Loading...
1 Jefferson St stamped4" UNDERGROUNDWITH 58" RETAININGRODS (2 REQ'D.)FINISHED FLOOR @ +3'-6" ELWET PIPE VALVE STATION DETAILNOT TO SCALE4" TO FDC CONNECTION WITHCHECK VALVE AND BALL DRIP6" AMES MODEL C200 BACKFLOWPREVENTER ASSEMBLYCONTROL VALVES &TAMPER SWITCHES4" UNDERGROUNDFLUSH, TEST, ANDCHLORINATE PER NFPA 24 &TOWN OF SALEM.SPARE HEADCABINET2" DRAIN TO EXTERIOR4" VIKING EASY RISER WET VALVEASSEMBLY WITH 2" DRAIN ANDPRESSURE GAUGE.FLOW SWITCHSTORZ FIRE DEPARTMENT CONNECTIONDIAGRAMUPRIGHTSPRINKLERN.T.S.DESIGN CRITERIA:NEW GARAGE BUILDING :OCCUPANCY: STORAGEHAZARD CLASS: ORDINARY GROUP IISPRINKLERS: GLOBE UPRIGHT QRTEMPERATURE: 155 DEGREEK= FACTOR: 5.6PIPE SIZE: 12" IPS.AREA PER SPRINKLER: 130 SQ/FT.AREA OF APPLICATION: 1540 SQ/FT.DENSITY: .20HOSE ALLOWANCE: 250 GPMNFPA 13 - 2013 EDITIONCHAPTER 5 PARA. 5.3.2DESIGN CRITERIA:FIRST FLOOR TENANT:OCCUPANCY: COMMERCIAL SPACEHAZARD CLASS: ORDINARY GROUP IISPRINKLERS: GLOBE UPRIGHT QRTEMPERATURE: 155 DEGREEK= FACTOR: 5.6PIPE SIZE: 12" IPS.AREA PER SPRINKLER: 130 SQ/FT.AREA OF APPLICATION: 1040 SQ/FT.DENSITY: .20HOSE ALLOWANCE: 250 GPMNFPA 13 - 2013 EDITIONCHAPTER 5 PARA. 5.3CHAPTER 11- 11.2.3.3.1DESIGN AREA REDUCTIONBUILDING DESCRIPTION & USAGE:DESIGN METHODOLOGY & SCOPE OF WORK:MISCELLANEOUS NOTES:FLOWWET SYSTEM RISERN.T.S.WATER FLOW DATASTATIC:85 #RESIDUAL: 76 #FLOW:1190 GPMHYDRANT: "A"BUTT SIZE:2.5"DATE:10/01/19TIME: 22:00 HOURSLOCATION: Building & SiteBY: Metro Swift Corp.325 North Main Street, Unit: CMiddleton, MA 01949PH: 978-655-7002FAX: 978-824-2557www.frontlinefp.comSC License: 210048 SALEM DPWMECH.TENANT3 spacesTENANTVEST.STORAGEMBTA ACCESS ROAD 1 spaceGARAGE TOILET TOILET CUST.TOILET TOILET CUST. TOILET TOILET CUST. TOILET TOILET CUST. TOILET TOILET CUST. TOILET TOILET CUST. TOILET TOILET CUST. TOILET TOILET CUST. 1 2A B C D E GARAGE GARAGE GARAGE GARAGE GARAGE GARAGE GARAGE²²FINISHED FLOOR @ +3'-6" ELFINISHED FLOOR @ +0'-0" EL325 North Main Street, Unit: CMiddleton, MA 01949PH: 978-655-7002FAX: 978-824-2557www.frontlinefp.comSC License: 210048 MBTA R.O.W.SALEM DPWEXIST. BLDG.²325 North Main Street, Unit: CMiddleton, MA 01949PH: 978-655-7002FAX: 978-824-2557www.frontlinefp.comSC License: 210048 SALEM DPWMECH.TENANT3 spacesTENANTVEST.STORAGEMBTA ACCESS ROAD 1 spaceGARAGE TOILET TOILET CUST. TOILET TOILET CUST. TOILET TOILET CUST. TOILET TOILET CUST. TOILET TOILET CUST. TOILET TOILET CUST. TOILET TOILET CUST. TOILET TOILET CUST. 1 2A B C D E GARAGE GARAGE GARAGE GARAGE GARAGE GARAGE GARAGE325 North Main Street, Unit: CMiddleton, MA 01949PH: 978-655-7002FAX: 978-824-2557www.frontlinefp.comSC License: 210048 Front-Line Fire Protection LLC 325 North Main Street Unit: C Middleton, MA. 01949 978-655-7002 Job Name : Railworks rental Condominiums Drawing : FP-2 Location : 1 Jefferson Ave, Salem, MA Remote Area : Area #1 Contract : Data File : Jefferson-Salem Area 1.WXF Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Front-Line Fire Protection LLC Page 1 Railworks rental Condominiums Date 04/22/20 HYDRAULIC CALCULATIONS for Project name:Railworks rental Condominiums Location:1 Jefferson Ave, Salem, MA Drawing no:FP-2 Date:04/22/20 Design Remote area number:Area #1 Remote area location:New Building Garage Area Occupancy classification:Ordinary Group 2 Density:0.2 - Gpm/SqFt Area of application:1540 - SqFt Coverage per sprinkler:120 - SqFt Type of sprinklers calculated:QR Uprights No. of sprinklers calculated:14 In-rack demand:-0- - GPM Hose streams:250 - GPM Total water required (including hose streams):618.01 - GPM @ 60.7556 - Psi Type of system:Wet System Volume of dry or preaction system:NA - Gal Water supply information Date:10/01/19 Location:Jefferson & Winthrop Source:Metro-Swift Corp Name of contractor:Front-Line Fire Protection LLC Address:325 North Main Street / Unit: C / Middleton, MA. 01949 Phone number:978-655-7002 Name of designer:J. Larkin Authority having jurisdiction:Salem Fire Notes: (Include peaking information or gridded systems here.) Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Front-Line Fire Protection LLC Page 2 Railworks rental Condominiums Date 04/22/20 10 20 30 40 E 50 R 60 U 70 S 80 S 90 E 100 R 110 P 120 130 140 150 200 400 600 800 1000 1200 1400 1600 1800 FLOW ( N ^ 1.85 ) City Water Supply: Demand: C1 C2 C1 - Static Pressure : 85 C2 - Residual Pressure: 76 C2 - Residual Flow : 1190 D1 - Elevation : 10.827 D2 - System Flow : 368.01 D2 - System Pressure : 60.756 Hose ( Demand ) : 250 D3 - System Demand : 618.01 Safety Margin : 21.566 D1 D2 D3 Water Supply Curve C Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Front-Line Fire Protection LLC Page 3 Railworks rental Condominiums Date 04/22/20 Fitting Legend Abbrev. Name ½ ¾ 1 1¼ 1½ 2 2½ 3 3½ 4 5 6 8 10 12 14 16 18 20 24 E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow G NFPA 13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 T NFPA 13 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 V 90' Ell Firelock #001 0 0 0 0 0 3.5 4.3 5 0 6.8 8.5 10 13 0 0 0 0 0 0 0 X 90'Tee-BranchFirelock002 0 0 0 0 0 8.5 10.8 13 0 16 21 25 33 0 0 0 0 0 0 0 Xaa Check Vik E Riser E1-F1 6 10 13 20 23 Zia Wilkins 350 Fitting generates a Fixed Loss Based on Flow Unit Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Fittings Used Summary Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Front-Line Fire Protection LLC Page 4 Railworks rental Condominiums Date 04/22/20 SUPPLY ANALYSIS Node at Static Residual Available Source Pressure Pressure Flow Pressure Total Demand Required Pressure TEST 85.0 76 1190.0 82.322 618.01 60.756 NODE ANALYSIS Pressure Discharge Node Tag Elevation Node Type at Node at Node Notes 10 25.0 5.6 18.37 24.0 11 24.17 5.6 18.91 24.35 12 23.33 5.6 19.94 25.01 13 22.5 5.6 23.18 26.96 14 20.0 27.47 15 20.0 27.59 16 20.0 27.97 17 20.0 38.82 18 13.83 44.37 TOR 13.83 44.75 BOR 6.5 51.68 BKFL 6.5 56.42 UG -5.5 61.95 TEST 0.0 60.76 250.0 19 25.0 5.6 18.46 24.06 20 24.17 5.6 19.0 24.41 21 23.33 5.6 20.04 25.07 22 22.5 5.6 23.29 27.03 23 25.0 5.6 18.75 24.25 24 24.17 5.6 19.29 24.6 25 23.33 5.6 20.34 25.26 26 22.5 5.6 23.63 27.22 27 25.0 5.6 34.5 32.89 28 22.5 36.9 29 20.0 38.39 30 20.0 38.4 31 25.0 5.6 34.52 32.9 32 22.5 36.91 Flow Summary - NFPA 2007 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Front-Line Fire Protection LLC Page 5 Railworks rental Condominiums Date 04/22/20 Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt to or Ftng's Pe ******* Notes ****** Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf 10 25 5.60 24.00 1.5 0.0 10.030 120 18.367 to 0.0 0.0 0.359 11 24.17 24.0 1.682 0.0 10.030 0.0183 0.184 Vel = 3.47 11 24.17 5.60 24.35 1.5 0.0 10.030 120 18.910 to 0.0 0.0 0.364 12 23.33 48.35 1.682 0.0 10.030 0.0668 0.670 Vel = 6.98 12 23.33 5.60 25.01 1.5 T 9.9 10.030 120 19.944 to 0.0 9.900 0.359 13 22.5 73.36 1.682 0.0 19.930 0.1446 2.882 Vel = 10.59 13 22.5 5.60 26.97 1.5 T 9.9 2.500 120 23.185 to 0.0 9.900 1.083 14 20 100.33 1.682 0.0 12.400 0.2579 3.198 Vel = 14.49 14 20 0.0 3 0.0 12.000 120 27.466 to 0.0 0.0 0.0 15 20 100.33 3.26 0.0 12.000 0.0102 0.123 Vel = 3.86 15 20 100.56 3 0.0 10.330 120 27.589 to 0.0 0.0 0.0 16 20 200.89 3.26 0.0 10.330 0.0372 0.384 Vel = 7.72 16 20 101.32 3 V 6.72 130.530 120 27.973 to 0.0 6.720 0.0 17 20 302.21 3.26 0.0 137.250 0.0790 10.849 Vel = 11.62 17 20 65.80 3 2V 13.44 11.840 120 38.822 to 0.0 13.440 2.672 18 13.83 368.01 3.26 0.0 25.280 0.1138 2.876 Vel = 14.15 18 13.83 0.0 4 V 8.954 3.330 120 44.370 to 0.0 8.954 0.0 TOR 13.83 368.01 4.26 0.0 12.284 0.0309 0.380 Vel = 8.28 TOR 13.83 0.0 4 Xaa 17.117 7.330 120 44.750 to Fsp 0.0 17.117 6.175 * Fixed Loss = 3 BOR 6.5 368.01 4.26 0.0 24.447 0.0309 0.756 Vel = 8.28 BOR 6.5 0.0 4 2E 26.334 4.250 120 51.681 to Zia 0.0 26.334 3.789 * Fixed Loss = 3.789 BKFL 6.5 368.01 4.26 0.0 30.584 0.0309 0.945 Vel = 8.28 BKFL 6.5 0.0 4 0.0 12.000 140 56.415 to 0.0 0.0 5.197 UG -5.5 368.01 4.1 0.0 12.000 0.0281 0.337 Vel = 8.94 UG -5.5 0.0 4 E 14.534 25.000 140 61.949 to G 2.907 17.441 -2.382 TEST 0 368.01 4.1 0.0 42.441 0.0280 1.189 Vel = 8.94 250.00 Qa = 250.00 TEST 618.01 60.756 K Factor = 79.29 19 25 5.60 24.06 1.5 0.0 10.030 120 18.459 to 0.0 0.0 0.359 20 24.17 24.06 1.682 0.0 10.030 0.0184 0.185 Vel = 3.47 20 24.17 5.60 24.41 1.5 0.0 10.030 120 19.003 to 0.0 0.0 0.364 21 23.33 48.47 1.682 0.0 10.030 0.0671 0.673 Vel = 7.00 21 23.33 5.60 25.07 1.5 T 9.9 10.030 120 20.040 to 0.0 9.900 0.359 22 22.5 73.54 1.682 0.0 19.930 0.1453 2.895 Vel = 10.62 EOD Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Front-Line Fire Protection LLC Page 6 Railworks rental Condominiums Date 04/22/20 Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt to or Ftng's Pe ******* Notes ****** Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf 22 22.5 5.60 27.03 1.5 T 9.9 2.500 120 23.294 to 0.0 9.900 1.083 15 20 100.57 1.682 0.0 12.400 0.2590 3.212 Vel = 14.52 0.0 15 100.57 27.589 K Factor = 19.15 23 25 5.60 24.25 1.5 0.0 10.030 120 18.746 to 0.0 0.0 0.359 24 24.17 24.25 1.682 0.0 10.030 0.0186 0.187 Vel = 3.50 24 24.17 5.60 24.59 1.5 0.0 10.030 120 19.292 to 0.0 0.0 0.364 25 23.33 48.84 1.682 0.0 10.030 0.0681 0.683 Vel = 7.05 25 23.33 5.60 25.26 1.5 T 9.9 10.030 120 20.339 to 0.0 9.900 0.359 26 22.5 74.1 1.682 0.0 19.930 0.1473 2.935 Vel = 10.70 26 22.5 5.60 27.22 1.5 T 9.9 2.500 120 23.633 to 0.0 9.900 1.083 16 20 101.32 1.682 0.0 12.400 0.2627 3.257 Vel = 14.63 0.0 16 101.32 27.973 K Factor = 19.16 27 25 5.60 32.89 1.5 T 9.9 30.090 120 34.503 to 0.0 9.900 1.083 28 22.5 32.89 1.682 0.0 39.990 0.0328 1.310 Vel = 4.75 28 22.5 0.0 1.5 T 9.9 2.500 120 36.896 to 0.0 9.900 1.083 29 20 32.89 1.682 0.0 12.400 0.0327 0.406 Vel = 4.75 29 20 0.0 3 0.0 12.000 120 38.385 to 0.0 0.0 0.0 30 20 32.89 3.26 0.0 12.000 0.0013 0.016 Vel = 1.26 30 20 32.90 3 X 17.471 71.840 120 38.401 to 0.0 17.471 0.0 17 20 65.79 3.26 0.0 89.311 0.0047 0.421 Vel = 2.53 0.0 17 65.79 38.822 K Factor = 10.56 31 25 5.60 32.90 1.5 T 9.9 30.090 120 34.518 to 0.0 9.900 1.083 32 22.5 32.9 1.682 0.0 39.990 0.0328 1.311 Vel = 4.75 32 22.5 0.0 1.5 T 9.9 2.500 120 36.912 to 0.0 9.900 1.083 30 20 32.9 1.682 0.0 12.400 0.0327 0.406 Vel = 4.75 0.0 30 32.90 38.401 K Factor = 5.31 Final Calculations - Hazen-Williams Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Front-Line Fire Protection LLC 325 North Main Street Unit: C Middleton, MA. 01949 978-655-7002 Job Name : Railworks Rental Condo Drawing : FP-2 Location : 1 Jefferson Ave, Salem, MA Remote Area : Area #2 Contract : Data File : Jefferson-Salem Area 2.WXF Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Front-Line Fire Protection LLC Page 1 Railworks Rental Condo Date 04/22/20 HYDRAULIC CALCULATIONS for Project name:Railworks Rental Condominiums Location:1 Jefferson Ave, Salem, MA Drawing no:FP-2 Date:04/22/20 Design Remote area number:Area #2 Remote area location:Existing Building Tenat 1st Floor Area Occupancy classification:Ordinary Group 2 Density:0.2 - Gpm/SqFt Area of application:1140 - SqFt Coverage per sprinkler:120 - SqFt Type of sprinklers calculated:QR Uprights No. of sprinklers calculated:10 In-rack demand:-0- - GPM Hose streams:250 - GPM Total water required (including hose streams):502.414 - GPM @ 60.060 - Psi Type of system:Wet System Volume of dry or preaction system:NA - Gal Water supply information Date:10/01/19 Location:Jefferson & Winthrop Source:Metro-Swift Corp Name of contractor:Front-Line Fire Protection LLC Address:325 North Main Street / Unit: C / Middleton, MA. 01949 Phone number:978-655-7002 Name of designer:J. Larkin Authority having jurisdiction:Salem Fire Notes: (Include peaking information or gridded systems here.) Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Front-Line Fire Protection LLC Page 2 Railworks Rental Condo Date 04/22/20 10 20 30 40 E 50 R 60 U 70 S 80 S 90 E 100 R 110 P 120 130 140 150 200 400 600 800 1000 1200 1400 1600 1800 FLOW ( N ^ 1.85 ) City Water Supply: Demand: C1 C2 C1 - Static Pressure : 85 C2 - Residual Pressure: 76 C2 - Residual Flow : 1190 D1 - Elevation : 5.990 D2 - System Flow : 252.414 D2 - System Pressure : 60.060 Hose ( Demand ) : 250 D3 - System Demand : 502.414 Safety Margin : 23.114 D1 D2 D3 Water Supply Curve C Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Front-Line Fire Protection LLC Page 3 Railworks Rental Condo Date 04/22/20 Fitting Legend Abbrev. Name ½ ¾ 1 1¼ 1½ 2 2½ 3 3½ 4 5 6 8 10 12 14 16 18 20 24 E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow G NFPA 13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 T NFPA 13 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 V 90' Ell Firelock #001 0 0 0 0 0 3.5 4.3 5 0 6.8 8.5 10 13 0 0 0 0 0 0 0 X 90'Tee-BranchFirelock002 0 0 0 0 0 8.5 10.8 13 0 16 21 25 33 0 0 0 0 0 0 0 Xaa Check Vik E Riser E1-F1 6 10 13 20 23 Zia Wilkins 350 Fitting generates a Fixed Loss Based on Flow Unit Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Fittings Used Summary Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Front-Line Fire Protection LLC Page 4 Railworks Rental Condo Date 04/22/20 SUPPLY ANALYSIS Node at Static Residual Available Source Pressure Pressure Flow Pressure Total Demand Required Pressure TEST 85.0 76 1190.0 83.174 502.41 60.06 NODE ANALYSIS Pressure Discharge Node Tag Elevation Node Type at Node at Node Notes 33 13.83 5.6 18.37 24.0 34 13.83 5.6 18.59 24.14 35 13.83 5.6 19.38 24.65 36 13.83 5.6 21.09 25.72 37 13.83 5.6 23.66 27.24 38 13.83 33.06 39 13.83 33.52 18 13.83 45.62 TOR 13.83 45.81 BOR 6.5 52.36 BKFL 6.5 56.49 UG -5.5 61.85 TEST 0.0 60.06 250.0 40 13.83 5.6 18.63 24.17 41 13.83 5.6 18.86 24.32 42 13.83 5.6 19.66 24.83 43 13.83 5.6 21.4 25.9 44 13.83 5.6 24.0 27.43 Flow Summary - NFPA 2007 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Front-Line Fire Protection LLC Page 5 Railworks Rental Condo Date 04/22/20 Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt to or Ftng's Pe ******* Notes ****** Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf 33 13.83 5.60 24.00 1.5 0.0 12.000 120 18.367 to 0.0 0.0 0.0 34 13.83 24.0 1.682 0.0 12.000 0.0183 0.220 Vel = 3.47 34 13.83 5.60 24.14 1.5 0.0 12.000 120 18.587 to 0.0 0.0 0.0 35 13.83 48.14 1.682 0.0 12.000 0.0663 0.796 Vel = 6.95 35 13.83 5.60 24.66 1.5 0.0 12.000 120 19.383 to 0.0 0.0 0.0 36 13.83 72.8 1.682 0.0 12.000 0.1424 1.709 Vel = 10.51 36 13.83 5.60 25.72 1.5 0.0 10.300 120 21.092 to 0.0 0.0 0.0 37 13.83 98.52 1.682 0.0 10.300 0.2494 2.569 Vel = 14.23 37 13.83 5.60 27.24 1.5 T 9.9 14.090 120 23.661 to 0.0 9.900 0.0 38 13.83 125.76 1.682 0.0 23.990 0.3917 9.398 Vel = 18.16 38 13.83 0.0 2.5 0.0 10.500 120 33.059 to 0.0 0.0 0.0 39 13.83 125.76 2.635 0.0 10.500 0.0440 0.462 Vel = 7.40 39 13.83 126.65 2.5 X 14.827 60.900 120 33.521 to 0.0 14.827 0.0 18 13.83 252.41 2.635 0.0 75.727 0.1597 12.096 Vel = 14.85 18 13.83 0.0 4 V 8.954 3.330 120 45.617 to 0.0 8.954 0.0 TOR 13.83 252.41 4.26 0.0 12.284 0.0154 0.189 Vel = 5.68 TOR 13.83 0.0 4 Xaa 17.117 7.330 120 45.806 to Fsp 0.0 17.117 6.175 * Fixed Loss = 3 BOR 6.5 252.41 4.26 0.0 24.447 0.0154 0.376 Vel = 5.68 BOR 6.5 0.0 4 2E 26.334 4.250 120 52.357 to Zia 0.0 26.334 3.658 * Fixed Loss = 3.658 BKFL 6.5 252.41 4.26 0.0 30.584 0.0154 0.470 Vel = 5.68 BKFL 6.5 0.0 4 0.0 12.000 140 56.485 to 0.0 0.0 5.197 UG -5.5 252.41 4.1 0.0 12.000 0.0140 0.168 Vel = 6.13 UG -5.5 0.0 4 E 14.534 25.000 140 61.850 to G 2.907 17.441 -2.382 TEST 0 252.41 4.1 0.0 42.441 0.0139 0.592 Vel = 6.13 250.00 Qa = 250.00 TEST 502.41 60.060 K Factor = 64.83 40 13.83 5.60 24.17 1.5 0.0 12.000 120 18.634 to 0.0 0.0 0.0 41 13.83 24.17 1.682 0.0 12.000 0.0185 0.222 Vel = 3.49 41 13.83 5.60 24.32 1.5 0.0 12.000 120 18.856 to 0.0 0.0 0.0 42 13.83 48.49 1.682 0.0 12.000 0.0672 0.806 Vel = 7.00 42 13.83 5.60 24.83 1.5 0.0 12.000 120 19.662 to 0.0 0.0 0.0 43 13.83 73.32 1.682 0.0 12.000 0.1444 1.733 Vel = 10.59 43 13.83 5.60 25.90 1.5 0.0 10.300 120 21.395 to 0.0 0.0 0.0 44 13.83 99.22 1.682 0.0 10.300 0.2527 2.603 Vel = 14.33 EOD Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Front-Line Fire Protection LLC Page 6 Railworks Rental Condo Date 04/22/20 Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt to or Ftng's Pe ******* Notes ****** Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf 44 13.83 5.60 27.44 1.5 T 9.9 14.090 120 23.998 to 0.0 9.900 0.0 39 13.83 126.66 1.682 0.0 23.990 0.3970 9.523 Vel = 18.29 0.0 39 126.66 33.521 K Factor = 21.88 Final Calculations - Hazen-Williams Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Front-Line Fire Protection LLC 325 North Main Street Unit: C Middleton, MA. 01949 978-655-7002 Job Name : Railworks Rental Condo Drawing : FP-3 Location : 1 Jefferson Ave, Salem, MA Remote Area : Area #3 Contract : Data File : Jefferson-Salem Area 3.WXF Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Front-Line Fire Protection LLC Page 1 Railworks Rental Condo Date 04/22/20 HYDRAULIC CALCULATIONS for Project name:Railworks rental Condominiums Location:1 Jefferson Ave, Salem, MA Drawing no:FP-3 Date:04/22/20 Design Remote area number:Area #3 Remote area location:Existing Building 2nd Floor Office Occupancy classification:Ordinary Group 1 Density:0.15 - Gpm/SqFt Area of application:1023 - SqFt Coverage per sprinkler:120 - SqFt Type of sprinklers calculated:QR Uprights No. of sprinklers calculated:13 In-rack demand:-0- - GPM Hose streams:250 - GPM Total water required (including hose streams):518.496 - GPM @ 62.320 - Psi Type of system:Wet System Volume of dry or preaction system:NA - Gal Water supply information Date:10/01/19 Location:Jefferson & Winthrop Source:Metro-Swift Corp Name of contractor:Front-Line Fire Protection LLC Address:325 North Main Street / Unit: C / Middleton, MA. 01949 Phone number:978-655-7002 Name of designer:J. Larkin Authority having jurisdiction:Salem Fire Notes: (Include peaking information or gridded systems here.) Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Front-Line Fire Protection LLC Page 2 Railworks Rental Condo Date 04/22/20 10 20 30 40 E 50 R 60 U 70 S 80 S 90 E 100 R 110 P 120 130 140 150 200 400 600 800 1000 1200 1400 1600 1800 FLOW ( N ^ 1.85 ) City Water Supply: Demand: C1 C2 C1 - Static Pressure : 85 C2 - Residual Pressure: 76 C2 - Residual Flow : 1190 D1 - Elevation : 10.827 D2 - System Flow : 268.496 D2 - System Pressure : 62.320 Hose ( Demand ) : 250 D3 - System Demand : 518.496 Safety Margin : 20.745 D1 D2 D3 Water Supply Curve C Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Front-Line Fire Protection LLC Page 3 Railworks Rental Condo Date 04/22/20 Fitting Legend Abbrev. Name ½ ¾ 1 1¼ 1½ 2 2½ 3 3½ 4 5 6 8 10 12 14 16 18 20 24 E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow G NFPA 13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 T NFPA 13 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 V 90' Ell Firelock #001 0 0 0 0 0 3.5 4.3 5 0 6.8 8.5 10 13 0 0 0 0 0 0 0 X 90'Tee-BranchFirelock002 0 0 0 0 0 8.5 10.8 13 0 16 21 25 33 0 0 0 0 0 0 0 Xaa Check Vik E Riser E1-F1 6 10 13 20 23 Zia Wilkins 350 Fitting generates a Fixed Loss Based on Flow Unit Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Fittings Used Summary Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Front-Line Fire Protection LLC Page 4 Railworks Rental Condo Date 04/22/20 SUPPLY ANALYSIS Node at Static Residual Available Source Pressure Pressure Flow Pressure Total Demand Required Pressure TEST 85.0 76 1190.0 83.065 518.5 62.32 NODE ANALYSIS Pressure Discharge Node Tag Elevation Node Type at Node at Node Notes 45 25.0 5.6 10.33 18.0 46 25.0 5.6 10.44 18.09 47 25.0 5.6 10.83 18.43 48 25.0 5.6 11.39 18.9 49 25.0 5.6 12.56 19.85 50 25.0 5.6 14.81 21.55 51 25.0 5.6 17.74 23.58 52 25.0 23.77 53 25.0 24.3 TASR 25.0 25.2 BASR 13.83 35.76 54 13.83 38.5 18 13.83 47.64 TOR 13.83 47.85 BOR 6.5 54.45 BKFL 6.5 58.65 UG -5.5 64.04 TEST 0.0 62.32 250.0 55 25.0 5.6 13.27 20.4 56 25.0 5.6 13.41 20.51 57 25.0 5.6 13.74 20.76 58 25.0 5.6 14.59 21.39 59 25.0 5.6 16.41 22.68 60 25.0 5.6 18.92 24.36 Flow Summary - NFPA 2007 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Front-Line Fire Protection LLC Page 5 Railworks Rental Condo Date 04/22/20 Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt to or Ftng's Pe ******* Notes ****** Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf 45 25 5.60 18.00 1.5 0.0 10.000 120 10.332 to 0.0 0.0 0.0 46 25 18.0 1.682 0.0 10.000 0.0107 0.107 Vel = 2.60 46 25 5.60 18.09 1.5 0.0 10.000 120 10.439 to 0.0 0.0 0.0 47 25 36.09 1.682 0.0 10.000 0.0389 0.389 Vel = 5.21 47 25 5.60 18.43 1.5 0.0 6.730 120 10.828 to 0.0 0.0 0.0 48 25 54.52 1.682 0.0 6.730 0.0835 0.562 Vel = 7.87 48 25 5.60 18.90 1.5 0.0 8.080 120 11.390 to 0.0 0.0 0.0 49 25 73.42 1.682 0.0 8.080 0.1448 1.170 Vel = 10.60 49 25 5.60 19.85 1.5 0.0 10.000 120 12.560 to 0.0 0.0 0.0 50 25 93.27 1.682 0.0 10.000 0.2253 2.253 Vel = 13.47 50 25 5.60 21.55 1.5 0.0 8.830 120 14.813 to 0.0 0.0 0.0 51 25 114.82 1.682 0.0 8.830 0.3310 2.923 Vel = 16.58 51 25 5.60 23.58 1.5 T 9.9 3.000 120 17.736 to 0.0 9.900 0.0 52 25 138.4 1.682 0.0 12.900 0.4678 6.034 Vel = 19.98 52 25 0.0 2.5 0.0 10.000 120 23.770 to 0.0 0.0 0.0 53 25 138.4 2.635 0.0 10.000 0.0526 0.526 Vel = 8.14 53 25 130.10 2.5 0.0 5.050 120 24.296 to 0.0 0.0 0.0 TASR 25 268.5 2.635 0.0 5.050 0.1790 0.904 Vel = 15.80 TASR 25 0.0 2.5 X 14.827 11.200 120 25.200 to V 5.903 20.730 4.838 BASR 13.83 268.5 2.635 0.0 31.930 0.1790 5.717 Vel = 15.80 BASR 13.83 0.0 2.5 X 14.827 0.500 120 35.755 to 0.0 14.827 0.0 54 13.83 268.5 2.635 0.0 15.327 0.1790 2.744 Vel = 15.80 54 13.83 0.0 2.5 X 14.827 36.230 120 38.499 to 0.0 14.827 0.0 18 13.83 268.5 2.635 0.0 51.057 0.1791 9.142 Vel = 15.80 18 13.83 0.0 4 V 8.954 3.330 120 47.641 to 0.0 8.954 0.0 TOR 13.83 268.5 4.26 0.0 12.284 0.0173 0.212 Vel = 6.04 TOR 13.83 0.0 4 Xaa 17.117 7.330 120 47.853 to Fsp 0.0 17.117 6.175 * Fixed Loss = 3 BOR 6.5 268.5 4.26 0.0 24.447 0.0173 0.422 Vel = 6.04 BOR 6.5 0.0 4 2E 26.334 4.250 120 54.450 to Zia 0.0 26.334 3.676 * Fixed Loss = 3.676 BKFL 6.5 268.5 4.26 0.0 30.584 0.0173 0.528 Vel = 6.04 BKFL 6.5 0.0 4 0.0 12.000 140 58.654 to 0.0 0.0 5.197 UG -5.5 268.5 4.1 0.0 12.000 0.0156 0.187 Vel = 6.52 EOD Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Front-Line Fire Protection LLC Page 6 Railworks Rental Condo Date 04/22/20 Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt to or Ftng's Pe ******* Notes ****** Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf UG -5.5 0.0 4 E 14.534 25.000 140 64.038 to G 2.907 17.441 -2.382 TEST 0 268.5 4.1 0.0 42.441 0.0156 0.664 Vel = 6.52 250.00 Qa = 250.00 TEST 518.50 62.320 K Factor = 65.68 55 25 5.60 20.40 1.5 0.0 10.000 120 13.274 to 0.0 0.0 0.0 56 25 20.4 1.682 0.0 10.000 0.0136 0.136 Vel = 2.95 56 25 5.60 20.51 1.5 0.0 6.730 120 13.410 to 0.0 0.0 0.0 57 25 40.91 1.682 0.0 6.730 0.0490 0.330 Vel = 5.91 57 25 5.60 20.76 1.5 0.0 8.080 120 13.740 to 0.0 0.0 0.0 58 25 61.67 1.682 0.0 8.080 0.1048 0.847 Vel = 8.90 58 25 5.60 21.39 1.5 0.0 10.000 120 14.587 to 0.0 0.0 0.0 59 25 83.06 1.682 0.0 10.000 0.1818 1.818 Vel = 11.99 59 25 5.60 22.68 1.5 0.0 8.830 120 16.405 to 0.0 0.0 0.0 60 25 105.74 1.682 0.0 8.830 0.2843 2.510 Vel = 15.27 60 25 5.60 24.35 1.5 T 9.9 3.000 120 18.915 to 0.0 9.900 0.0 53 25 130.09 1.682 0.0 12.900 0.4171 5.381 Vel = 18.78 0.0 53 130.09 24.296 K Factor = 26.39 Final Calculations - Hazen-Williams Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 325 North Main Street, Unit C Phone: 978-655-7002 Middleton, MA 01949 SC License #210048 1 FIRE PROTECTION NARRATIVE COMMONWEALTH OF MASSACHUSETTS STATE BUILDING CODE 780 CMR 901.2.1, 9th Edition FIRE PROTECTION SYSTEMS CHAPTER 9 Project: Rail Works Rental Condominiums 1 Jefferson Ave Salem, MA Date: April 23, 2020 SCOPE OF PROJECT: The fire sprinkler system consists of a complete new wet pipe automatic fire sprinkler system throughout the new garage building & existing two-story building as shown on fire protection drawings, dated April 22, 2020 by Frontline Fire Protection. The new sprinkler system will be supplied by a new 4" Ductile Iron underground supply entering in the North corner of the building and is supplied from Jefferson Ave. A 4” Storz type Fire department connection will exit the building in the North West side of the building to supplement the system. 901.2.1 (1a) BASIS (METHODOLOGY) OF DESIGN Section 1 –Building Description 1. Building “Use” Group: Mixed-Use Assembly ☐ Business ☒ Educational ☐ Industrial ☐ High Hazard ☐ Institutional ☐ Mercantile ☐ Residential ☐ Storage ☒ Utility and Miscellaneous ☐ 2. Square footage of Building footprint: 10,820 including existing Square footage of total project area: 15,140 Square Footage of new building: 9,640 including mezzanine Square Footage of Existing: 5,520 3. New Building height: 27’-0 +- Finished grade to roof peak: 27’-0” Finished grade to floor of top occupied story: 15’-6” 4. Number of floors above grade: 2 Existing Building New addition is a slab on grade single story with a mezzanine. 5. Number of floors below grade: 0 7. Type(s) of occupancies (hazards) within building: Ordinary Group 2 8. Type(s) of construction: Wood☒ Steel☒ Concrete☐ Brick☐ Mixed☒ 9. Hazardous material usage and storage: None 10. Site access for emergency response vehicles: Jefferson Ave 325 North Main Street, Unit C Phone: 978-655-7002 Middleton, MA 01949 SC License #210048 2 Section 2 – Applicable Laws and Governing Codes 1. Building Code: Massachusetts State Building Code, 780 CMR, 9th Edition 2. Referenced Standards: NFPA 13, NFPA 72, NFPA 25 3. Applicable Sections of M.G.L., Chapter 148, “Fire Protection.” 4. Applicable Sections of 527 CMR “Fire Prevention Regulations.” 5. Applicable Specialized Codes (plumbing, electrical and architectural access.) 6. Applicable Federal Laws such as OSHA, ADA, etc. 7. 2015 International Building Code Section 3 – Design Responsibility 1. Fire sprinkler design provided by Front-Line Fire Protection LLC. 2. Specifications are provided by Architect, and Owner, and are modified only in so far as to conform to NFPA standards and Massachusetts State Code Chapter 9. 3. The drawings submitted with this Narrative are Concept ☐ Permit ☒ Installation ☒ Record ☐. 4. The Fire Protection Engineer of record responsible for the fire sprinkler suppression system will be Lawrence V. Roy, PE. MA Registration Number 38913 (Fire Protection) 88 Foundry Street, Wakefield, Massachusetts (781)245-9888 Section 4a – Fire Protection System Description: 1. Wet Pipe Automatic Fire Sprinkler System. 2. Water supply– New 4” CLDI52 from Street. 3. Standpipe systems and components – Not Required. 4. Fire alarm systems and components – New by Fire Alarm Contractor. 5. Manual suppression systems – None. 6. Smoke control/management systems – Not Required. Section 4b – Fire Alarm System Description: 1. Main addressable Fire Alarm Panel located in front entry. 2. Exterior Weatherproof red rotating beacon at main entrance. 3. Knox Box at main entrance. 4. Pull Stations at building exits. 5. Horn-Strobe units & strobe-only units (ADA). 6. Central station notification to fire department thru digital communicator. 7. Fire sprinkler fire alarm activation thru water flow switches. 8. Fire sprinkler supervision (Trouble/Supervisory) thru tamper switches. 9. Carbon Monoxide Detectors / Smoke Detectors per City of Revere & NFPA 72, CMR 780. Note: Final Approved Fire Alarm design, components, and related documents are the sole responsibility of the fire alarm contractor. Fire alarm contractor will have his own design professional responsible for the fire alarm system. 325 North Main Street, Unit C Phone: 978-655-7002 Middleton, MA 01949 SC License #210048 3 Section 5 – Special Consideration and Description There is no intent to deviate from the prescriptive building code and standards. Sequence of Operation Fire Alarm System: Initiating Devices / Alarms: The fire alarm system shall be automatic and upon operation of any manual station, smoke detector, flow switch, thermal detector of other automatic alarm initiating device shall automatically: a. Activate the all call code 3 pulse temporal pattern over all audio circuits within the building. b. Flash all visual signals throughout building. c. Flash an alarm LED and sound an audible signal at the FACP and remote annunciator (if applicable). Upon acknowledgement, the alarm LED shall light steadily and the audible shall silence. Subsequent alarms shall re-initiate this sequence. d. Initiate a transmission of an alarm to the fire department thru digital communicator (central station). e. Visually indicate the addressable device or circuit of alarm initiation in plain English via the LCD display at the FACP and remote annunciator. f. Activate the outside weatherproof rotating red beacon, location and style approved by fire department. Troubles / Supervisory Signals: Upon operation of any trouble or supervisory signal (i.e. sprinkler tamper switches) the system shall automatically: a. Flash an alarm LED and sound an audible signal at the FACP and remote annunciator. Upon acknowledgement, the alarm LED shall light steadily and the audible shall silence. Subsequent alarms shall re-initiate this sequence. b. Visually indicate the addressable trouble / supervisory device in plain English via the LCD display at the FACP and remote annunciator. c. Initiate a transmission of a supervisory/trouble signal thru the digital communicator to the central station. The addressable trouble/supervisory signal device description shall be transmitted to the central station. Wet-Pipe Automatic Sprinkler System: Heat produced from a fire melts the fusible element in a sprinkler head or group of sprinkler heads. The sprinkler head(s) is opened and water is immediately discharged to control the fire. Water flow alarms are tripped upon sprinkler flow indicating an alarm condition in the fire alarm panel. Water will continue to flow from the open sprinkler head(s) until the valves serving that area are manually closed. The sprinkler system is zoned by floor with shutoff valves (with tamper switches) and flow switches such that each floor is annunciated separately. 325 North Main Street, Unit C Phone: 978-655-7002 Middleton, MA 01949 SC License #210048 4 903.1.1 (1.c) TESTING CRITERIA SECTION 1 – TESTING CRITERIA The fire alarm and fire protection contractors shall be responsible for performing the final acceptance tests of his system, completing the required testing certificates, and distributing them to the necessary parties. The final acceptance tests shall be witnessed by the Fire Department. FIRE ALARM: 1. Fire Alarm contractor shall submit a test plan in accordance with NFPA 72 Chapter 14. Follow all requirements and recommendations of NFPA 72 Chapter 14. 2. Fire Alarm contractor shall provide typewritten full NFPA 72 test report for initial acceptance testing. The completed system shall be subject to the final test and acceptance, UL certification and periodic inspection, testing and maintenance, in accordance with the Town of Brookline, Massachusetts State Building Code and NFPA 72 Chapter 10 as follows: 3. The initial acceptance test shall include functional testing of each device shall be functionally tested. All fire alarm devices shall be listed on test report with addressable numeric designation, location of device and device description, test results for device 4. Upon function test of each device, the corresponding programmed event sequences shall be verified. Subsequent events shall include occupant notification, system annunciation, and municipal reporting. 5. Proper visual notification and synchronization shall be verified. 6. Audible sound pressure levels shall be measured and recorded. 7. Fault conditions shall be simulated and verified as to their proper reporting and system response. These shall include loss of AC power, battery standby operation, and wiring faults of each and every circuit. 8. A complete report demonstrating the activation and subsequent acknowledgement of each activation shall be generated. 9. An annual test and inspection contract will be in evidence at the time of final testing. The final system acceptance test shall be conducted by the holder of the test contract and witnessed by the local authority having jurisdiction. Upon successful test and acceptance, a UL certificate and final report of compliance shall be issued by the testing company. 10. Testing and inspection shall be conducted by the testing company of record as described and in accordance with NFPA 72. In addition to device testing, maintenance (sensitivity) reports shall be generated directly from the system during each quarterly test. These reports shall include a complete listing of each analog device in the system, their corresponding programmed sensitivity setting, and their current sensitivity level, and the number of times each device has entered alarm verification mode. FIRE SPRINKLER SYSTEM 1. Fire sprinkler contractor shall provide Above Ground test certificate for completed fire sprinkler system. All requirements of NFPA 13 and NFPA 25 shall be followed for initial acceptance testing of fire protection systems. 325 North Main Street, Unit C Phone: 978-655-7002 Middleton, MA 01949 SC License #210048 5 SECTION 2 – EQUIPMENT AND TOOLS All required equipment, tools, and literature shall be supplied by the appropriate contractor at the time of testing including, but not limited to: • Manufacturer’s literature • This approved Narrative report • Flow measuring devices • Gauges • Communication radios • Hydrostatic testing equipment • Fire hoses, nozzles • Smoke detector test magnets and/or test smoke. SECTION 3 – APPROVAL REQUIREMENTS The following shall be supplied to the Fire Department upon final completion and acceptance of the systems: • Name, address, and telephone number of installing contractor for each system • Contractor’s Material and Test Certificate NFPA 13 Aboveground and Underground • NFPA 72 Test Report • As-Built drawings END OF NARRATIVE Version 06_11_2013 Initial Construction Control Document To be submitted with the building permit application by a Registered Design Professional for work per the 9th edition of the Massachusetts State Building Code, 780 CMR, Section 107 Project Title: Rail Works Rental Condo Date: April 23, 2020 Property Address: 1 Jefferson Ave, Salem, MA Project: Check (x) one or both as applicable: XXX New construction XXX Existing Construction Project description: New wet fire sprinkler system throughout the new addition & existing building, as shown on FP1- FP4, by Front-Line Fire Protection, dated April 22, 2020, per NFPA 13. I Lawrence Roy, MA Registration Number: 38913 Expiration date: 06/30/20 , am a registered design professional, and I have prepared or directly supervised the preparation of all design plans, computations and specifications concerning1: Architectural Structural Mechanical XXX Fire Protection Electrical Other: for the above named project and that to the best of my knowledge, information, and belief such plans, computations and specifications meet the applicable provisions of the Massachusetts State Building Code, (780 CMR), and accepted engineering practices for the proposed project. I understand and agree that I (or my designee) shall perform the necessary professional services and be present on the construction site on a regular and periodic basis to: 1. Review, for conformance to this code and the design concept, shop drawings, samples and other submittals by the contractor in accordance with the requirements of the construction documents. 2. Perform the duties for registered design professionals in 780 CMR Chapter 17, as applicable. 3. Be present at intervals appropriate to the stage of construction to become generally familiar with the progress and quality of the work and to determine if the work is being performed in a manner consistent with the approved construction documents and this code. Nothing in this document relieves the contractor of its responsibility regarding the provisions of 780 CMR 107. When required by the building official, I shall submit field/progress reports (see item 3.) together with pertinent comments, in a form acceptable to the building official. Upon completion of the work, I shall submit to the building official a ‘Final Construction Control Document’. Enter in the space to the right a “wet” or electronic signature and seal: Phone number: 781-245-9888 Email: larry@lvrcorp.com Building Official Use Only Building Official Name: Permit No.: Date: Note 1. Indicate with an ‘x’ project design plans, computations and specifications that you prepared or dire ctly supervised. If ‘other’ is chosen, provide a description.