERS AS
REQUIRED(COORDINATE WITH MECH. CONTRACTOR AND MANUFACTURER).
ALL CONDUIT PATHS SHALL BE COORDINATED WITH. EXISTING CONDITIONS
AND ABATEMENT CONSULTANT/CONTRACTOR PRIOR TO ROUGH -IN.
NEW. SMOKE.DETECTOR TO REPLACE EXISTING DEVICE UTILIZE EXISTING
JUNCTION BOX; CONDUIT, AND ASSOCIATED WIRING FOR NEW DETECTOR.
EXTEND. EXISTING WIRING AS NECESSARY TO ACCOMMODATE •
REPLACEMENT. • • •
NEW LIGHT SWITCH(ES) TO CONTROL ALL EXISTING LIGHT FIXTURES AS
INDICATED IN DESIGNATED PER FLOOR. SWITCH(ES) SHALL BE INSTALLED TO
HAVE BASIC ON/OFF CONTROL TO ALLOW SERVICE, SECURITY, POLICE,
AND/OR SFD PERSONNEL TO EASILY SWITCH ON/OFF BUILDING LIGHTS.
COORDINATE EXACT LOCATION OF SWITCHES WITH ARCHITECT AND FIRE
DEPARTMENT PRIOR TO INSTALLATION. EXTEND EXISTING BRANCH CIRCUIT
WIRING AND CONDUIT AND DISCONNECT ALL OTHER. EXISTING CONTROLS AS
NECESSARY TO ACCOMODATE NEW. SWITCHING SCHEME. CONTRACTOR
SHALL FIELD VERIFY COUNT AND LOAD OF EXISTING BRANCH CIRCUITS FOR
QUANTITY OF SWITCHES (SHOWN ON DWGS AS LOCATION REFERENCE
ONLY). CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING WIRING AND
CONDUIT TO ACCOMODATE ANY VOLTAGE DROP TO THE NEW SWITCH. ALL
CONDUIT PATHS AND BACK BOXES SHALL BE COORDINATED WITH EXISTING
CONDITIONS AND ABATEMENT CONSULTANT/CONTRACTOR PRIOR TO
ROUGH -IN. (B.00.: CONTRACTOR TO CARRY COST FOR FOUR BRANCH
CIRCUITS AND EACH CIRCUIT WITH (3)THREE WAY SWITCHES PER FLOOR).
Office of Planning
Design and Construction
McCormack Building
One Ashburton Place
Boston MA 02108
617 727 4050
vvvvw.mass.govicam
Project Name:
SALEM SUPERIOR
COURT & COUNTY
COMMISSIONER
BUILDINGS WARM
MOTHBALLING
DCAMM Project Number
DCP1726 FC1
Project Location
32-34 FEDERAL ST,
SALEM, MA
01970
Project Architect
PERRY DEAN ROGERS PARTNERS
177. MILK STREET
BOSTON, MA 02109
T. 617-423-0100
F. 617-426-2274
www.perrydean.com
Project Consultant •
ENHI
integrated
services
One Gateway Center, Suite 701
Newton, MA 02458
Tel: (617) 658-9008 www.bvhis.com
(
Professional Stamp
Site Number:
CAMIS Number:
Building Number:
Secretariat:
Original Issue Date
01/26/2018 BID DOCUMENTS
Revisions
Plan Name:
BASEMENT ELECTRICAL
POWER PLAN
Drawing Number:
EPI -00
GENERAL NOTES
DRAWING NOTES
NEW
EXHAUST
UNIT
APPROXIMATE PATHWAY OF NEW
CONDUIT. COORDINATE IN FIELD
WITH CONTRACTOR (TYPICAL).
EXISTING TO
REMAIN
KNOX BOX __W.
POWER -LEVEL 1
118" = 1'-0"
0 I--
1
EX
EX
ALL CONDUIT WITHIN THIS
CORRIDOR SHALL BE
MOUNTED ON BRICK WALL
NEW
EXHAUST
UNIT
NEW
EXHAUST
UNIT
NEW
EXHAUST
UNIT
1 COORDINATE EXACT LOCATIONS OF NEW SMOKE DETECTORS WITH
ARCHITECT AND FIRE DEPARTMENT PRIOR TO ROUGH -IN. VERIFY NEW
SMOKE COVERAGE IS ADEQUATE WITH FIRE DEPARTMENT,
2. ALL NEW SMOKE DETECTORS SHALL BE COMPATIBLE WITH EXISTING
BUILDING'S FIRE ALARM CONTROL PANEL. ALL NEW INITIATION DEVICES
SHALL BE WIRED BACK TO EXISTING CONTROL PANEL. EXTEND EXISTING
WIRING AS NECESSARY TO ACCOMMODATE RENOVATION. PANEL ZONING
SHALL ALSO BE EXTENDED AS NEEDED TO PROVIDE CAPACITY FOR NEW
DEVICES. COORDINATE WITH FIRE ALARM MANUFACTURER.
3. ALL CONDUIT PATHWAYS SHOWN ARE IN LOCATIONS WHERE
ABATEMENT IS NECESSARY. COORDINATE NEW ELECTRICAL AND/OR FIRE
ALARM CONDUIT ROUTING IN FIELD WITH ASBESTOS REMOVAL
CONTRACTOR. UNLESS OTHERWISE INDICATED ON PLANS, CONDUIT SHALL
BE MOUNTED ON WOOD STRAPPING. CONDUIT MOUNTING AND WOOD
STRAPPING INSTALLATION SHALL BE COORDINATE WITH
ARCHITECT/CONTRACTOR PRIOR TO INSTALLATION, IF CONDUIT ROUTING
NOT INDICATEDON PLANS, EXTEND EXISTING CONDUIT TO SERVE NEW
DEVICES. .
4. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING
LOCATION AND QUANTITY OF ALL EXISTING PANELBOARDS.
5. ELECTRICAL CONTRACTOR SHALL TRACE ALL BRANCH CIRCUITS IN ALL
EXISTING PANELBOARDS.
6. CONTRACTOR SHALL PLACE IN THE OFF POSITION ALL EXITING C/B'S
SERVING RECEPTACLES AND NON -ESSENTIAL LIGHTING (ANY CIRCUITS
THAT DO NOT SERVE LIGHT FIXTURES IN THE MAIN CORRIDORS INDICATED
ON FLOOR PLANS).
7. ELECTRICAL CONTRACTOR SHALL PLACE IN THE OFF POSITION ALL
EXISTING C/B'S THAT SERVE HVAC EQUIPMENT NOT PART OF THE HEATING
SYSTEM. VERIFY WITH MECHANICAL CONTRACTOR ALL HVAC EQUIPMENT
THAT SHALL REMAIN IN USE.
, NEW
EXHAUST
UNIT
NEW
EXHAUST
UNIT
EXACT LOCATION OF ELEV. AND WHEELCHAIR LIFT DISCONNECT SWITCHES
SHALL BE VERIFIED IN FIELD. SWITCHES SHALL BE PLACED IN THE OFF
POSITION AND SECURED WITH PADLOCK KEY SHALL BE LABELED AND
HANDED OVER TO OWNERS REPRESENTATIVE.
ALL LIGHT FIXTURES, BATTERY LIGHT UNITS, EXIT SIGNS, FIRE ALARM
DEVICES, AND ASSOCIATED WIRING AND RACEWAY WITHIN THE AREA SHALL
REMAIN AS IS UNLESS OTHERWISE INDICATED. ELECTRICAL CONTRACTOR
SHALL BE RESPONSIBLE FOR TRACING CIRCUITS BACK TO SOURCE. CIRCUIT
BREAKERS: SERVING THE ABOVE ITEMS SHALL BE LEFT IN THE ON POSITION
AND CLEARLY LABELED AS LIGHTING CIRCUIT.
PROVIDE 30A-1 P C/B IN. NEAREST PANELBOARD. C/B SHALL SERVE NEW
EXHAUST FAN VIA 2#1O & 1#1O GND IN 3/4" CONDUIT. PROVIDE 25A FUSED
DISCONNECT SWITCH.. ELEC. CONTRACTOR SHALL UTILIZE SPARE SPACE
WITHIN THE PANELBOARD. IF NO SPACE AVAILABLE, DISCONNECT AND
REMOVE ANY C/B'S (SERVING EXISTING RECEPTACLES) THAT WERE PLACED
IN THE OFF POSITION. PROVIDE MOTOR CONTROLLERS AND/OR
COMBINATION DISCONNECT/MOTOR CONTROLLER AS REQUIRED
(COORDINATE WITH MECH. CONTRACTOR AND MANUFACTURER). ALL
CONDUIT PATHS SHALL BE COORDINATED WITH EXISTING CONDITIONS AND
ABATEMENT CONSULTANT/CONTRACTOR PRIOR TO ROUGH -IN.
PROVIDE 20A-1P C/B IN NEAREST PANELBOARD. C/B SHALL SERVE NEW
MOTORIZED DAMPER VIA 2#12 & 1#12 GND - 3/4" CONDUIT. PROVIDE
OVERCURRENT PROTECTION SWITCH. ELEC. CONTRACTOR SHALL UTILIZE
SPARE SPACE WITHIN THE PANELBOARD. IF NO SPACE AVAILABLE,
DISCONNECT AND UTILIZE A C/B(SERVING EXISTING RECEPTACLES) THAT
WAS PLACED IN THE OFF POSITION. PROVIDE MOTOR CONTROLLERS AS
REQUIRED(COORDINATE WITH MECH. CONTRACTOR AND MANUFACTURER).
ALL CONDUIT PATHS SHALL BE COORDINATED WITH EXISTING CONDITIONS
AND ABATEMENT CONSULTANT/CONTRACTOR PRIOR TO ROUGH -IN.
NEW SMOKE DETECTOR TO REPLACE EXISTING DEVICE. UTILIZE EXISTING
JUNCTION BOX, CONDUIT, AND ASSOCIATED WIRING FOR NEW DETECTOR.
EXTEND EXISTING WIRING AS NECESSARY TO ACCOMMODATE
REPLACEMENT.
NEW LIGHT SWITCH(ES) TO CONTROL ALL EXISTING LIGHT FIXTURES AS
INDICATED IN DESIGNATED PER FLOOR. SWITCH(ES) SHALL BE INSTALLED TO
HAVE BASIC ON/OFF CONTROL TO ALLOW. SERVICE, SECURITY, POLICE,
AND/OR SFD PERSONNEL TO EASILY SWITCH ON/OFF BUILDING LIGHTS.
COORDINATE EXACT LOCATION OF SWITCHES WITH ARCHITECT AND FIRE
DEPARTMENT PRIOR TO INSTALLATION. EXTEND EXISTING BRANCH CIRCUIT
WIRING AND CONDUIT AND DISCONNECT ALL OTHER EXISTING CONTROLS AS
NECESSARY TO ACCOMODATE NEW SWITCHING SCHEME. CONTRACTOR
SHALL FIELD VERIFY COUNT AND LOAD OF EXISTING BRANCH CIRCUITS FOR
QUANTITY OF SWITCHES (SHOWN ON DWGS:AS LOCATION REFERENCE
ONLY). CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING WIRING AND
CONDUIT TO ACCOMODATE ANY VOLTAGE DROP TO THE NEW SWITCH. ALL
CONDUIT PATHS AND BACK BOXES SHALL BE COORDINATED WITH EXISTING
CONDITIONS AND ABATEMENT CONSULTANT/CONTRACTOR PRIOR TO
ROUGH -IN, (B.O.D.: CONTRACTOR TO CARRY COST FOR FOUR BRANCH
CIRCUITS AND EACH CIRCUIT WITH (3)THREE WAY SWITCHES PER FLOOR).
Office of Planning
Design and Construction
McCormack Building
One Ashburton Place
Boston MA 02108
617 727 4050
wwvv.mass.gov/cam
Project Name:
SALEM SUPERIOR
COURT & COUNTY
COMMISSIONER
BUILDINGS WARM
MOTHBALLING
DCAMM Project Number
DCP1726 FC7
Project Location
32-34 FEDERAL ST,
SALEM, MA
01970
Project Architect
PERRY DEAN ROGERS PARTNERS
177 MILK STREET
BOSTON, MA 02109
T. 617-423-0100
F. 617-426-2274
www.perrydean.com
Project Consultant
17 ;II 1117
Elli1H1
integrated
services
One Gateway Center, Suite 701
Newton, MA 02458
Tel: (617) 658-9008 www.bvhis.Com
Professional Stamp
J
Site Number:
CAMIS Number:
Building Number:
Secretariat:
Original Issue Date
01/26/2018 BID DOCUMENTS
Revisions
Plan Name:
LEVEL 'l ELECTRICAL
POWER PLAN
Drawing Number:
EPIOl
GENERAL NOTES
DRAWING. NOTES
NEW
EXHAUST
UNIT
POWER -LEVEL 2
-- 1/8" = 1 t-Or' -..
EX
EF-1
NEW
EXHAUST
UNIT
4
L
L- I
o-t
1
4
EX
APPROXIMATE PATHWAY OF NEW
CONDUIT. COORDINATE IN FIELD (TYPICAL).
NEW
EXHAUST
UNIT
J
EX
EX
Ho r ---
EX EX'‘,
EEC EX
LC-2 AC-1
1. COORDINATE EXACT LOCATIONS OF NEW SMOKE DETECTORS WITH
ARCHITECT AND. FIRE DEPARTMENT PRIOR TO ROUGH -IN. VERIFY NEW
SMOKE COVERAGE IS ADEQUATE WITH FIRE DEPARTMENT.
2. ALL NEW SMOKE DETECTORS SHALL BE COMPATIBLE WITH EXISTING
BUILDING'S FIRE ALARM CONTROL PANEL ALL NEW INITIATION DEVICES
SHALL BE WIRED BACK TO EXISTING CONTROL PANEL. EXTEND EXISTING
WIRING AS NECESSARY TO ACCOMMODATE RENOVATION. PANEL ZONING
SHALL ALSO BE EXTENDED AS NEEDED TO PROVIDE CAPACITY FOR NEW
DEVICES. COORDINATE WITH FIRE ALARM MANUFACTURER.
3. ALL CONDUIT PATHWAYS SHOWN ARE IN LOCATIONS WHERE
ABATEMENT IS NECESSARY. COORDINATE NEW ELECTRICAL AND/OR FIRE
ALARM CONDUIT ROUTING IN FIELD WITH ASBESTOS REMOVAL
CONTRACTOR. UNLESS OTHERWISE INDICATED ON PLANS, CONDUIT SHALL
BE MOUNTED ON. WOOD STRAPPING. CONDUIT MOUNTING AND WOOD
STRAPPING INSTALLATION SHALL BE: COORDINATE WITH
ARCHITECT/CONTRACTOR PRIOR TO INSTALLATION. IF CONDUIT ROUTING
NOT INDICATEDON PLANS, EXTEND EXISTING CONDUIT TO SERVE NEW
DEVICES.
4, ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING
LOCATION AND QUANTITY OF ALL EXISTING PANELBOARDS.
5. ELECTRICAL CONTRACTOR SHALL TRACE ALL BRANCH CIRCUITS IN ALL
EXISTING PANELBOARDS,
6. CONTRACTOR SHALL PLACE IN THE OFF POSITION ALL EXITING C/B'S
SERVING RECEPTACLES AND NON -ESSENTIAL LIGHTING (ANY CIRCUITS
THAT DO NOT SERVE LIGHT FIXTURES IN THE MAIN CORRIDORS INDICATED
ON FLOOR PLANS).
7. ELECTRICAL CONTRACTOR SHALL PLACE IN THE OFF POSITION ALL
EXISTING C/B'S THAT SERVE HVAC EQUIPMENT NOT PART OF THE HEATING
SYSTEM, VERIFY WITH MECHANICAL CONTRACTOR ALL HVAC EQUIPMENT
THAT SHALL REMAIN IN USE.
l—,
EX
NEW
EXHAUST
UNIT
NEW
EXHAUST
UNIT
[[]
EX
1
0
0
EXACT LOCATION OF ELEV. AND WHEELCHAIR LIFT DISCONNECT SWITCHES
SHALL BE VERIFIED IN FIELD. SWITCHES SHALL BE PLACED IN THE OFF
POSITION AND SECURED WITH PADLOCK.. KEY SHALL BE LABELED AND
HANDED OVER TO OWNER'S REPRESENTATIVE:
ALL LIGHT FIXTURES,BATTERY LIGHT UNITS, EXIT SIGNS, FIRE ALARM
DEVICES, AND ASSOCIATED WIRING AND RACEWAY WITHIN THE AREA SHALL
REMAIN AS IS UNLESS OTHERWISE: INDICATED. ELECTRICAL CONTRACTOR
SHALL BE RESPONSIBLE. FOR TRACING CIRCUITS BACK TO SOURCE. CIRCUIT
BREAKERS SERVING THE ABOVE ITEMS SHALL BE LEFT IN THE ON POSITION
AND CLEARLY LABELED AS LIGHTING CIRCUIT.
PROVIDE 30A-1P C/B IN NEAREST PANELBOARD. C/B SHALL SERVE NEW
EXHAUST FAN VIA 2#10 & 1#10 GND IN 3/4" CONDUIT. PROVIDE 25A FUSED
DISCONNECT SWITCH. ELEC. CONTRACTOR SHALL UTILIZE SPARE SPACE
WITHIN THE PANELBOARD, IF NO SPACE AVAILABLE, DISCONNECT AND
REMOVE ANY C/B'S (SERVING EXISTING RECEPTACLES) THAT WERE PLACED
IN THE OFF POSITION, PROVIDE MOTOR CONTROLLERS AND/OR
COMBINATION DISCONNECT/MOTOR CONTROLLER AS REQUIRED
(COORDINATE WITH MECH. CONTRACTOR AND MANUFACTURER). ALL
CONDUIT PATHS SHALL BE. COORDINATED WITH EXISTING CONDITIONS AND
ABATEMENT. CONSULTANT/CONTRACTOR PRIOR TO ROUGH -IN,
PROVIDE 20A-1 P C/B IN NEAREST PANELBOAR. C/B SHALL SERVE NEW
MOTORIZED DAMPER VIA 2#12 & 1#12 GND - 3/4" CONDUIT. PROVIDE
OVERCURRENT PROTECTION SWITCH. ELEC, CONTRACTOR. SHALL UTILIZE
SPARE SPACE WITHIN THE PANELBOARD. IF NO SPACE AVAILABLE,
DISCONNECT AND UTILIZE A C/B(SERVING EXISTING RECEPTACLES) THAT
WAS PLACED IN THE OFF POSITION. PROVIDE MOTOR. CONTROLLERS AS
REQUIRED(COORDINATE WITH MECH. CONTRACTOR. AND MANUFACTURER).
ALL CONDUIT PATHS SHALL BE COORDINATED WITH EXISTING CONDITIONS
AND ABATEMENT CONSULTANT/CONTRACTOR PRIOR TO ROUGH -IN.
NEW SMOKE DETECTOR TO REPLACE EXISTING DEVICE. UTILIZE EXISTING
JUNCTION BOX, CONDUIT, AND ASSOCIATED WIRING FOR NEW DETECTOR.
EXTEND EXISTING WIRING AS NECESSARY TO ACCOMMODATE
REPLACEMENT. .
NEW LIGHT SWITCH(ES) TO CONTROL ALL EXISTING LIGHT FIXTURES AS
INDICATED IN DESIGNATED PER FLOOR. SWITCH(ES) SHALL BE INSTALLED TO
HAVE BASIC ON/OFF CONTROL TO ALLOW SERVICE, SECURITY, POLICE,
AND/OR SFD PERSONNEL TO EASILY SWITCH ON/OFF BUILDING LIGHTS.
COORDINATE EXACT LOCATION. OF SWITCHES WITH ARCHITECT AND FIRE
DEPARTMENT PRIOR TO INSTALLATION: EXTEND EXISTING BRANCH CIRCUIT
WIRING AND CONDUIT AND DISCONNECT ALL OTHER EXISTING CONTROLS AS
NECESSARY TO ACCOMODATENEW SWITCHING SCHEME. CONTRACTOR
SHALL FIELD VERIFY COUNT AND LOAD OF EXISTING BRANCH CIRCUITS FOR
QUANTITY OF SWITCHES (SHOWN ON DINGS AS LOCATION REFERENCE
ONLY). CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING WIRING AND
CONDUIT TO ACCOMODATE ANY VOLTAGE DROP TO THE NEW SWITCH. ALL
CONDUIT PATHS AND BACK BOXES SHALL BE COORDINATED WITH EXISTING
CONDITIONS AND ABATEMENT CONSULTANT/CONTRACTOR PRIOR TO
ROUGH -IN, (B.O.D.: CONTRACTOR TO CARRY COST FOR FOUR BRANCH
CIRCUITS AND EACH CIRCUIT WITH (3)THREE WAY SWITCHES PER FLOOR).
Office of Planning
Design and Construction
McCormack Building
One Ashburton Place
Boston MA 02108
617 727 4050
www.mass.govlcam
Project Name:
SALEM SUPERIOR
COURT & COUNTY
COMMISSIONER
BUILDINGS WARM
MOTHBALLING
DCAMM Project Number
DCP1726 FC1
Project Location
32-34 FEDERAL ST,
SALEM, MA
01970
Project Architect
PERRY DEAN ROGERS PARTNERS
177 MILK STREET
BOSTON, MA 02109
T. 617-423-0100
F. 617-426-2274
www.perrydean.com
Project Consullan
BVH
integrated
services
One Gateway Center, Suite 701
Newton, MA 02458
Tel: (617) 658-9008 www.bvhis.com
Professional Stamp
Site. Number:
CAM1S Number:
Building Number:
Secretariat:
Original Issue Date
01/26/2018 BID DOCUMENTS
Revisions
Plan Name:
LEVEL 2 ELECTRICAL
POWER PLAN
Drawing Number:
EP1 -02
L
POWER -LEVEL 3
1/8" = 1 t_O"
NEW
EXHAUST
UNIT
0
APPROXIMATE LOCATION OF
NEW CONDUIT.
COORDINATE IN FIELD WITH
CONTRACTOR (TYPICAL)
EX
EX
r__
GENERAL NOTES
1. COORDINATE EXACT LOCATIONS OF NEW SMOKE DETECTORS WITH
ARCHITECT AND FIFRE DEPARTMENT PRIOR TO ROUGH -IN. VERIFY NEW
SMOKE COVERAGE IS ADEQUATE WITH FIRE DEPARTMENT:
2. ALL NEW SMOKE DETECTORS SHALL BE COMPATIBLE WITH EXISTING
BUILDING'S FIRE ALARM CONTROL PANEL. ALL NEW INITIATION DEVICES
SHALL BE. WIRED BACK TO EXISTING CONTROL PANEL. EXTEND EXISTING
WIRING AS NECESSARY TO ACCOMMODATE RENOVATION. PANEL ZONING
SHALL ALSO BE EXTENDED AS NEEDED TO PROVIDE CAPACITY FOR NEW
DEVICES. COORDINATE WITH FIRE ALARM MANUFACTURER..
3, ALL CONDUIT PATHWAYS SHOWN ARE IN LOCATIONS WHERE
ABATEMENT IS NECESSARY. COORDINATE NEW ELECTRICAL AND/OR FIRE
ALARM CONDUIT ROUTING IN FIELD.WITH ASBESTOS REMOVAL
CONTRACTOR. UNLESS OTHERWISE INDICATED ON PLANS, CONDUIT SHALL
BE MOUNTED.ON WOOD STRAPPING. CONDUIT MOUNTING AND WOOD
STRAPPING INSTALLATION SHALL BE COORDINATE WITH
ARCHITECT/CONTRACTOR PRIOR'TO INSTALLATION. IF CONDUIT ROUTING
NOT INDICATEDON PLANS, EXTEND EXISTING CONDUIT TO SERVE NEW
DEVICES. •
4. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING
LOCATION AND QUANTITY OF ALL EXISTING PANELBOARDS.
5. ELECTRICAL CONTRACTOR SHALL TRACE ALL BRANCH CIRCUITS IN ALL
EXISTING PANELBOARDS.
6. CONTRACTOR SHALL PLACE IN THE OFF POSITION ALL EXITING CIB'S
SERVING RECEPTACLES AND NON -ESSENTIAL LIGHTING (ANY CIRCUITS
THAT DO NOT SERVE LIGHT FIXTURES IN THE MAIN CORRIDORS INDICATED
ON FLOOR PLANS). -
7. ELECTRICAL CONTRACTOR SHALL PLACE IN THE OFF POSITION ALL
EXISTING CIB'S THAT SERVE HVAC EQUIPMENT NOT PART OF THE HEATING
SYSTEM. VERIFY WITH MECHANICAL CONTRACTOR ALL HVAC EQUIPMENT
THAT SHALL REMAIN IN USE,
LJ
0
:WJ
DRAWING NOTES
EXACT LOCATION OF ELEV. AND WHEELCHAIR LIFT DISCONNECT. SWITCHES
SHALL BE VERIFIED IN FIELD. SWITCHES SHALL BE PLACED IN THE OFF
POSITION AND SECURED WITH PADLOCK. KEY SHALL BE LABELED AND
HANDED OVER TO OWNER'S REPRESENTATIVE .
ALL LIGHT FIXTURES,BATTERY LIGHT UNITS, EXIT, SIGNS, FIRE ALARM
DEVICES, AND ASSOCIATED WIRING AND RACEWAY WITHIN THE AREA SHALL
REMAIN AS IS UNLESS OTHERWISE INDICATED. ELECTRICAL CONTRACTOR
SHALL BE RESPONSIBLE FOR TRACING CIRCUITS BACK TO SOURCE. CIRCUIT
BREAKERS SERVING THE ABOVE ITEMS SHALL BE LEFT IN THE ON POSITION
AND CLEARLY LABELED AS LIGHTING CIRCUIT.
PROVIDE 30A-1 P C/B IN NEAREST PANELBOARD. C/B SHALL SERVE NEW
EXHAUST FAN VIA 2#10 & 1#10 GND IN 3/4" CONDUIT. PROVIDE 25A FUSED
DISCONNECT SWITCH. ELEC. CONTRACTOR SHALL UTILIZE SPARE SPACE
WITHIN THE PANELBOARD. IF NO SPACE AVAILABLE, DISCONNECT AND
REMOVE ANY GIB''S (SERVING EXISTING RECEPTACLES) THAT WERE PLACED
IN THE OFF POSITION. PROVIDE MOTOR CONTROLLERS AND/OR
COMBINATION DISCONNECT/MOTOR CONTROLLER AS REQUIRED
(COORDINATE WITH MECH. CONTRACTOR AND MANUFACTURER). ALL
CONDUIT PATHS SHALL BE COORDINATED WITH EXISTING CONDITIONS AND
ABATEMENT CONSULTANT/CONTRACTOR PRIOR TO ROUGH -IN,
PROVIDE 20A-1 P C/B IN NEAREST PANELBOARD. C/B SHALL SERVE NEW
MOTORIZED DAMPER VIA 2#12 & 1#12 GND - 3/4" CONDUIT. PROVIDE
OVERCURRENT PROTECTION SWITCH, ELEC. CONTRACTOR SHALL UTILIZE
SPARE SPACE WITHIN THE PANELBOARD. IF NO SPACE AVAILABLE,
DISCONNECT AND UTILIZE A C/B(SERVING EXISTING RECEPTACLES) THAT
WAS PLACED IN THE OFF POSITION. PROVIDE MOTOR CONTROLLERS AS
REQUIRED(COORDINATEWITH MECH. CONTRACTOR AND MANUFACTURER).
ALL CONDUIT PATHS SHALL BE COORDINATED WITH EXISTING CONDITIONS
AND ABATEMENT CONSULTANT/CONTRACTOR PRIOR TO ROUGH -IN.
NEW SMOKE DETECTOR TO REPLACE EXISTING DEVICE: UTILIZE EXISTING
JUNCTION BOX, CONDUIT, AND ASSOCIATED WIRING FOR NEW DETECTOR.
EXTEND EXISTING WIRING AS NECESSARY TO ACCOMMODATE
REPLACEMENT.
NEW LIGHT SWITCHES) TO CONTROL ALL EXISTING LIGHT FIXTURES AS
INDICATED IN DESIGNATED PER FLOOR. SWITCH(ES) SHALL BE INSTALLED TO
HAVE BASIC ON/OFF CONTROL TO ALLOW SERVICE, SECURITY, POLICE,
AND/OR SFD PERSONNEL TO EASILY SWITCH ON/OFF BUILDING LIGHTS..
COORDINATE EXACT LOCATION OF SWITCHES WITH ARCHITECT AND FIRE
DEPARTMENT PRIOR TO INSTALLATION. EXTENDEXISTING BRANCH CIRCUIT
WIRING AND CONDUIT AND DISCONNECT ALL OTHER EXISTING CONTROLS AS
NECESSARY TO ACCOMODATE NEW SWITCHING SCHEME. CONTRACTOR
SHALL FIELD VERIFY COUNT AND LOAD OF EXISTING BRANCH CIRCUITS FOR
QUANTITY OF SWITCHES (SHOWN ON DINGS AS LOCATION REFERENCE
ONLY). CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING WIRING AND
CONDUIT TO ACCOMODATE ANY VOLTAGE DROP TO THE NEW SWITCH, ALL
CONDUIT PATHS AND BACK BOXES SHALL BE COORDINATED WITH EXISTING
CONDITIONS AND ABATEMENT CONSULTANT/CONTRACTOR PRIOR TO
ROUGH -IN. (B.O.D.: CONTRACTOR TO CARRY COST FOR FOUR BRANCH
CIRCUITS AND EACH CIRCUIT WITH (3)THREE WAY SWITCHES PER FLOOR).
Office of Planning
Design and Construction
McCormack Building
One Ashburton Place
Boston MA 02108
617 727 4050
www.mass.govlcam
Project Name:
SALEM SUPERIOR
COURT & COUNTY
COMMISSIONER
BUILDINGS WARM
MOTHBALLING
DCAMM Project Number
DCP1726 FCI
Project Location
32-34 FEDERAL ST,
SALEM, MA
01970
Project Architect
PERRY DEAN ROGERS PARTNERS
177 MILK STREET
BOSTON, MA 02109
T. 617-423-0100
F. 617-426-2274
www.perrydean.com
Project G.hint
all 11 .t►
'141.11-
131/11
integrated
services
One Gateway Center, Suite 701
Newton, MA 02458
Tel: (617) 658-9008 www.bvhis.com
1
Professional Stamp
Site Number:
CAMIS Number:
Building Number:
Secretariat:
Original Issue Date
01/26/2018 BIDDOCUMENTS
Revisions
Plan Name:
LEVEL 3 ELECTRICAL
POWER PLAN
Drawing Number:
E-!Pi-03
ii 711.€ ii; l: Ili
� Vr[ I Ifj
I H
If i I'1 1
�_1`l fl.l_ tl�t�ll,It.- 1
LI.II.i',_•I
I1
1 � I 1 .,
� `3 1.L.Lil 1 I I i f l
€Ii E 1 111
L 1 "T.`i T 1—r� i L i h t
1_,_:_ 1 LI 1-,11 11 L.L�__l.Lf�.!
j J. 11f 1
?tI t11 11J LL1"1t1
Ii rTfEtiI.;Ii
T i i1_I €1Li_I 1 '
Ll 1 I i! L l T 1 L
- —L-T T 1 13 1 1:
I I I,' I_ €1 11
I i -
1 1_: 1 1 1,
Li IT:
1.
1 1 1 _.il _.� :=�111 i'ill,_:l_iII1
11 t i 1, 1_LI1
.-111-Ft`11
]tiJ__Tj_ Ii_1_Et
€l T-1T1 €I l 1
1_ITL L 1 t_
€IiII1T JI 11I'
�1....L_I. 1.1
1 �T= t [ ICI, 1
1,1 1.1. L.
LI.1"Li 1.1
(1 IJ_11
H.
T=`_1 1 .I..1 RE• -
LI#° 1_
I.i1_
DISCONNECT AND REMOVE OVERCURRENT-,
PROTECTION DEVICE AND POWER FEED TO
—EXISTING TO BE REMOVED CONDENSER UNITS.
REMOVE FEEDER'S ASSOCIATED WIRING AND
-__RACEWAY BACK TO SOURCE. PLACE BREAKER IN
OFF POSITION AND LABEL AS SPARE.
1I
J1€IiL
I. 1.. IiJT[
1 111J..1_.f _-
III 1'1I [I<Iii-f�l)Ilil 1
1
I°1 i 111 1=i�1I.� ,.11i :li{1,I.lt. i
0) POWER DEMO -ROOF
1/8" = 1'-0"
;_! < <<;.ii._..1
i__ . n..i. .l E I•I L I �I 1i,il< i';11 <
Iiii;i I;I.
f IlrllaL lI; ti�.._�=l ll€`_ •1�. 1T`IIIITI r��I T 11 1 1_ fl 3 1 t�l 1`1 1 I '"
f j ! ili li; I E) i iiE it l 11_i I .11lll I!i i �I
.I. - J J_l ! 1 ; 1 I Li_ 1.. J. I . __ t `. I . .t t l .l ' i
j"j"' I. 1 i i" I. i, I I I J f-_I ` € 1 I I;L-,'<
1 s i° 1 1 l 1 .1 "I i 1_ i "l € I �i 1 [ I I 11
I I 1-111 1 I I I1 1 1 j i [i , i , ,
F_{ I I I t 1 , ' ; , 1. 1. € ? .L 1 '
-1 i
RE ..
;. 1
JI
1;11TT
-Ell 11 I J
1-r
1 I d3._L_I1. l f ?
1�iff
T Z;m u ILLLLl..
T l
LTT 1.1 '. 1.� i L�
ii`f"lit€ELT_.
1 .1 l..I i1 I.11
L1T1T i
LI 11• SElimT 1
;
11
i i_ L E I .. I I T._ 1 r.
€I LLIi1._:1 .il.i .lIT+11
i 1 1E .1. I. L_i, t
-1.1 1. ;—
_I__i _I,l..11
it
1i13_`i -}
Li. ': 1 T T
I i
.. l 1
I11
1
}
_L
Office of Planning
Design and Construction
McCormack Building
One Ashburton Place
Boston MA 02108
617 727 4050
Project Name:
SALEM SUPERIOR
COURT & COUNTY
COMMISSIONER
BUILDINGS WARM
MOTHBALLING
DCAMM Project Number
Project Location
32 34 FEDERAL ST,
SALEM, MA
01970
Project Architect
PERRY DEAN ROGERS PARTNERS
177 MILK STREET
BOSTON, MA 02109
T. 617-423-0100
F. 617-426-2274
Project Co-nsultarl
17111 FIr
131/11
integated
services
One Gateway Center, Suite 701
Newton, MA 02458
Tel: (617) 658-9008 www.bvhis.com
Professional Stamp
Site Number:
CAMIS Number:
Building Number:
Secretariat:
Original Issue Date
01/26/2018 BID DOCUMENTS
Revisions
Plan Name:
ROOF ELECTRICAL
POWER DEMOLITION
PLAN
Drawing Number:
EPD 04
TYPICAL EXISTING FIRE ALARM
SPEAKER STROBE UNIT
TYPICAL EXISTING FIRE
ALARM STROBE UNIT
EX
EX
EXISTING WRING. EXTEND
WIRING AS NECESSARY TO
ACCOMODATE RENOVATION.
EX
NEW BATTERIES SHALL BE PROVIDED
FOR EXISTING TO REMAIN SYSTEM.
REFER TO SPECIFICATIONS FOR
FURTHER INFORMATION.
EX
EXISTING
FCI 7200
FACP
BATTERIES
EX
FIRE ALARM RISER
NOT TO SCALE
C
EX
TYPICAL EXISITNG SMOKE DETECTOR
TYPICAL EXISTING MANUAL PULL STATION
TYPICAL NEW SMOKE DETECTOR.
/
NEW DEVICE SHALL BE COMPATIBLE
WITH EXISTING SYSTEM.
FIRE ALARM RISER GENERAL NOTES
1. SEE SECTION 260001 SPECIFICATION FOR ADDITIONAL INFORMATION.
2. DEVICES AND CIRCUITS ARE ILLUSTRATED FOR TYPICAL ARRANGEMENT ONLY.
REFER TO PLANS AND DETAILS FOR QUANTITIES AND TYPES OF DEVICES.
3. PROVIDE ADDRESSABLE INTERFACE DEVICES AS REQUIRED. DEVICES ARE NOT
SPECIFICALLY INDICATED ON PLANS OR RISER.
4, PROVIDE WIRING PER APPROVED MANUFACTURER'S DIRECTION.
5. ALL WIRING IS IN RACEWAY.
6. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING EXISTING BATTERY
CAPACITY FOR ENTIRE SYSTEM AND PROVIDING NEW BATTERIES AS REQUIRED
TO MAINTAIN CODE COMPLAINT SYSTEM.
7. CONTRACTOR SHALL PROVIDE ALL CARDS, CONNECTIONS, BATTERIES,
ACCESSORIES, PROGRAMMING, AND TESTING TO ALLOW FOR NEW SMOKE
DETECTOR DEVICES.
8. CONTRACTOR SHALL BE RESPONSIBLE FOR REPLACING ANY EXISTING
EQUIPMENT, CONNECTIONS, OR ASSOCIATED PARTS THAT ARE DEEMED
DEFECTIVE DURING THE PROGRAMMING AND TESTING OF THE UPDATED SYSTEM.
FIRE ALARM MATRIX. GENERAL NOTES
1. DETECTORS ON ALARM VERIFICATION SHOULD "SNIFF" THE
AIR, THEN CHECK AGAIN. IF THE SMOKE IS STILL THERE,
THEN A GENERAL ALARM SHOULD SOUND TO EVACUATE.
THESE ARE THE ALARMS THAT DO NOT HAVE CROSS -ZONE
CAPABILITY.
EX EX
EXISTING WIRING. EXTEND
WIRING AS NECESSARY TO
ACCOMODATE RENOVATION.
SYSTEM OUTPUTS
CONTROL. UNIT ANNUNCIATION
1
EXISTING MANUAL FIRE ALARM BOXES
I
I
I
I
I
I
1
2
EXISTING CO DETECTORS
I
I
I
I
I
I
2
3
EXISTING SMOKE DETECTORS
I
3
4
NEW SMOKE DETECTORS
I
I
I
I
I
I
4
5
EXISTING NOTIFICATION APPLIANCE CIRCUIT SHORT
I
I
I
I
5
6
EXISTING HEAT DETECTORS - MECH AREA
I
I
I
I
I
I
6
7
EXISTING DUCT SMOKE DETECTORS
I
I
I
I
1
I
7
8
FIRE ALARM SYSTEM LOW BATT
I
I
I
I
8
9
OPEN CIRCUIT
I
I
I
I
9
10
GROUND FAULT
I
I
I
I
10
A
F G
FIRE ALARM MATRIX
NOT TO SCALE
NOTIFICATION
EQUIPMENT MOTOR ---
(NOT SPECIFICALLY
INDICATED ON FLOOR
PLANS)
EQUIPMENT TAG -■
A
NON -FUSED ENCLOSED
SWITCH PER SECTION 260001
SPECIFICATIONS WITH
AUXILIARY CONTACTS. MOUNT
IN SIGHT OF EQUIPMENT.
MOTOR. PROVIDE SWITCH
ONLY WHENEVER
CONTROLLER AND SWITCH
CANNOT BE MOUNTED WITHIN
SIGHT OF EQUIPMENT
X
BRANCH CIRCUIT BY SECTION 260001 SPEC.
CONTRACTOR. SEE SECTION 260001 SPEC.
AND FLOOR PLANS FOR BRANCH CIRCUIT
REQUIREMENTS AND SECTION 230001
SPECIFICATION AND EQUIPMENT
SCHEDULES FOR SIZING.
EQUIPMENT TAG REFERENCES
MEP AND OWNER SCHEDULES
TERMINAL BOX
BRANCH CIRCUIT WIRING BY SECTION 260001
CONTRACTOR PER SECTION 260001
SPECIFICATION. PROVIDE ADDITIONAL
WIRING AS. REQUIRED TO MATCH
CONTROLLER. COORDINATE WITH SECTION
230001 SPECIFICATION CONTRACTOR.
FOR EQUIPMENT REQUIRING A
COMBINATION MOTOR
CONTROLLER/DISCONNECT SWITCH,
FURNISH AND INSTALL
CONTROLLER/SWITCH PER SECTION
260001 SPECIFICATION, UNLESS
OTHERWISE PROVIDED BY
MANUFACTURER. MOUNT ADJACENT TO
EQUIPMENT: SWITCH. TO BE FUSED.
SECTION 230001 AND SECTION 260001
CONTRACTORS SHALL COORDINATE
MOTOR AND CONTROLLER
REQUIREMENTS AND INSTALLATION.
NOTE:
THIS DETAIL IS. FOR ALL EQUIPMENT MOTORS. SECTION 260001 SPECIFICATION
CONTRACTOR TO PROVIDE WIRING BETWEEN REMOTE COMBINATION MOTOR
CONTROLLER/ DISC SWITCH AND MOTORS. REFER TO SECTION 260001 AND 230001
SPECIFICATIONS, AND MEP EQUIPMENT SCHEDULES AND/OR FLOOR PLANS . IF NOT NOTED
OTHERWISE IN EQUIPMENT SCHEDULES, SECTION 260001 SPECIFICATION CONTRACTOR
SHALL PROVIDE A COMBINATION MOTOR CONTROLLER/DISC: SWITCH. SECTION 230001 AND
SECTION 260001 SPECIFICATION CONTRACTORS SHALL BE RESPONSIBLE FOR
COORDINATING EXACT SIZE AND REQUIREMENTS OF COMBINATION DEVICE AND THE
SEQUENCE OF INSTALLATION,.
NON -FUSED ENCLOSED
SWITCH PER SECTION
260001 SPECIFICATIONS
WITH AUXILIARY
CONTACTS. MOUNT IN
SIGHT OF EQUIPMENT
MOTOR. COORDINATE
WITH SECTION 230001
SPECIFICATION
CONTRACTOR.
EQUIPMENT TAG
REFERENCES MEP
SCHEDULES/FLOOR PLANS
TERMINAL BOX
BRANCH CIRCUIT WIRING BY
SECTION 260001 CONTRACTOR
PER SECTION 260001
SPECIFICATION. PROVIDE
ADDITIONAL WIRING AS
REQUIRED TO MATCH
CONTROLLER. COORDINATE
WITH SECTION 230001
SPECIFICATION CONTRACTOR.
--- BRANCH CIRCUIT BY SECTION
260001 SPEC: CONTRACTOR.
SEE SECTION 260001 SPEC. AND
FLOOR PLANS FOR BRANCH
CIRCUIT REQUIREMENTS AND
SECTION 230001 SPECIFICATION
AND EQUIPMENT SCHEDULES
FOR SIZING.
NOTE:
THIS DETAIL IS FOR ALL EQUIPMENT WHERE EQUIPMENT REQUIRES POWER AND
WHERE THERE ARE NO MOTORS INVOLVED OR WHERE SPECIFICATIONS OR
SCHEDULES FOR MULTIPLE MOTOR EQUIPMENT SPECIFICALLY INDICATE. ONE
POINT POWER CONNECTION. SECTION 260001 SPECIFICATION CONTRACTOR TO.
PROVIDE WIRING BETWEEN REMOTE DISCONNECTS, STARTERS AND MOTORS.
SEE SECTION 230001 EQUIPMENT SCHEDULES AND SECTION 260001
SPECIFICATIONS,
EXISTING UNDERGROUND UTILITY
PRIMARY FEEDER TO REMAIN.
EXISTING UNDERGROUND SECONDARY
FEEDER INTO MAIN ELEC. RM WITHIN
SUPERIOR COURT BLDG.
EXISTING UTILITY OWNED,
CONCRETE PAD MTD,
EXTERIOR TRANSFORMER
1600AF
1600AT
EXISTING DPB, 1600A MCB, 208/120V, 3PH, 4W
100A
EX
60A
TO ALL EXISTING
COURTROOM
PANELBOARDS.
FIELD VERIFY
EXACT LOCATION IN
FIELD.
) 100A
) 100A
LB-2 EX LB-3 EX
I
1100A
LB-4 EX
) 150A
LB-5
EX
100A
LB-6
EXISTING
40HP
ELEVATOR
EXISTING ELECTRICAL ONE -LINE DIAGRAM
NOT TO SCALE
EXISTING
ELEV.
CONTROL
) 400A
) 400A
J
1.
GENERAL NOTES
ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING LOCATION AND QUANTITY OF ALL
EXISTING PANELBOARDS, NOT ALL PANELBOARDS ARE INDICATED ON THIS ONE -LINE DIAGRAM OR FLOOR
PLANS.
2. ELECTRICAL CONTRACTOR SHALL TRACE ALL BRANCH CIRCUITS IN ALL EXISTING PANELBOARDS.
3. CONTRACTOR SHALL PLACE IN THE OFF POSITION ALL EXISTING C/B'S SERVING RECEPTACLES AND NON-
ESSTIONAL LIGHTING (ANY CIRCUITS THAT DO NOT SERVE LIGHT FIXTURES IN THE MAIN CORRIDORS INDICATED
ON FLOOR PLANS).
4. ELECTRICAL CONTRACTOR SHALL PLACE IN THE OFF POSITION ALL EXISTING C/B'S THAT SERVE HVAC
EQUIPMENT NOT PART OF THE HEATING SYSTEM. VERIFY WITH MECHANICAL CONTRACTOR ALL HVAC
EQUIPMENT THAT SHALL REMAIN IN USE.
PANELBOARD AND SWITCHBOARD LEGEND
INDICATES MAINS TYPE
j (CIRCUIT BREAKER).
�,
7,
NI 225AF ""
225AT �_.__
XXXXX
INDICATES MAINS TYPE
-'A (MAIN LUG ONLY)
INDICATES PANEL
INDICATES PANEL I XXXXX DESIGNATION.
DESIGNATION.
INDICATES FRAME SIZE
INDICATES TRIP SETTING
INDICATES FEED
THROUGH LUGS.
EXISTING DPC, 400A MCB, 208/120V, 3PH, 4W
EX
ELC-B
) 150A
LC-2
100A
V^
TO EXISTING
PANELBOARD.
FIELD VERIFY EXACT
LOCATION IN FIELD.
) 100A
W-
TO EXISTING
PANELBOARD.
FIELD VERIFY EXACT
LOCATION IN FIELD.
) 100A
TO EXISTING
PANELBOARD.
FIELD VERIFY EXACT
LOCATION IN FIELD.
4-
) 100A
A
TO EXISTING
PANELBOARD.
FIELD VERIFY EXACT
LOCATION IN FIELD.
POWER RISER DIAGRAM FEEDER SIZING CHART
(SEE FEEDER LEGEND FOR APPLICATION OF THIS CHART)
AMPERAGE
NUMBER OF
PARALLEL
SETS
PHASE
CONDUCTOR(S)
NEUTRAL CONDUCTOR(S)
GROUNDING CONDUCTOR(S)
RACEWAY
SIZE
AMPERAGE
NUMBER OF
PARALLEL
SETS
PHASE
CONDUCTOR(S)
NEUTRAL CONDUCTOR(S)
GROUNDING CONDUCTOR(S)
RACEWAY
SIZE
STANDARD
OVERSIZED
EQUIPMENT
ISOLATED
OVERSIZED
STANDARD
OVERSIZED
EQUIPMENT
ISOLATED
OVERSIZED
20or30
1
(3)#10
(1)#10
(1)#8
(1)#10
(1)#10
8
1"
400
1
(3)#500
(1)#500
(2)#350
(1)#3
(1)#3
3/0
4"
40 or 50
1
(3) # 8
(1) # 8
NA
(1) # 10
NA
8
1"
420
1
(3) # 600
(1) # 600
(2) # 350
(1) # 2
(1) # 2
3/0
4"
60
1
(3)#6
(1)#6
(1)#3
(1)#10
(1)#10
8
11/4"
450
2
(3)#4/0
(1)#4/0
(2)#2/0
(1)#2
(1)#2
3/0
3"
70
1
(3)#4
(1)#4
NA
(1)#8
NA
8
11/4"
500
2
(3)#250
(1)#250
(2)#3/0
(1)#2
(1)#2
3/0
3"
80
1
(3)#4
(1)#4
NA
(1)# 8
NA
6
1 1/4"
600
2
(3)#350
(1)#350
(2)#4/0
(1)# 1
(1)#1
4/0
4"
90
1
(3) # 3
(1) # 3
NA
(1) # 8
NA
6
1 1/2"
700
2
(3) # 500
(1) # 500
(2) # 300
(1) # 1/0
(1) # 1/0
4/0
4"
100
1
(3)#2
(1)#2
(1)#1/0
(1)#8
(1)#8
4
11/2"
800
2
(3)#500
(1)#500
(2)#350
(1)#1/0
(1)#1/0
250
4"
840
2
(3) # 600
(1) # 600
(1) # 350
(1) # 2
(1) # 2
3/0
4"
110
1
(3) # 2
(1) # 2
(1) # 2/0
(1) # 6
(1) # 6
3
2"
1000
3
(3) # 500
(1) # 500
(2) # 500
(1) # 2/0
N.A.
500
4"
125
1
(3)# 1
(1)# 1
(1)#3/0
(1)#6
(1)#6
2
2"
1200
4
(3)#500
(1)#500
(2)#500
(1)#3/0
N.A.
500
4"
150
1
(3) # 1/0
(1) # 1/0
(1) # 4/0
(1) # 6
(1) # 6
2
2"
1600
5
(3) # 500
(1) # 500
(2) # 500
(1) # 4/0
N.A.
500
4"
175
1
(3) # 2/0
(1) # 2/0
(1) # 300
(1) # 6
(1) # 6
1
2 1/2"
2000
6
(3) # 500
(1) # 500
N.A.
(1) # 250
N.A.
500
4"
200
1
(3) # 3/0
(1) # 3/0
(2) # 1/0
(1) # 6
(1) # 6
1
2.1/2"
2500
7
(3) # 500
(1) # 500
N.A.
(1) # 350
N.A.
500
4"
225
1
(3) # 4/0
(1) #4/0
(2) ## 2/0
(1) # 4
(1) # 4
1/0
3"
3000
8
(3) # 500
(1) # 500
N.A,
(1) ## 400
N.A.
500
4,,
250
1
(3) # 250
(1) # 250
(2) # 3/0
(1) # 4
(1) # 4
2/0
3"
3200
9
(3) # 500
(1) # 500
N.A.
(1) # 500
N.A.
500
4"
300
1
(3) # 350
(1). # 350
(2) # 4/0
(1) ## 4
(1) # 4
2/0
4"
3600
10
(3) # 500
(1) # 500
N.A,
(1) ## 500
N.A. .
5.00
4"
350
1
(3) # 400
(1) # 400
(2) # 300
(1) # 3
(1) # 3
3/0
4"
4000
11
(3) # 500
(1) # 500
N.A.
(1) # 500
N,A.
500
4"
NOTES:
CONDUCTORS LISTED ABOVE ARE THHN/THWN, COPPER.
MAY ELECT TO INCREASE SIZE OF CONDUCTORS LISTED ABOVE IF THERE IS NO INCREASE IN COST. INCREASE SIZE OF RACEWAY PER CODE AS REQUIRED.
AUXILIARY LUGS AND OVERSIZED GUTTERS IN DISTRIBUTION EQUIPMENT TO ACCOMMODATE OVERSIZED CONDUTORS.
1. • ALL
2. CONTRACTOR
3. PROVIDE
Office of Planning
Design and Construction
McCormack Building
One Ashburton Place
Boston MA 02108
617 727 4050
www.mass.gov/cam
Project Name:
SALEM SUPERIOR
COURT & COUNTY
COMMISSIONER
BUILDINGS WARM
MOTHBALLING
DCAMM Project Number
DCP1726 FC1
Project Location
3234 FEDERAL ST,
SALEM, MA
01970
Project Architect
PERRY DEAN ROGERS PARTNERS
177 MILK STREET
BOSTON, MA 02109
T. 617-423-0100
F. 617-426-2274
www.perrydean.com
Project COnsutnt
/A �,
all !Mil II ilk
1111111407
integrated
services
One Gateway Center, Suite 701
Newton, MA 02458
Tel: (617) 658-9008 www.bvhis,com
Professional Stamp
N.
Site Number:
CAM'S Number:
Building Number:
Secretariat:
Original Issue Date
01/26/2018 BID DOCUMENTS
Revisions
Plan Name:
ELECTRICAL ONE -LINE
DIAGRAM, FIRE ALARM
RISER, AND DETAILS
Drawing Number:
TYPICAL. COMBINATION MOTOR CONTROLLER/DISC SWITCH DETAIL
NOT TO SCALE
TYPICAL EQUIPMENT CONNECTION DETAIL
NOT TO SCALE
E3-01