Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
PE STAMPED THERMAL CIRCUITS CALC AREA 1 10-13-17
EBACHER FIRE PROTECTION MA LICENSE SC 210058 40 PORTSMOUTH ROAD AMESBURY, MA 01913 978-388-4086 Job Name : THERMAL CIRCUITS COMPILED A1 Building : ONE TECHNOLOGY WAY Location : SALEM, MA 01970 System : 1 Contract : Data File : THERMAL CIRCUITS COMPILED 10-11-17 CALC Area 1.WXF Computer Programs by Hydratec Inc. Revision: 50.53.1 EBACHER FIRE PROTECTION Page 1 THERMAL CIRCUITS COMPILED A1 Date 10-11-17 HYDRAULIC CALCULATIONS for Project name:THERMAL CIRCUITS COMPILED Location:SALEM, MA 01970 Drawing no:ONE TECHNOLOGY WAY Date:10-11-17 Design Remote area number:1 Remote area location:FACTORY AREA UPPER LEFT SIDE Occupancy classification:LIGHT MANUFACTURING - CONTRACT DOCUMENTS Density:0.2 - Gpm/SqFt Area of application:1598 - SqFt Coverage per sprinkler:120 - SqFt Type of sprinklers calculated:UPRIGHT No. of sprinklers calculated:16 In-rack demand: - GPM Hose streams:250 - GPM Total water required (including hose streams):691.425 - GPM @ 82.4213 - Psi Type of system:WET Volume of dry or preaction system: - Gal Water supply information Date:04-26-17 Location:BUILDING AT SITE Source:HAYES ENGINEERING, INC. Name of contractor:EBACHER FIRE PROTECTION Address:MA LICENSE SC 210058 / 40 PORTSMOUTH ROAD / AMESBURY, MA 019 Phone number:978-388-4086 Name of designer:R. LARKIN Authority having jurisdiction:SALEM FIRE DEPARTMENT Notes: (Include peaking information or gridded systems here.) Computer Programs by Hydratec Inc. Revision: 50.53.1 EBACHER FIRE PROTECTIONPage 2 THERMAL CIRCUITS COMPILED A1Date 10-11-17 10203040E50R60U70S80S90E100R110P120130140150200 400 600 800 1000 1200 1400 1600 1800FLOW ( N ^ 1.85 )City Water Supply:Demand:C1C2C1 - Static Pressure : 90 C2 - Residual Pressure: 88 C2 - Residual Flow : 1403 D1 - Elevation : 6.787 D2 - System Flow : 441.425 D2 - System Pressure : 82.421 Hose ( Demand ) : 250 D3 - System Demand : 691.425 Safety Margin : 7.039 D1D2D3Water Supply Curve CComputer Programs by Hydratec Inc. Revision: 50.53.1 EBACHER FIRE PROTECTION Page 3 THERMAL CIRCUITS COMPILED A1 Date 10-11-17 24 75.1 73.1 158.5 160.1 54 54 441.4 441.4 441.4 441.4 101 102 103 104 105 L7 L6 L5 L4 L3 L2 L1 106 107 R1 WP1 TOR BOR BASE UG1 UG2 UG3 TEST 49.3 101.8 104 213.3 106.8 54 54 441.4 441.4 441.4 441.4 25.3 109 102 28.7 57.8 171.1 281.3 387.4 105 110 111 R7 R6 R5 R4 R3 R2 R1 57.8 114.1 228.1 334.6 27 82.1 112 113 114 115 L6 54.3 54.5 |158.5 27.6 57 | 115 116 117 R6 | 57 | | 27.2 82.3 | 118 119 120 121 L5 54.5 54.8 27.6 57 121 122 123 R5 57 28.6 26.6 56.3 124 125 126 127 128 R8 R7 57.4 56.3 56.3 30.9 126 L8 L7 30.9 53.2 53.2 L4 129 130 R4 53.2 |160.1 |281.3 |53.3 53.3| L3 131 132 R3 53.3 |106.8 |334.6 |52.8 52.8| L2 133 134 R2 52.8 Flow Diagram Computer Programs by Hydratec Inc. Revision: 50.53.1 EBACHER FIRE PROTECTIONPage 4 THERMAL CIRCUITS COMPILED A1Date 10-11-17 Fitting Legend Abbrev. Name ½ ¾ 1 1¼ 1½ 2 2½ 3 3½ 4 5 6 8 10 12 14 16 18 20 24 B NFPA 13 Butterfly Valve 0 0 0 0 0 6 7 10 0 12 9 10 12 19 21 0 0 0 0 0 E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow G NFPA 13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 T NFPA 13 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 6071 81 91 101 121 Zac Ames 2000SS Fitting generates a Fixed Loss Based on Flow Unit Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Fittings Used SummaryComputer Programs by Hydratec Inc. Revision: 50.53.1 EBACHER FIRE PROTECTION Page 5 THERMAL CIRCUITS COMPILED A1 Date 10-11-17 Node Elevation K-Fact Pt Pn Flow Density Area Press No.Actual Actual Req. 101 15.67 5.6 18.37 na 24.0 0.2 120 7.0 102 15.67 20.52 na 103 15.67 5.6 21.13 na 25.74 0.2 120 7.0 104 15.67 5.6 22.81 na 26.74 0.2 120 7.0 105 15.67 26.44 na L7 14.67 28.47 na L6 14.67 28.5 na L5 14.67 28.57 na L4 14.67 28.68 na L3 14.67 28.75 na L2 14.67 28.77 na L1 14.67 28.78 na 106 15.67 29.26 na 107 15.67 52.18 na R1 14.67 53.53 na WP1 14.0 53.9 na TOR 14.0 65.13 na BOR 3.0 74.63 na BASE 3.0 79.5 na UG1 0.0 81.36 na UG2 0.0 81.79 na UG3 0.0 82.17 na TEST 0.0 82.42 na 250.0 109 15.67 5.6 20.44 na 25.32 0.2 120 7.0 110 15.67 5.6 26.97 na 29.08 0.2 120 7.0 111 15.67 51.04 na R7 14.67 52.5 na R6 14.67 52.54 na R5 14.67 52.62 na R4 14.67 52.74 na R3 14.67 52.93 na R2 14.67 53.19 na 112 15.67 5.6 23.21 na 26.98 0.2 120 7.0 113 15.67 5.6 23.77 na 27.31 0.2 120 7.0 114 15.67 5.6 24.7 na 27.83 0.2 120 7.0 115 15.67 27.14 na 116 15.67 5.6 27.63 na 29.44 0.2 120 7.0 117 15.67 51.1 na 118 15.67 5.6 23.53 na 27.16 0.2 120 7.0 119 15.67 5.6 23.81 na 27.33 0.2 120 7.0 120 15.67 5.6 24.74 na 27.86 0.2 120 7.0 121 15.67 27.2 na 122 15.67 5.6 27.69 na 29.47 0.2 120 7.0 123 15.67 51.17 na 124 15.67 5.6 26.17 na 28.65 0.2 120 7.0 125 15.67 5.6 26.45 na 28.8 0.2 120 7.0 126 15.67 27.71 na 127 15.67 5.6 28.17 na 29.72 0.2 120 7.0 128 15.67 51.08 na R8 14.67 52.5 na L8 14.67 28.47 na 129 15.67 29.13 na 130 15.67 51.42 na 131 15.67 29.2 na 132 15.67 51.61 na 133 15.67 29.21 na 134 15.67 51.88 na The maximum velocity is 16.04 and it occurs in the pipe between nodes 104 and 105 Pressure / Flow Summary - STANDARD Computer Programs by Hydratec Inc. Revision: 50.53.1 EBACHER FIRE PROTECTION Page 6 THERMAL CIRCUITS COMPILED A1 Date 10-11-17 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 101 24.00 1.049 T 5.0 6.780 18.367 K Factor = 5.60 to 120.0 0.0 5.000 0.0 102 24.0 0.1823 0.0 11.780 2.148 Vel = 8.91 102 25.32 1.61 0.0 7.130 20.515 to 120.0 0.0 0.0 0.0 103 49.32 0.0858 0.0 7.130 0.612 Vel = 7.77 103 25.74 1.61 0.0 9.000 21.127 K Factor = 5.60 to 120.0 0.0 0.0 0.0 104 75.06 0.1866 0.0 9.000 1.679 Vel = 11.83 104 26.74 1.61 T 8.0 3.080 22.806 K Factor = 5.60 to 120.0 0.0 8.000 0.0 105 101.8 0.3280 0.0 11.080 3.634 Vel = 16.04 105 -28.72 1.61 T 8.0 1.000 26.440 to 120.0 0.0 8.000 0.433 L7 73.08 0.1777 0.0 9.000 1.599 Vel = 11.52 L7 30.89 4.26 0.0 10.000 28.472 to 120.0 0.0 0.0 0.0 L6 103.97 0.0029 0.0 10.000 0.029 Vel = 2.34 L6 54.53 4.26 0.0 10.000 28.501 to 120.0 0.0 0.0 0.0 L5 158.5 0.0065 0.0 10.000 0.065 Vel = 3.57 L5 54.78 4.26 0.0 10.000 28.566 to 120.0 0.0 0.0 0.0 L4 213.28 0.0113 0.0 10.000 0.113 Vel = 4.80 L4 -53.18 4.26 0.0 10.000 28.679 to 120.0 0.0 0.0 0.0 L3 160.1 0.0066 0.0 10.000 0.066 Vel = 3.60 L3 -53.32 4.26 0.0 7.000 28.745 to 120.0 0.0 0.0 0.0 L2 106.78 0.0031 0.0 7.000 0.022 Vel = 2.40 L2 -52.79 4.26 0.0 13.000 28.767 to 120.0 0.0 0.0 0.0 L1 53.99 0.0009 0.0 13.000 0.012 Vel = 1.22 L1 0.0 1.61 T 8.0 1.000 28.779 to 120.0 0.0 8.000 -0.433 106 53.99 0.1014 0.0 9.000 0.913 Vel = 8.51 106 0.0 1.61 2T 16.0 210.000 29.259 to 120.0 0.0 16.000 0.0 107 53.99 0.1014 0.0 226.000 22.925 Vel = 8.51 107 0.0 1.61 T 8.0 1.000 52.184 to 120.0 0.0 8.000 0.433 R1 53.99 0.1014 0.0 9.000 0.913 Vel = 8.51 R1 387.43 4.26 0.0 1.940 53.530 to 120.0 0.0 0.0 0.290 WP1 441.42 0.0433 0.0 1.940 0.084 Vel = 9.94 WP1 0.0 4.26 T 26.334 167.200 53.904 to 120.0 5E 65.835 92.169 0.0 TOR 441.42 0.0433 0.0 259.369 11.229 Vel = 9.94 Final Calculations - Hazen-Williams - 2007 Computer Programs by Hydratec Inc. Revision: 50.53.1 EBACHER FIRE PROTECTION Page 7 THERMAL CIRCUITS COMPILED A1 Date 10-11-17 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn TOR 0.0 4.26 Fsp 0.0 11.000 65.133 to 120.0 B 15.8 28.967 7.764 * Fixed Loss = 3 BOR 441.42 0.0433 E 13.167 39.967 1.731 Vel = 9.94 BOR 0.0 4.26 Zac 0.0 6.000 74.628 to 120.0 E 13.167 13.167 4.046 * Fixed Loss = 4.046 BASE 441.42 0.0433 0.0 19.167 0.829 Vel = 9.94 BASE 0.0 6.16 G 4.304 35.000 79.503 to 140.0 T 43.037 67.425 1.299 UG1 441.42 0.0054 E 20.084 102.425 0.554 Vel = 4.75 UG1 0.0 8.27 E 28.468 310.000 81.356 to 140.0 0.0 28.468 0.0 UG2 441.42 0.0013 0.0 338.468 0.436 Vel = 2.64 UG2 0.0 8.27 G 6.326 202.000 81.792 to 140.0 E 28.468 90.148 0.0 UG3 441.42 0.0013 T 55.354 292.148 0.376 Vel = 2.64 UG3 0.0 10.28 2E 66.296 420.000 82.168 to 140.0 G 7.534 149.166 0.0 TEST 441.42 0.0004 T 75.336 569.166 0.253 Vel = 1.71 250.00 Qa = 250.00 691.42 82.421 K Factor = 76.16 109 25.32 1.61 0.0 2.870 20.444 K Factor = 5.60 to 120.0 0.0 0.0 0.0 102 25.32 0.0247 0.0 2.870 0.071 Vel = 3.99 0.0 25.32 20.515 K Factor = 5.59 105 28.72 1.61 T 8.0 8.920 26.440 to 120.0 0.0 8.000 0.0 110 28.72 0.0316 0.0 16.920 0.534 Vel = 4.53 110 29.08 1.61 T 8.0 201.080 26.974 K Factor = 5.60 to 120.0 0.0 8.000 0.0 111 57.8 0.1151 0.0 209.080 24.062 Vel = 9.11 111 0.0 1.61 T 8.0 1.000 51.036 to 120.0 0.0 8.000 0.433 R7 57.8 0.1151 0.0 9.000 1.036 Vel = 9.11 R7 56.28 4.26 0.0 10.000 52.505 to 120.0 0.0 0.0 0.0 R6 114.08 0.0035 0.0 10.000 0.035 Vel = 2.57 R6 57.03 4.26 0.0 10.000 52.540 to 120.0 0.0 0.0 0.0 R5 171.11 0.0075 0.0 10.000 0.075 Vel = 3.85 R5 57.04 4.26 0.0 10.000 52.615 to 120.0 0.0 0.0 0.0 R4 228.15 0.0128 0.0 10.000 0.128 Vel = 5.14 R4 53.17 4.26 0.0 10.000 52.743 to 120.0 0.0 0.0 0.0 R3 281.32 0.0188 0.0 10.000 0.188 Vel = 6.33 R3 53.32 4.26 0.0 10.000 52.931 to 120.0 0.0 0.0 0.0 R2 334.64 0.0259 0.0 10.000 0.259 Vel = 7.53 Final Calculations - Hazen-Williams Computer Programs by Hydratec Inc. Revision: 50.53.1 EBACHER FIRE PROTECTION Page 8 THERMAL CIRCUITS COMPILED A1 Date 10-11-17 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn R2 52.79 4.26 0.0 10.000 53.190 to 120.0 0.0 0.0 0.0 R1 387.43 0.0340 0.0 10.000 0.340 Vel = 8.72 0.0 387.43 53.530 K Factor = 52.95 112 26.98 1.61 0.0 20.000 23.212 K Factor = 5.60 to 120.0 0.0 0.0 0.0 113 26.98 0.0282 0.0 20.000 0.563 Vel = 4.25 113 27.31 1.61 0.0 9.000 23.775 K Factor = 5.60 to 120.0 0.0 0.0 0.0 114 54.29 0.1024 0.0 9.000 0.922 Vel = 8.56 114 27.83 1.61 T 8.0 3.080 24.697 K Factor = 5.60 to 120.0 0.0 8.000 0.0 115 82.12 0.2203 0.0 11.080 2.441 Vel = 12.94 115 -27.59 1.61 T 8.0 1.000 27.138 to 120.0 0.0 8.000 0.433 L6 54.53 0.1033 0.0 9.000 0.930 Vel = 8.59 0.0 54.53 28.501 K Factor = 10.21 115 27.58 1.61 T 8.0 8.920 27.138 to 120.0 0.0 8.000 0.0 116 27.58 0.0293 0.0 16.920 0.496 Vel = 4.35 116 29.44 1.61 T 8.0 201.080 27.634 K Factor = 5.60 to 120.0 0.0 8.000 0.0 117 57.02 0.1122 0.0 209.080 23.463 Vel = 8.99 117 0.0 1.61 T 8.0 1.000 51.097 to 120.0 0.0 8.000 0.433 R6 57.02 0.1122 0.0 9.000 1.010 Vel = 8.99 0.0 57.02 52.540 K Factor = 7.87 118 27.16 1.61 0.0 10.000 23.528 K Factor = 5.60 to 120.0 0.0 0.0 0.0 119 27.16 0.0285 0.0 10.000 0.285 Vel = 4.28 119 27.33 1.61 0.0 9.000 23.813 K Factor = 5.60 to 120.0 0.0 0.0 0.0 120 54.49 0.1032 0.0 9.000 0.929 Vel = 8.59 120 27.86 1.61 T 8.0 3.080 24.742 K Factor = 5.60 to 120.0 0.0 8.000 0.0 121 82.35 0.2215 0.0 11.080 2.454 Vel = 12.98 121 -27.58 1.61 T 8.0 1.000 27.196 to 120.0 0.0 8.000 0.433 L5 54.77 0.1041 0.0 9.000 0.937 Vel = 8.63 0.0 54.77 28.566 K Factor = 10.25 121 27.57 1.61 T 8.0 8.920 27.196 to 120.0 0.0 8.000 0.0 122 27.57 0.0293 0.0 16.920 0.495 Vel = 4.34 Final Calculations - Hazen-Williams Computer Programs by Hydratec Inc. Revision: 50.53.1 EBACHER FIRE PROTECTION Page 9 THERMAL CIRCUITS COMPILED A1 Date 10-11-17 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 122 29.47 1.61 T 8.0 201.080 27.691 K Factor = 5.60 to 120.0 0.0 8.000 0.0 123 57.04 0.1123 0.0 209.080 23.480 Vel = 8.99 123 0.0 1.61 T 8.0 1.000 51.171 to 120.0 0.0 8.000 0.433 R5 57.04 0.1123 0.0 9.000 1.011 Vel = 8.99 0.0 57.04 52.615 K Factor = 7.86 124 28.65 1.61 0.0 9.000 26.167 K Factor = 5.60 to 120.0 0.0 0.0 0.0 125 28.65 0.0314 0.0 9.000 0.283 Vel = 4.52 125 28.80 1.61 T 8.0 3.080 26.450 K Factor = 5.60 to 120.0 0.0 8.000 0.0 126 57.45 0.1137 0.0 11.080 1.260 Vel = 9.05 126 -30.89 1.61 T 8.0 8.920 27.710 to 120.0 0.0 8.000 0.0 127 26.56 0.0273 0.0 16.920 0.462 Vel = 4.19 127 29.72 1.61 T 8.0 201.080 28.172 K Factor = 5.60 to 120.0 0.0 8.000 0.0 128 56.28 0.1095 0.0 209.080 22.904 Vel = 8.87 128 0.0 1.61 T 8.0 1.000 51.076 to 120.0 0.0 8.000 0.433 R8 56.28 0.1096 0.0 9.000 0.986 Vel = 8.87 R8 0.0 4.26 0.0 10.000 52.495 to 120.0 0.0 0.0 0.0 R7 56.28 0.0010 0.0 10.000 0.010 Vel = 1.27 0.0 56.28 52.505 K Factor = 7.77 126 30.89 1.61 T 8.0 1.000 27.710 to 120.0 0.0 8.000 0.433 L8 30.89 0.0361 0.0 9.000 0.325 Vel = 4.87 L8 0.0 4.26 0.0 10.000 28.468 to 120.0 0.0 0.0 0.0 L7 30.89 0.0004 0.0 10.000 0.004 Vel = 0.70 0.0 30.89 28.472 K Factor = 5.79 L4 53.18 1.61 T 8.0 1.000 28.679 to 120.0 0.0 8.000 -0.433 129 53.18 0.0987 0.0 9.000 0.888 Vel = 8.38 129 0.0 1.61 2T 16.0 210.000 29.134 to 120.0 0.0 16.000 0.0 130 53.18 0.0986 0.0 226.000 22.288 Vel = 8.38 130 0.0 1.61 T 8.0 1.000 51.422 to 120.0 0.0 8.000 0.433 R4 53.18 0.0987 0.0 9.000 0.888 Vel = 8.38 0.0 53.18 52.743 K Factor = 7.32 L3 53.32 1.61 T 8.0 1.000 28.745 to 120.0 0.0 8.000 -0.433 131 53.32 0.0991 0.0 9.000 0.892 Vel = 8.40 Final Calculations - Hazen-Williams Computer Programs by Hydratec Inc. Revision: 50.53.1 EBACHER FIRE PROTECTION Page 10 THERMAL CIRCUITS COMPILED A1 Date 10-11-17 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 131 0.0 1.61 2T 16.0 210.000 29.204 to 120.0 0.0 16.000 0.0 132 53.32 0.0991 0.0 226.000 22.402 Vel = 8.40 132 0.0 1.61 T 8.0 1.000 51.606 to 120.0 0.0 8.000 0.433 R3 53.32 0.0991 0.0 9.000 0.892 Vel = 8.40 0.0 53.32 52.931 K Factor = 7.33 L2 52.79 1.61 T 8.0 1.000 28.767 to 120.0 0.0 8.000 -0.433 133 52.79 0.0973 0.0 9.000 0.876 Vel = 8.32 133 0.0 1.61 3E 12.0 213.000 29.210 to 120.0 T 8.0 20.000 0.0 134 52.79 0.0973 0.0 233.000 22.671 Vel = 8.32 134 0.0 1.61 T 8.0 1.000 51.881 to 120.0 0.0 8.000 0.433 R2 52.79 0.0973 0.0 9.000 0.876 Vel = 8.32 0.0 52.79 53.190 K Factor = 7.24 Final Calculations - Hazen-Williams Computer Programs by Hydratec Inc. Revision: 50.53.1