wug of 'Stttem, assarljusetts
dire Ocpartttuni Bradgaarirra
February 6. 1975
James F. Brennan, Chief Rel J, J. Welch & Sons
Salem Fire Dept. . Front St. Restoration
Sirs 12-16-Front Street
As a result of an inspection conducted at 2190 P.M. this date of the
above construction area, the following recommendations are made which
will be in the interest of fire prevention and required to comply
with the code prior to certification by this office.
1. It is to be noted for the record that this office was requested
at the Noon hour to make an inspection of this new restoration
area for an approval of same. While it is our policy due to a
lack of experienced specialists in this office, to request an
appointment for said inspections at least 48 hours in advance,
I did provide this inspection on short notice, because I was told
it would create a hardship on the developers if not done immediately.
and the work was completed.
2. Upon inspection I found the following work was not done as noted$
a. Sprinkler systems
1. No notice for proper test has been received from the installer.
This is a requirement of the various codes.
2. The plans were approved on Dec. 17, 1974, which it shallbe
noted was long after the construction began.
3. Upon inspection I find no electric bell in place for sprinkler
alarm notification. ( The water motor gong requirement has
been eliminated as a deviation rec_uest for aesthetic reasons. )
4. The fire department connection appears in proper order, but
no test could be madeq because of advance notice lacking and
it was found that an opening was still existing on this supply
line in the basement. This would have flodded the basement
if used.
3. The supply side pressure gage on the O. S, & Y valve was not
working because it lacked a plug on the piping.
6. No pressure gage is installed at the inspectors pipe on the
third floor. This shall be installed on the system side of
the valve to show the static pressure at the high p6int and
the residual pressure upon a flow test. This shall be a per-
manant part of the system.
7' In the center stairwell between the second and third floor,
one sprinkler head was installed at a point directly in the
path of the partition. This necessitated the sheet rock being
_gut out which left an opening in the wall and will also
make the head deficient in operation.
8. It is also to be noted that the sprinklers are to remain
behind the lowered ceiling tiles. This was not approved as
part of the installation by this office. The subsequent
samples submitted to this office latter in the afternoon
i
Inspection report of Welch Properties 12-18 Front St. Page #2.
8i ..Continued:
were manufactured by Preferred Plastics Inc. and the data
sheets attached did not show this product to have an under-
writer of factory mutual approval for use below sprinklers.
Upon further investigation in my office I can not find this
company or product listed as approved in my copies of the
Building Materials Directory, This material to be .acceptable
under sprinklerso must therefore be certified by some testing
labatory in writing for acceptance by this office,
3. It has been found that the stairways to the third floor are open
from the second floor and it is hereby requested of the building
inspector to check for proper classification of the stairwell doors.
$. As of this date certain areas have been occupied prior to approval.
i On the first floor a clothing shop has occupied one section.
On the second floor a suite has been occupied by an attorneys
office and also an architect and others.
5. Carpeting has been installed in the second floor corridors and
the offices as well as the Hardiman dress shop, without any
certification as to the flame spread and smoke contribution. .
Said certification shall be made by the installers of the carpeting
as required by code.
6. An appointment has been made with Mr. Vini Amanti to re-inspect
for approval the sprinkler systemo at 200 P.M. on Monday Feb.
4 log 1975.
7. The Boiler room door is off its hinges and no emergency lights exist.
Re pectf ly subm' tted, `
ieut. David J. / ogg' "
I Salem Fire Mars. al
ccs Building Insp. Powers
Mayor Jean A. Levesque
J.J. Welch & Sons.
City Electrician Condon.
Itnama Associates Inc.
WOODMAN INSURANCE AGENCY, INC.
221 ESSEX STREET SALEM, MASSACHUSETTS 01970
)—(l
EDWARD R.CARROL:L -e1cphone
EDWARD R.C:ARROU-JR. ?+ 7442557
October 25 , 1983 ON 26 1983
SALEM PLANNING DEPT. I
Mr. Greg Senko
Planning Board ,
City of Salem "`'
One Salem Green
Salem, MA 01970 Q, �ii�l� . ✓
Re: Toy Emporium Co. LTD 1 11rt10` r,0-
Bond #06S86093BCA & v U
Bond #06S86111BCA �
Dear Mr. Senko: 0
The above has been out of business for some time.
Would you kindly respond releasing the City's interest in the
two Sign Permit Bonds mentioned above. This will allow us to
process cancellation of these bonds.
Thank you for your cooperation.
Sincerely,
WOODMAN INSURANCE AGENCY, INC.
Edward R. Carroll, Jr.
ERCj
COMMONWEALTHOF MASSACHUSETTS
CITY/` @Wi- OF S A L E M
APPLICATION FOR CERTIFICATE OF INSPECTION
Date 7-5-79 ( ) Fee Required (Amount )
( ) No Fee Required
In accordance with the provisions of the Massachusetts State Building
Code , Section 108 ,15 , I hereby apply for a Certificate of Inspection for .
the below-named premises located at the following address :
Street and Number 24 Front Street
Name of Premises Kate Hardiman
Purpose for Which Premises is Used women' s apparel
License( s ) or Permit ( s ) Required for the Premises by Other Governmental
Agencies :
License or Permit Agency
,
Certificate to be Issued to Kate Hardiman
Address 24 Front Street, Salem, MA
Owner 'of Record of Building Welch Family Trust
Address 8 Front Street, Salem MA
Name of Present Holder of Certificate same
Name of Agent , if any
SIGNATURE OF PERSON TO WHOM TITLE
CERTIFICATE IS ISSUED OR HIS
AUTHORIZED AGENT
DATE
INSTRUCTIONS :
1 ) Make check payable to : CITY OF SALEM
2 ) Return this application with your check to : John B. Powers, Inspector of
Buildings, City Hall Annex, One Salem Green, Salem, Massachusetts 01970
PLEASE NOTE :
1 ) Application form with accompanying fee must be submitted for each build-
ing or structure or part thereof to be certified.
2 ) Application and fee must be received before the certificate will be issued .
3 )' The building official shall be notified within ten ( 10) days of any change
in the above information.
CERTIFICATE N EXPIRATION DATE :
FORM SBCC-3-74
PERIODIC INSPECTION INFORMATION SHEET
Instructions: This information sheet is not an inspection checklist. Each time
a permanent file card is typed for a new building or a new card for an old build-
ing, this information sheet can be prepared by the building inspector as a work
sheet from which the file card can be typed. The items of information on this
sheet are identical to the items on the file card. If all the information on this
sheet cannot be entered on the file card, this sheet should be filled out and
not discarded.
Street and Number 24 Front Street
Name of Premises Kate Hardiman
Other Licenses or Permits Required NONE
Owner of Record of Building Welch Family Trust
Address 8 Front Street, Salem, MA
Certificate to be Issued to Kate Hardiman
Address
Use Group Classification Purpose Used woman's apparel
Public or privateublic
Number of Stories 3 Class of Construction woodDate Erected 1850
Certified Capacity (By Story or Type)
Number of Rooms - Hospitals, Schools, Hotels (By Story or Type)
Number of Dwelling Units Per Story NONE
Emergency Lighting System WET
Means of Detecting and Extinguishing Fire Sprinkler System
Fire Alarm System through Automatic Sprinkler
Number of Elevators NONE
How Heated forced hot water
Boiler or Other Heating Apparatus boiler
How Lighted gas How Ventilated flue
Place of Assembly: Yes—No X Purpose Used Commercial
In Which Story first
Standard Booth Installed Location
Fixed Seating NONE
Number of Aisles and Width of Each
Fire Resistance of Curtains or Draperies
Number of Sanitaries 1 Location Adiacent
Number of Grade Floor Means of Egress Doorways two
Number of Separate Stairways Accessible Per Story three
Number of Approved Independent Exitways Per Story, three
Remarks:
Date Certificate Issued Date Certificate Expires
Date Orders Issued Date Orders Complied
Inspector Date
FORM SBCC-1-74
1
• w�T,.coew,�t
e 6p��u OF FA^F
u�♦'�+rruc ca�� ��Uri O tnpa
CITY OF SALEM HEALTH DEPARTMENT U `l7
$aIeBOARD MassaOchuset�ts 011970 CITY
of.. L`r AC {d SS
' ROBERT E. BLENKHORN 9 NORTH STREET
HEALTH AGENT August 7, 1987
(617) 741-1800
Ms. Deborah Spillane
Copley Investments /
Suite 417 (6/
One Salem Green I
Salem, MA 01970 I�'
Dear Ms. Spillane,
This letter is a clearification of the July 27, 1987 Building Inspector's
Department correspondence (see enclosed) . On Friday July 24, 1987 Robert E.
Blenkhorn, Health Agent, and William Burke, R.S. , met with a member of the
building Inspector's Office for a site assessment of the airconditioning unit
located on Front Street. Mr. Blenkhorn stated that the noise was not ex-
cessive; however, the large fan was not operating during the time of ob-
servation.
The Health Department requests anon site meeting with you and any other
individuals you feel necessary to get the whole scope of the problem.
The Health Department appreciates your cooperation in this matter.
If you have any questions feel free to contact this office. at 741-1800.
FOR THE BOARD OF HEALTH
t'
R0OB E. BLENKHORN, C.H.O.
HEALTH AGENT
cc: Building Inspector's Office
Lenard O'Leary, Councillor
Steve Jepsky, 20 Central Street, Apt. 408,
Salem, MA 01970
Alfred Cicconi, 10 Newbury Street, Boston, MA 02116
Ctu of
Gam.
3 �ublir Properfu Pepartuieut
rl' uillitiq epurtmetlt
(nnr nlrm (4rern
743-0213
William H. Munroe
Director of Public Property Maurice M. Martineau, Asst Inspector
Inspector of Buildings Edgar J. Paquin, Asst Inspector
Zoning Enforcement Officer John L. LeClerc, Plumbing/Gas Insp.
July 27, 1987 Dc ��
EAUG 6 1987
Leonard F. O'Leary, President
City Council Ll . t OF SALEM
93 Washington St. HEALTH DEPT.
Salem, MA 01970
A RE: Central Plaza
Dear Councillor O'Leary:
In response to the attached Order this Department, accompanied
by Robert E. Blenkhorn, Health Agent, investigated the complaint. ' In
Mr. BlenkhornIs professional opinion the-noise emitted by this unit does
not constitute noise polution and the complaint would not appear to be
inforceable.
Respectfully,
William H. Munroe
Director of Public Property
WHM:bms
cc: Ms. Deborah Spillane
Copley Investments
i Suite 417.
One Salem Green
I. Enclosure: ( 1 )
i
CERTIFICATE DATA
EXPIRES ISSUED CERTIFICATE NO. INSPECTOR
Change Usel 6 2/80 48-80 Mansur
Occupancy
'- ' ORDERS •
ISSUED COMPLIED ISSUED COMPLIED
19 19 19 19
19 19 19 19
19 19 19 19
REMARKS
STREET & NUMBER 16 Front St. DATE
OTHER LICENSES OR PERMITS REQUIRED
OWNER OF RECORD OF BUILDING Welch Family Trust
ADDRESS 8 Front St. , Salem, MA.
CERTIPICATE ISSUED TO Toy Emporium Company Ltd.
ADDRESS 16 Front St. , Salem, MA
NAME OR ADDRESS I JAN FEB MARAPR MAY JUN I JUL JAUG SEP OCT NOV DEC USE YEAR
16 Front St. (The Toy Emporium Co. , Ltd.) M 80
P 16 Front Street (Toy Emporium Co, Ltd.) I M 80 -1
NAME OR ADDRESS I JANI FEOMAqAPRIMAY[JUNIJULl AU SEP OCT NI OEC USE YEAR
PURPOSE USED toy store
PROVIDE THE FOLLOWING INFORMATION AS APPLICABLE
# OF STORIES 3 CLASS OF CONSTRUCTION masonry wood DATE ERECTED 18550
CERTIFIED CAPACITY: (BY STORY OR TYPE)
Toy Store-30-First Floor
NUMBER OF ROOMS - HOSPITALS, SCHOOLS, HOTELS: (BY STORY OR TYPE)
NUMBER OF DWELLING UNITS PER STORY
• FORM SBCC-274 •
EMERGENCY LIGHTING SYSTEM WET
MEANS OF DETECTING AND EXTINGUISHING FIRE Sprinkler System
# OF ELEVATORS NONE
HOW HEATED forced hot water
BOILER OR OTHER HEATING APPARATUS boiler
HOW LIGHTED gas HOW VENTILATED flue
PLACE OF ASSEMBLY: YES NO X
PURPOSE USED
IN WHICH STORY first
STANDARD BOOTH INSTALLED LOCATION
FIXED SEATING NONE
# OF AISLES AND WIDTH
FIRE RESISTANCE OF CURTAINS OR DRAPERIES
# OF SANITARIES 1 LOCATION Adjacent
# OF GRADE FLOOR MEANS OF EGRESS DOORWAYS two
# OF SEPARATE STAIRWAYS ACCESSIBLE PER STORY three
# OF APPROVED INDEPENDENT EXITWAYS PER STORY tree
Vilols Associates
Arcnilecis/Planners
!230 Sailer Office Building --
20slon, MA 02115
617-482-!990 - 7
Q n!t f
V. Victors Vitcls. AIA U
Liviu Brill. Ala
Marquis G. Major, AIA CII;
Bailey S. Silbert, AIA orif'�O'
William B. Fitzpatrick
In Mellon
H. Martin Stockman
Hirosm Yoneyama
October 14 , 1987
THE WELCH GROUP , INC .
15 Front Street
Salem, MA 01970
ATTENTION : Bob Cervone
Al Valley
Dear Sirs:
Enclosed please find a letter from Rona Associates
outlining their suggestions regarding structural
issues on Essex Court,,specifically column base
plate repairs , cold weather concreting and
structural steel inspection. These last two issues
are addressed in detail in the Specifications , under
Division 3 and 5 respectively.
As far as the base plate repairs are concerned,
these should be undertaken as soon as possible,
before further loads are applied, and ought to be
completed - subject to the approval of the Architect
and Engineer - before any concrete slabs are poured
on the Essex Street building.
Please forward your proposals for repair to me and
to Rona Associates as soon as possible . If you have
any further questions regarding these matters ,
please let me know.
Sincerely ,
VITOLS ASSOCIATES
Denise Carcia
CC: Richard Ness
Stanley Sidney
Rona Associates
Bill Monroe , Building Inspector
Thomas Rona Associates, Inc.
Consulting Engineers Thomas S. Rona
711 Boylston Street Roger J. Hobeika
Boston. Massachusetts 02116 Karl A.Anderson
(617) 536--9800
October 9 , 1987
Vitols Associates , Architects/Planners
1230 Statler Office Building
Boston, MA. 02116
Attn: Ms . Denise Garcia
Dear Denise :
This letter adresses structural issues outstanding as of
October 7 , 1987 .
1) Grout at column base plates : under ,no_ circumstances should
the -thickness,-of-grout-under-said base. plates exceed the
�3/4' specified in-.�:dr_aw,� gs . In the future, The Welch
Group should have sufficient leveling plates at the site to
use in compensation of errors of elevations of tops of
footings .
For_ hbase plates already�set[on—more than 3/4" of grout-an
on wd
hiccolumns have been erected,tThe_Welcti Group is re-
quested-to -submit proposals fon reDairlsub7ect to the ap- '.
proval of the architect and the engineer.
2) Cold Weather Concreting: the project specifications , divi-
sion 3, section 03310 treats procedures for pouring conn-
crete in cold weather conditions . Said section generally
refers to ACI Code requirements .
3) Structural_,Steel Inspection: uality control of structural
steel is treated _qted in division 5 , section 015120 . More , 1
specifically, moment connections should be tested as per
Massachusetts Building Code requirements using ultrasonic
testing. Bolted connections should-be_tested according to
.the latest edition of the -AISC-Code as specified- in- the
chapter -entitled Strutural Joints Using ASTM A325-_or.
�—A490 Bolts _
I trust these issues are now resolved to your satisfaction.
Should you have further inquiry, please inform me as soon as
possible .
Respectfully,
irmando Castro
AC/ac
ARCHITECT ' S SITE INSPECTION REPORT
PROJECT: Essex Court Condominium, Salem, MA
ARCHITECT: Vitols Associates
CLIENT/OWNER: Essex Court Development Corp.
CONTRACTOR: The Welch Group
OFFICE NUMBER: 8631
DATE: 10/14/87 INSPECTED BY: Denise Garcia
ATTENDING : Richard Ness, Stanley Sidney, Victor Vitols , Elliott
Steinberg , Bob Cervone , Al Valley, Armando Castro
WEATHER CONDITIONS : Sunny, 60 ' s
EQUIPMENT ON SITE: One steel erection crane
OBSERVATIONS :
1 . Last 3 '-0 " portion of strip footing @ 5-line adjacent to
elevator #2 - unsuitable fill beneath has been chased out.
Concrete to be poured (Friday) to within 3 " of bottom of
footing and remaining cavity packed with grout.
2 . Well point system on around pump chamber in courtyard -
re-excavation to begin when water table has dropped
sufficiently (el . 2 '-0 " - 3 '-0 " ) . Elliot Steinberg to
supervise stabilizing of footing @ D-12 and resetting of pump
chamber to proper elevation.
3 . Steel erection: structural steel up to 5th level on Essex
St. building . Bar joists tack welded to level 2 , and metal
decking in place.
4 . Underslab drainage system - PVC piping being installed in
last portion of link building , to approximately P-line.
SIGNED :
COPIES TO: Richard Ness , Real Estate Development Group, Inc.
Bill Monroe, Salem Building Department
VITOLS ASSOCIATES 482-1990