UTS Job 23418 Report 23 Compressive Strength Report - Concrete 07-26-2019 (003)-Page 1
5 Richardson Lane, Stoneham, MA 02180 781-438-7755 (Voice) 781-438-6216 (Fax)
Report Date 07-26-2019Compressive Strength Report - Concrete
Report No.23
Distribution Copy Job Number 23418
Project Halstead Salem Station, 72 Flint Street
Salem, MA
Contractor Fulcrum Associates
Concrete Co.J.G. MacLellan
ALL FIELD TESTS DONE ACCORDING TO ASTM:C-172 C-31 C-143 C-1064
C-39 C-1231ALL COMPRESSIVE STRENGTH TESTS DONE ACCORDING TO ASTM:
CLASS CONCRETE:3000# 3/4"No. Of Sets:1 27CUBIC YARDS:
SET 1 LOCATION:Wall; Building 2, Column lines L at 7
Total Unit
Lab Size Area Date Date Age Load Load Fracture
No.(in.)(sq. in.)Condition Cast Tested Days (lbs.)(psi.)Type
V747 4.00 x 8.00 12.57 Good 07/26/19 08/02/19 7 30,000 2,390 1
V748 4.00 x 8.00 12.57 Good 07/26/19 08/09/19 14 43,000 3,420 1
V749 4.00 x 8.00 12.57 Good 07/26/19 08/23/19 28 54,000 4,300 2
V750 4.00 x 8.00 12.57 Good 07/26/19 08/23/19 28 53,000 4,220 3
V751 4.00 x 8.00 12.57 Good 07/26/19 08/23/19 28 48,000 3,820 1
Slump (in.)5 3/4
Air Temp. (F.)80
Conc Temp (F)86
Truck No.233
Ticket No.9211
Time 1:50
Unit Wt lbs/cu ft
Air Content (%)
GENERAL REMARKS:Cylinders received on 07/30/19.
Inspector Premium Travel
Name Time Hours Time
M. Chace No
REVIEWED BY:Bryan M. Crabtree
FRACTURE TYPES
Type 1 Type 2 Type 3 Type 4 Type5 Type 6
Reasonably well-formed Well-formed cone on Columner vertical Diagonal fracture Side fractures at top Similar to Type 5
cones on both ends,one end, vertical cracks cracking through with no cracking or bottom (occur but end of
less than 1 in.running through caps,both ends, no through ends; tap commonly with cylinder is
[25 mm] of cracking no well-defined cone well-formed cones with hammer to unbonded caps)pointed
throught caps on other end distinguish from
Type 1
Our reports are available in PDF form via email. Please email us at reports@utsofmass.com for more information.
Page 2
5 Richardson Lane, Stoneham, MA 02180 781-438-7755 (Voice) 781-438-6216 (Fax)
Report Date 07-26-2019Compressive Strength Report - Concrete
Report No.23
Distribution Copy Job Number 23418
Project Halstead Salem Station, 72 Flint Street
Salem, MA
Contractor Fulcrum Associates
Concrete Co.J.G. MacLellan
cc:Fulcrum Associates Bob Levesque
Fulcrum Associates Brad Scott
Fulcrum Associates Darrin Standish
DMS Design Sid Silveira
DMS Design Dan Skolski
City of Salem Steve Cummings
Veitas & Veitas Linas Dabrila
DSF Group Paul Bowie
DSF Group Benjamin Greene
Fulcrum Group Patricia Dwyer
UTS Matt Chace
Page 3
5 Richardson Lane, Stoneham, MA 02180 781-438-7755 (Voice) 781-438-6216 (Fax)
Report Date 07-26-2019Compressive Strength Report - Concrete
Report No.23
Distribution Copy Job Number 23418
Project Halstead Salem Station, 72 Flint Street
Salem, MA
Contractor Fulcrum Associates
Concrete Co.J.G. MacLellan
FIELD SUMMARY REPORT
Total Pour:Wall; Building 2, Column lines H.8 at 2 - J.6 at 8
Method of Placement:Pump Chute Discharge Bucket OtherX
Other:
Vibrator OtherMethod of Concrete Consolidation:X
Other:
Cylinder Fabrication Location:Truck Discharge Chute End of Pump HoseX
Cylinder Storage:Curing Box Thermal Blanket Hay/Straw Trailer FieldX
Other
Placement Protection:Thermal Blankets Heat NoneX
Other
Slump Specification (in.)4-6
Number of slumps out of specification reported to
If rejected
Approved by
Remarks: