Dibiase Strongwater Derby Manual JProject Name:Project Name: Dibiase Strongwater Derby Address:Address: 30 Osborne Hill Drive, Salem, MA FormType: FormType: HVAC System HVAC System Name: HVAC System Name: whole house BOSTON, LOGAN IAP, MABOSTON, LOGAN IAP, MA Summer Outdoor F:8888 Summer Indoor F:7575 Design Grains:2828 Daily Range:MediumMedium Winter Outdoor F:1212 Winter Indoor F:7070 Cooling RH:50%50%Elevation (Ft):3030 LOAD CALCULATION TOTALSLOAD CALCULATION TOTALS Heating BTU:5890958909 Cooling BTU:2833928339 SHR:0.9000.900 CFM:12901290 Cooling Loads NameName AreaArea SensibleSensible LatentLatent AEDExcursion 0.00 0.00 0.00 aboveGradeWalls 2097.90 2086.36 0.00 belowGradeWalls 0.00 0.00 0.00 blowerMotor 0.00 0.00 0.00 ceilings 2193.70 2851.81 0.00 ducts 0.00 1326.47 469.89 floors 2193.70 3623.99 0.00 infiltration 0.00 987.24 1314.48 internalLoads 0.00 3550.00 1000.00 skylights 0.00 0.00 0.00 ventilation 0.00 0.00 0.00 windows 396.00 11128.57 0.00 winterHumidification 0.00 0.00 0.00 Totals -25554.44 2784.36 Heating Loads NameName AreaArea Heat LossHeat Loss AEDExcursion 0.00 0.00 aboveGradeWalls 2097.90 7909.08 belowGradeWalls 0.00 0.00 blowerMotor 0.00 0.00 ceilings 2193.70 3308.10 ducts 0.00 4550.49 floors 2193.70 14560.68 infiltration 0.00 8599.47 internalLoads 0.00 0.00 skylights 0.00 0.00 ventilation 0.00 0.00 windows 396.00 19982.16 winterHumidification 0.00 0.00 Totals -58909.98 AED Graph Report Id:Report Id: NP1-SM0V-137 Approved ACCA MJ8 CalculationsApproved ACCA MJ8 Calculations Calculations are based on the ACCA Manual J 8th Edition and are approved by ACCA. All computed calculations are estimates on building use, weather data, and inputted values such a R-Values, window types, duct loss, etc. Equipment selections should meet both the latent and sensible gain as well as building heat loss. See Cool Calc Manual S Report for equipment sizing verification. aboveGradeWalls 7.4% ceilings 10.1% ducts 6.3% floors 12.8% infiltration 8.1%internalLoads 16.1% windows 39.3% aboveGradeWalls 13.4% ceilings 5.6% ducts 7.7% floors 24.7%infiltration 14.6% windows 33.9% AED Graph HTM Average Average * 1.3 8 9 10 11 12 13 14 15 16 17 18 19 200 4,000 8,000 12,000 16,000 HoursBTUH 1/4 Project Name:Project Name: Dibiase Strongwater Derby Address:Address: 30 Osborne Hill Drive, Salem, MA FormType: FormType: HVAC System HVAC System Name: HVAC System Name: whole house COMPONENT LOADS Above Grade WallsAbove Grade Walls Construction Nr.Construction Nr.ExposureExposure AreaArea Heating HTMHeating HTM Cooling HTMCooling HTM Heating BTUHeating BTU Sensible BTUSensible BTU Latent BTULatent BTU 12F-0s w N 60.30 3.77 0.99 227.33 59.97 0.00 12F-0s w N 211.20 3.77 0.99 796.22 210.04 0.00 12F-0s w E 302.70 3.77 0.99 1141.18 301.04 0.00 12F-0s w S 253.50 3.77 0.99 955.70 252.11 0.00 12F-0s w W 176.40 3.77 0.99 665.03 175.43 0.00 12F-0s w NW 142.80 3.77 0.99 538.36 142.01 0.00 12F-0s w N 207.60 3.77 0.99 782.65 206.46 0.00 12F-0s w E 262.50 3.77 0.99 989.63 261.06 0.00 12F-0s w S 213.90 3.77 0.99 806.40 212.72 0.00 12F-0s w NW 267.00 3.77 0.99 1006.59 265.53 0.00 Below Grade WallsBelow Grade Walls (none) Blower MotorBlower Motor (none) CeilingsCeilings Construction Nr.Construction Nr.AreaArea Heating HTMHeating HTM Cooling HTMCooling HTM Heating BTUHeating BTU Sensible BTUSensible BTU Latent BTULatent BTU 16B-38 ad 1210.10 1.51 1.30 1824.83 1573.13 0.00 16B-38 ad 983.60 1.51 1.30 1483.27 1278.68 0.00 DuctsDucts EHLFEHLF ESGFESGF ELGELG Heating BTUHeating BTU Sensible BTUSensible BTU Latent BTULatent BTU 0.08 0.05 469.89 0.00 0.00 0.00 FloorsFloors Construction Nr.Construction Nr.AreaArea Heating HTMHeating HTM Heating BTUHeating BTU Sensible BTUSensible BTU Latent BTULatent BTU 19A-0cp 1210.10 6.64 8032.04 1999.09 0.00 19A-0cp 983.60 6.64 6528.64 1624.91 0.00 InfiltrationInfiltration NCFM HeatingNCFM Heating NCFM CoolingNCFM Cooling Heating BTUHeating BTU Sensible BTUSensible BTU Latent BTULatent BTU 134.91 69.10 8599.47 987.24 1314.48 Internal LoadsInternal Loads Heating BTUHeating BTU Sensible BTUSensible BTU Latent BTULatent BTU 0.00 1150.00 1000.00 0.00 2400.00 0.00 VentilationVentilation (none) WindowsWindows Construction Nr.Construction Nr.ExposureExposure AreaArea Heating HTMHeating HTM Heating BTUHeating BTU Sensible BTU Avg.Sensible BTU Avg.Sensible BTU PeakSensible BTU Peak Latent BTULatent BTU 1G N 6.00 50.46 302.76 97.28 127.26 0.00 1G N 24.00 50.46 1211.04 389.13 509.04 0.00 1G E 6.00 50.46 302.76 191.81 389.93 0.00 1G E 36.00 50.46 1816.56 1150.84 2339.57 0.00 1G E 36.00 50.46 1816.56 1150.84 2339.57 0.00 1G S 6.00 50.46 302.76 188.95 325.17 0.00 1G S 24.00 50.46 1211.04 755.79 1300.68 0.00 1G S 36.00 50.46 1816.56 1133.68 1951.02 0.00 1G NW 12.00 50.46 605.52 289.87 607.12 0.00 1G W 6.00 50.46 302.76 219.79 457.42 0.00 1G W 12.00 50.46 605.52 439.58 914.83 0.00 1G N 6.00 50.46 302.76 97.28 127.26 0.00 1G N 24.00 50.46 1211.04 389.13 509.04 0.00 1G E 6.00 50.46 302.76 191.81 389.93 0.00 2/4 1G E 24.00 50.46 1211.04 767.23 1559.71 0.00 1G E 36.00 50.46 1816.56 1150.84 2339.57 0.00 1G S 6.00 50.46 302.76 185.38 325.17 0.00 1G S 24.00 50.46 1211.04 745.07 1300.68 0.00 1G NW 6.00 50.46 302.76 144.93 303.56 0.00 1G NW 24.00 50.46 1211.04 579.73 1214.24 0.00 1G NW 36.00 50.46 1816.56 869.60 1821.36 0.00 Construction Nr.Construction Nr.ExposureExposure AreaArea Heating HTMHeating HTM Heating BTUHeating BTU Sensible BTU Avg.Sensible BTU Avg.Sensible BTU PeakSensible BTU Peak Latent BTULatent BTU Winter HumidificationWinter Humidification (none) 3/4 Project Name:Project Name: Dibiase Strongwater Derby Address:Address: 30 Osborne Hill Drive, Salem, MA FormType: FormType: HVAC System HVAC System Name: HVAC System Name: whole house ROOM LOADS Room NameRoom Name HeatingHeating SensibleSensible LatentLatent CoolingCooling CFMCFM first floor 31571.42 11871.35 712.03 12583.38 599.00 second floor 27338.56 9938.73 602.45 10541.18 501.00 4/4