65FederalSt-Salem- S-1 Dwg - 122319-stamped-f-red 10STRUCTURAL NOTES
1. FOUNDATIONS:
A) ALL FOOTINGS SHALL BEAR ON UNDISTURBED VIRGIN SOIL HAVING A MINIMUM SOIL BEARING CAPACITY OF
4,000 PSF (POUNDS PER SQUARE FOOT) PER GSI FIELD REPORT DATED 10/17/19. NOTIFY ENGINEER IF POOR
SOIL, FILL MATERIAL, CLAYS, SILTS, WATER TABLE, ETC. IS ENCOUNTERED.
B) THE BOTTOM ELEVATION OF EXTERIOR FOOTINGS SHALL BE A MINIMUM OF 4'-0" BELOW OUTSIDE GRADE.
LOWER FOOTINGS AS REQUIRED TO REACH SOIL PROVIDING THE REQUIRED BEARING CAPACITY.
C) ALL FOOTING EXCAVATIONS SHALL BE FINISHED BY HAND AND SHALL BE THOROUGHLY COMPACTED PRIOR TO
FORMING FOOTINGS. ALL FINISHED FOUNDATION EXCAVATIONS SHALL BE INSPECTED AND APPROVED BY THE
OWNER'S QUALIFIED REPRESENTATIVE OR BUILDING OFFICIAL PRIOR TO CONCRETE PLACEMENT.
D) ALL CONCRETE SHALL BE PLACED IN DRY EXCAVATIONS. PUMP AWAY GROUND WATER AS REQUIRED.
E) UNLESS OTHERWISE NOTED ON THE STRUCTURAL DRAWINGS ALL FOUNDATION SPREAD AND CONTINUOUS
FOOTINGS SHALL BE CENTERED UNDER THE COLUMN ABOVE.
F) FOUNDATION WALLS SHALL BE BACKFILLED EVENLY ON BOTH SIDES WHERE POSSIBLE.
2. CONCRETE:
A) ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 4,000 PSI AT 28 DAYS UNLESS
OTHERWISE SPECIFIED HEREIN, OR NOTED ON THE DRAWINGS, OR REQUIRED BY CODE. SLABS SHALL BE FIBERMESH
REINFORCED CONCRETE.
B) MAXIMUM ALLOWABLE SLUMP OF CONCRETE SHALL NOT EXCEED 4".
C) ALL CONCRETE EXPOSED TO WEATHER OR POSSIBLE FREEZE/THAW CYCLES SHALL CONTAIN AN AIR
ENTRAINMENT ADMIXTURE AS REQUIRED TO PROVIDE A TOTAL AIR CONTENT OF 6% +/-1.5% UNLESS OTHERWISE
SPECIFIED OR NOTED ON THE DRAWINGS.
D) ALL CONCRETE SLABS SHALL BE CURED ACCORDING TO ACI SPECIFICATIONS. SLABS SHALL BE REINFORCED
WITH FIBERMESH APPROVED EQUAL. PROVIDE PER MANUFACTURER'S GUIDELINES AND SPECIFICATIONS.
E) ALL CONCRETE WORK SHALL COMPLY WITH THE LATEST EDITION OF THE ACI "BUILDING CODE REQUIREMENTS
FOR STRUCTURAL CONCRETE (ACI 318)" AND THE LATEST MASSACHUSETTS STATE BUILDING CODE. IN CASES OF
CONFLICT, THE REQUIREMENTS OF THE MORE STRINGENT CODE SHALL GOVERN.
F) ALL CONCRETE SHALL BE PLACED UNDER THE SUPERVISION OF THE OWNERS QUALIFIED REPRESENTATIVE OR
BUILDING OFFICIAL.
G) ALL KEYS SHALL BE A MINIMUM OF 2 BY 4 INCHES (NOMINAL) UNLESS OTHERWISE NOTED ON THE
DRAWINGS.
H) NO CONCRETE SHALL BE PLACED UNTIL THE REINFORCEMENT STEEL AND/OR EMBEDDED ITEMS HAVE BEEN
REVIEWED AND APPROVED BY THE OWNERS REPRESENTATIVE OR BUILDING OFFICIAL.
I) REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS AND SIZES OF ALL DOOR AND WINDOW OPENINGS,
REGLETS, WASHES, SLOPES, CONCRETE FINISHES, MASONRY ANCHORS, MISCELLANEOUS EMBEDDED ITEMS AND ALL
OTHER ITEMS THAT MUST BE OTHERWISE INCORPORATED INTO THE CONCRETE WORK.
J) THE PLACEMENT OF SLEEVES, OUTLET BOXES, CONDUIT, BOX —OUTS, ANCHORS, ETC. FOR THE MECHANICAL,
ELECTRICAL, PLUMBING AND FIRE PROTECTION SYSTEMS ARE THE RESPONSIBILITY OF THE TRADE INVOLVED.
HOWEVER, ANY BOX —OUTS, OR OTHER OPENINGS IN THE CONCRETE, NOT INDICATED ON THE STRUCTURAL DRAWINGS,
SHALL BE SUBMITTED TO THE ENGINEER FOR REVIEW AND APPROVAL PRIOR TO INSTALLATION IN THE FORMWORK.
K) THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING AND COORDINATING ALL ELEVATIONS
RELATED TO THE CONCRETE WORK WITH THE ARCHITECTURAL DRAWINGS OR SITE CONDITIONS.
L) GROUT UNDER ALL COLUMN BASE PLATES AND ALL OTHER SETTING AND BEARING PLATES SHALL BE
NON—METALLIC, NON —SHRINK GROUT WITH A MINIMUM COMPRESSIVE STRENGTH OF 5,000 PSI AT 3—DAYS.
3. REINFORCING STEEL:
A) ALL REINFORCING STEEL SHALL BE ASTM A615, GRADE 60, AND SHALL BE COLD BENT.
B) DETAILING AND FABRICATION OF CONCRETE REINFORCEMENT AND RELATED ACCESSORIES SHALL BE IN
ACCORDANCE WITH LATEST EDITION OF "ACI 315 — DETAILS AND DETAILING OF CONCRETE REINFORCEMENT".
C) WELDED WIRE FABRIC (W.W.F.), IF APPROVED IN PLACE OF FIBER MESH REINFORCING IN SLABS, SHALL
BE ASTM A-185 (Fy = 65 ksi MINIMUM). LAP ALL SPLICES 12" MINIMUM AND SECURELY FASTEN W.W.F. IN
PLACE TO PREVENT MOVEMENT DURING CONCRETE PLACEMENT. ALL W.W.F. SHALL BE FURNISHED IN FLAT SHEETS
ONLY AND SHALL BE SUPPORTED ON APPROVED SLAB BOLSTERS ONLY. PROVIDE PROPER COVER. DO NOT USE W.W.F.
WITHOUT APPROVAL FROM ARCHITECT AND ENGINEER.
D) ALL HORIZONTAL RODS ARE CONTINUOUS. THE LENGTH OF ALL LAP SPLICES SHALL BE 48 DIAMETERS.
PROVIDE WALL CORNER AND INTERSECTING BARS PER INDUSTRY STANDARDS.
E) PROVIDE A CLEAR COVER FROM REINFORCING STEEL TO ADJACENT CONCRETE SURFACES AS FOLLOWS:
SURFACES CAST AGAINST EARTH: 3"
BOTTOM OF FOOTINGS: 3"
PIERS AND WALLS: 1-1/2" at #5
2" at #6 and
and smaller
larger
FORMED SURFACES NOT EXPOSED TO EARTH OR WEATHER:
WALLS: 3/4"
SLABS ON GRADE: 1" below top of slab
THESE DIMENSIONS SHALL BE CONSIDERED ACTUAL AND ARE NOT TO BE ADJUSTED IN EITHER DIRECTION UNLESS
OTHERWISE DETAILED ON THE STRUCTURAL DRAWINGS.
F) SUBMIT REINFORCING STEEL SHOP DRAWINGS FOR REVIEW BY THE ENGINEER.
G) ALL REINFORCING RODS AND W.W.F. SHALL BE SECURED IN PROPER POSITION ON CHAIRS, STANDEES,
BOLSTERS, ETC. AS MANUFACTURED BY RICHMOND SCREW ANCHOR CO. OR APPROVED EQUAL. LINES OF CHAIRS,
HIGH —CHAIRS AND BOLSTERS SHALL BE SPACED AT MAXIMUM 4'-0" O.C.
H) PROVIDE ADDITIONAL REINFORCEMENT AT SIDES AND CORNERS OF ALL OPENINGS IN SLABS AND WALLS AS
DETAILED ON THE STRUCTURAL DRAWINGS AND PER INDUSTRY STANDARDS. PROVIDE MINIMUM LAP LENGTHS EACH
SIDE OF OPENING AND PROVIDE STANDARD HOOKED ENDS WHERE REQUIRED LAP IS NOT POSSIBLE.
I) THE FOUNDATION CONTRACTOR/ SUBCONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR FULL COMPLIANCE WITH
ALL FEDERAL OSHA SAFETY REGULATIONS AND REQUIREMENTS RELATED TO THE WORK PERFORMED BY THEM ON THIS
PROJECT.
J) ALL DOWELS FROM FOOTINGS INTO PIERS, COLUMNS, PILASTERS, BUTTRESSES OR WALLS ABOVE SHALL BE
THE SAME SIZE AND NUMBER AS THE VERTICAL REINFORCEMENT IN THE PIER, COLUMN, PILASTER AND WALLS ABOVE
EXCEPT WHERE NOTED OTHERWISE ON THE DRAWINGS. ALL DOWELS SHALL HAVE 90 DEGREE STANDARD HOOKED ENDS
IN THE FOOTING UNLESS OTHERWISE NOTED ON THE DRAWINGS.
4. TIMBER:
A) ALL LUMBER USED SHALL BE S—P—F (SPRUCE —PINE —FIR) NO. 2 OR BETTER (EXCEPT FOR PRESSURE TREATED
LUMBER), AND SHALL BEAR THE STAMP OF THE APPROVING GRADING AGENCY. ALL FRAMING LUMBER USED ON THE
PROJECT SHALL BE KILN DRIED LUMBER AND SHALL BE STORED OFF THE GROUND AND COVERED WITH WATERPROOF
SHEETING TO PROTECT IT FROM WEATHER.
B) ALL WOOD IN CONTACT WITH MASONRY OR CONCRETE SHALL BE PRESERVATIVE TREATED LUMBER.
PRESERVATIVE TREATED LUMBER SHALL BE SOUTHERN YELLOW PINE NO. 2 OR BETTER.
C) FASTEN LUMBER SECURELY TOGETHER AND TO ALL SUPPORTS AS DETAILED ON THE DRAWINGS AND PER
INDUSTRY STANDARDS.
D) ALL PLYWOOD SHALL BE APA CD EXTERIOR GRADE UNLESS OTHERWISE NOTED. SEE ARCHITECTURAL
DRAWINGS FOR THICKNESSES.
E) ALL TIMBER FRAMING SHALL COMPLY WITH THE NDS (NATIONAL DESIGN SPECIFICATION) AND ALL
APPLICABLE BUILDING CODES.
F) THE GENERAL CONTRACTOR AND THIS SUBCONTRACTOR SHALL NOTIFY THE STRUCTURAL ENGINEER OF RECORD
(S.E.R.) OF ANY AND ALL CHANGES TO TIMBER COMPONENTS AND MATERIAL SUBSTITUTIONS FROM THOSE ON THE
APPROVED SHOP DRAWINGS OR STRUCTURL DRAWINGS SO THE S.E.R. CAN REVIEW THE MODIFICATIONS PRIOR TO
INSTALLATION.
G) ALL JOIST HANGERS AND OTHER METAL ACCESSORIES USED FOR ATTACHING STRUCTURAL COMPONENTS
TOGETHER SHALL BE AS MANUFACTURED BY "SIMPSON/STRONG TIE COMPANY". IF THE TYPE OR SIZE OF HANGER IS
NOT SPECIFIED ON THE DRAWINGS, HARDWARE CONSISTENT WITH INDUSTRY STANDARDS SHALL BE USED PENDING
VERIFICATION OF ADEQUACY WITH THE ENGINEER. HARDWARE SHALL BE INSTALLED USING THE NUMBER AND TYPE
OF FASTENERS SPECIFIED BY THE MANUFACTURER FOR THAT SPECIFIC CONNECTION. SUBSTITUTIONS FOR PRODUCTS
EQUAL TO THOSE MANUFACTURED BY SIMPSON SHALL BE SUBMITTED WITH FULL CATALOG DOCUMENTATION OF
CONFIGURATIONS AND LOAD RATINGS. REFER TO FOLLOWING FOR REQUIREMENTS WHEN ATTACHING TO PRESSURE
TREATED LUMBER.
H) ALL METAL PLATE FRAMING CONNECTORS (i.e. TIE STRAPS, JOIST HANGERS, HOLDOWNS, HURRICANE
CLIPS, POST CAPS, POST BASES, ETC.) IN DIRECT CONTACT WITH CROMATED COPPER ARSENATE (CCA—C), SODIUM
BORATE (SBX), ALKALINE COPPER QUAT (ACQ—C & ACQ—D), COPPER AZOLE (CBA—A & CA—B) OR SBX w/ NaSi02
PRESERVATIVE TREATED LUMBER SHALL HAVE HOT DIPPED GALVANIZED (G135 HDG PER ASTM A653) FINISH SUCH AS
"ZMAX" FINISH BY SIMPSON STRONG —TIE, OR APPROVED EQUAL. ALL FRAMING CONNECTORS IN CONTACT WITH ANY
OTHER TYPE OF PRESERVATIVE TREATMENT SHALL BE FABRICATED FROM TYPE 306 AND TYPE 316 STAINLESS STEEL.
THE FASTENERS USED TO SECURE THESE CONNECTORS SHALL BE OF THE SAME FINISH AS THE CONNECTORS. SOME
STAINLESS STEEL "SIMPSON" CONNECTORS MAY REQUIRE TO BE SPECIAL ORDERED. NOTIFY ENGINEER OF ANY
SUBSTITUTES IF STAINLESS STEEL CANNOT BE ORDERED.
I) ALL FASTENERS (i.e. CARRAIGE BOLTS, ANCHOR RODS, LAG BOLTS, NAILS, SCREWS, ETC.) IN DIRECT
CONTACT WITH CROMATED COPPER ARSENATE (CCA—C), SODIUM BORATE (SBX), ALKALINE COPPER QUAT (ACQ—C &
ACQ—D), COPPER AZOLE (CBA—A & CA—B) OR SBX w/ NaSi02 PRESERVATIVE TREATMENTED WOOD SHALL HAVE HOT
DIPPED GALVANIZED (G135 HDG PER ASTM A653) FINISH, OR APPROVED EQUAL. ALL FASTENERS IN CONTACT WITH
ANY OTHER TYPE OF PRESERVATIVE TREATED WOOD SHALL BE FABRICATED FROM TYPE 306 AND TYPE 316 STAINLESS
STEEL.
5. BCI "I —JOIST" MEMBERS:
A) ALL BCI LUMBER SHALL BE MANUFACTURED BY BOISE CASCADE OR APPROVED EQUAL. SUBSTITUTIONS WILL ONLY
BE REVIEWED FOR USE IF ALL SUBSTITUTIONS ARE CLEARLY NOTED ON SHOP DRAWINGS AND ALL PERTINENT LOAD
CAPACITY INFORMATION IS SUBMITTED.
B) THE CONTRACTOR MUST HAVE A COPY OF THE "BUILDER'S GUIDE TO THE FRAMEWORKS BUILDING SYSTEM" ON THE
JOB AT ALL TIMES WHILE THE FRAMING IS BEING CONSTRUCTED.
C) THE GENERAL NOTES LISTED IN THE "BUILDER'S GUIDE TO THE FRAMEWORKS BUILDING SYSTEM" REFERENCED IN
ITEM 5B ABOVE IS HEREBY INCORPORATED IN THIS PROJECT ALONG WITH ALL ASSOCIATED DETAILS,
RECOMMENDATIONS AND NOTES.
D) PROVIDE SQUASH BLOCKS, WEB STIFFENERS ETC. AS REQUIRED BY BOISE CASCADE AND THE STRUCTURAL
DRAWINGS.
E) CORING OF HOLES THROUGH BCIs SHALL CONFORM WITH THE REQUIREMENTS SET FORTH BY THE MANUFACTURERS
DESIGN BROCHURE.
F) BCI JOISTS NOT DESIGNED TO SUPPORT NATURAL STONE FLOORING. CONSULT WITH ENGINEER.
6. LAMINATED VENEER LUMBER (NOTED AS "LVL" OR VL ON DRAWINGS):
A) ALL LAMINATED VENEER LUMBER SHALL BE BY BOISE CASCADE OR APPROVED EQUAL.
B) ALL LAMINATED VENEER LUMBER SHALL HAVE THE FOLLOWING MINIMUM ALLOWABLE DESIGN PROPERTIES:
Fb = 3,100 PSI
Fv = 285 PSI
E = 2,000,000 PSI
C) FASTEN MULTIPLE MEMBER LAMINATED VENEER BEAMS ACCORDING TO MANUFACTURER'S SPECIFICATIONS
UNLESS OTHERWISE NOTED OR DETAILED ON THE STRUCTURAL DRAWINGS.
D) THE GENERAL CONTRACTOR AND/OR SUBCONTRACTOR SHALL NOTIFY THE STRUCTURAL ENGINEER OF RECORD
(S.E.R.) OF ANY AND ALL CUTS, CORED HOLES AND NOTCHES OTHER THAN THOSE INDICATED ON THE DRAWINGS SO
THE S.E.R. CAN REVIEW THE MODIFICATIONS PRIOR TO INSTALLATION.
7. EPDXY ANCHORS:
A) ANCHORS WHICH ARE TO BE EPDXIED INTO CONCRETE OR MASONRY ARE TO BE DONE SO USING "HILTI"
FASTENERS. UNLESS SPECIFIED ELSEWHERE ON THE DRAWINGS, ANCHORS SHALL BE OF THE FOLLOWING TYPE BASED
ON THE MATERIAL IN WHICH THEY ARE TO BE EMBEDDED:
CONCRETE — "HIT—HY 200"; OR, "HIT —ICE" (FOR WINTER CONDITIONS)
BRICK, STONE OR CONCRETE BLOCK — "HIT—HY 270"
ALTERNATE MATERIALS MAY BE USED; HOWEVER, ANY SUBSTITUTION MUST BE APPROVED BY THE ENGINEER PRIOR TO
ITS USE.
B) HOLES TO BE DRILLED FOR THE ANCHORS SHALL BE OF THE DIAMETER SPECIFIED BY THE MANUFACTURER
FOR THAT SPECIFIC ANCHOR, AND THE EMBEDMENT DEPTH SHALL BE AS NOTED ON THESE DRAWINGS. IF EMBEDMENT
IS NOT NOTED, THE MAXIMUM DEPTH SPECIFIED BY THE MANUFACTURER FOR THAT ANCHOR DIAMETER SHALL BE
USED. NOTIFY ENGINEER OF MISSING EMBEDMENT INFORMATION PRIOR TO IMPLEMENTATION.
C) HOLES SHALL BE CLEANED THOROUGHLY BEFORE PROCEEDING WITH THE ANCHOR EMBEDMENT. AT A MINIMUM,
THE FOLLOWING HOLE PREPARATION AND CLEANING SHALL BE FOLLOWED AT ALL HOLES DRILLED FOR EPDXY
ANCHORS:
"STEP 1" — REMOVE ALL DUST AND DEBRIS FROM HOLE WITH COMPRESSED OR VACUUM WITH A NOZZLE INSERTED TO
THE BOTTOM OF HOLE;
"STEP 2" — WIRE BRUSH ALL PERIMETER SURFACES OF INSIDE OF HOLE WITH BRUSH EQUAL TO HOLE DIAMTER;
"STEP 3" — REPEAT HOLE CLEANING OUTLINED IN "STEP 1" ABOVE. THESE PREPARATION AND CLEANING
REQUIREMENTS ARE A MINIMUM, IF BOLT MANUFACTURER'S REQUIREMENTS ARE MORE STRINGENT THEY SHALL BE
FOLLOWED.
D) ANCHORS INTO MASONRY SHALL HAVE A SCREEN INSERT AS SPECIFIED BY THE ANCHOR MANUFACTURER.
E) ALL INSTALLATION REQUIREMENTS SPECIFIED BY THE MANUFACTURER MUST BE STRICTLY FOLLOWED.
8. EXPANSION BOLTS:
A) EXPANSION BOLTS SHALL BE "HILTI— KWIK BOLT TZ" FASTENERS UNLESS OTHERWISE NOTED ON THE
DRAWINGS. SIZE OF ANCHORS SHALL BE AS SPECIFIED ON THE DRAWINGS.
B) HOLES TO BE DRILLED FOR THE ANCHORS SHALL BE OF THE DIAMETER SPECIFIED BY THE MANUFACTURER
FOR THAT SPECIFIC ANCHOR, AND THE EMBEDMENT DEPTH SHALL BE AS NOTED ON THESE DRAWINGS. IF EMBEDMENT
IS NOT NOTED, THE MAXIMUM DEPTH SPECIFIED BY THE MANUFACTURER FOR THAT ANCHOR SHALL BE USED. NOTIFY
ENGINEER OF MISSING EMBEDMENT INFORMATION PRIOR TO IMPLEMENTATION.
C) HOLES SHALL BE CLEANED THOROUGHLY BEFORE PROCEEDING WITH THE ANCHOR EMBEDMENT.
D) ALL INSTALLATION REQUIREMENTS SPECIFIED BY THE MANUFACTURER MUST BE STRICTLY FOLLOWED.
E) DO NOT CUT OR DAMAGE EXISTING EMBEDDED CONCRETE REINFORCEMENT DURING INSTALLATION WITHOUT
PRIOR APPROVAL FROM THE ENGINEER.
9. TEMPORARY SHORING AND BRACING:
A) THE GENERAL CONTRACTOR SHALL PROVIDE ALL TEMPORARY SHORING AND BRACING NECESSARY TO PROTECT
THE STRUCTURE FROM DAMAGE DURING THE WORK. ALL SHORING AND BRACING SHALL BE DESIGNED AND INSTALLED
BY QUALIFIED PERSONNEL EXPERIENCED WITH THIS SPECIFIC TYPE OF WORK.
B) ALL SHORING SHALL BE FOUNDED ON STRUCTURAL ELEMENTS CAPABLE OF SUPPORTING THE LOAD. RESHORE
TO LOWER LEVELS AS REQUIRED.
C) PROVIDE ALL NECESSARY TEMPORARY BRACING TO HOLD STRUCTURAL COMPONENTS IN POSITION UNTIL
PERMANENT BRACES AND/ OR SHEATHING ARE INSTALLED.
10. MISCELLANEOUS:
A) THE GENERAL CONTRACTOR SHALL VERIFY ALL DETAILS AND DIMENSIONS BEFORE PROCEEDING WITH THE
WORK. NOTIFY ENGINEER OF ANY DISCREPANCIES.
B) ALL WORK SHALL COMPLY WITH THE CURRENT EDITION OF THE MASSACHUSETTS STATE BUILDING CODE, AND
ANY APPLICABLE LOCAL CODES.
C) THE STRUCTURAL DRAWINGS SHALL NOT BE SCALED TO OBTAIN DIMENSIONS, OFFSETS, SPACINGS, ETC. FOR
ANY STRUCTURAL FRAMING MEMBERS, FOUNDATION WALLS, ETC. WRITTEN DIMENSIONS ON THE STRUCTURAL AND
ARCHITECTURAL DRAWINGS SHALL BE USED. IF A CONFLICT OR DISCREPANCY IS FOUND BETWEEN WRITTEN
DIMENSIONS ON ARCHITECTURAL AND STRUCTURAL DRAWINGS, THE CONTRACTOR SHALL SUBMIT A WRITTEN "REQUEST
FOR INFORMATION" TO THE ARCHITECT PRIOR TO PROCEEDING WITH THE WORK.
D) ALL MATERIAL, PRODUCT AND COMPONENT SUBSTITUTIONS SHALL BE PRE —APPROVED BY DAIGLE ENGINEERS,
INC. AND MUST HAVE EQUAL PROPERTIES AND LOAD CARRYING CAPACITIES AS DOCUMENTED IN THE MANUFACTURER'S
SPECIFICATIONS.
PROPOSED RENOVATION & ADDITION
65 FEDERAL STREET . SALEM, MASSACHUSETTS
OWNER: 65 FEDERAL STREET LLC
I
V
1'-6" WALL
2'-9„
-
L_
I
I4 I SEE NOTE "A" BELOW FOR
SHEAR WALL ANCHOR'
I 2'-6"x12"THICK CONT. CONC FOOTING
W/#4's @ 12" EACH WAY
(3" BOTTOM COVER)
4'-2" 2'-4 1/2"
4'_2„
NEW 12"x2'-6" REINF CONCRETE FOOTING —
I NEW REINF CONCRETE FOUNDATION
WALL W/ WATERPROOFING
& RIGID INSULATION (EXT)
-EXISTING FOUNDATION
WALL TO REMAIN
24"x10" EOOTIIIIGS
W/ 10" CMU WALL,
SEE SHEET S4
SEE SECTION 'Al" FOR
NEW FOUND. ANCHORS @
EXIST. FOUNDATIONS-TYP.
FACE OF BRICK
FOUNDATION
8'-1 1 /2" (+/-)
+ NOTE "A": AT BASEMENT DESIGNATED SHEAR WALLS
PROVIDE 5/8" DIA. ANCHOR BOLTS
@ 4 FT. MAX. -EMBED 4" INTO FOOTINGS.
DAIGLE ENGINEERS, INC
STRUCTURAL_ ENGINEERING
1 EAST RIVER PLACE
METHUEN, MA 01844-3818
978-682-1748
L_
40'-0"
T-
ALL VERIFY
•
EXISTING FOUNDATICN
WALLS TO BE REMOVED
I- , LC -
A
•-•
L — —
UNDERPIN
EXISTG
V CHIMNEY
-UNDERPIN EXISTING
FOUNDATION WALL AS REQUIRED
TO LOWER EXISTING BASEMENT
FLOOR LEVEL AS INDICATED
(TYP ALL EXIST'G FOUNDATION
WALLS TO REMAIN)
SEE NOTE "A" BELOW FOR
SHEAR WALL ANCHORS
I I /
t— — I I
FTGS SIM. TO `N
"5" LINE —
II
LC
0000000
LC I
EXISNG P
W--R70- MEtLS1@NS
II
OPERTY LI4F 4'-2„
10" WALL
LIGHT WELLS
4T
—1
SEE NOTE "A" BELOW FOR
SHEAR WALL ANCHORS
- TOP OF WALL @ 15" BELOW 1ST FF
LALL" COLUMNS (LC)
UP TO BEAM LINE (TYP)
1 LJ�
2'-01'x10'THICK CONT. CONC FOOTING
W/#4's @ 12" EACH WAY
(3" BOTTOM COVER)
-41-
4"SLAB ON GRADE W,/
FIBER MESH REINF.-
PROVIDE CONTROL JOINTS
EACH WAY @ 12' MAX (PROVIDE
SQUARE PNLS WHERE PO
11
1 1 J/4" TOP OF WALLI @ 15" BELOW 1ST FF-
14'-11 1/2" I I
I I
,_2 -3 1.10 1/2 4,-0„1 1 -4 3/4
2'-6"x12"THICK CONT. CONC FOOTING
W/#4's @ 12" EACH WAYI
(3" BOTTOM COVER) I 11
N—r 13_10 1/2"
00000��♦
- REMOVE EXISTING
BRICK PIERS AND RE'LACE
W/ LALLY COLS AND
CONC STRIP FOOTINGS (TYP FOR 2)
FURRED OUT WALLS W/ SPRAY FOAM
INSULATION AT INTERIOR OF EXISTING
FOUNDATION WALLS TO REMAIN (TV)
L_ L
FEDERAGABLE END
L
REtT
24"x10" FOOTINGS
W/ 10" CMU WALL,
SEE SHEET S4
TOP OF WALL
@ 2'-3" BELOW 1ST FF
10" WALL
3'-11 1/2"
NOTE: ALL NEW EXTERIOR ALLS
ARE 2x6 UNLESS OTHERWI bE NOTED
NOTE: ALL NEW INTERIOR \
ARE 2x4 UNLESS OTHERWI
W-3 (2x6
= WALL TYPE
(SEE WALL N
DETILS)
FOUNDATION PAN
1
2
3
FACE OF BRICK
FOUNDATION
4
8 I SCALE IN FEET 16
I GB-B-1(2x49I = SHEAR WALL (SEE WALL DETAILS)
14'-8 1 /4I'
FOUNDATION PLAN Sc STRUCTURAL NOTES
6
U
VINCENT
PULSELLI
STRUCTURAL
No. 40739
4)4scisTei'.0
SCALE : AS NOTED
DATE : 23 DEC 2019
Z
0
W
cc
JOB* : J 2019-03
SHEET * :
s-i