102119 Lynco Lynde St LFP001 signedk 3RD FLOOR
I. ELEV.21'-2"
0
k 2ND FLOOR
7
Z ELEV 11'-0"
W
J
U-
- r 1ST FLOOR
N ELEV.0'-0"
O
PLOT DATE:
BASEMENT FLOOR
ELEV. -8'-4"
CLOSETS:
PER SECTION 6.6.3 (NFPA 13R, 2013 EDITION),
SPRINKLERS SHALL NOT BE REQUIRED IN
CLOTHES CLOSETS, LINEN CLOSETS, AND
PANTRIES THAT MEETALL OF THE FOLLOWING:
1)THE AREA OF THE SPACE DOES NOT EXCEED 24
SF
2) THE LEAST DIMENSION DOES NOT EXCEED 3 FT.
3) THE WALLS AND CEILINGS ARE SURFACED WITH
NONCOMBUSTIBLE OR
LIMITED -COMBUSTIBLE MATERIALS AS DEFINED IN
NFPA 220.
NOTE: WHEN MECHANICAL EQUIPMENT OR
LAUNDRY MACHINES ARE PLACED IN THE
CLOSETS, THE CLOSET IS NO LONGER
CONSIDEREDACLOTHES CLOSET, LINEN CLOSET,
OR PANTRY, SO THE EXCEPTION OF 8.6.3. IS NO
LONGER VALID AND SPRINKLER MUST BE
INSTALLED.
Supply Flow Test Data
Test Conducted By
Lynco Fire Protection
Date of Test
8/12/19
Time of Test
10:00 pm
Static Pressure
80.000
Residual Pressure:
77.000
Flow
1190.00
ATTIC
ELEV. ..���
29-1" �
....Am■I■■ r■■. ■■rll timm
.; ammmwmaammmam
.. ;ir7�ni ■EE r� .■n -..ra :a—�■:
I — — — ■■. ■■. ■■. ■■. — ■■. — — — — — ■■.I ..
-——————————————-
r---.---- --.— —I —
■1�— I
-r—.r—�r---r—.i
--r�r��I.■gi �.. ..= Iam■l2.■..rl
__
�■I��i�I�l,�I i�����.■�■..I
1..
...in .�� L.��1 Ma
I_■■.■�_■. ..UMIMM•MMMINI
N
r
9 1
0
(4)
I
1
1
1
6
W/D
Bathroom
( 0'0
LN
1 •1
0 2'-6
CL
5
Q
O4
153
O MECH
•
Hall
1
•
1
-51/2
1
1
LN
W/D
Bathroom
MECH.
Bedroom
6'-6
8'-5'/
•
Bedroom
U14 i `,
Bedroom 2
1
•2'-
2'-6
N
co
CL
•
JQ
ti
25'-
9
O
Bathroom
(-WT
1
2r_
1
Bedroom 1
( 000
O
_r
1
O
9
1N
CL
•
1w
2'-4 \
3'-MC-
2_
' UTL.
▪ vo
•
O
Cot
J
CL •
10
•
UTL. _ 2'-2
•
Hall
9
io
c
•
CL
1
11'-2
LN
Bedroom 1
BASEMENT FLOOR PLAN
SCALE:1 /4' =1'-0
Sprinkler Legend
Symbol
Manufacturer
SIN
Model
Quantity
K-Factor
Type
Size
Response
Finish
Temperature
Note
Globe
GL4906
GL-RES
64
4.9
Pendent
'A
Quick
White Polyester
155°F
16x16 Maximum
U
Globe
GL5606
GL/QR
1
5.6
Pendent
'A
Quick
Wax Over Polyester
200°F
Globe
GL5641
GL-0R/SW
4
5.6
Sidewall
1
Quick
White
155°F
DRY SIDEWALL
Total = 69
Living Room
108 i
0
Kitchen
( 104(,
Dining r -
*in
Living Room
(1O2 )
///////////////.l
FIRST FLOOR PLAN
SCALE: 1/4' =1'-0
ELECTRIC BELL
2-1/2" FDC
FDC CHECK VALVE
(LOCATION TO BE FIELD
eff
2'
Kitchen
()
Lay
( 110
i
prinlder' -
TOTO N
Hallway 1
• (_)
Electric
(-TO�
Hallway 1
(T0'I-1
Living Room
112
Lay
( 114 J
( 11b
Dining
)
Living Room
1
• '-O+
2" DCVA BACKFLOW RISER
CHECK VALVE
AND DRAIN
Side Beam
DROP -IN ANCHOR HANGER RO
LOCKING NUT
PER NFPA 13 SECTION 8.17.4.6.1 TO WET
MEANS SHALL BE PROVIDED
DOWNSTREAM OF ALL SYSTEM
BACKFLOW PREVENTION✓\_
VALVES FOR TEST AT SYSTEM
DEMAND
�'0
WALL
WALL PLATE
Lag
,
Bracket
Screw
,,/,,,''
/ \ SUPPORT NUT
..,
Nut & Wash. BAND HANGER
',
S
ii
A.T.Rod TRod -
Hanger Ring 1 PIPE y'I
1"DROP NIPPLE
FIELD SET
1"x 1/2'
REDUCER
CEILING
I
v
BRANCH LINE
„1--r
ra3 4 9
^
CHECK VALVE
FIRE
DEPARTMENT ,....4.--BALL DRIP a —
CONNECTION TO
—
FLOW
SWITCH
RISER CHECK
(TYPICAL)
FIRE DEPARTMENT
° f
HANGER
Hanger Ring ROD SUPPORTED
I
I
CONNECTION TYPE,
FINISH & LOCATION TO BE
COORDINATED WITH FIRE
HANGER ROD SPACING
HANGER ROD SPACING
- -f= i
BE APPROVED
VALVE
Steel
PIPE SIZEMAX.
SPACING
PIPE SIZgMAX. SPACING
DRAIN ELBOW
FOR BALL DRIP
VALVE
Th.
DEPT., OWNER &
ARCHITECT
_
AND FIELD - DRAIN - - BUTTERFLY
LOCATED I VALVE
DCVA BACKFLOW
- - .
STEEL
1"- 1 1/4"
12'-0
CPVC
1"
6'-0
mP
STEEL
11/2"-8"
15-0
CPVC
1 1/4"
6'-6
HORIZONTAL
MOUNTED BAL
DRIP VALVE
PIPE TO OUTSIDE
-18"TO48"
THINWALL
1"-3"
17-0
CPVC
11/2"
7'-0
A.T.Rod
DUCTILE
3,4,6,8,
15'-0
CPVC
2"
8'-0
CPVC
21/2'
9-0
��—�
. BUTTERFLY _
VALVE W/
•
18" M
/�
CPVC
3"
1U-0
-
CONCEALED
PENDENT SPRINKLER
RATED AT 155°, U.O.N.
Hanger Ring
FROM STRUCTURE
`
12" MIN.
TAMPER
SWITCH TYP.
(TYP.) -
2-1/2" VALVE FOR
- BACKFLOW p
=',
I
ADJUSTABLE SWIVEL RING
UL/FM HANGER ASSEMBLY I /_'
EXISTING GRADE
EXTEND HANGER ROD
�
p
FORWARD UNI FLANGE o ° Y
SHALL BE MIN TESTING (TYP.) o o a
SERVICE 12" ABOVE o 0
LINEFP FINISH FLOOR SQ BOLT HOLES TO
WALLS (TYP.)
FLOOR
TIGHTTO PIPE
NOTE: SURGE CLIPS TO BE ALTERNATE: USE UUFM
PROVIDED AT END OF ALL SURGE SUPPRESSOR CLIPS
BRANCH LINES. TYPICAL END -OF -LINE BRANCH
N.T.S.
GENERAL HANGER DETAILS
N.T.S.
RISER DETAIL UNI FLANGE SIDEWALL
N.T.S.
TYPICAL FIRE DEPT. CONNECTION DETAIL
N.T.S.
SPRINKLER ARM -OVER DETAIL
I•I
I•I
ice■■. ■■■►.
II
no
'LZ
A.
00
El
III
•
A
7
OA I
W/D
Kitchen
E)
E2ZZZ7T77a
Living Room
20/
i
1
CD
ath
209 j
1
1
9
6'-8
1
Bedroom 1
\ /
CL.
4'-2
I T_
MECH.
1 1
•
O
1
7'-0
Bedroom 2
( 1 )
///, /, //, /, ////_ ///, /c
1 • 1
W/D
•
CD
r
U)
1
Bath
( 206 )
1
1
-10
Bedroom 2'-0
i` 205 J
CL.
Kitchen
()
Living Room
( 203
7
9
O
•
CL.
Hall
(202)
0' II
SECOND FLOOR PLAN
SCALE: 1/4" =1'-0
O
If)
8'-0
1
n
CL.
•
O
U)
M
O
O
1
4'-0
i
Hydraulic Information
Remote Area 3rd Floor 4 Remote
OCCUPANCY CLASSIFICATION
Residential
DENSITY (gpm/ft°)
0.10 for 900.00fF (Actual 431.388°)
TOTAL HOSE STREAMS
100.00
TOTAL HEADS FLOWING
4
K-FACTOR
4.9
TOTAL WATER REQUIRED
155.25
TOTAL PRESSURE REQUIRED
53.062
BASE of RISER (gpm)
55.25
BASE of RISER (psi)
35.718
SAFETY MARGIN (psi)
+26.869 (33.6%)
t_ J
i
i
I
le
1
Bath
•
W/D
1
5'-8
Bedroom
.1 CLOSET
Kitchen
Living Room
IMP
2▪ '-
9
FIRE SPRINKLER NARRATIVE
THE PURPOSE OF THIS NARRATIVE IS TO DESCRIBE THE FIRE PROTECTION SPRINKLER SYSTEM AT 12
LYNDE ST. IN SALEM, MA.
THIS IS AN EXISTING RESIDENTIAL 3 STORY FRAMED BUILDING HOME OF COMBUSTIBLE MATERIAL
CONSISTING OF RESIDENTIAL OCCUPANCY THROUGHOUT THE ENTIRE AREA.
THE PROPOSED NEW SPRINKLER SYSTEM SHALL BE CONNECTED TO THE NEW 2" SERVICE (PROVIDED
BY OTHERS).
THE SCOPE OF WORK CONSIST OF A NEW AUTOMATIC WET SPRINKLER SYSTEM THAT IS FED FROM THE
RISER ASSEMBLY LOCATED ON THE FIRST FLOOR IN THE SPRINKLER ROOM. THE NEW BACKFLOW
PREVENTER ARE LOCATED IN THIS ROOM. THE WET IS SUPPLYING THE ENTIRE BUILDING.
THE SYSTEM SHALL BE DESIGNED AND HYDRAULICALLY CALCULATED ON THE THIRD FLOOR FOR
RESIDENTIAL HAZARD OCCUPANCYAND SHALL PROVIDER A .05 DESIGN DENSITY FOR FOUR REMOTE
HEADS WITH AN OUTSIDE HOSE OF 100 GPM.
THE SYSTEM SHALL BE ACTIVATED WHEN A HEAT SOURCE WOULD FUSE A FIRE SPRINKLER HEAD,
CAUSING THE HEAD TO OPEN AND FLOW WATER, WHICH SIMULTANEOUSLY TRIGGERS THE ALARM
SYSTEM THAT WILL SIGNAL TO THE LOCAL FIRE DEPT. AND AN APPROVED CENTRAL LOCATION.
THE BUILDING SHALL BE FITTED WITH AN AUTOMATIC FIRE ALARM SYSTEM (BY OTHERS) THAT SHALL
PROVIDE AN AUDIBLE ALARM UPON ACTIVATION OF A FIRE SPRINKLER HEAD AND/OR TEST VALVE.
THIS DRAWING IS INTENDED TO SHOW GENERAL ARRANGEMENTAND SCOPE OF WORK TO BE
PERFORMED. ALL LOCATIONS ARE APPROXIMATE AND ARE SUBJECT TO CHANGE TO CONFORM TO
STRUCTURAL AND/OR JOB CONDITIONS.
COMM
MEMBRANE ROOF SYSTEM
rTh
Bedroom
MECH. 4
o
•
Living
0
9
Room
9
Kitchen
Bath
223
Kitchen
CL
•
Living Room
CL
1
9
9
CL
Bedroom
0
102
101
THIRD FLOOR PLAN
FIRE PROTECTION NOTES:
1 .SYSTEM DESIGN AND INSTALLATION TO CONFORM TO N.F.P.A. 13R - 2013 EDITION REQUIRED BY THE
MASSACHUSETTS STATE BUILDING CODE - 9TH EDITION
2.ALL MATERIAL, DESIGN AND WORKMANSHIP TO CONFORM TO N.F.P.A. 13 & THE LOCAL FIRE DEPARTMENT
AND ALL APPLICABLE CODES.
3.ALL NEW PIPING 1-1/4" AND SMALLER TO BE SCHEDULE 40 BLACK STEEL WITH CAST IRON SCREWED
FITTINGS. ALL NEW PIPING 1-1/2" AND LARGER TO BE SCHEDULE 10 BLACK STEEL WITH GROOVED
COUPLINGS, FITTINGS, MECHANICAL TEES AND WELDED OUTLETS.
4. RESIDENTIAL AREAS: BLAZEMASTER SHALL MEET THE REQUIREMENTS OF THE INSTALLATION GUIDE. IT IS
THE CONTRACTORS RESPONSIBILTY TO VERIFY CONSTRUCTION TYPE, HEIGHTS AND ALL OTHER FACTORS
ASSOCIATED WITH THE INSTALLATION GUIDE. ALL CONCEALED PIPING TO BE BLAZEMASTER CPVC WITH
CPVC GLUED FITTINGS.
5.ALL SPRINKLER HEADS SHALL BE QUICK RESPONSE AND RESIDENTIAL TYPE. SEE SPRINKLER LEGEND FOR
TYPE AND QUANTITIES.
6.FIRE STOP PROVIDED AT ALL PIPING PENETRATIONS THROUGH RATED WALLS.
7.ALL PIPES SHALL BE SUPPORTED PER N.F.P.A. 13, 2013 EDITION AND MANUFACTURERS INSTALLATION
REQUIREMENTS.
8.ALL EQUIPMENTAND DEVICES TO BE U.L. LISTED AND/ OR F.M. APPROVED.
9ALL CONNECTIONS OF SPRINKLER DEVICES TO THE FIRE ALARM SYSTEM SHALL BE PERFORMED BY
OTHERS.
10. ALL ELECTRICAL WIRING OF THE SPRINKLER DEVICES SHALL BE DONE BYA LICENSED ELECTRICIAN.
11. HEAT TO BE PROVIDED BY THE OWNER AT 40 DEG. F MINIMUM IN ALL AREAS WITH SPRINKLER HEADS OR
PIPING.
12. PER NFPA13 8.3.2.5 - SPRINKLERS LOCATED WITHIN 12" OF HEAT SOURCES SHALL REQUIRE
INTERMEDIATE TEMPERATURE SPRINKLER HEADS.
ELEVATIONS
AND SECTION DETAIL
SITE MAP
NOT TO SCALE
re
Lightshed
Opus :
LYNCO
FIRE PROTECTION INC.
CONTRACTORS -ENGINEERS -INSTALLATIONS
SALES -REPAIRS -INSPECTIONS
FAX - 781-229-8323
19 GRANT AVE
BURLINGTON, MA
Revisions
Rev
Date
Description
GENERAL NOTES:
1. THIS DRAWING IS PREPARED BY LYNCO FIRE PROTECTION FOR USE IN CONNECTION WITH THIS
PROJECT FOR USE SOLELY WITH RESPECT TO LYNCO FIRE PROTECTION WORK ON SUCH PROJECT
LYNCO FIRE PROTECTION RETAINS ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS,
INCLUDING COPYRIGHT, THE DRAWING SHALL NOT BE USED BY OTHERS ON OTHER PROJECTS OR FOR
PERFORMANCE, COMPLETION, OR ADDITION TO THIS PROJECT BY OTHERS EXCEPT BY AGREEMENT OF
LYNCO FIRE PROTECTION IN WRITING AND WITH APPROPRIATE COMPENSATION TO LYNCO FIRE
PROTECTION.
2. WHETHER OR NOT INDICATED IN THE DRAWINGS, THE FOLLOWING ITEMS SHALL BE PROVIDED: SPARE
HEAD BOX, FLUSHING CONNECTIONS & INSPECTOR'S TEST VALVE.
3. ALL CONNECTIONS OF SPRINKLER DEVICES TO THE FIRE ALARM SYSTEM SHALL BE PERFORMED BY
OTHERS.
4. OWNER IS RESPONSIBLE TO MAINTAIN THE SPRINKLER SYSTEM(S) IN ACCORDANCE WITH THE LATEST
N.F.P.A. 25. "INSPECTION & MAINTENANCE OF WATER BASED FIRE PROTECTION SYSTEMS AND/ OR ALL
APPLICABLE FEDERAL STATE AND/ OR LOCAL LAWS, CODES AND ORDINANCES.
5.MA STATE FIRE SPRINKLER CONTRACTOR
Stamp:
North Arrow:
Scale:
I I
0'
2' 4'
Water Information
Static:
80 psi
Residual:
77 psi
Flow:
1190 gpm
Date:
8/12/19
Job Name:
Residential
10-12 Lynde St.
Salem, MA. 01970
Location:
Information By:
Lynco Fire Protection
Designer
Date:
10/16/19
Designed by:
B.G.
Contractor:
Roost Living
900 Cummings Center
Suite #215 U
Beverly, MA. 01915
Dwg Name:
Fire Protection
Basement Thru 3rd Floor
Plans, Notes and Details
Dwg No:
Sheet:
of