5_MechanicalMECHANICAL SYMBOL LEGEND ALL ITEMS SHOWN HERE ARE NOT NECESSARILY USED ON THIS PROJECT ABBREVIATIONS DUCTWORK AIR CONDITIONING UNIT ACCESS DOOR AIR FILTER AIR HANDLING UNIT ACCESS PANEL AUTOMATIC TEMPERATURE CONTROL AIR SEPARATOR AIR VENT BAROMETRIC DAMPER BACKDRAFT DAMPER BRAKE HORSEPOWER BOTTOM OF DUCT BOTTOM OF PIPE BRITISH THERMAL UNITS BALL VALVE COOLING COIL CEILING SUPPLY DIFFUSER CUBIC FEET PER MINUTE CONTROL PANEL CLEAN OUT CENTER OF PIPE CEIUNG RETURN DIFFUSER CONTRACTOR CABINET UNIT HEATER CONDENSING UNIT DRY BULB DIAMETER DIFFUSER DOWN DIRECT EXPANSION DRAWING EXISTING ENTERING AIR TEMPERATURE ELEC BASEBOARD RADIATION EFFICIENCY EXHAUST FAN ELECTRICAL ELEVATION EXTERNAL STATIC PRESSURE EXPANSION TANK ELECTRIC UNIT HEATER ELECTRIC WALL HEATER ENTERING WATER TEMPERATURE EXHAUST DEGREES FAHRENHEIT FIRE DAMPER FULL LOAD AMPS FLEXIBLE FLOW MEASURING STATION FEET PER MINUTE FINNED TUBE RADIATION FEET GALLONS GALVANIZED GENERAL CONTRACTOR GALLONS PER MINUTE GATE VAVLE HEATING COIL HORSEPOWER HEAT PUMP HEAT RECOVERY VENTILATOR HEATING, VENTILATION, & AIR CONDITIONING HOT WATER HEAT EXCHANGER HERTZ INCHES KILOWATT LEAVING AIR TEMPERATURE LINEAR FEET LEAVING WATER TEMPERATURE THOUSANDS OF BTU'S PER HOUR MOTORIZED DAMPER MECHANICAL NOT APPUCABLE NORMALLY CLOSED NORMALLY OPEN NOT TO SCALE OUTSIDE AIR OUTSIDE AIR TEMPERATURE OPPOSED BLADE DAMPER OPEN ENDED DUCT OUTSIDE DIAMETER PRESSURE DROP PHASE RETURN RETURN AIR ROOF EXHAUST FAN REQUIRED RETURN GRILLE RELATIVE HUMIDITY REHEAT COIL REVOLUTIONS PER MINUTE RETURN REGISTER ROOF TOP UNIT SUPPLY SUPPLY AIR SUPPLY AIR TEMPERATURE SQUARE FEET SMOKE/FIRE DAMPER STATIC PRESSURE SQUARE SUPPLY REGISTER SATURATED CONDENSING TEMPERATURE STEEL THERMOSTAT TO BE DEMOLISHED TYPICAL UNDERCUT DOOR 3/4" (MIN) UNIT HEATER VOLTS VARIABLE AIR VOLUME VOLUME DAMPER VARIABLE FREQUENCY DRIVE WITH WITHOUT WET BULB TEMPERATURE WATER GAUGE WATER HEATER ZONE VALVE I��1 SUPPLY CEILING DIFFUSER 1^J� THROW PATTERN ▪ RETURN CEILING REGISTER r-AAAAr2 z rVDz FD FD z CEILING EXHAUST FAN WITH FLEXIBLE CONNECTION SIDE WALL GRILLE/REGISTER FLOOR GRILLE/REGISTER SUPPLY DUCT UP SUPPLY DUCT DOWN RETURN/EXHAUST DUCT UP RETURN/EXHAUST DUCT DN. MITERED ELBOW TURNING VANES STANDARD RADIUS ELBOW (R=W) STANDARD DUCT TAKE -OFF W/ BRANCH DAMPERS BULLHEAD SPLIT SUPPLY BULLHEAD CONVERGE RETURN/EXHAUST HORIZONTAL OFFSET FLEXIBLE CONNECTION (6' NEOPRENE) ACOUSTICALLY LINED DUCT VOLUME DAMPER (OPPOSED BLADE TYPE) FIRE DAMPER SMOKE/FIRE DAMPER DUCT CAP ACCESS PANEL IN BOTTOM OR SIDE OF DUCT TRANSITION - ECCENTRIC TRANSITION - CONCENTRIC RECTANGULAR TO ROUND TRANSITION EXHAUST/RETURN/INTAKE SUPPLY AIR BLOW DIRECTION azi Tiv I �• 1-VD ;13 t lSFD t I t r] L�J� $> DUCTS - TYPES AND ABBREVIATIONS DUCTS- DUCTS- DUCTS- DUCTS- DUCTS- DUCTS - SUPPLY AIR (SA) RETURN AIR (RA) TOILET EXHAUST (TE) FLUE EXHAUST (FE) DRYER EXHAUST (DE) COMBUSTION AIR (CA) GENERAL SYMBOL LEGEND SWITCH TEMPERATURE SENSOR WALL THERMOSTAT DUCT SMOKE DETECTOR CO DETECTOR HVAC GENERAL NOTES 1. THESE DRAWINGS ARE SCHEMATIC AND ARE INTENDED TO CONVEY A FULLY FUNCTI❑NAL HVAC SYSTEM. DRAWINGS DEPICT THE GENERAL LOCATION OF THE NEW HVAC COMPONENTS AND EXACT L❑CATIONS SHALL BE FIELD C❑❑RDINATE WITH ALL TRADES AND C❑NDITI❑NS. HVAC CONTRACTOR SHALL PR❑VIDE ALL NECESSARY ACCESS❑RIES AND DEVICES, WHETHER SPECIFICALLY SHOWN OR NOT, TO PR❑VIDE PROPER ❑PERATI❑N WITH FULL BALANCING AND ADJUSTING PER QUANTITIES NOTED ON PLANS AND IN SCHEDULES. 2, CONTRACTOR SHALL EXAMINE THE CONTRACT DOCUMENTS AND CONDUCT A COMPLETE FIELD SURVEY TO FAMILIARIZE HIMSELF WITH ALL THE REQUIREMENTS OF THE PROJECT AND SHALL NOTIFY THE OWNER OF ANY OBSERVED FAULTS AND AMBIGUITY IN THE CONTRACT DOCUMENTS SO THAT THE MATTER MAY BE RESOLVED PRIOR TO SUBMISSION OF BIDS. 3, BY SUBMISSION OF BID, THE CONTRACTOR SHALL ACKNOWLEDGE ACCEPTANCE OF THE CONTRACT DOCUMENTS AS AN ADEQUATE DEFINITION OF THE SCOPE OF WORK AND EXTRA COST CLAIMS BASED ON INADEQUACY OF CONTRACT DOCUMENTS WILL NOT BE CONSIDERED. 4. SUBMISSION OF PROPOSAL SHALL BE CONSTRUED AS EVIDENCE THAT A CAREFUL EXAMINATION OF THE P❑RTI❑NS OF THE EXISTING BUILDING, EQUIPMENT, ETC, WHICH AFFECT THIS WORK AND THE ACCESS TO SUCH SPACES, HAS BEEN MADE AND THAT THE CONTRACTOR IS FAMILIAR WITH EXISTING C❑NDITI❑NS AND DIFFICULTIES THAT WILL AFFECT THE EXECUTION OF THE WORK, LATER CLAIMS SHALL NOT BE MADE FOR LABOR, EQUIPMENT OR MATERIALS REQUIRED BECAUSE OF DIFFICULTIES ENCOUNTERED WHICH COULD HAVE BEEN FORESEEN DURING SUCH AN EXAMINATION 5. ALL APPLICABLE CODES, LAWS AND REGULATIONS GOVERNING OR RELATING TO ANY P❑RTI❑N OF THIS WORK ARE HEREBY INC❑RP❑RATED INTO AND MADE A PART OF THESE SPECIFICATIONS, AND THEIR PROVISIONS SHALL BE CARRIED OUT BY THE CONTRACTOR WHO SHALL INFORM THE OWNER PRIOR TO SUBMITTING A PROPOSAL, OF ANY WORK OR MATERIALS WHICH VI❑LATE ANY OF THE ABOVE LAWS AND REGULATIONS, ANY WORK DONE BY THE CONTRACTOR CAUSING SUCH VIOLATION SHALL BE CORRECTED BY THE C❑NTRACT❑R, 6. INSTALL WORK S❑ AS TO BE READILY ACCESSIBLE FOR OPERATION, MAINTENANCE AND REPAIR. MINOR DEVIATIONS FROM DRAWINGS MAY BE TO ACCOMPLISH THIS, BUT CHANGES WHICH INVOLVE EXTRA COST SHALL NOT BE MADE WITH❑UT APPROVAL. 7. INSTALLATION OF ALL EQUIPMENT AND THEIR ACCESS❑RIES SHALL BE PER MANUFACTURER'S PUBLISHED REC❑MMENDATI❑NS. 8, CONTRACTOR SHALL VERIFY VOLTAGES AND POWER REQUIREMENTS FOR ALL EQUIPMENT, SHALL C❑❑RDINATE WITH THE ELECTRICAL CONTRACT DRAWINGS PRIOR TO SUBMISSION OF SHOP DRAWINGS AND PURCHASE OF EQUIPMENT. 9, MOTOR CONTROLLERS (STARTERS) OR COMBINATION STARTER/DISCONNECT SWITCHES FOR MECHANICAL EQUIPMENT ARE FURNISHED BY MECHANICAL CONTRACTOR AND INSTALLED BY ELECTRICAL CONTRACTOR. 10. PR❑VIDE ALL REQUIRED LABOR, MATERIALS, EQUIPMENT, AND SERVICES NECESSARY FOR COMPLETE AND SAFE INSTALLATION OF HVAC IN FULL CONFORMITY WITH REQUIREMENTS OF ALL AUTHORITIES HAVING JURISDICTION, ALL AS INDICATED ON DRAWINGS AND/OR HEREIN SPECIFIED FOR THE SYSTEMS INCLUDED. WORK SHALL BE INSTALLED IN A NEAT, WORKMANLIKE MANNER. INCLUDE ALL COSTS FOR PERMITS, LICENSES, CERTIFICATES, FILING AND INSPECTIONS REQUIRED BY AUTHORITIES HAVING JURISDICTION. 11. ALL SYSTEMS SHALL BE CLEAN OF F❑REIGN MATERIAL AND ROUGH SPOTS PRIOR TO BEING PLACED IN SERVICE AND BEFORE ❑PERATI❑NAL TESTS ARE PERFORMED. 12. PR❑VIDE EQUIPMENT CURBS AND DUNNAGE STEEL AS REQUIRED. 13. ALL MATERIAL AND EQUIPMENT TO BE NEW UNLESS OTHERWISE NOTED. 14. SUPPORT ALL DUCTWORK AND PIPING FROM BUILDING STRUCTURE AND/OR FRAMING IN AN APPROVED MANNER. WHERE OVERHEAD CONSTRUCTION DOES NOT PERMIT FASTENING OF SUPPORTS FOR EQUIPMENT, FURNISH ADDITI❑NAL STEEL FRAMING. 15. NEW DUCTWORK SHALL BE FABRICATED FROM GALVANIZED SHEET METAL IN ACCORDANCE WITH 'SMACNA DUCT CONSTRUCTION STANDARD', CURRENT EDITION, TRANSVERSE JOINTS SHALL BE 'DUCTMATE' OR APPROVED EQUAL. 16. INSTALL FIRE DAMPERS WHERE NECESSARY AS PER NFPA, LOCAL CODES AND MANUFACTURER'S RECOMMENDATIONS. PR❑VIDE ACCESS PANEL/DOORS TO FIRE DAMPERS WHERE REQUIRED. 17. INSTALL VOLUME DAMPERS FOR ALL BRANCH TAKE OFF AND EXHAUST SYSTEM AS PER PLAN, PR❑VIDE ACCESS PANEL/DOORS TO VOLUME DAMPERS WHERE REQUIRED. 18. PR❑VIDE AIR TURNING DEVICES IN DUCTWORK AT ANY CHANGES IN DIRECTION, AND VOLUME DAMPERS IN ALL DUCTWORK BRANCH -TAKE OFFS. 19. REFER TO THE SCHEDULES FOR ACCEPTABLE REGISTER, DIFFUSER AND GRILLES. C❑❑RDINATE FINISHES AND STYLES WITH THE ADJACENT CEILINGS AND WALL. REFER TO THE PROJECT ARCHITECT FOR ADDITI❑NAL INFORMATION. 20. HVAC CONTRACTOR SHALL C❑❑RDINATE ALL WALL, CEILING, FLOOR, ROOF AND BEAM PENETRATIONS WITH ARCHITECT. 21. EXACT ELEVATION FOR SIDE WALL DIFFUSERS, REGISTERS AND GRILLES SHALL BE APPROVED BY THE ARCHITECT BEFORE INSTALLATION. 22. ALL ROOF CUTTING, FLASHING, SEALING, ETC. TO BE ACC❑MPLISHED BY A R❑❑FING CONTRACTOR APPROVED BY THE ROOF MANUFACTURER AND INSTALLED IN ACCORDANCE WITH ROOF MANUFACTURER'S REC❑MMENDATI❑N SO AS NOT TO V❑ID ROOF WARRANTY. 23. ALL MISCELLANE❑US STRUCTURAL SUPPORTS REQUIRED FOR HVAC EQUIPMENT INSTALLATION SHALL BE PROVIDED BY HVAC SUBCONTRACTOR. 24, SEAL OPENINGS AROUND DUCTS AND PIPING THOUGH PARTITIONS WALLS AND FLOORS (NOT IN SHAFTS) WITH MINERAL WOOL OR OTHER N❑N-COMBUSTIBLE MATERIAL. 25. THE CONTRACTOR SHALL THOROUGHLY CLEAN HIS WORK AREA DAILY. CONTRACTOR SHALL ALSO REMOVE ALL TRASH AFTER COMPLETION OF WORK. WORK DONE UNDER THIS CONTRACT SHALL BE ACC❑MPLISHED WITH MINIMUM IMPACT ON THE ❑PERATI❑N OF THE BUILDING AND IT'S TENANTS. 26, THE CONTRACTOR SHALL KEEP ALL EQUIPMENT AND MATERIALS, AND ALL PARTS OF THE BUILDING, EXTERIOR SPACES AND ADJACENT STREETS, SIDEWALKS AND PAVEMENTS, FREE FROM MATERIAL AND DEBRIS RESULTING FROM EXECUTION OF THIS WORK. EXCESS MATERIALS WILL NOT BE PERMITTED TO ACCUMULATE ON EITHER THE INTERIOR OR THE EXTERIOR. 27. ACCESS TILE IDENTIFICATION PR❑VIDE BUTTONS, TABS AND MARKERS TO IDENTIFY L❑CATION OF CONCEALED VALVES, DAMPERS AND EQUIPMENT. 28, THE CONTRACTOR SHALL FURNISHED A WRITTEN GUARANTEE TO REPLACE OR REPAIR PROMPTLY AND ASSUME RESP❑NSIBILITY FOR ALL EXPENSES INCURRED FOR ANY WORKMANSHIP AND EQUIPMENT IN WHICH DEFECTS DEVELOP WITHIN ONE YEAR FROM THE DATE OF ACCEPTANCE BY OWNER. THIS WORK SHALL BE DONE AS DIRECTED BY THE ❑WNER. THIS GUARANTEE SHALL ALSO PR❑VIDE THAT WHERE DEFECTS OCCUR, THE CONTRACTOR WILL ASSUME RESP❑NSIBILITY FOR EXPENSES INCURRED IN REPAIRING AND REPLACING WORK OF OTHER TRADES AFFECTED BY DEFECTS, REPAIRS OR REPLACEMENTS IN EQUIPMENT SUPPLIED BY THE C❑NTRACT❑R, 29. CONTRACTOR SHALL SUBMIT COPIES OF COMPLETE BALANCE TO THE OWNERS FOR FINAL APPROVAL. BALANCE REPORT SHOULD SHOW METHODS AND RESULTS OF PERFORMED, TESTING AND BALANCING. CONTRACTOR SHALL BE 'AABC' AND 'NEBB' CERTIFIED. 30, BALANCE THE ENTIRE MECHANICAL SYSTEM USING CAPACITIES AS INDICATED ON THESE DRAWINGS. 31. CONTRACTOR SHALL SUBMIT COPIES OF COMPLETE BALANCE TO THE OWNERS FOR FINAL APPROVAL. BALANCE REPORT SHOULD SHOW METHODS AND RESULTS OF PERFORMED, TESTING AND BALANCING. CONTRACTOR SHALL BE 'AABC' AND 'NEBB' CERTIFIED. HVAC NARRATIVE 1. DESIGN INTENT a. THE HVAC DESIGN INTENT IS TO PROVIDE NEW, COMPLETE INDIVIDUAL HVAC SYSTEMS FOR EACH OF THE 61 APARTMENTS WITH A HIGH EFFICIENCY VARIABLE REFRIGERANT FLOW (VRF) SYSTEM WITH AN AIR SOURCE HEAT PUMP UNIT ON THE ROOF AND A DUCTED INDOOR AIR HANDLER OR FAN COIL UNIT. b. SEPARATE NARRATIVES FOR FIRE PROTECTION AND FIRE ALARM WILL BE PROVIDED. c.THE BUILDING WILL HAVE FIVE (5) UPPER RESIDENTIAL FLOORS. THE FIRST FLOOR AT GRADE WILL HAVE THE MAIN ENTRY LOBBY, A TRASH ROOM, A RETAIL SPACE AND THE MIDDLE AND UPPER GARAGES. THERE WILL BE A LOWER GARAGE IN THE BASEMENT OF THE OLD COURT ROOM BUILDING, UNDER THE UPPER GARAGE. THE MIDDLE GARAGE IS LOCATED ON THE OLD EXTERIOR PARKING FOR THE COURT ROOM BUILDING. d.THE APARTMENTS WILL OPERATE 24 HOURS/DAY AND 7 DAYS/WEEK AND WILL HAVE THE CAPACITY TO RUN ON REDUCED TEMPERATURES FOR UN -OCCUPIED AND NIGHT SET BACK. e.e. THE DESIGNER OF RECORD (EDE) WILL CERTIFY THAT ALL NEW SYSTEMS HAVE BEEN INSTALLED IN ACCORDANCE WITH THE APPROVED CONSTRUCTION DOCUMENTS, PER 780 CMR 1301.0 2. BASIS OF DESIGN a. THE DESIGN CONDITIONS ARE BASED ON CLIMATE ZONE # 13A WITH EXTERIOR DESIGN TEMPERATURES OF 7 'F WINTER AND 87 'F DB AND 74 T WB SUMMER. b. THE INDOOR DESIGN CONDITIONS ARE BASED ON 72 T OF WINTER AND 78 T SUMMER. c. HEATING AND COOLING CALCULATIONS SHALL BE BASED ON ENVELOP ASSEMBLIES OF: • UPPER LEVEL WALLS WITH R-20 INSULATION AND A TOTAL U = 0.04. • WINDOWS WITH DOUBLE PANE GLASS AND U= 0.35. • ROOF WITH A TOTAL U = 0.03. d.000UPANCY AND VENTILATION IS BASED ON STANDARD POPULATIONS PER NUMBER OF BEDROOMS PER IMC-2015 AND ASHRAE 62.2 WITH INDIVIDUAL EXHAUSTS FOR KITCHENS AND BATH ROOMS. 3. SEQUENCE OF OPERATION a. EACH HP SYSTEM WILL HAVE ITS OWN PROGRAMMABLE THERMOSTAT WITH SEVEN (7) DAY, 24 HOUR PROGRAMMABLE SETTINGS WITH UN -OCCUPIED AND NIGHT -SET BACK CAPACITIES ENERGY SAVING CAPACITY. b. THE TOILETS WILL HAVE INDIVIDUAL EXHAUST FANS WITH A LOW, UNOCCUPIED RATE OF 50 CFM AND A HIGH, OCCUPIED RATE OF 100 CFM CYCLED BY A BUILT-IN MOTION SENSOR AND DUCTED TO A WALL CAP. e. KITCHEN HOOD EXHAUST SHALL BE CONTROLLED BY MANUAL SWITCH AND RUN TO A WALL CAP. f. RTU-1 WILL PROVIDE 200 CFM OF OUTSIDE TO EACH RESIDENTIAL CORRIDOR TO MEET IMC VENTILATION REQUIREMENTS. g. LAUNDRY DRYER EXHAUSTS SHALL BE RUN TO RISERS, EACH WITH A ROOF MOUNTED BOOSTER EXHAUST FAN CONTROLLED BY A STATIC PRESSURE SENSOR TO MAINTAIN A SLIGHT NEGATIVE PRESSURE. 4.0 SYSTEMS AND EQUIPMENT CAPACITIES. 4.1 LARGER 2 AND 3 BEDROOM UNITS RANGE FROM 1100 TO 1400 SqFt AND WILL HAVE 3.0 COOLING TO SYSTEM WITH A HEATING OUTPUT OF 38.0 MBH FOR RATES OF 35 TO 27 BTUH/SqFt AND COOLING RATES OF 366 TO 464 SqFt PER TON. 4.2 SMALLER 1 BEDROOM UNITS RANGE FROM 700 TO 1000 SqFt AND WILL HAVE A 2.5 TON COOLING SYSTEM WITH TOTAL HEATING OUTPUT OF 32 MBH FOR RATES OF 46 & 32 BTUH/SqFt HEATING AND COOLING COIL RATES OF 280 TO 400 SqFt PER TON. 5. TESTING AND BALANCING a. THE FOLLOWING TESTS AND INSPECTIONS SHALL BE PERFORMED BY THIS CONTRACTOR WITH THE OWNER AND THE OWNER'S REPRESENTATIVE PRESENT. THE TESTS AND INSPECTIONS MUST COMPLY WITH THE PROJECT DESIGN CRITERIA BEFORE ACCEPTANCE OF WORK. • INSPECT THAT ALL NEW UNITS ARE FUNCTIONING AND ARE IN GOOD CONDITION. • DEMONSTRATE THE OPERATION OF EACH T-STAT, FAN COIL UNIT AND OUTDOOR CONDENSING UNIT IN BOTH HEATING AND COOLING MODES. • PERFORM A TAB REPORT ON THE FCUs AND THE EXHAUST AIR SYSTEMS. • SUBMIT TAB REPORT FOR REVIEW BY/APPROVAL FROM THE ENGINEER OF RECORD. b. IF ADDITIONAL TESTS OR INSPECTIONS ARE REQUIRED BECAUSE THE INITIAL TEST AND/OR INSPECTION REVEALED UNACCEPTABLE CONDITIONS, THE CONTRACTOR SHALL RECTIFY ALL UNACCEPTABLE CONDITIONS WITHOUT ADDITIONAL COST TO THE OWNER. ADDITIONAL TESTS OR INSPECTIONS SHALL BE PERFORMED ONLY AFTER THE CONTRACTOR HAS COMPLETED THE CORRECTIVE WORK. 6. OPERATIONS MANUALS AND MAINTENANCE MANUALS a. WHEN THE PROJECT IS COMPLETE AND READY FOR OCCUPANCY, THIS CONTRACTOR SHALL PROVIDE SIX COMPLETE SETS OF OPERATING AND MAINTENANCE MANUALS BEFORE THE FINAL REVIEW AND TESTING. MANUALS SHALL COVER: • THE FCU, CONTROLS AND THERMOSTATS. • THE DX COOLING COILS AND OUTDOOR CONDENSERS • TOILET EXHAUST FANS. HVAC ACCESSORIES AND BALANCING DEVICES. 7. RECORD DRAWINGS AND CONTROL DOCUMENTS a. WHEN PROJECT IS COMPLETE AND READY FOR OCCUPANCY, THIS CONTRACTOR SHALL PROVIDE THE FOLLOWING ITEMS BEFORE FINAL REVIEW AND TESTING SHALL BEGIN. • TWO SETS OF AS -BUILT DRAWINGS FOR THE HVAC SYSTEMS AT 1/8" SCALE. • SIX COPIES OF FINAL TEST, ADJUST AND BALANCE (TAB) REPORT. H0.1 H0.2 H0.3 H0.4 H0.5 H1.OSB H1.0 H1.1 H1.2 H1.3 H1.4 H1.5 H1.6 H1.7 H2.1 H2.2 H2.3 H2.4 H2.5 H3.1 H3.2 LIST OF HVAC DRAWINGS HVAC HVAC HVAC HVAC HVAC HVAC HVAC HVAC HVAC HVAC HVAC HVAC HVAC HVAC HVAC HVAC HVAC HVAC HVAC HVAC HVAC LEGEND AND NOTES SCHEDULES RISER DIAGRAMS A RISER DIAGRAMS B PIPING SCHEMATIC SUB -BASEMENT FLOOR PLAN BASEMENT FLOOR PLAN FIRST FLOOR PLAN SECOND FLOOR PLAN THIRD FLOOR PLAN FOURTH FLOOR PLAN FIFTH FLOOR PLAN SIXTH FLOOR PLAN ROOF PLAN ENLARGED UNIT PLANS TYPE-A,B,C,D & B1,B1 & A2,B2 ENLARGED UNIT PLANS TYPE-A2,B2,C2 & B3,C1 ENLARGED UNIT PLANS TYPE-E,F,G & G1,G2 & H,K ENLARGED UNIT PLANS TYPE-L,P,T & J,U ENLARGED UNIT PLANS COMMON AREA & RETAIL SPACE DETAILS A DETAILS B THE E EDE, INC. MEP/FP ENGINEERS 1185 Washington St. Suite 4 West Newton, Ma. 02465 Tel. (617)-969-7700 Fax. (617)-969-7709 E-Mail. ede@edemep.com COPYRIGHT 2015-EDE Inc ©ALL RIGHTS RESERVED Project #: 4017 E 0) C6 2 0 0 C) cc 0 a) 1192 WI I��I N o C) Q LL c/D O d CC PROGRESS SET CO 0 CVL1J - o SCALE: PROJECT#: SALEM, MASSACHUSETTS 01970 MAR 22,2019 BUILDING PERMIT SET URBAN SPACES L.L.C. & DIAMOND & SINACORI L.L.C. Cyr) (7) C) DRAWING TITLE: REGISTRATION: DRAWING #: 246 Walnut Street CD CD QD CA U OD U) 03 2 coo Co • Co O 1-0 N T- Z co NTS V ) O z z z W w 1-1 z H3.1 00 ✓ CC) co N- CC) ©TISE DESIGN ASSOCIATES, INC 2019 ELECTRIC UNIT AND WALL HEATER SCHEDULE MARK CUH-1 CUH-2 CUH-3 CUH-4 CUH-5 CUH-6 CUH-7 CUH-8 CUH-9 CUH-10 EUH-1A EUH-1B EUH-1C EUH-2A EUH-2B EUH-3A EUH-3B EUH-4A EUH-4B SERVES BASEMENT ELEC ROOM BASEMENT ELEV LOBBY BASEMENT STAIR 1 1st FLOOR PACKAGE 1st FLOOR ELEV LOBBY 1st FLOOR WAITING 1st FLOOR LOBBY REAR 1st FLOOR STAIR 2 ROOF - MECH ROOM ROOF - STAIR 1 GARAGE-LOWER/BSMT GARAGE-LOWER/BSMT GARAGE-LOWER/BSMT GARAGE-lst MIDDLE GARAGE-lst MIDDLE GARAGE-lst UPPER GARAGE-lst UPPER RETAIL RETAIL CFM 100 100 175 175 175 100 175 175 175 100 2,000 2,000 2,000 2,000 2,000 2,000 2,000 1,100 1,100 BTU/HR CAP. 6820 6820 16380 16380 16380 6820 16380 16380 16380 6820 102,400 85,300 102,400 102,400 85,300 85,300 85,300 51,150 51,150 KW AMPS CB V-PH-HZ 2.0 8.3 208-1-60 2.0 8.3 208-1-60 4.0 19,2 208-1-60 4.0 19,2 208-1-60 4.0 19,2 208-1-60 2,0 8.3 208-1-60 4.0 19,2 208-1-60 4.0 19,2 208-1-60 4.0 19.2 208-1-60 2.0 8.3 208-1-60 30 83,5 110 208-3-60 25 69.5 90 208-3-60 30 83,5 110 208-3-60 30 83,5 110 208-3-60 25 69.5 90 208-3-60 25 69.5 90 208-3-60 25 69.5 90 208-3-60 15 41.7 60 208-3-60 15 41.7 60 208-3-60 NOTES: 1) HVAC CONTRACTOR SHALL PR❑VIDE AND ELECTRICAL CONTRACTOR SHALL WIRE. 2) PR❑VIDE WITH BUILT-IN THERMOSTAT. 3) PR❑VIDE SURFACE M❑UNTING KIT. 4) PR❑VIDE WITH WALL HANGING KIT. 5) PR❑VIDE WALL MOUNTED REMOTE T-STAT. 6) ON STAND-BY POWER DIMENSI❑NS (W x H x D) 9,25x12,13x3,63 9.25x12.13x3.63 14.19x19.94x4.0 14.19x19.94x4.0 14.19x19.94x4.0 9.25x12.13x3.63 19.19x19.19x4.0 14.19x19.94x4.0 14.19x19.94x4.0 9.25x12.13x3.63 29x34x10 29x34x10 29x34x10 29x34x10 29x34x10 29x34x10 29x34x10 21x28x6.5 21x28x6.5 GRILLES, DIFFUSERS & REGISTERS SCHEDULE TAG CD-1 CD-2 RR-1 RR-2 CR-1 ER-1 ❑PD REGISTER/DIFFUSER/GRILLE CEILING SUPPLY DIFFUSER CEILING SUPPLY DIFFUSER RETURN AIR REGISTER RETURN AIR REGISTER CEILING RA REGISTER EXHAUST AIR REGISTER OPEN ENDED DUCT CFM RANGE SEE PLANS SEE PLANS SEE PLANS SEE PLANS SEE PLANS SEE PLANS SEE PLANS DESIGN MAX S.P.-NC 0.09-20 0.09-20 0.09-20 0.09-20 0.09-20 0.09-20 0.09-20 NECK/ INLET SEE PLANS SEE PLANS SEE PLANS SEE PLANS SEE PLANS 6' ROUND SEE PLANS LAY -IN PANEL NO NO NO NO NO NO NO MANUFACTURER & MODEL TITUS TDC TITUS TDC TITUS 355-RL TITUS 355-RL TITUS 355-RL TROX VFL NONE MANU MARKEL MARKEL MARKEL MARKEL MARKEL MARKEL MARKEL MARKEL MARKEL MARKEL TRANE TRANE TRANE TRANE TRANE TRANE TRANE TRANE TRANE NOTES: 1) FOR BLOW PATTERNS, SEE FLOOR PLANS FOR ARROWS. 2) PR❑VIDE A NECK MOUNTED, VOLUME DAMPER FOR EACH REGISTER AND DIFFUSER AS WELL AS VD AT BRANCH TAKE -OFF. 3) PR❑VIDE BORDERS TO MATCH CEILING AND WALL TYPES. 4) DEVICE TO BE DUCT MOUNTED. 5) PR❑VIDE CEILING RADIATI❑N DAMPER. 6) ALTERNATE MANUFACTURERS TO INCLUDE NAIL❑R, CARNES OR PRICE. 7) PR❑VIDE WITH WIRE MESH OVER ❑PENING. MARK GEF-la GEF-2 GEF-3 GEF-lb EF-1 EF-2 TEF-1 REF-1 DEF-1/12 SF-2 SF-3A SF-3B SF-4A SF-4B SF-5A SF-5B SF-6A SF-6B EXHAUST & SUPPLY FAN SCHEDULE SERVING GARAGE - BSMT/LOWER GARAGE - 1st/UPPER GARAGE - 1st/MIDDLE GARAGE - BSMT/LOWER 1st TRASH RM SUB BSMT VENTILATI❑N BATHROOMS TRASH RISER DRYER EXHAUST RISER ❑A- ❑A- ❑A- ❑A- ❑A- ❑A- ❑A- ❑A- ❑A- 2nd 3rd 3rd 4th 4th 5th 5th 6th 6th FLR FLR FLR FLR FLR FLR FLR FLR FLR CONDOS CONDOS CONDOS CONDOS CONDOS CONDOS CONDOS CONDOS CONDOS CFM 7,000 3,700 4,500 600 1,000 700 30/110 S.P. (INCHES) 0.40 0.40 0.40 0.40 0.60 0.60 0.25 MODEL F3052TDWB F3052TDWB F3316TRP F3316TRP F3316TRP F3052TDWB F3386D-RP-T F3316TRP F3316TRP F3052TDWB UHEC-30-3A-ACA UHEC-25-3A-ACA UHEC-30-3A-ACA UHEC-30-3A-ACA UHEC-25-3A-ACA UHEC-25-3A-ACA UHEC-25-3A-ACA UHEC-15-3A-ACA UHEC-15-3A-ACA NOTES 1+2+3+5+6 1+2+3+6 2+3+6 2+3+6 2+3+5+6 3 7 R.P.M. DRIVE WATTS AMPS V-Ph-Hz MODEL MANUFACTURER 1703 1635 1557 1844 DIR DIR DIR DIR 2744 DIR 2744 DIR 1050 DIR 625 0.50 1670 DIR 500 0.65 1621 DIR 685 350 350 350 350 350 350 350 350 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 2814 2624 2624 2624 2624 2624 2624 2624 2624 DIR DIR DIR DIR DIR DIR DIR DIR DIR 2116 1450 1436 164 484 484 9.8 4.0 4.5 11.8 2.1 4.86 4.86 0.10 230-3-60 230-3-60 120-1-60 120-1-60 120-1-60 120-1-60 120-1-60 FSD-26 FKD-18-3 FSD-22 PRI❑AIR-10-EC FKD-12 FKD-12 FV05-11VK1 FANTECH FANTECH FANTECH FANTECH FANTECH FANTECH PANAS❑NIC 185 - 120-1-60 G-098-VG-B GREENHECK 125 - 120-1-60 G-095-VG GREENHECK 300 155 155 155 155 155 155 155 155 2.54 1.23 1.23 1.23 1.23 1.23 1.23 1.23 1.23 120-1-60 120-1-60 120-1-60 120-1-60 120-1-60 120-1-60 120-1-60 120-1-60 120-1-60 FG-12XL FG-10 FG-10 FG-10 FG-10 FG-10 FG-10 FG-10 FG-10 FANTECH FANTECH FANTECH FANTECH FANTECH FANTECH FANTECH FANTECH FANTECH NOTES: 1) POWER AS NOTED 2) PR❑VIDE EACH WITH WC-15 SPEED CONTROL FOR BALANCING. 3) PR❑VIDE WITH M❑UNTING CLAMPS 4) PR❑VIDE WITH RSK-12 BACK DRAFT DAMPER. 5) EF-1 TO ALSO SERVE AS MINIMUM MIDDLE AND UPPER GARAGE EXHAUST. 6) FAN TO RUN C❑NTINU❑USLY. 7) FAN CONTROLLED BY GARAGE CO SYSTEM. 8) PR❑VIDE WITH M❑TI❑N SENSOR ❑PTI❑N. 9) PR❑VIDE WITH STATIC PRESSURE SENSOR TO VARY FAN TO MAINTAIN NEGATIVE STATIC IN RISER. ELECTRIC BASEBOARD SCHEDULE MARK EBB-24 L❑CATI❑N EXT BATHS TOTAL TOTAL BTU/HR WATTS/FT. LENGTH VOLTS PHASE HZ 1706 500 28' 120 MANUFACTURER & MODEL NO. REMARKS 1 60 QMARK - HBB500 1+2+3 NOTES: 1) HVAC TO PR❑VIDE AND ELECTRICAL TO WIRE. 2) PR❑VIDE WITH ❑PTI❑NAL HBB-11 T-STAT. 3) PR❑VIDE WITH JUNCTI❑N BOX FOR FIELD INSTALLATI❑N OF T-STAT. WALL CAP SCHEDULE MARK WC-A2 WC-A4 WC-A6 WC-B4 WC-B6 MODEL (XVENT) DHEB-DL-S 4SEB-S 6SEB-S 4SEB-BR 6SEB-BR C❑NNECTI❑NS 1@ 4" + 1@ 6' 1 @ 4' 1 @ 6' 1 @ 4' 1 @ 6' WALL ❑PENING (H x W) 8.0 x 12.0 7.125 x 8.125 7.125 x 8.125 7.125 x 8.125 7.125 x 8.125 EXT FACE (H x W) 8.75 x 12.937 10.875 x 11.75 10.875 x 11.75 REMARKS 1+2 1+2 1+2 10.875 x 11.75 1+2 10.875 x 11.75 1+2 NOTES; 1) HVAC TO PR❑VIDE WITH COLOR SET BY ARCHITECT. 2) GC TO INSTALL PER ARCH ELEVATI❑NS, REMARKS 1+2+3 1+2+3 1+2+3 1+2+3 1+2+3 1+2+3 1+2+5 1+2+3 1+2+3 1+2+3 1+2+4 1+2+4+6 1+2+4 1+2+4 1+2+4+6 1+2+4 1+2+4+6 1+2+4 1+2+4 Lbs NOTES 122 127 98 9.4 1+2+3+4+7 1+2+3+4+7 1+2+3+4+7 1+2+3+4+6 20 1+2+3+4+5+6 20 1+2+3+4+6 12 1+8 60 1+6 47 1+6+9 13.7 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 1+2+3+4 1+2+3+4 1+2+3+4 1+2+3+4 1+2+3+4 1+2+3+4 1+2+3+4 1+2+3+4 1+2+3+4 TAG RTU-1 PACKAGED ROOFTOP UNIT SERVICE/L❑CATI❑N C❑RRID❑RS/R❑❑F MFG'R MODEL CARRIER 48LCD012 12.0 4400 1100 1.00 120 101 NOTES: 1) PR❑VIDE WITH ROOF CURB. 2) PR❑VIDE WITH PROGRAMMABLE THERMOSTAT. 3) PR❑VIDE WITH DOWN H❑RIZ❑NTAL DUCTING & EC❑N❑MIZER W/ BAR❑METRIC RELIEF. 4) PR❑VIDE WITH MEDIUM STATIC, BELT DRIVEN FAN WITH VFD C❑NTR❑LLER, 5) PR❑VIDE WITH C❑NVENIENCE OUTLET AND NON -FUSED DISC❑NNECT. 6) PR❑VIDE WITH 5 YEAR REPLACEMENT COMPRESSOR WARRANTY. 7) PR❑VIDE 10 YEAR ALUMINIZED HEAT EXCHANGER WARRANTY. NOM. AIR CAPACITY DX C❑❑LING CAPACITY TONS CFM MIN O.A. E.S.P. TOTAL SENS. EAT EAT LAT LAT SEER CFM ("W,G,) MBH MBH DB (°F) WB (°F) DB (°F) WB (°F) 79 I 65 57.6 I HEAT PUMP SCHEDULE - OUTDOOR UNITS (AIR COOLED) MARK HP-x36 HP-x30 HP-xl HP-x2 HP-x3 TONS (NOM) 3.0 MODEL (MITSUBISHI) PUZ-HA36-NHAS ROOF 2.5 PUZ-HA30-NHA5 ROOF 2.0 PUZ-A24NHA7 4.0 PUMY-P48NKMU-1 4.0 PUMY-P48NKMU-1 ROOF ROOF ROOF L❑CATI❑N SERVICE L❑ADING (%) C❑❑LING MBH WATTS CONDOS 14-100 36 2,980 CONDOS 14-100 30 3,850 ELEV MACH RM FITNESS/C❑MM RM 1st Fir L❑BBIES 14-100 14-100 14-100 24 48 48 1,960 2.27 2.27 GAS HEATING CAP. MBH MBH NO. INPUT OUTPUT STAGES EFF 56.1 13.0 144/180 118/146 I 2 HEATING SEER MAX/MIN (MBH) 16.8 38.0/18.0 16.8 32.0/12.0 21.4 21.4 21.4 28.0/- 54.0 54.0/ WATTS 6,100 2,750 2,600 2.33 2.33 HSPF 10.4 9.4 11.0 11.0 11.0 COMPRESSORS NO. @ RLA/LRA 1 @ 18/27.5 1 @ 18/27.5 1 @ 7/11 1 @ -/- 1 @ -/- SUPPLY SUPPLY ELECTRICAL ❑PERATING FAN FAN MOTOR WEIGHT V/0 MCA M❑CP RPM HP (LB'S) 81% 759 3.0 COND FANS NO @ WATT - FLA 2 @ 86 - 0.40 1 @ 0.08 - 0.75 2 @ 0.08 - 0.4 2 @ 74 - 0.4 2 @ 74 - 0.4 208/3 59.0 70 ELEC (AMPS) MCA CB M❑CP 28 30 40 25 30 40 19 25 26 31 40 44 269 31 40 44 269 NOTES: 1) ELECRICAL BASED ON 208/230-1-60. 2) PR❑VIDE WITH SIX (6) YEAR COMPRESSOR WARRANTIES. 3) PR❑VIDE WITH VFD CONTROLLED OUTDOOR FAN MOTOR. 4) PR❑VIDE WITH INVERTER DRIVEN, VARIABLE SPEED, SCROLL COMPRESSOR. 5) C❑❑LING CAPACITY BASED ON 95 °F OA AND 80/67 °F RA. 6) HEATING HIGH CAPACITY BASED ON 47 °F ❑A AND 70 °F RA AND LOW BASED ON 6 °F, 7) C❑❑LING RANGE TO BE 23°F-122°F DB AND HEATING RANGE TO BE-4°F-60°F DB. 8) PR❑VIDE SUPPORT FOR THE UNIT BY AIRTEC PRODUCTS CORP.'S 'BIG FOOT SYSTEMS' OR EQUAL. UNIT NO. HEAT PUMP UNIT SCHEDULE - INDOOR UNITS SERVES FCU-36 CONDOS FCU-30 CONDOS AHU-36 CONDOS AHU-30 CONDOS HP-1,1 HP-2.1 HP-3.1 HP-3.2 ELEV MACH RM FITNESS/C❑MM RM ELEV LOBBY MAIN LOBBY STYLE CFM L❑/HI TOTAL MBH C❑❑LING SENS INPUT MBH WATTS H❑RIZ❑NTAL 847/1201 36.0 27.9 H❑RIZ❑NTAL 618/883 30.0 23.3 VERTICAL VERTICAL WALL VERTICAL VERTICAL VERTICAL HEATING TOTAL INPUT MBH WATTS 38.0 6,100 32.0 5420 788/1125 36.0 27.9 - 38.0 6,100 613/875 30.0 23.3 - 32.0 5320 635/775 980/1400 515/735 515/735 24.0 48.0 24.0 24.0 19.6 33.5 16.9 16.9 FAN MOTOR ELEC SOUND (dBA) ESP WATTS FLA MCA MOCP HI/L❑ NOTES 2000 1+2+3+4+5+6+7 WEIGHT SOUND REMARKS (LBS) (dB) 265 52/53 1+2+3+4+5+6+7+8 165 52/53 1+2+3+4+5+6+7+8 153 47/48 1+2+3+4+5+6+7+8 47/48 1+2+3+4+5+6+7+8 47/48 1+2+3+4+5+6+7+8 WEIGHT MODEL NO. (LBs) (MITSUBISHI) 0.60 - - N/A N/A 42/33 86 0.60 - - N/A N/A 39/30 73 0.80 - - 5.50 15 38/30 172 0.80 - - 5.50 15 38/30 141 26.0 - N/A - - N/A N/A 45/39 46 54.0 - 0.80 - - 5.63 15 43/35 172 27.0 - 0.80 - - 5.50 15 45/39 113 27.0 - 0.80 - - 5.50 15 45/39 113 NOTES: 1) ELECTRIC BASED ON 230/208-1-60. 2) C❑❑LING BASED ON 95 °F OA AND 80/67 °F DB/WB RA ANII HEATING BASED ON 47 °F OA AND 70 °F RA. 3) PR❑VIDE REFRIGERANT PIPING DIAGRAM BY MANU WITH SUBMITTAL AND PIPE IN FIELD TO DIAGRAM. 4) PR❑VIDE FILTER ON RETURN REGISTER (RR-x). 5) POWERED BY OUTDOOR UNIT. co Nx 4 16x12 41 8"0 10'0 0 , ►'�' __� (5) LI ® 0 ® 0 S. U 1, SHEETROCK AT BOTTOM OF TJI AS PART OF RATED ASSEMBLY TO RUN C❑NTINU❑USLY OVER HP UNIT AND BE MAIN CEILING AT ABOUT 9'-0" AFF, 2, C❑RRID❑R CEILING AT ABOUT 8'-0" AFF, 3. UN -RATED S❑FFIT TO HIDE HP UNIT AT ABOUT 7'-6' AFF WITH INTERNAL CLEAR OF 72"x84"x15" DEEP , 4. RETURN AIR AT 36x10 WITH GRILLE WITH FILTER. 5, HEAT PUMP (HP) IND❑❑R UNIT AT 3.0 TON WITH CABINET OF 8-9/16' HIGH BY 27-9/16' LONG BY 55-1/8' WIDE. 6. BOTTOM SERVICE/DR❑P-❑UT PANEL AT 30x60, 7. SIDE SERVICE PANEL FOR ELEC BOX AND PIPING C❑NNECTI❑NS AT 18x18, 8, FIRE DAMPER IN SUPPLY DISCHARGE DUCT AT 52x8 TO BE SUPPORTED FROM STRUCTURE INDEPENDENTLY FROM HP UNIT. 9. 18x8 ACCESS PANEL TO SERVICE FIRE DAMPER. 10. RUN CONDENSATE DRAIN TO NEAREST INDIRECT DRAIN. INDOOR FAN COIL UNIT (FCU) DETAIL NOTES PEAD-A36-AA7 1+2+3+4+5 PEAD-A30-AA7 1+2+3+4+5 PVA-A36-AA7 1+2+3+4 PVA-A30-AA7 1+2+3+4 PKA-A24KA7 PVFY-P48NAMU-E1 PVFY-P24NAMU-E1 PVFY-P24NAMU-E1 NTS 1+2+3+5 1+2+3+4 1+2+3+4 1+2+3+4 E EDE, INC. MEP/FP ENGINEERS 1185 Washington St. Suite 4 West Newton, Ma. 02465 Tel. (617)-969-7700 Fax. (617)-969-7709 E-Mail. ede@edemep.com COPYRIGHT 2015-EDE Inc ©ALL RIGHTS RESERVED Project #: 4017 246 Walnut Street O d CC PROGRESS SET CO 0 w ~Q SCALE: PROJECT#: SALEM, MASSACHUSETTS 01970 MAR 22,2019 BUILDING PERMIT SET URBAN SPACES L.L.C. & DIAMOND & SINACORI L.L.C. DRAWING TITLE: REGISTRATION: DRAWING #: tB 4- O CO 71- co co CN U) -C U CO U) 03 O 6 O • 0 • Z CO NTS SCHEDULES 0 ©TISE DESIGN ASSOCIATES, INC 2019 22' TURN -UP (TYPICAL) L_ O x O L_ L_ L_ O x 0 L JANITOR EXHAUST TRASH EXHAUST 4" O i 4. TEF-1 4" O i 4. TEF-1 4" O i 4. TEF-1 = 625 ROOF I I ROOF 12x12 r CVR 6 "0 ER-1 8x8 125 6TH FLOOR 6TH FLOOR 6"0 I ER-1 - CVR 8x8 N I 125 x O 5TH FLOOR L O x 0 CVR 6 "0 ER-1 8x8 125 DER 1-6, 8-1 1 x I L DRYER 4 DRYER DER 7 ROOF DER 12,13 4 DRYER ROOF 6TH FLOOR 6TH FLOOR 5TH FLOOR 5TH FLOOR 4TH FLOOR 4TH FLOOR L 00 x 0 CVR 6 "0 ER-1 —� 8x8 125 3RD FLOOR 3RD FLOOR 8" 0 r r 1 I I I TEF-1 TEF-1 TEF-1 L CVR 6 "0 ER-1 8x8 125 2ND FLOOR 2ND FLOOR FIRST FLOOR BASEMENT/PARKING JANITOR EXHAUST RISER DIAGRAM NTS 22' TURN -UP (TYPICAL) I L N N x Co x x N I I I I L i L i 800 f ) 16x 10 SFD i * SFD 12x 10� -----4- 600 cis _1_ _1_ O 0_ DRYER 800 4400 SA I < 16x10 ) N x 0 N SFD._ 0 N x N 0 N x N 0 N x 0 N 1100 OA 13300 RA ROOF #FD 12x10S 600 800 f • 16x10 SFD r_ FD 12x 10-S 600 0 N x 0 N SIXTH FLOOR 5TH FLOOR FIFTH FLOOR 0 CC DRYER DRYER co 4TH FLOOR 4TH FLOOR N N x N N I I I _1_ 4 DRYER 0_ x N L 4 DRYER :1 CO 22' TURN -UP (TYPICAL) �C 3RD FLOOR i 3RD FLOOR _1_ 4. DRYER 2ND FLOOR 2ND FLOOR FIRST FLOOR RETAIL SPACE 800 f < 16x10 SFD# 800 300 < 16x10 SFD ) < 12x6 ) SF DI* CO C0 x CO 0 RETAIL SPACE FIRST FLOOR N x 0 N 1SFD 12x 10_s 600 SFD 12x 10- ± 600 0 x co SFD L --"± 300 FOURTH FLOOR THIRD FLOOR SECOND FLOOR 100 SFD BASEMENT/PARKING BASEMENT/PARKING BASEMENT/PARKING BASEMENT/PARKING TRASH EXHAUST RISER DIAGRAM NOTES: ALL TURN UPS ARE 22" NTS DRYER EXHAUST RISER DIAGRAM NTS CORRIDOR SA/RA RISER DIAGRAM NTS E EDE, INC. MEP/FP ENGINEERS 1185 Washington St. Suite 4 West Newton, Ma. 02465 Tel. (617)-969-7700 Fax. (617)-969-7709 E-Mail. ede@edemep.com COPYRIGHT 2015-EDE Inc ©ALL RIGHTS RESERVED Project #: 4017 PROGRESS SET CO 0 w N } Q o � SCALE: PROJECT#: SALEM, MASSACHUSETTS 01970 MAR 22,2019 BUILDING PERMIT SET URBAN SPACES L.L.C. & DIAMOND & SINACORI L.L.C. C) C) DRAWING TITLE: REGISTRATION: DRAWING #: 246 Walnut Street 4- O � CO CO 71- CO O U) co a) v) ti O - CO U) tt3 � 2 • CO C 00 • Z (o NTS DIAGRAMS ©TISE DESIGN ASSOCIATES, INC 2019 12'0 GOOSENECK WITH BOTTOM AT 7-36' ABOVE ROOF FOR ❑A INTAKE. ROOF ROOF L' 0 L' 0 8' r 8' r g C7 Y� g C7 Y� CVR C7 Y� g C7 Y� 1 1 1 1 60 50 50 55 603 B2-3/2 602 C2-2/2 601 D1-2/2 604 A2-2/2 10'0 CVR 55 605 A2-2/2 CVR 85 606 T-3/2 10'0 12'0 z CVR 40 612 E1-1/1 10'0 K ) SF SF 6A 66 10'0 8'0 8'0 6'0 CVR � CVR 1 1 1 55 40 80 608 S-3/2 E2-1/1 R-3/2 607 611 610 F1-2/2 609 G2-1/1 SIXTH FLOOR SIXTH FLOOR 24x12 LOUVER BY GC. HVAC TO PR❑VIDE FULL SIZE INSULATED 6 PLENUM 12' DEEP. 6'0 6'0 8'0 8'0 10'0 CVR 121 CVR 121 121 60 50 50 55 55 503 B-3/2 502 C-2/2 501 D1-2/2 504 A-2/2 505 A-2/2 16x10 CVR 80 506 L-2/2 10'0 SF 5B 10'0 10'0 121 40 513 E1-1/1 10'0 8'0 CVR CVR CVR 1 1 1 50 507 K-2/2 50 508 K-2/2 40 512 E-1/1 8'0 6'0 6'0 CVR 60 509 H-2/2 65 511 F-2/2 45 510 G-1/1 FIFTH FLOOR FIFTH FLOOR FOURTH FLOOR 60 403 B3-3/2 24x12 LOUVER BY GC. HVAC TO PR❑VIDE FULL SIZE INSULATED G PLENUM 12' DEEP. 6'0 6'0 8'0 8'0 10'0 CVR CVR CVR 1 1 1 1 50 50 55 401 404 C1-2/2 D-2/2 A-2/2 402 55 405 A-2/2 24x12 LOUVER BY GC. HVAC TO PR❑VIDE FULL SIZE INSULATED 6 PLENUM 12' DEEP. 6'0 6'0 8'0 8'0 g 1/ CVR g 1 1 1 1 60 50 50 55 303 B-3/2 302 C-2/2 301 D2-2/2 304 A-2/2 10'0 CVR 55 305 A-2/2 16x10 80 406 L-2/2 CVR 80 306 L-2/2 10'0 16x1n 10'0 SF \ SF 4A/ 4B SF 3B 10'0 10'0 40 413 E-1/1 10'0 11 CVR 50 409 10'0 121 40 313 E1-1/1 K-2/2 10'0 8'o 12/ 40 45 408 D-2/1 412 E-1/1 10'0 8'0 CVR CVR CVR 1 1 1 50 207 K-2/2 40 312 E1-1/1 50 308 K-2/2 8'0 CVR 60 409 U-2/2 6'0 6'0 11 CVR CVR 1 1 65 411 F-2/2 8'0 E'0 E'0 CVR 60 309 H-2/2 65 311 F-2/2 45 410 G-1/1 45 310 G-1/1 FOURTH FLOOR THIRD FLOOR THIRD FLOOR 24x12 LOUVER BY GC. HVAC TO c PR❑VIDE FULL SIZE INSULATED PLENUM 12' DEEP. 6x8 10x8 10x8 CVR � � CVR CVR 60 203 B1-3/2 SECOND FLOOR 50 202 C1-2/2 50 201 D1-2/2 55 204 Al-2/2 55 205 Al-2/2 80 206 P-3/2 50 212 COMM 14x10 10x10 10x8 CVR CVR 100 211 FITNESS 208 M-2/2 65 210 F-2/2 CONSTANT VOLUME REGULATOR EQUAL TO A TROX MODEL VFC, LOCATE IN C❑RRID❑R AND C❑❑RDINATE WITH GC ON CEILING ACCESS PANEL (TYPICAL) 45 209 G1-1/1 SECOND FLOOR APARTMENT FRESH AIR RISER DIAGRAM NTS E EDE, INC. MEP/FP ENGINEERS 1185 Washington St. Suite 4 West Newton, Ma. 02465 Tel. (617)-969-7700 Fax. (617)-969-7709 E-Mail. ede@edemep.com COPYRIGHT 2015-EDE Inc ALL RIGHTS RESERVED (,--;-,-Project #: 4017 a) E 0) co 2 I. U a) 0 0) 0 (7 1192 WI I��I N o U Q O 0_ CC PROGRESS SET CO 0 N W } Q o SCALE: PROJECT#: SALEM, MASSACHUSETTS 01970 MAR 22,2019 BUILDING PERMIT SET URBAN SPACES L.L.C. & DIAMOND & SINACORI L.L.C. C) C) DRAWING TITLE: REGISTRATION: DRAWING #: is FL 246 Walnut Street 03 4- O CO COO O T- 00 v) U - CO U) 03 T- O CO a) (1) • 0 • T- Z co NTS 1221 DIAGRAMS 0 z ©TISE DESIGN ASSOCIATES, INC 2019 Tpical 2.5 ton 1 N with AHU 208-230V/60H FUSE /// P U Z - HA30-NHAS L1L2 TB7 HPDIP SWITCH 7-3 OFF 3C TB3 G (s) j> I N 208-230V FusE P1 1 L1 L2 G AHU-30 TB5 TB15 Gpl PVA- A30-AA7 22.16-2 AWG CR PIPING AND CEJNTREJL� SYMBOL BRANCH PIPE MODEL NAME Jl CMY-Y62-G-E SYMBOL LIQUID PIPE/GAS PIPE SIZE PI 3/8 / 5/8 SYMBOL MODEL NUMBER CR PAC-YT53CRAU-J \DON Typical 3,0 ton 1 N with AHU 208-230V/60H FUSE /// P U Z - HA36-NHAS L1L2 TB7 u\ HPDIP SWITCH 7-3 OFF 36 TB3 G (S)°I N 208-230V FusE P1 L L2 G AHU-36 TB5TB15 Gpl PVA- A36-AA7 22,.16-2 AWG CR I IN DIAGRAM SYMBOL LEGEND DISPLAY DESCRIPTION iii POWER WIRE CONTROL WIRE — — REF. PIPE ONE''', 'OVJE� Comm Room 1 Fitness 208-230V/60H FUSE P U M Y - P48NKMU1 L1L2 TB7 HPDIP SWITCH 7-3 OFF x2 TB3 G (S)°I N 208-230V FUSE P1 1 L L2 G AHU-2,1 TB5 B15 Gpl PVFY- P48NAMU-E1 22.16-2 AWG CR SyST SC Lobby [MAT 1 208-230V/60H FUSE /// P U M Y - P48NKMU1 N 208-230V FusE IP1 N 98-230V FUSE L1 L2 G AHU-3.1 TB5TB15 Gp2 PVFY- P24NAMU-E1 _1 _2 H TB7 DIP SWITCH 7-3 OFF x3 TB3 G (S) I \ 16-2 AWG(S) 22,.16-2 AWG CR P1 L1 L2- G AHU-3.2 TB5 TB15 Gp3 PVFY- P24NAMU-E1 22.16-2 AWG CR DINS Additional refrigerant charge is needed Please refer the amount of pre -charge the data book. 1.25mmt16 AWG) : 1.25mm16 AWG) or more. depending on the size and length of and the formula of calculation which 0.75mm(20 AWG) : between 0.5mm(24 AWG) 208-230V/60H FUSE extended piping. is mentioned on and 0.75mm(20 AWG) ,GOR Elev Mech Room PUZ- A24-NHA7 HP xl E P1 1 T 4 G- HP-1,1 T35 Gp4 PKA— A24KA7.TH 22.16-2 AWG CR T J C')IIi11LR FROM 0 Typical 2,5 ton 1 N with FCU 208-230V/60H FUSE /// PUZ- HA30-NHAS HP 3C P1 TE4 1 G - FCU-30 T35 Gp4 PEAD— A30—AA7 22.16-2 AWG CR ,\ Typical 3,0 ton 1 N with FCU 208-230V/60H FUSE /// PUZ- HA36-NHAS HP 36 E P1 T>}4 - G - FCU-36 T35 Gp4 PEAD— A36—AA7 22.16-2 AWG CR EDE, INC. MEP/FP ENGINEERS 1185 Washington St. Suite 4 West Newton, Ma. 02465 Tel. (617)-969-7700 Fax. (617)-969-7709 E-Mail. ede@edemep.com COPYRIGHT 2015-EDE Inc ©ALL RIGHTS RESERVED Project #: 4017 U- w 0 CC 0_ W Q ArchitectureSite Planning Project Management PROGRESS SET CO N SCALE: PROJECT#: SALEM, MASSACHUSETTS 01970 MAR 22,2019 BUILDING PERMIT SET URBAN SPACES L.L.C. & DIAMOND & SINACORI L.L.C. DRAWING TITLE: REGISTRATION: DRAWING #: 246 Walnut Street 4— Co L ti CO tD co ti NTS ©TISE DESIGN ASSOCIATES, INC 2019 II I I I II BAB SCA 12"0 EXHAUST DUCT UP FROM SUB BASEMENT AND TO 1st F_❑❑R AB❑VE, GC TO PR❑VIDE S❑FFIT TO ALLOW DUCT TO PASS THROUGH ELECTRICAL ROOM 99 STA R 1 ELECTRICAL R(DO v 302 op C U H\ 1/ TR-1 24x1 q 750 I GC TO PR❑VIDE RATED ENCLOSURE FOR 12"0 EXH AND TRANSFER AIR DUCTS FOR DROP TO SUB BASEMENT BELOW ER-1 48x12 2400 20"0 EUH 1B PR❑VIDE A CO M❑NIT❑RING/C❑NTR❑L SYSTEM FOR THE LOWER/BASEMENT PARKING GARAGE. STANDARD OF ACCEPTANCE SHALL BE INTEC, GRAYSTONE, VULCAIN, OR APPROVED EQUAL. 1, SENSORS SHALL BE OF THE ELECTR❑CHEMICAL TYPE. 2. LOCATE SENSING P❑INTS ON WALLS AND COLUMNS AT 5.5 FOOT ABOVE FLOOR LEVEL LOCATE ONE SENSING P❑INT PER 7500 FT2 (SENSOR RANGE OF COVERAGE SHALL BE C❑NSIDERED AS APPR❑XIMATELY 50 FOOT RADIUS). DO NOT LOCATE SENSING P❑INTS CLOSER THAN 6 FOOT TO TRAFFIC LANES. 3. SENSOR RANGE SHALL BE OF 0 TO 300 PPM FOR 7% ACCURACY CELL OR 500 PPM FOR 3% ACCURATE CELL. 4. THE PROPOSED SENSOR L❑CATI❑NS SHALL BE SUBMITTED AT THE SHOP DRAWING STAGE AND SHALL BE AMENDED AS DIRECTED BY THE OWNER AND/OR ENGINEER. 5. SENSORS SHALL BE FACTORY CALIBRATED AND WILL ONLY REQUIRE CALIBRATI❑N AFTER A MINIMUM ONE (1) YEAR SERVICE. 6, SEQUENCES FOR THE BASEMENT GARAGE CO SYSTEMS SHALL BE AS NOTED AND AS FOLLOWS: 21 6,1, AT A RISE TO 25 PPM, INTAKE AND EXHAUST ACDs SHALL OPEN AND MAIN GEF SHALL ENERGIZE. 6.2, AT A RISE TO 50 PPM, THE CO SYSTEM SHALL ACTIVATE WARNING STROBES AND HORNS FOR IMMEDIATE EVACUATI❑N, 6.3, AS PPMs DROP 5 OR MORE BELOW ACTIVATI❑N LEVELS, SEQUENCES SHALL REVERSE. EUH WITH BUILT—IN T—STAT SET AT 55 T (ADJUSTABLE). TYPICAL FOR ALL EUHs. 30'93 UP KGEF 1b GEF a ACD`r— 1\ ER-1F 48x12 2400 ER-1 48x12 2400 A( C F-1 b SHALL RUN WHENEVER THE CO SYSTEM IS INACTIVE AND DISCHARGE ACD SHALL BE OPEN AND GEF-1a SHALL BE OFF D ACD CLOSED. UPON ACTIVATION OF CO SYSTEM, GEF-1 b ACD SHALL FAIL CLOSED AND GEF-1 B SHALL BE DEACTIVATED BY END SWITCH AS ACD STARTS TO CLOSE. ACD FOR GEF-1a SHALL FAIL OPEN AND HAVE AN END SWITCH THAT WILL ENERGIZE GEF-1 a ONCE ACD FULLY OPENED. (4)E EDE, INC. MEP/FP ENGINEERS 1185 Washington St. Suite 4 West Newton, Ma. 02465 Tel. (617)-969-7700 Fax. (617)-969-7709 E-Mail. ede@edemep.com COPYRIGHT 2015-EDE Inc ©ALL RIGHTS RESERVED Project #: 4017 If U- Cl) 0_ OC c ArchitectureSite Planning Project Management PROGRESS SET CO N J u CD F MAR 22,2019 BUILDING PERMIT SET 246 Walnut Street 617 . 581 . 6611 fax 617 . 581 . 6601 SCALE: 1"=8,-0, PROJECT#: SALEM, MASSACHUSETTS 01970 URBAN SPACES L.L.C. & DIAMOND & SINACORI L.L.C. DRAWING TITLE: REGISTRATION: DRAWING #: 0 0 BASEMENT 0 ©TISE DESIGN ASSOCIATES, INC 2019 II II II II II I I I I I I I I I I S,8 SCAL - .1 / BAS V 8,, 12'0 T RA_NSFER--DUCT DOWN FROM BASEMENT ABOVE 12"9. Ex A TO B TR-1 -I— 24x 1 750 FD R_ 1 L t DUCT UP UP GC TE PRI]VIDE NEW RATED CHASE F R TRANSFER AND EXHAUST DUI; S AND HVAC TO PR❑VIDE FDs IN NEW DUCTWORK \T HLOOR PLA\ 1 9 0 99 [I __ I(-2 ----T 1 x12F=== -H $00 `, LJ = = 12" 0 [I} ER-1 12r(1Q 150 T ER-1 12x10 300 '<F__ ER-1 �1— 12x10 300 rr Tn PFMn\ VENTILATI❑N (E Al I DBMS TO PR❑VIDE THROUGH ]LIT SUB BSMT EDE, INC. MEP/FP ENGINEERS 1185 Washington St. Suite 4 West Newton, Ma. 02465 Tel. (617)-969-7700 Fax. (617)-969-7709 E-Mail. ede@edemep.com COPYRIGHT 2015-EDE Inc ©ALL RIGHTS RESERVED Project #: 4017 0— OC W ArchitectureSite Planning Project Management PROGRESS SET CO N u U H MAR 22,2019 BUILDING PERMIT SET 246 Walnut Street O CO O cn U) - cn U) 2 Q) 0 a) z 617 . 581 . 6601 SCALE: 1'-8/-0• PROJECT#: SALEM, MASSACHUSETTS 01970 URBAN SPACES L.L.C. & DIAMOND & SINACORI L.L.C. DRAWING TITLE: REGISTRATION: DRAWING #: z 0 0 SUB -BASEMENT ©TISE DESIGN ASSOCIATES, INC 2019 I (ID 72x2 OA LOUVER (BY GC). PROVIDE A PAIR OF INSULATED SHEET METAL PLENUMS AS NOTED AND EACH 12" DEEP AND CONNECT DUCTS FROM EXHAUST FANS. EF-1 FOR TRASH ROOM TO RUN CONSTANTLY AND WILL PROVIDE MINIMUM CONSTANT EXHAUST FOR MIDDLE AND UPPER GARAGE SYSTEMS. GEF-3 TO RUN WHEN ENERGIZED BY CO SYSTEM. PROVIDE NORMALLY OPENED ACD FOR GEF-3 WHICH WILL BE POWERED CLOSED WHEN CO SYSTEM IS INACTIVE. o-- I OAL-3B 54x24 18x24 S A TRAS ROOM 104 ACD 7 F1r28"0 ER-1 14x14 1000 /8" ER-1 48x24 4500 FD FD 99 ° EUH \n 2B 22 R D OAL-3A 66x24 OPD-1 42x18 ELEV. 106 LOBBY (AHU 3,2, CEUH\ 3B 66x24 OA LOUVER (BY GC) WITH FULL SIZE SHEET METAL PLENUM 12" DEEP TO 42x18 OPEN DUCT WITH ACD INTERLOCKED WITH MIDDLE GARAGE CO SYSTEM. ER-1 36x12 1850 P 42x24 OA LOUVER (BY GC) WITH FULL SIZE SHEET METAL PLENUM 12" DEEP TO BE OPEN 24/7 FOR THE MINIMUM CONTINUOUS VENTILATION REQUIRED BY CODE 20" {b L ROO LOBBY 102 1 P FD 'I CUH —6 S AHU 3.1 R ETA 107 78x60 OA INTAKE LOUVEROU�(BY Go WITH A FULL SIZE, NSULATED UPPER—S C110N\ k2 II�RREEP. DIVIDE PLENUM ORUPPER GARAGE INTO ANAND LOWER PLENUM AT 78x36 FOR LOWER GARAGE. PROVIDE A 12" LONG DUCT AT 3 x18 FOR UPPER PLENUM WITH ACD INTERLOCKED WITH UPPER GARAGE CO SYSTEM TO OPEN WHENEVER THAT SYSTEM IS ACTIVATED. PROVIDE A 12" LONG DUCT AT 36x24 FOR LOWER PLENUM WITH ACD INTERLOCKED WITH LOWER GARAGE CO SYSTEM TO OPEN WHENEVER THAT SYSTEM IS ACTIVATED. i 32 CHURCH ST. / l /v /UH 4B L FD I I I rt I - r 1-1- 11 1 1 1 1 1 1 1 1 1 I I 1A 1 1 1 CEUH 4A N ACD N ER-1 36x12 1850or _ 20"0 UP (CUH) —8 FD FJ I N(.D 'O CARBON MONOXIDE VENTILATION SYSTEM PR❑VIDE CO M❑NIT❑RING/C❑NTR❑L SYSTEMS FOR THE MIDDLE AND UPPER PARKING GARAGES. STANDARD OF ACCEPTANCE SHALL BE INTEC, GRAYSTONE, VULCAIN, OR APPROVED EQUAL. 1, SENSORS SHALL BE OF THE ELECTR❑CHEMICAL TYPE. 2, LOCATE SENSING P❑INTS ON WALLS AND COLUMNS AT 5-6FT ABOVE FLOOR LEVEL LOCATE ONE SENSING P❑INT PER 7500 FT2 (SENSOR RANGE OF COVERAGE SHALL BE C❑NSIDERED AS APPR❑XIMATELY 50 FT). DO NOT LOCATE SENSING P❑INTS CLOSER THAN 6 FT TO TRAFFIC LANES. SLNS❑R RANGE SHALL BE OF 0 TO 300 PPM FOR 7% ACCURACY CELL OR 500 PPM FOR 37. ACCURATE CELL. 4, THE PROPOSED SENSOR L❑CATI❑NS SHALL BE SUBMITTED AT THE SHOP DRAWING STAGE AND SHALL BE AMENDED AS DIRECTED BY THE OWNER AND/OR ENGINEER. 5, SENSOR SHALL BE FACTORY CALIBRATED AND WILL ONLY REQUIRE CALIBRATI❑N AFTER A MINIMUM ONE (1) YEAR SERVICE. 6, SEQUENCES FOR THE FIRST FLOOR GARAGE CO SYSTEM SHALL BE 6,1, AT A RISE TO 25 PPM, INTAKE LOUVERS SHALL OPEN AND GEF-2a+3a SHALL ENERGIZE AND GEF-2b & GEF-3b SHALL SWITCH FROM CONSTANT ON TO OFF, 6,2, AT A RISE TO 50 PPM, THE CO SYSTEM SHALL ACTIVATE WARNING STROBES AND HORNS FOR IMMEDIATE EVACUATI❑N, 6.3, AS PPMs DROP 5 OR MORE BELOW ACTIVATI❑N LEVELS, SEQUENCES SHALL REVERSE. 78x60 OA LOUVER (BY GC). PROVIDE WITH A FULL SIZE SHEET METAL PLENUM 12" DEEP AND DIVIDE INTO HIGH PLENUM FOR UPPER GARAGE AT 78x24 AND LOWER PLENUM AT 78x36 FOR LOWER GARAGE. GEF-2 WILL BE OFF WHENEVER CO SYSTEM FOR UPPER GARAGE IS INACTIVE AND ACD SHALL BE CLOSED. UPON CO ACTIVATION, ACD SHALL FAIL OPEN AND END SWITCH WHEN FULLY OPEN SHALL ENERGIZE GEF-2. E EDE, INC. MEP/FP ENGINEERS 1185 Washington St. Suite 4 West Newton, Ma. 02465 Tel. (617)-969-7700 Fax. (617)-969-7709 E-Mail. ede@edemep.com COPYRIGHT 2015-EDE Inc ©ALL RIGHTS RESERVED Project #: 4017 w O 0_ CC 0_ PROGRESS SET CO 0 N MAR 22,2019 BUILDING PERMIT SET 00 O 00 a) U) 246 Walnut Street X (13 (0 CO LO N- CALE: 1"=8,-0N PROJECT#: LC) (C) SALEM, MASSACHUSETTS 01970 URBAN SPACES L.L.C. & DIAMOND & SINACORI L.L.C. DRAWING TITLE: REGISTRATION: DRAWING #: nL oL ©TISE DESIGN ASSOCIATES, INC 2019 \RD Al 204 I V SSA Al 205 P DER 3 DER 4 CD-2 L 9x9 75 t I 206 II OW II TRASH RISEN WITH 22' 6"0 NS co fit W/D RR-1 10x10 300 SFD L co co TRAS $x8' \_\ I TURN up. 10x8 UP II II II II II � II II I I II II II II II II II I. RD 99 J Cl AFFORDABLE 202 JI Dl A S1 201 ELEV. DATA1ox8 SLOSH I i 2x1 0 DER 7 AD r AD PITCH Y4 R FOOT 211 PITCH YA PER FOOT PITCH A" PER FOOT PITCH A" PER FOOT RAC x \ / \ / \ / \ / OD \I/ TO 114 BT110\W / \ / \ / \ � E\ TO-v RD AD PITCH YA PER FOOT CD-2 9x9 1 x 275 CORRIDOR -- N S DER 8 212 II II l I AC AD REF 4n 4n KAHU 36 AFFORDABLE 207 RD D D 24x12 LOVER BY GC. HVAC TO PR❑VIDE FULL SIZE PLENUM 12' DEEP WITH INSULATI❑N AND 14x10 DUCT RUN BELOW CEILING IN S❑FFIT PR❑VIDED BY GC. DER 11 8"0 r' n W/D LJ FCU 36 P---0 0 I low REF - DER 10 DER 9 M F 210 G1 208 II IL RD J 209 RJ 9 Lr= RD l S 6'0 OA DUCT WITH CONSTANT VOLUME REGULATOR AND C❑NNECTI❑N TO RA DUCT (TYP FOR ALL 13 THIS FLOOR) S N� E EDE, INC. MEP/FP ENGINEERS 1185 Washington St. Suite 4 West Newton, Ma. 02465 Tel. (617)-969-7700 Fax. (617)-969-7709 E-Mail. ede@edemep.com COPYRIGHT 2015-EDE Inc ©ALL RIGHTS RESERVED Project #: 4017 a) E 0) 2 U a) a_ 0) 0 a) W1E = U Q LL� CID O 0 CC Q 0 PROGRESS SET CO 0 SALEM, MASSACHUSETTS 01970 MAR 22,2019 BUILDING PERMIT SET URBAN SPACES L.L.C. & DIAMOND & SINACORI L.L.C. DRAWING TITLE: REGISTRATION: DRAWING #: 246 Walnut Street CN co co CO CO CO CO CO CO LO CO ©TISE DESIGN ASSOCIATES, INC 2019 r 1 303 \ A 304 DER 4 (FCU 36 \ A 305 w D DER L5 DER 6 L - 6"0 (, O O DW •1 r 6"0 II II II II II I � I I L--- TRASH RISER WITH 22' TURN UP. 10x10 Up 11 & 10x8 DN RR-1 10x10 300 SFD rJy e. FCU 36 STAIR c, UP TRASH L � 306 VH L SCALH : 1 /8"-19 99 i ID dR < Iz < i0 < D2 AFFORDABLE 301 ECU 36 24x12 LOVER BY 'GC. HVAC TO PR❑VIDE FULL SIZE PLENUM 12" DEEP WITH INSULATI❑N AND 14x10 DUCT RUN BELOW CEILING IN S❑FFIIT PR❑VIDED BY GC. DER 7 r ICI 1 El 1313 1 DW II DER c0 11�3 I 12x10 REF K 307 OP O (ECU 36 it: r • r AFFORDABLE 1312 1 11 ow DER 8 = r REF K 308 P EBB 24 w/o DER FCU �36/ OP O - 11 C " Q V a F CU 36 CD-2 9x9 275 Ek. co I I FCU\ 36 i rrp JDN r D. DW I J 309 H G 310 IR 2 DER 9 7 1 1 1 - -6"o OA DUCT WITH CONSTANT VOLUME REGULATOR AND C❑NNECTI❑N TO RA DUCT (TYP FOR ALL 13 THIS FLOOR) N4 E EDE, INC. MEP/FP ENGINEERS 1185 Washington St. Suite 4 West Newton, Ma. 02465 Tel. (617)-969-7700 Fax. (617)-969-7709 E-Mail. ede@edemep.com COPYRIGHT 2015-EDE Inc ALL RIGHTS RESERVED ©Project #: 4017 C z w UD O 0_ CC L Q 0 Project Management PROGRESS SET F— u U • • il l II •. • CO T o -. N ›- SCALE: PROJECT#: S. S. Cr) CD a) z U) MAR 22,2019 BUILDING PERMIT SET URBAN SPACES L.L.C. & DIAMOND & SINACORI L.L.C. DRAWING TITLE: REGISTRATION: DRAWING #: O CO 0 z ©TISE DESIGN ASSOCIATES, INC 2019 D B3 403 i A 404 11 I DER 4 FCU 36 DER 6 to 0 O w/o DW II — — -1 DER 3 REF s _j 6"0 0 ITC r- Dw - 1 o n c1,142- II GL—_ II II -- II Dw III I DER 2 1"-J 29. -00 TRASH RISER WITH 22' TURN UP, 10x10 UPS i & 10x8 DN L 406 I oI L—VI—L 4 SCALDo'/8"_1 9 `0] RR-11 10x10L 300 DN STAR UP Cl AFFORDABLE 1402 D1 401 TRASH 1 /FCU) DD JJ DER 7 24x12 LOVER BY GC, HVAC TO PROVIDE FULL SIZE PLENUM 12' DEEP WITH INSULATION AND 14x10 DUCT RUN BELOW CEILING IN SOFFIT PROVIDED BY GC, tj'1, E 1 413 REF 407 REF FCU)36 E2 412 W/D JQF DW Li DER 8 12 Clq REF J AFFORDABLE 3 gi OP 0 DER ffe (EBB) 24 CC CIO t? 6E' - DW DER 9 409 411 410 f 6'0 OA DUCT WITH CONSTANT VOLUME REGULATOR AND CONNECTION TO RA DUCT (TYP FOR ALL 13 THIS FLOOR) EDE INC. MEP/FP ENGINEERS 1185 Washington St. Suite 4 West Newton, Ma. 02465 Tel. (617)-969-7700 Fax. (617)-969-7709 COPYRIGHT 2015-EDE Inc tr--.-ALL RIGHTS RESERVED CID CC LIU a) (13 .65 if LT- lE PROGRESS SET co SCALE: LJJ LJJ 0 CD < coo< LO ul REGISTRATION: MAR 22,2019 BUILDING PERMIT SET URBAN SPACES L.L.C. & DIAMOND & SINACORI L.L.C. DRAWING #: DRAWING TITLE: CD 71- CO 0 CD co TO • CD OTISE DESIGN ASSOCIATES, INC 2019 i B I 10 I 11 Iu lI L1� 503 DER � A 0 504 \ A REF 5�5 505 4 1 1 J DER 3 O O II II II II r� RR-1 10x10 300 N. y DN STAIR` UP TRASH rsco e. 3-31 x TRA H RISER WITH 22' TURN UP. 12x10 UP10x10 DN L 506 El L- I- VI- L 5 SCALL 0 1 /899 -1 99 D1 1501 1 FCU 36 _)Q 24x12 LOVER BY GC. HVAC TO PR❑VIDE FULL SIZE PLENUM 12' DEEP WITH INSULATI❑N AND 14x10 DUCT RUN BELOW CEILING IN S❑FFIT PR❑VIDED BY GC. DER 7 IP El E2 513 lr �I DW ;I I DER 13 1o. REF REF --� 00 K 507 lUR (FCU 36 u 512 FCU 30 1111 ! li DW ; ( ° ) I ' 1 o11 p IIlk DER 7REF I=IN 1 74411 II 12 DER 8 U REF K 1508 1 00 O KE 24 DER 11 Q - r -i-- I i I I I FCU FCU 36 36 [ft low REF O O 6"0 I� l DW F 511 G 510 IR 2 eDI v42)_ W/D C �i 509 DER 9 FCU 30 _Li —6"cti OA DUCT WITH CONSTANT VOLUME REGULATOR AND C❑NNECTI❑N TO RA DUCT (TYP FOR ALL 13 THIS FLOOR) E EDE, INC. MEP/FP ENGINEERS 1185 Washington St. Suite 4 West Newton, Ma. 02465 Tel. (617)-969-7700 Fax. (617)-969-7709 E-Mail. ede@edemep.com COPYRIGHT 2015-EDE Inc ALL RIGHTS RESERVED ©Project #: 4017 z n w 0 CC a_ W F— Q P PROGRESS SET 00 N SCALE: PROJECT#: F— u C-) F_- • • .. • •. • •• •• S. MAR 22,2019 BUILDING PERMIT SET URBAN SPACES L.L.C. & DIAMOND & SINACORI L.L.C. X O � CV O (D▪ O 0 - (0 _ C6 2 (6 2 co co CU co c .� co 0 N (0 U) c\I Z co 1"=8/-0" z a 0 0 w-'1'� 1J--I 4-1 0 �-I DRAWING TITLE: REGISTRATION: DRAWING #: ©TISE DESIGN ASSOCIATES, INC 2019 603 604 V SCA A2 605 L 4„0 TE UP 11c, 0 0.---'6 o I DE' 14x12 CR-1 12x1 0 300 0 oL_J "0 P -0 4"0 TE UPI I TRA RISER WITH 22' TURN UP. 12x12 UP 12x10 DN TI I 606 O >.< RD 6 01/8" 19 99 C2 602 10"0DATA CL_OSH DER 7 (FCU) 30 4"0 TEp C) 6 KE UP El 612 - T 1 T-- 71 OW p 6"0 KE UP REF SKYLIGHT L A o - Ll IF c F�FciC�Crr� TO 8"0 CD-2 4"0 TE UP DER 8 E2 611 DER 12 REF KE 11 D100 80 J ion (FCU) 36 FCU 30 UP DER 11 TE UP Q Q TE SKYLIGHT I U P L — J 1 Q Q (EBB) 24 I c 0 0 Fl 610 TE o Ih R 608 V RDA Er (FCU) 30 0 0 11 IP KE L1It UP C —6"0 ❑A DUCT WITH CONSTANT VOLUME REGULATOR AND C❑NNECTI❑N TO RA DUCT (TYP FOR ALL 13 THIS FLOOR) ___›—KITCHEN EXHAUST FOR 61L❑❑R TO RISE UP THROUGH ROOF TO GOOSENECK WITH BOTTOM 36' ABOVE ROOF, (TYP) i T❑ILET EXHAUST FOR 6th FLl TO RISE UP THROUGH ROOF TO GOOSENECK WITH BOTTOM 36' ABOVE ROOF (TYP) DRYER EXHAUST FOR 6th FLOOR TO RISE UP THROUGH ROOF TO GOOSENECK WITH BOTTOM 36' ABOVE ROOF, (TYP FOR ALL 6th FLOOR DRYERS) N 4 E EDE, INC. MEP/FP ENGINEERS 1185 Washington St. Suite 4 West Newton, Ma. 02465 Tel. (617)-969-7700 Fax. (617)-969-7709 E-Mail. ede@edemep.com COPYRIGHT 2015-EDE Inc /ALL RIGHTS RESERVED Project #: 4017 O 0 CC 0 W PROGRESS SET CO i 0 SALEM, MASSACHUSETTS 01970 z 0 MAR 22,2019 BUILDING PERMIT SET URBAN SPACES L.L.C. & DIAMOND & SINACORI L.L.C. 00 O 00 a)) C!) DRAWING TITLE: REGISTRATION: DRAWING #: FL L 246 Walnut Street CO CO CO N— CO CO CO CO CO ©TISE DESIGN ASSOCIATES, INC 2019 601 501 HP 36 403 303 203 401 301 201 _14 LAI TE DE ( HP 36 506 "0 TE KE KE TE KE ul PITCH 1/4" PER FOOT — 17:=Li KE TE HP HP 36 36 406 306 SCA :1/8" RD DE ----BOILERS BY PLBG. PROVIDE 4"0 FLUE PITCH 1/4" PEP TE u 6"0 KE I 18x 0 0 0 4"0 DE EXHAUST AND COMBUSTON MR WAKES • OT BOILER ROOM ROOM AP DEF) 4"0 TE ROOM 02 HP COMM/ 313 FITNESS - 0 KE PITCH A" PER FOOT DE- - 0 - 36 x3 HP ) 206 LOBBY KE TE 13 TE HP )30 612 DEFf KE LRD DE TE ore 4"0 1-(D E F) TE TE TE LI DE TE H1 BOTTOM 36" ABOVE ROOF AND 12x12 " DUCT DROP TO 6th FLOOR PITCH A" PER OOT RD PITCH PER FOOT DEF)10 210 311 411 511 610 TE DE PITCH 209 310 410 A" PER Fa urP KE 609 — 4"0 GOOSENECK FOR TOILET EXHAUST WITH BOTTOM 36" ABOVE ROOF OW) 4'0 GOOSENECK FOR DRYER EXHAUST WITH BOTTOM 36" ABOVE ROOF OYP) 6"0 GOOSENECK FOR KITCHEN EXHAUST wall BOTTOM 36' ABOVE ROOF OW) ELEVATOR RELIEF VENT 1. GC TO PROVIDE 36x24 LOUVER IN EXTERIOR WALL. 2. HVAC TO PROVIDE FULL SIZE PLENUM 12' DEEP FOR LOUVER AND INSULATE PER ENERGY CODE. POWERED CLOSED. ON LOSS OF POWER BY FA RISING TO ABOVE 85°F, ACD SHALL FAIL OPEN. 4. HVAC TO PROVIDE T—STAT AND WIRE TO OPEN ABOVE 85°F AND TO CLOSE WHENEVER BELOW AREA) WITH ACD ACTIVATION OR ACD WHENEVER 80°F. T—STAT TEMP. EDE, INC. MEP/FP ENGINEERS 1185 Washington St. Suite 4 West Newton, Ma. 02465 Tel. (617)-969-7700 Fax. (617)-969-7709 E-Mail. ede@edemep.com COPYRIGHT 2015-EDE Inc ALL RIGHTS RESERVED 246 Walnut Street CC Lij PROGRESS SET CO CD 0 SALEM, MASSACHUSETTS 01970 MAR 22,2019 BUILDING PERMIT SET URBAN SPACES L.L.C. & DIAMOND & SINACORI L.L.C. DRAWING TITLE: REGISTRATION: DRAWING #: CN CD co CO CO LO ©TISE DESIGN ASSOCIATES, INC 2019 SE SFII° SE SF BEDROOM M5 SF S J� VAC T SCAL B M3 M9 D BED M5 Pr) H NINC ROOM H A R 30[VINC/D N M3 B MASTER BEDROOM M9 D BEDROOM M5 NG "P CA J\ 1 ' 0" BAT M4 A E B LOW WALL TC M2 LAUNDRY M7 E WAL IN CLOS LAUND M7 4 A TYP. , II MASTER BAT M6 LOW WALL TC EN M2 O 0- U U, WALK-IN CLOS M8 A TYP. P LA \ S T"P U\ITS SHOWN 8c TYPICAL POH: 302 =C TYP PO 502 8c 602 EN u BEDROOM M5 A2 C D HALL M1 C D D SF (1) \ L SF E_ a • C 4101:EC. (JOKE _ , - - �-�- WC-A2 _ COKE __----nT T •r �_ �1. � I R� 1 6'0DAI A L`° M1 t0 RR-2 36x10 N 1100 x M4 A TY M9 C_1 0 0 CD-1 -12x30120 02 BEDROOM M5 _ = — — 6"EKE II r ..._—{ OIRAGE I I I I I C C c �4.'NF LAUNDRY _; w_gin C U7 A, 8, C V D E C 10� CLOS B Cp-1 12x120 40 CD-1 12x12 300 4"OTE----------]*-WC-A4 4"ATE - - - - — - 1 WC-A4 1 CD-1 �- 12x1 2 10'0 M ASTER + 300 BEDROOM U9 B D 2 CBD _ CD1 — 12x12 10'0 AFFOP �PL 400 L 110/b NINC 10'0 D\ <0 U U3 A TYP. B WC-A4 24x12 LOUVER i BEDOOM I -- 4'_TE ---- U5 CD-1 -12x12 inn 0 �( 4"FTE BEL M5 CD-1 � 9x9 - I�y R10 250 BEDHOO SF SF M5 CD-1 12x12 - 300 V\ _IVINC/D B MASTER EIE IDOCR rAJ 9x9 250 N 8'0 N WC-B4 4'OTE -- - SE -N-LI-- -�- D C 4'0T — �— WC-B4 -r+-[�— - _ BEDROOM CD-1 12x12 ~� 300 S CD-1 12x12 300 WC-B6 -N`E- WC-B4-,rr-E- M5 B B v ASTER M9 BEDROOVI M5 NINC U 1 LCW Wf LL M2 " (AI + - - - - - 9x9 150 LAUNDRY 9x9 BEDROOVI 250 M7 9x9 LOW 150 WALL RR-2 36x12 1100 r TC M2 FT EN IZD A2 HALL Zo sh U2 LOW wALLt - LAT-WY' 201 D1 TYP FI:D 401, 501 & 601 & 301 (D2) Zo A2 F SF U4 C OS A TYP jollo 150 cLos MASTER U9 RR-1 36x12 1100 NINTA 4- BEDROO M5 M3 NING 300 400 300 12x12 300 12x12 400 CD-1 I EDE, INC. MEP/FP ENGINEERS 1185 Washington St. Suite 4 West Newton, Ma. 02465 Tel. (617)-969-7700 Fax. (617)-969-7709 E-Mail. ede@edemep.com COPYRIGHT 2015-EDE Inc ALL RIGHTS RESERVED UD CC CL 13 141 .g ArchitectureSite PROGRESS SET 00 SCALE: 0 SALEM, MASSACHUSETTS 01970 MAR 22,2019 BUILDING PERMIT SET URBAN SPACES L.L.C. & DIAMOND & SINACORI L.L.C. a) DRAWING TITLE: REGISTRATION: DRAWING #: rill 246 Walnut Street co co co a) 617 . 581 . 6611 fax co LO CO rnryd 0(5 (26 ©TISE DESIGN ASSOCIATES, INC 2019 _ UNIT 603 TYPE,, B2U,IS SIMILAR TO UNI 3 TYPE B1 ON S EEt H-2'1E, ` M G❑ ll E TO AND D ARE INDIVIDUAL UP THRU SE \SERSF ❑OF PER H-1,6 1,7 S 1:3•2 .S BR NING SE B IV ASTER BEDROOM M9 SF SF cn U D BEDROOM M5 B A2 6o R LIVING/DIN M3 —I LAUNDK M7 NG ATH LOW WALL E LAUNDRY A TYP. I a CLOS UNIT UNIT 6041`TYPE A2 IS - SIMILAR TO UNIT 204 TYPE Al O�N�T SHEET H-2,1 E4OR TE' KE AND DE 22 : GO INDIVIDUAL UP THRU sFROOF PER H-1,6 & 1,7 SF SF VAC SCALE: 1 / BEDROOM M5 CA C\ P B MASTER. BATH E LOW WALL WALK—IN CLOS M8 P TYP. A\S —l1 "P It KITCHEN M2 TC M2 A2 C EN O O u BEDROOM M5 HALL M1 C D D --I-i O O 0 KITCHEN M2 LOW WALL LAUNDRY B M7 HALL M1 C A?, 8 2 (Sc C2 A2 F M6 M4 4 6'� QKE I UP O 0 F S M8 K TC �L H UNIT 1602 TYPE C2 IS SIMILAR TO UNIT 202 I YPE C ON SHEET H-2,1 XC T TE) KE AND DE ipo' N/cGO INDIVIDUAL THRU ROOF PER H-1,6 & 1,7 C2 CBR WING,/ IN NG 2 EN M2 �5J VAC J\ SCALE: 1 /4" CI)-1 I2xI2 300 C 1 ' O 99 ROOM D 0 4'0 DE UP C —II A\S SF Nr B T01 LAUNDRY M7 LIVING/DII,' "P 'C CD-1 12x12 300 J A SF i F BAT M4 SE C=JF BEDROOV UNIT 46 TYPE B3 IS SIMILAR TO UNIT 2 3�� TYPE B1 ON H-21i SE • rrr SF ( SF VAC SCALE: 1 /L O `0B RR-2 36x10 1100 BEDROOM CD-1 9x9 200 Ba CBR LIVING/D N NG 403 99 C U3 "P - ^ 9 B D CA f' l� 1 r ' 36x8 WA CL M8 A T`f X MASTER co C8a0 8N0_) J\ BEDRVOM CD-1 9x9 225 `) O 0 CC L LOW WALL B WALK IN CLOS M8 II A TYP. PLA\S T"P MASTER BATH M6 KITS M2 M7 GC TO PROVIDE DROPPED CEILING FOR A LIMITED RA PLENUM. COORD WITH ELECTRICAL TO AVOID WIRING IN PLENUM (TYP) SF SF SF AST R BED 9x9 200 LY LY BEDROOM M5 N 36x8 co D S Ci B LOW WALL RR-2 12x12 DROOM 9x9 200 SF CLOS 4 ASTER BATH A TYP ASTEll UNITE4icm TYPE Cl IS SAME AS UNIT 202 TYPE C1 ON H-2,1 U3 M7 DE U'i 402 DAHL NG DER 9 IN 12x12 275 NG U5 SF CLOS M8 LOW WALL SF SF BEDROOlv 0511 200 — CLOS 300 EDE, INC. MEP/FP ENGINEERS 1185 Washington St. Suite 4 West Newton, Ma. 02465 Tel. (617)-969-7700 Fax. (617)-969-7709 E-Mail. ede@edemep.com COPYRIGHT 2015-EDE Inc ALL RIGHTS RESERVED PROGRESS SET CO Llj SCALE: 0 SALEM, MASSACHUSETTS 01970 MAR 22,2019 BUILDING PERMIT SET URBAN SPACES L.L.C. & DIAMOND & SINACORI L.L.C. DRAWING TITLE: REGISTRATION: DRAWING #: 246 Walnut Street co 1.0 LO cia z cc`3 11-L1202 ©TISE DESIGN ASSOCIATES, INC 2019 SF J t—� — D CD-1 12x12 400 ■ 1 ■ A= FORABLE 1BR LIVING/DINI 2 SF U3 U) O ;IDOR 11 BATH U4 JVALK-IN �LOS ROOD A i 2 ) 0 RR-1 In' 24x12 I o 14x12 Ti Je BB �DROOM I` CD-1 12x12 300 f 8x12 ❑�I VAC T"P CAL \ SCALE: 1 /4" = 1' — 0" WC-A2� _'- -,J WC-A4 -yrcj-- 4-toTE= BED U5 CD-1 12x12 300 CD-1 12x12 300 MASTER BEDROOM U9 LIN r D CD-1 12x12 300 i9P- D ASTE BEDRC�_h U9 LEI I F- •I vl I YN. WALK-IN CLCIS KITCHEN CD-1 9x9 - ® — 175 1‘ V U2 0 a 0 10 16x12 RR-2 36x12 14' 1100 LIVING/DINING U3 CD-1 1 2x1 2 400 ;I T PLA\S T"�E B MAST BATH r Iu X 20x12 izr BATE ,,, U6 MASTEIR BEDROOM U9 9 CD-1 12x12 300 1/40 pa U E V B�� IL B A44•0D Lai ZO '0. F B AUNDRY cu RI-1 x- 3-x10 cc 100 H '0 pa UI C I N FCU 36 6'OKE B V 0 0 0 0 KITCHEN U2 490DE= IIi KITCHEN U2 CD-1 9x9 150 B CD-1 9x9 200 1 F LIVING/DINING U3 6'OKE CD-1 12x12 300 SF /FD W/� - - - .11 CLI/ FCU 30 I 308 F•......1JP1D1...... LAUNDR:Y:::::::::::8 a I I RR-2 30x10 840 [U7 0 z J 4"OTE D A TY cu 10'0 / x ‘U;0 MASTER BEDROOM 11 OD 1 12x12 300 n 0 -N -D- - WC-B6 - - WC-B4 10'o0 1 CD-1 -8. --12x12 ---- LIVING/DINING 375 U3 D RA TFR, • ID ATH / 16x12 i? 30x8 I MASTER BEDROOM U9 U\ITS SHOW\ & TYPICAL FOB: 308 =K TYP 307, 407, 507 8c 508 309 = H TYP F0. 509 0� 310 = G TYP F410 & 510 311 = F TYP F 0 211, 411, 511 & 610 312 = E1 TYP 312 0\LY CD-1 12x12 300 LIN if ° ",B,I o ; 4"ODEC-1 co It S T RR-1 36x10 1100 16x121) 10x12 } CD-1 4.N 9x9 150 CI 05 MASTER() BATH n 0 HEN I_ ❑ B 0 1 LIN WALK-IN .COS M8 INING D SE SF SF A TYP. MASTER BEDROOM M9 GIB BR LIVING/DINING M3 209 -IJ- WC-B4 G i 0 L-� CD-1 1 2x1 2 275 Bo9 BR LIVING/DINING U3 I ,111 II ;I Ij ❑ D 4'OTE CLOS KITCHEN U2 CD-1 12x12 300 �w-VC-B4 -El-w-WC-B4 SF -0-11V-WC—B6 C—B6 - L- C—B4 7 33— i G WALK-IIN CLOS M8 1 SF 4-VJIL �- VAC PART AL \ T"P H L & — — �OI D 1, D T PLA\S __-_------- 4'TE LAUNDRY vf1 KITCHEN M2 LOW WALL CD-1 12x12 250 CD-1 9 xP. 175 1 306 M3 250 12x12 TCHEN o ER LAUNDRY 0 HEN r__ „[J LIN 250 WALK-IN CLOS Fl LIN SF SF MASTE BEDROOM M9 G2 M3 609 WALK-IN CLOS SF SF SF VAC PART AL \IT PLA\S 0 LIN ETE ci_d010 3 CLOS MASTER 4'0TE M6 SF 250 <FCU 36 NAR A TYF. FD ultra MASTE BEDROOM M9 SF SF CLOS BEDOOM 'EDE, INC. MEP/FP ENGINEERS 1185 Washington St. Suite 4 West Newton, Ma. 02465 Tel. (617)-969-7700 Fax. (617)-969-7709 E-Mail. ede@edemep.com COPYRIGHT 2015-EDE Inc RIGHTS RESERVED E5 co ,_ o c:) (s) co ,_ 0 .1-(1) (.1 0 c) u) --co c: CD CD LO E,7, 5: -....t ii c° 0 cr8c,r) (75-eff 21 :0 0 . WNZap co 0 co cn MAR 22,2019 BUILDING PERMIT SET URBAN SPACES L.L.C. & DIAMOND & SINACORI L.L.C. DRAWING TITLE: REGISTRATION: DRAWING #: LIT1 cki bTISE DESIGN ASSOCIATES, INC 2019 -B6 D—_ 6• CEI� -B4 -0 — KITCHEN M2 LOW WALL CD-1 9x9 /5 171 vvALK—IN CLOS JUR II LIVING/DINING 1,1 206 M3 I I RISE } CD-1 9x9 200 RD U\ITS SHOW\ 8c TYPICAL FOB: 206 =P TYP F0206 0\LY VAC J\ T PLA\S ) SCALE: 1 /4" = 1 ' — 0" LOW WALL I O I I I . I I0I I I \ B R LIVING/DININ�� M3 kis ;OIL 01 6'0 KITCHEN uP M2 CD-1 9x9 175 I CD-1 9x9 200 6 CD-1 i 9x9 200 WALK—IN CLOS VAC \ T PLA\S T"Ph SCALE: 1 /4" = 1' — 0" VAC J\ SCALE: 1 /4" — 1 P A\ S 0„ G 1- I DER FS - F �\ E D t � SF SF B B BEDROOM M5 Ii A T H B M5 I I 14x8 r111 DROP co, L I I B CLOS CD-1 9x9 200 M7 CLOS CD-1 9x9 200 B 0 J 0 A2 LAUNDRY M7 J BEDROOV } IM5 S C , 4bxb :•:•OPD1•:•: ; ;•;� RR-2 36x12 111J0 : OLDS 5-1( co CD- I } 8'0 8'� 9x9 B P F 001 T-- 200 717- 14x12 DA I E CL 0/11 /DE / UP _„ RR-2 36x10 11(40 3 /FCU �36/ C', 36x8 IL B METER CLOS VALK--IN LOS 1 CD-1 9x9 BED(F)VI 200 } M8 U\ITS SHOW\ & TYPICAL FOB: 606 =T TYP FOB 606 0\LY OPD-1 - - 30x8 840 Kt UP ' u B B z RR-2 30x10 840 Cn F LOVE ' CD-1 WALL ++ — 9x9 KITCHEN150 :off LAUNDRY M7 M21 CD-1 12x12 400 SF SE D U4 DOR F MI A:al-}E H CD-1 E34 1(4/I 9x9 u91 + 200 •41- P4 U E IbERI 7 I w F- LiJ 0 MASTET \] BATH OF A T1' GC TO PR❑VIDE DROPPED CEILING FOR A LIMITED RA PLENUM, C❑❑RD) WITH ELECTRICAL TO AV❑ID WIRING IN PLENUM (TYPICAL) - STER 3EDROOv } M9 CD-1 i 9x9 SF P 200 E A () 0 J 0 I I A TYP. II SF IV ASTER BEDRC}; EJ91 1 CD-1 9x9 225 VAC J\ SCALE: 1 /4" = 1 r 4'ODE 11 D SF A2 10x12 CLOS C • l c> LUND IU7I B KITCHEN U2 —LOW WALL a 0I's 1 I % I I O I I '-' I U 2BR AFFOPDABL LIVINGNINC VAC T"P CAL J\ SCALE: 1 /4" = 1' — 0" U4 BEDE 1 CD-1 9x9 225 TEr H r- B cn 0 J 0 Rh S 20/ 10 0^ — 14x12 FD RK 24x14 1100 D B rI ❑ T PLA\S T w I- CLOS SF f ; 0 U\ITS SHOW\ Sc TYPICAL 175 Liz 12x12 207A U3 325 RD • LOW WALL 14x12 00 RR-1 -24x14 1100 RDABLE DINING • BATH :9•1 Trl M6 CLOS L1-1 -El_ 9x9 225 D w F- SH 1F s. J FCLA A TYP. TER 300 24x10 A TYP. MASTER 275 6x10 cu 16x12 LAUNDRY - Cs 1 I TSJI 300 300 A2 A2 M3 LIVIZa8NiNG M3 • LOW WALL CLOS M8 300 ITCHEN EM2 300 DF .496 275 ILDROOM LOW WALL 300 SF 4_ vc- D SF C. MEP/FP ENGINEERS 1185 Wa shington St. Suite 4 Tel. (617)-969-7700 r-r,ALL RIGHTS RESERVED Lij CL CC IL co -51 CD IL 15) PROGRESS SET 00 SCALE: LU LLI 0 URBAN SPACES L.L.C. & DIAMOND & SINACORI L.L.C. BUILDING PERMIT SET DRAWING TITLE: REGISTRATION: DRAWING #: CV co co c CO • CO 1.0 CO CO LO N- CO ©TISE DESIGN ASSOCIATES, INC 2019 Si S t� D vN 0D\ 2R CD-1 -12x12 inn I 0 SR-1 12x8 375 T 1Ox10 9\ ELEV 0 -LIVATOR _OBEY 106 R SR-1 12x8 375 T VD D VD 10x10 X 07 F] RR-1 16x16 750 R -S 101 0 EF r°1 VAC \LARC SCALE: 1 /L" — 1' — 0' C SF -11-WC—A4 V GAS FIREPLACE Il �d II I VAC \ ARC ) SCALE: 1 /L" — 1' -D RDA\S ALL 104 12'0 UP FROM BELOW [11 MAIL BOX N/A 0002 103 0 �B B Y 02 102 24x16 EXHAUST LOUVER BY GC. PR❑VIDE FULL SIZE I/.ISULATED PLENUM 12' DEEP AND CONNECTION TO EF-2 DUCTWORK HST H GAS FIR LACE BY GC. PROVIDE VENTING WITH NER FLUE EXHAUST AND OUTER COMB STI❑N AIR EQUAL TO DIRECT VENT PRO BY i URAVENT OR EQUAL CO R 0O COVMUL POOH 12111 CORR CD-1 12x12 400 } OVS0 V ITY DOR T01 -D O A\ CD-1 12x12 400 S RR-3 1 Ex 1 E 750 10'o 10'0 CD-1 6x6R 150 0 X 0 VD u 14x10 IN N CD-1 9x9 } 300 OOR COV C 0\ AR CORR TO' -CO\D H C N SA DUCT TO RUN IN S❑FFIT AND TURN AND RISE TO RUN ABOVE HIGH CEILING. RR-1 PR❑VIDE SIDEWALL RR-1 HIGH BUT 16x16 BELOW CEILING WITH 16x8 DROP TO 750 — AHU BOTTOM RETURN (TYP FOR 2). A & 24x12 LOVER BY GC. HVAC TO PR❑VIDE FULL SIZE PL UM 12' DEEP WITH INSULATION AND 14x10 DUCT RUN IN CEILING PL UM N x N C N x co 2 DOR UEJ 10'0 10'0 A MOUNT HIGH ON SIDEWALL C OOR COV C 0\ AR -A CD-1 12x12 300 D SPAC \- SS E TiNESS CD 12x12 300 } \ S R 204 n ROOM MASTER BEDROO U9 14x10 D SF SA \ A 2 D SF'\ —2 EUH 48 RETAIL TO BE PR❑VIDED WITH TEMPORARY HEAT UNDER BASE BUILDING SCOPE, RETAIL FIT —OUT WILL BE UNDER FUTURE CONTRACT. A TYP. V ASTER /j (A T U6 O 8'0 fly 22' TURN UP IN JANITOR EXH RISER) C EUH 4A STA STAR 'Th S2 R i I I E EDE, INC. MEP/FP ENGINEERS 1185 Washington St. Suite 4 West Newton, Ma. 02465 Tel. (617)-969-7700 Fax. (617)-969-7709 E-Mail. ede@edemep.com COPYRIGHT 2015-EDE Inc ©ALL RIGHTS RESERVED Project #: 4017 ArchitectureSite PROGRESS SET 00 N W 0 u CD F SCALE: PROJECT#: SALEM, MASSACHUSETTS 01970 MAR 22,2019 BUILDING PERMIT SET URBAN SPACES L.L.C. & DIAMOND & SINACORI L.L.C. O a) DRAWING TITLE: REGISTRATION: DRAWING #: 246 Walnut Street 0 co O co U, L CO co 2 C 0 z 11-L1205 CO CO CO 00 I CO 617 . 581 . 6601 ©TISE DESIGN ASSOCIATES, INC 2019 EXTENSION FOR WRAPPED DUCT C WING NUT & ARM (TYP) ROUND DAMPER 3/8" QUADRANT NOTES: DUCT MATERIAL TO MATCH DUCT MATERIAL f DUCT 3/8"0 ROD 22 GA. BLADE TWO BLADE DAMPER ARRANGEMENT 1/2" QUADRANT 1/3' ALL AROUND RECTANGULAR DAMPER FOR DUCTS UP TO 18"x12" DUCT 3/8"0 ROD PIN r3' ALL AROUND 16 GA. BLADE RECTANGULAR DAMPER FOR DUCTS 19" TO 48"x12" 1. FOR DUCTS OVER 12" HIGH USE MULTIPLE BLADES. 2. ALL BRANCH DUCTS (SUPPLY, RETURN & EXHAUST) SHALL HAVE VOLUME DAMPERS, INCLUDING RUNOUTS TO DIFFUSERS (MANDATORY). SEAL AND CAULK ALL WALL PENETRATIONS ALL CONCEALED DUCT SHALL BE ALUMINUM WITH SEALED JOINTS HEIGHT PER DRYER Y OUTLET DET# LAUNDRY RM WALLJ WALL CAP WITH BACKDRAFT DAMPER &BIRDSCREEN CEILING VOLUME DAMPER (SINGLE BLADE) EXTERIOR WALL -/ DRYER EXHAUST DETAIL CONNECT WITH LIQUID ADHESIVE AND DRAW BAND TYPE CLAMP FLEXIBLE OR BUCK DUCT (AS REQUIRED). SEE PLANS FOR SIZES SEE PLANS FOR ALL RUN OUT DUCT SIZES LOW VELOCITY ELBOWS RADIUS ELBOW SEAL AND CAULK ALL WALL PENETRATIONS ALL CONCEALED DUCT SHALL BE ALUMINUM WITH SEALED JOINTS DRYER AND KITCHEN EXHAUST DETAIL MAIN DUCT ROUND BRANCH DUCT TAKE -OFF DETAIL DOUBLE THICKNESS TURNING VANES (SEE TURNING VANE DETAIL) RECTANGULAR ELBOW DET# LOW VELOCITY TRANSITIONS AIR FLOW DIVERGING FLOW AIR FLOW CONTRACTION FLOW DAMPER STIFFENING DUCT SIDE ELEVATION OUTSIDE END BEARING INSIDE END BEARING WALL CAP WITH BACKDRAFT DAMPER & BIRDSCREEN CEILING MICROWAVE WITH EXHAUST EXTERIOR WALL -/ KITCHEN EXHAUST DETAIL "METALAIRE" MODEL "MD" SPIN -IN FITTING WITH QUADRANT OPERATED ROUND VOLUME DAMPER LOW VELOCITY TRANSITION TAKEOFFS & ELBOWS N.T.S. LOW VELOCITY OFFSETS FULL RADIUS WHERE POSSIBLE (R=W) TRANSFER DUCT SCHEDULE CFM DUCT SIZE 0-300 10X8 310-500 12X12 510-800 18X12 WALL SEE NOTE NOTES: 0 TRANSFER DUCTS TO BE SUPPORTED FROM STRUCTURE ABOVE. @ FIRE DAMPER WHERE APPLICABLE, SEE ARCHITECTURAL PLANS FOR RATED WALLS. @ OPEN END DUCT WxH, SEE TRANSFER DUCT SCHEDULE. CLOTHES DRYER NOTE: 1. REFER TO ARCHITECTURAL DRAWINGS FOR FULL HEIGHT WALL PARTITIONS. PROVIDE TRANSFER AIR DUCT IN EACH AND/OR WHERE SHOWN ON THE DRAWINGS. WHERE ROOM CFMS ARE GREATER THAN ABOVE SCHEDULE, MULTIPLE TRANSFER DUCTS SHALL BE UTILIZED. CLOTHES DRYER NTS , 12 , WALL OR PARTITION THERMAL BLANKET ALL AROUND SLEEVE DUCT ACCESS DOOR SLEEVE, WRAPPED WITH FACTORY PROVIDED THERMAL BLANKET FASTEN DAMPER FRAME TO COLLAR (SEE NOTE 11) NTS DET# 30° ELBOWS 45° MAX. U-1 MAIN DUCT -SEE SPECIFICATION FOR INSULATION REQUIREMENTS NYLON TY-WRAP TIGHTENED WITH TY-WRAP TOOL OR REUSABLE STAINLESS STEEL DRAW BAND SUPPLY DIFFUSER (SEE FLOOR PLAN) 1/2" INTERNAL LINING (TYP) SEE NOTE@ SEE NOTE / V.D. PLAN VIEW (PLENUM TO PLENUM) V.D. r l l 18" ' 18" FINISHED CEILING TRANSFER DUCT DETAIL AND SCHEDULE VD VOLUME DAMPER SUPPLY BRANCH DUCT AIR FLOW \ I VDI DUCT TAKE -OFF NOTES SECTION (PLENUM TO PLENUM TRANSFER) 10 GAUGE ORY8" THICK RETAINING ANGLES SECURED TO SLEEVE.( SEE NOTE 12) DO NOT ATTACH TO WALL EPDM FLASHING W/LAP METAL CAP OR COUNTERFLASHING WATER CUT-OFF M LAP SEALANT P.T. BLOCK AS REQ. TO MATCH HEIGHT OF INSULATION ROOF INSULATION NTS DET# NOTES: 1. FIRE DAMPERS SHALL BE U.L. LISTED AND LABELED. 2. ALL FIRE AND SMOKE DAMPERS SHALL BE RATED TO MAINTAIN THE RATING OF THE FIRE SEPARATION. 3. TYPICAL INSTALLATION SHOWN. ACTUAL INSTALLATION SHALL COMPLY WITH REQUIREMENTS OF NFPA 90A, NFPA 101, UL 555 AND WITH ALL MANUFACTURER'S RECOMMENDATIONS. 4. LOCATE ACCESS DOOR FOR BEST ACCESS TO LINK. SLEEVE TO EXTEND 3"BEYOND WALL 5. FUSIBLE LINK TO BE RATED FOR 50 PERCENT ABOVE MAXIMUM OPERATING TEMPERATURE OF SYSTEM. METAL NOSING, TYP. DUCTWORK INSULATION AS SPECIFIED. BREAKAWAY SLIP TYPE DUCT CONNECTION (TYPICAL) 'U' CHANNEL HEADER ALL AROUND REFER TO SPECIFICATIONS FOR REQUIRED INSULATION & WEATHERPROOFING OF DUCTWORK. STAINLESS STEEL CLAMP WATER CUT-OFF MASTIC DUCTWORK ROOF PENETRATION 6. ALL DUCT -COLLAR CONNECTIONS SHALL COMPLY WITH UL 555 AND SMACNA. CONNECTIONS BETWEEN COLLAR AND DUCTWORK SHALL BE BREAKAWAY TYPE SUCH AS "S" SLIP, CRIMP, OR OTHER SLIP TYPE IN ACCORDANCE WITH SMACNA PLATE 15A, 4th EDITION AND PLATE 1, SMACNA FIRE DAMPER GUIDE, 1986 UNLESS OTHERWISE REQUIRED BY CODE. 7. GAUGES FOR COLLAR AND RECTANGULAR DUCT SHALL BE AS FOLLOWS: FIRE DAMPER COLLARS SHALL BE SAME GAUGE AS DUCTWORK WITH A MINIMUM OF 16 GAUGE FOR DUCTWORK UP TO 36" WIDE. FOR DUCTWORK ABOVE 36" WIDE, THE COLLAR SHALL BE 14 GAUGE. 8. PROVIDE STEEL STUD FRAMING AS REQUIRED, TO ACCEPT THE FIRE DAMPER ASSEMBLY (INCLUDING SLEEVES, ETC.). 9. AFTER THE INSTALLATION OF DAMPERS, THE CONTRACTOR SHALL SEAL AND TAPE ALL JOINTS FOR AIR TIGHTNESS. INSTALLATION SHALL BE MADE AVAILABLE FOR INSPECTION BY ARCHITECT BEFORE TAPING. MOTOR OPERATED FIRE/SMOKE DAMPER FLEXIBLE DUCT. (SEE NOTES 2 + 3). HARD DUCTED FOR AREAS WITHOUT CEILINGS TRANSITION ROUND TO SQUARE CEILING OFFSETS WITH FLEX DUCT SHALL NOT EXCEED 30" AND SHALL BE GRADUAL. OFFSETS IN EXCESS OF 30" SHALL BE HARD -DUCTED. 2. FLEX DUCT SHALL NOT HAVE MORE THAN 1/2" SAG PER FOOT. 3. LENGTH OF FLEX DUCT SHALL NOT EXCEED 3'-0". LONGER SHALL BE RIGID OR BUCK DUCT 4. PROVIDE DUCT MOUNTED VOLUME DAMPER TO DIFFUSER AS CLOSE TO MAIN DUCT AS POSSIBLE AND CEILING RADIATION DAMPER AS REQUIRED BY CEILING ASSEMBLY. CEILING RADIATION DAMPER/ • FIRE STOP FLAP THERMAL BLANKET LOUVERED DEFLECTOR CONE CORROSION RESISTANT STEEL DIFFUSER NTS DET# NOCX DIFFUSER CONNECTION DETAIL D = NOMINAL ROUND DUCT DIA. D-1/8" N.T.S. UL LISTED FUSIBLE LINK 212°F STANDARD FLEX DUCT CEILING MEMBRANE ifoAmmemf CEILING DIFFUSER W/ CEILING RADIATION DAMPER & THERMAL BLANKET 01-50 NTS RECTANGULAR BELL MOUTH FITTING MODEL RBMD DET# Va BELLMOUTH CONNECTION MODEL BMD VD\ BRANCH-, ti ROOF MEMBRANE 4" THICK RIGID INSULATION FLASHING RECIEVER FILL ENTIRE VOID WITH BATT INSULATION. LEAVE NO VOIDS. MIN. 4" CLEARANCE FROM PIPE TO TOP OF CURB.- MIN. 2" BETWEEN PIPES. DXL/S PIPING SEE PLANS ALL WORK RELATED TO ROOFING, FLASHING & COUNTERFLASHING SHALL BE DONE BY G.C. NTS \16J 10. TO ALLOW FOR EXPANSION DAMPERS SHALL HAVE A CLEARANCE EQUAL TO Y8" FOR EACH FOOT OF DAMPER HEIGHT. THE SIDE CLEARANCE SHALL BE Y8" FOR EACH FOOT OF DAMPER WIDTH EQUALLY DIVIDED TO THE LEFT AND THE RIGHT OF THE COLLAR. THE MAXIMUM CLEARANCE FOR THE TOP AND THE TOTAL OF BOTH SIDES SHALL BEY2" EACH. THE RETAINING ANGLES SHALL BE 1Y2"x1Y22"x1 " SO THAT THERE WILL BE A MINIMUM OF 1" OVERLAP ON THE FIRE SEPARATION. 11. DAMPER SHALL BE SECURED TO COLLAR, WITH EITHERY2" TACK WELDS, NO.10 SHEET METAL SCREWS,Y4" DIA. NUTS AND BOLTS, OR%s" STEEL POP RIVETS, ALL 6" ON CENTER. 12. RETAINING ANGLES SHALL BE SECURED TO COLLAR, SLEEVE OR PLATE WITH EITHERY2" TACK WELDS, NO. 10 SHEET METAL SCREWS,%" DIA. NUTS AND BOLTS, OR is" STEEL POP RIVETS, ALL 6" CENTER. 13. WHERE HUNG CEILING DOES NOT HAVE REMOVABLE TILES, AN ACCESS DOOR (FIRE RATED WHERE REQUIRED) SHALL BE INSTALLED IN CEILING OR WALL NEAR LOCATION OF FIRE DAMPER. 14. ALL RETAINING ANGLES SHALL BE GALVANIZED STEEL. 15. INSTALL FIRE DAMPERS SO THE LOCKING DEVICE CAN BE ACCESSED WHEN THE DAMPER IS CLOSED. 16. FIRE DAMPER ACCESS DOORS SHALL BE LABELED/STENCILED WITH MIN. 1" LETTER " FIRE DAMPER ". ACCESS DOOR ON SIDE AS SHOWN OR BOTTOM OF DUCT MINIMUM SIZE 18"X14" IF DUCT SIZE PERMITS. FOR SMALLER DUCTS MAKE DOOR 2" SMALLER THAN DUCT SIZE. AIR FLOW 0 VD BELLMOUTH MODEL BMD W/ END FLAPS BENT OVER AIR FLOW * VD ` 1 VD MINI-BELLMOUTH OVAL-BELLMOUTH CONNECTION CONNECTION MODEL MBMD MODEL OVBMD ROUND BRANCH DUCT TAKE OFFS 45° RECTANGULAR TAKE -OFF RECTANGULAR BRANCH DUCT TAKE -OFFS ALTERNATE LOCATION FOR ACCESS DOOR "S" JOINT COLLAR TO DUCT (TYP BOTH SIDES OF FIRE DAMPER) ONE PIECE ROLL FORMED GALVANIZED STEEL FRAME FIRE RETARDANT ROPE PACKING FUSIBLE LINK (REPLACEABLE SNAP LINK) 9/32" DIAMETER GALVANIZED STEEL PIVOT ROD OR RIVET ACCESS DOOR SHALL BE MIN. 8"x8" FOZ DUCTS UP TO 12"WIDE & 12"x12" FOR WIDER DUCTWORK DET# NTS i STANDARD 45° REGULAR TO ROUND BOOT CONNECTION MODEL 33000 NOTES: ALL ROUND AND RECTANGULAR BELLMOUTH FITTINGS SHALL BE INCLUDED WITH THE FOLLOWING STANDARD FEATURES: 1. NEOPRENE GASKET TO MINIMIZE AIR LEAKAGE. 2. PRE -DRILLED HOLES FOR QUICK MOUNTING. 3. CONSTRUCTED OF HEAVY DUTY GALVANIZED STEEL. 4. GALV. QUANDRANT VOLUME DAMPER W/TIGHT FITTING GASKETING TO MINIMIZE LEAKAGE AT DAMPER PIVOT POINTS. 5. HEAVY DUTY HARDWARE FOR APPLICATIONS WITH INCREASED STATIC PRESSURE. NOTES: TAKE -OFF MODELS BASED ON BUCKLEY. BRANCH CONNECTION DETAIL 0 C'J [J NTS FASTEN DAMPER TO SLEEVE BY WELDING 6" O.C. FLOOR OR WALL BUILDING CONSTRUCTION STAINLESS STEEL NEGATOR CLOSURE SPRING BLADE LOCK NOTE: FIRE DAMPER AND DAMPER INSTALLATION TO MEET ALL APPLICABLE "UL" REQUIREMENTS. REFER TO ARCHITECTURAL DRAWING FOR FIRE WALL RATING & ASSEMBLY LOCATIONS. FIRE DAMPER W/ BLADES OUTSIDE THE AIR STREAM NTS SHEET METAL COLLAR AT PIPE EXIT SLOPE PIPES AWAY FROM HOOD FASTENERS APPROX. 24" O.C. COUNTERFLASHING FASTENERS APPROX. 8" O.C. BASE FLASHING 2" NOMINAL FIBER CANT STRIP SET IN BITUMEN ROOF NOTE: 110 MPH WIND VELOCITY RATED ASSEMBLY PIPING ROOF PENETRATION DETAIL AIR HANDLING UNIT ////// / / / / / //// VIBRATION SPRING TUBULAR STEEL CURB BASE 4" RIGID FIBERGLASS INSULATION (BY HVAC CONTRACTOR) 2 LAYERS 5/8" DURO-ROCK (BY HVAC CONTRACTOR) DET# FLOOR (SEE ARCHITECTURAL) FLOOR FRAMING (SEE ARCHITECTURAL) CEILING FRAMING (SEE ARCHITECTURAL) BATT INSULATION SHALL BE IN CONTACT WITH DUCT INSULATION ON ALL DUCT SURFACES AT ALL POINTS. (SEE ARCHITECTURAL) 21� DET# RUBBER PAD (BY HVAC CONTRACTOR) STEEL CHANNEL (FLOATING) WEATHER SEAL (FLEXIBLE) REMOVABLE GALVANIZED STEEL SPRING ACCESS PANEL • WOOD NAILERS MEMBRANE ROOFING (BY ROOFING CONTRACTOR) CANT STRIP (BY ROOFING CONTRACTOR) 2" RIGID BOARD INSULATION (BY ROOFING CONTRACTOR) ACOUSTIC UNIT ROOF CURB DETAIL HEATING/COOLING DUCT C-CLAMP (TYPICAL) /'////////////%//////////////i BATT INSULATION IN ALL JOIST J CAVITY (SEE ARCHITECTURAL) - SPACES AND CAVITY. (SEE CEILING (SEE ARCHITECTURAL) ARCHITECTURAL) DUCTWORK INSULATION DETAIL } IT STRAP HANGER SPOT WELD ANGLE TO STRUCTURAL STEEL STRUCTURAL STEEL OR BUILDING STRUCTURE j TRAPEZE HANGER NOTES: 1. FOR STRAP AND TRAPEZE HANGER SIZE, REFER TO SMACNA DUCT STANDARDS. 2. NO POP RIVETS ALLOWED; USE SELF -TAPPING SHEET METAL SCREWS ONLY. 3. COORDINATE WITH STRUCTURAL. 4. REVIEW SEISMIC SECTION OF SPECS FOR ATTACHMENT. DUCT HANGER DETAIL (LOW VELOCITY) NTS NTS NTS NTS E EDE, INC. MEP/FP ENGINEERS 1185 Washington St. Suite 4 West Newton, Ma. 02465 Tel. (617)-969-7700 Fax. (617)-969-7709 E-Mail. ede@edemep.com COPYRIGHT 2015-EDE Inc ©ALL RIGHTS RESERVED Project #: 4017 w UD O 0_ CC W ArchitectureSite PROGRESS SET 00 N SCALE: PROJECT#: SALEM, MASSACHUSETTS 01970 MAR 22,2019 BUILDING PERMIT SET URBAN SPACES L.L.C. & DIAMOND & SINACORI L.L.C. 0 a) DRAWING TITLE: REGISTRATION: DRAWING #: 246 Walnut Street O CO O co -41 (A -C 0 U) co co a) c 0 a) z NTS 1-1 U) II I W 0 X CO CO CO 00 Ln CO 617 . 581 . 6601 ©TISE DESIGN ASSOCIATES, INC 2019 22 AIR HANDLING UNIT EXTEND TO AND TERMINATE OVER NEAREST DRAIN: SLOP LINE 1/8 INCH VERTICAL TO ONE FOOT HORIZONTAL AHU DRAIN CONNECTION SHORT NIPPLE I II 2" MIN. MIN. DROP 2" \\ NOT LIESS THAN TOTAL FAN SP +2" FULL SIZE OF AHU DRAIN CONNECTION. MINIMUM SIZE 1 1/4" INCH. TYPICAL AIR HANDLING UNIT CASING DRAIN DETAIL WATERPROOF FLEXIBLE VIBRATION ISOLATION SEALANT RIGID INSULATION PER SPECIFICATION. COVER WITH EPDM MEMBRANE FOR WEATHERPROOF SEAL COMPLETELY AROUND DUCT WATERPROOF ALL SEAMS AND ' JOINTS IN DUCTS (TYPICAL) SEE DUCT PENETRATION THROUGH ROOF DETAIL FLANGE, WATERPROOF AND MECHANICALLY FASTEN DUCT TO HVAC UNIT NOTE: 1. RATED FOR 110 OR 120 MPH WIND SPEED DET# RECTANGULAR DUCT AND ROOFTOP UNIT IS SHOWN BUT THE DETAIL APPLIES TO ANY SHAPE, EQUIPMENT OR ORIENTATION HVAC UNIT SEAL ALL DUCT WALL PENETRATIONS AT POINTS OF SUPPORT ATTACHMENT AND REINFORCEMENT ATTACHMENT SUPPORT DUCT PER ROOF -MOUNTED DUCT SUPPORT DETAIL. ELEVATE DUCTWORK TO MEET THE FOLLOWING CRITERIA (TYPICAL FOR ALL ROOFTOP DUCTWORK) WIDTH OF DUCT HEIGHT ABOVE ROOF UP TO 24" 14" 25" - 36" 18" ROOFTOP DUCT INSULATION DETAIL STORM -PROOF LOUVER CAULK ALL AROUND NTS DET# NTS /14/ NOTE: PIPING SIZED AS PER MANUFACTURER'S RECOMMENDATIONS WITH CONSIDERATIONS FOR DISTANCE OF PIPING AND HEIGHT OF RISERS. SIGHT GLA30 SOLENOID VA (TXV) THERMOST EXPANSION VALVE EVAPORATOR COIL SEE NOTE UP 1/2" BIRDSCREEN 12" DEEP LOUVER PLENUM INSULATE ALL EXPOSED PARTS W/ 2" RIGID BOARD INSULATION (ALSO INSULATE UNUSED LOUVER AREA) ACCESS DOOR HALF HEIGHT OF DUCT, 12" X 12" MIN (UNLESS SHOWN OTHERWISE ON PLANS) SOLDER BOTTOM JOINT & UP 12" — PITCH TO OUTSIDE SEAL AND CAULK ALL AROUND NOTE: WHEN "D" IS OVER 24" PROVIDE 3/4" DRAIN AT 5'-0" CENTERS 6" FROM LOUVER WITH TRAP LOUVER CONNECTION ROOF—N LIQUID LINE SUCTION RISER CONDENSING ‘-N_ GLOBE VALVE (TYP FOR 2) J-� FILTER/DRYER "P" TRAP SPLIT SYSTEM PIPING DETAIL ACCU AT ROOF 01-54 AIR COOLED CONDENSING UNIT NTS \\\\\\\\\\ NTS EQUIPMENT VIBRATION ISOLATION MOUNT (RESTRAINTS) AND CURBS SHALL BE SELECTED FOR 120 MPH WINDS. RAISED CANTE ROOF EQUIPMENT SUPPORT CURB (SIMILAR TO CAMBRIDGEPORT MODEL R.C.) RATED FOR 110 MPH WINDS EXTERIOR ROOF EQUIPMENT SUPPORT TO BE FURNISHED BY HVAC CONTRACTOR. INSTALLED AND FLASHED BY GENERAL CONTRACTOR. COUNTER FLASHING BY HVAC. EXTERIOR ROOF EQUIPMENT SUPPORT WITH EQUIPMENT EXTERIOR EQUIPMENT SUPPORT DETAIL NTS XXX E EDE, INC. MEP/FP ENGINEERS 1185 Washington St. Suite 4 West Newton, Ma. 02465 Tel. (617)-969-7700 Fax. (617)-969-7709 E-Mail. ede@edemep.com COPYRIGHT 2015-EDE Inc ©ALL RIGHTS RESERVED Project #: 4017 w UD 0 Iz CC W ArchitectureSite PROGRESS SET 0 C\J 0 J_ SCALE: PROJECT#: SALEM, MASSACHUSETTS 01970 MAR 22,2019 BUILDING PERMIT SET URBAN SPACES L.L.C. & DIAMOND & SINACORI L.L.C. C DRAWING TITLE: REGISTRATION: DRAWING #: 246 Walnut Street 4- CO CO � r C1 CO O • c N cr U CD co 2(D • co 0 a Z co NTS U) II E U ©TISE DESIGN ASSOCIATES, INC 2019