2017-06-01 Tech Way Pricing Set - ElectricalPOWER DISTRIBUTION LEGENDSYMBOLDESCRIPTION208Y/120 VOLT PANELBOARD, REFER TO SCHEDULE OFPANELBOARDSGROUND BARGBRANCH CIRCUIT & FEEDER LEGENDSYMBOLDESCRIPTIONBRANCH CIRCUIT HOME RUN. TYPICAL 2#12 & 1#12G IN 34"CMINIMUM. PP1-(1) INDICATES PANEL AND CIRCUIT DESIGNATIONFROM WHICH HOME RUN SHALL ORIGINATE. EACH CIRCUIT SHALLBE 20A-1P (20AMP SINGLE POLE) UNLESS NOTED OTHERWISE.PP1-(X)MOTOR & CONTROLS LEGENDSYMBOLDESCRIPTION"G" - INDICATES GENERATORMOTOR, NUMERAL INDICATES HORSEPOWERDISCONNECT SWITCH RATED 30AMP, 3-POLE, IN NEMA TYPE 1ENCLOSURE, UNLESS OTHERWISE NOTED"3R" - INDICATES NEMA TYPE 3R ENCLOSURE"2P" - INDICATES 2 POLE SINGLE PHASE DISCONNECT"30A" - INDICATES 60A SWITCHFUSED DISCONNECT SWITCH, 3-POLE, IN NEMA TYPE 1ENCLOSURE,UNLESS OTHERWISE NOTED"3R" - INDICATES NEMA TYPE 3R ENCLOSURE"60AS" - INDICATES 60AMP SWITCH"50AF" - INDICATES 50AMP FUSES30A2P30AS15AFTELECOMMUNICATIONS LEGENDALL DATA AND TELEPHONE CABLING SHALL BE BY OTHERS. ELECTRICAL DRAWINGSINDICATE RACEWAY AD BACKBOX SYSTEMS ONLY AND INDICATE TEL/DATA OUTLETCONFIGURATIONS FOR REFERENCE ONLY.SYMBOLDESCRIPTIONCOMBINATION TELEPHONE/DATA OUTLET34" PLYWOOD BACKBOARD WITH 2"x4" STUDS PLACED 16" OFFCENTERONE-LINE LEGENDSYMBOLDESCRIPTIONDISCONNECT SWITCH, FUSED"60AS" - INDICATES SWITCH SIZE"50AF" INDICATES FUSE SIZECIRCUIT BREAKER, FIXED"100AF" - INDICATES FRAME SIZE"80AT" - INDICATES TRIPCURRENT TRANSFORMERPANELBOARD"PP1" - INDICATES PANELBOARD NAMEREFER TO PANELBOARD SCHEDULES FOR ADDITIONALINFORMATIONUTILITY METERPANELPP1WIRING DEVICESSYMBOLDESCRIPTIONDUPLEX RECEPTACLE, GROUNDING TYPE, RATED 20A, 125V"#" - INDICATES CIRCUIT NUMBER (TYP FOR WIRING DEVICES)"WP" - INDICATES WEATHERPROOF (TYP FOR WIRING DEVICES)"C" - INDICATES COUNTER HEIGHT (TYP FOR WIRING DEVICES)SHADING INDICATES GROUND FAULT INTERRUPTERDOUBLE DUPLEX RECEPTACLE, GROUNDING TYPE, RATED 20A,125VFLOOR MOUNTED BOX WITH DOUBLE DUPLEX RECEPTACLE ANDTEL/DATA JACKRECEPTACLE OR DISCONNECT CORD DROP. SYMBOL INDICATESTYPE. REFER TO DETAIL FOR ADDITIONAL INFORMATIONWALL MOUNTED BOX FOR POWER CONNECTION TO PRE-WIREDFURNITURE PARTITIONSJUNCTION BOXJFIRE ALARM LEGENDSYMBOLDESCRIPTIONFIRE ALARM DEVICE"FACP" - INDICATES FIRE ALARM CONTROL PANEL"RTS" - INDICATES REMOTE TEST STATION"ACM" - INDICATES INDIVIDUAL ADDRESSABLE CONTROL MODULE"RPS" - INDICATES REMOTE POWER SUPPLYFIRE ALARM MANUAL PULL STATION"SC" - INDICATES STOPPER COVER"FIRE PROTECTION DEVICE"TS" - INDICATES TAMPER SWITCH"FS" - INDICATES FLOW SWITCH"PS" - INDICATES PRESSURE SWITCHFIRE ALARM SMOKE DETECTOR, PHOTO ELECTRIC UNLESS NOTEDOTHERWISE"ER" - INDICATES ELEVATOR RECALL),5($/$50+($7'(7(&725ƒ),;('7(03(5$785(UNLESS NOTED OTHERWISE"RR" - INDICATES RATE OF RISEDUCT MOUNTED SMOKE DETECTORFIRE ALARM NOTIFICATION APPLIANCESYMBOL LETTER:"F" - INDICATES AUDIBLE AND VISUAL DEVICE"L" - INDICATES VISUAL DEVICE ONLYOUTSIDE LETTER:"15cd" - INDICATES CANDELA VALUEXXXXFSCF15cdTYPICAL NAMEPLATE DETAILNOTES:1.REFER TO SPECIFICATIONS FOR ADDITIONAL NAMEPLATE REQUIREMENTS.2.NAMEPLATE TO BE 1/16" THICK PLASTIC WITH WHITE CENTER LAMINATION. FACESHALL BE BLACK, ENGRAVED LETTERS SHALL BE WHITE.3.SECURE NAMEPLATE TO SURFACES WITH HIGH STRENGTH ADHESIVE CEMENT.UTILIZE MECHANICAL FASTENERS FOR ALL EXTERIOR LOCATIONS.4.TYPICAL FOR "STARTERS", "DISCONNECTS", AND "TRANSFORMERS".1" 3"NOTES:1.ALL MOUNTING HEIGHTS SHALL BE MEASURED FROM FINISHED FLOOR TOCENTERLINE OF DEVICE EXCEPT EXIT SIGNS, CLOCKS, EMERGENCY LIGHTINGAND FIRE ALARM A/V DEVICES.2.DEVICES SHALL BE INSTALLED ON A COMMON VERTICAL CENTERLINE WHEREVERPOSSIBLE.3.ALL DEVICES SHALL BE INSTALLED AT MOUNTING HEIGHTS AS INDICATED ON THISDETAIL UNLESS OTHERWISE NOTED.4.STROBE HEIGHT ILLUSTRATED AT MAXIMUM HEIGHT. STROBE SHALL BE 80" AFFOR 6" BELOW CEILING, WHICHEVER IS LOWER.INTERCOMCLOCKEMERGENCY LIGHTINGEXIT SIGNOFFSWITCHESFIRE ALARM PULL STATIONWALL TELEPHONESRECEPTACLESTELEPHONE/DATA OUTLETSREFI8'-6"6'-8"ALARMFIREPULL DOWN4'-6"4'-0"1'-6"FINISHED FLOORPP1-1PP1-3GENERALPP1-3COMPUTERLABEL ALL RECEPTACLES WITHPANEL DESIGNATION ANDCIRCUIT NUMBER. LABEL SHALLBE CLEAR MYLAR. P-TOUCH TYPE.TYPICAL FLASH PROTECTION WARNING LABELNOTES:1.REFER TO SPECIFICATIONS FOR ADDITIONAL NAMEPLATE REQUIREMENTS.2.PROVIDE ON ALL IN-LINE METER SOCKETS, SWITCHBOARDS, DISTRIBUTIONPANELS, PANELBOARDS AND MOTOR CONTROL CENTERS IN ACCORDANCE WITHNEC 110.16.EQUIPMENT TYPE:GROUNDING:WORK DISTANCE:$9$,/$%/(݊%2/7('&855(17FLASH PROTECTION BOUNDARY:INCIDENT ENERGY AT 23 INCHES:PPE LEVEL:DATEY/N GROUNDEDINCHESkAINCHESFDOFPð4xx/xx/xxxxARC FLASH AND SHOCK HAZARDAPPROPRIATE PPE REQUIRED!RECEPTACLE LABEL REQUIREMENTSTYPICAL DEVICE MOUNTING HEIGHTS DETAIL225A 208Y/120VFED FROM MDPPANEL PP1FIRE ALARM AUDIO/VISUALDEVICES (MOUNTING HEIGHTMINIMUM TO BOTTOM OFSTROBE, SEE NOTE 4)GENERAL SYMBOLSDIRECTION OF VIEWSECTION NUMBERDWG NUMBER ON WHICHSECTION IS SHOWNDETAIL LETTERDWG NUMBER ON WHICHSECTION IS SHOWNEQUIPMENT SYMBOLS (REFER TO EQUIPMENT SCHEDULES)EQUIPMENT DESIGNATIONEQUIPMENT REFERENCE NUMBER (TYP)OFFOFFONONONEUH#ABBREVIATIONSA/AMPAMPERELTGLIGHTINGACALTERNATING CURRENTMCBMAIN CIRCUIT BREAKERADAAMERICAN WITH DISABILITIESACTMECMASSACHUSETTS ELECTRIC CODEAFAMPERE FRAMEMHMANHOLEAFFABOVE FINISHED FLOORMLOMAIN LUGS ONLYAFGABOVE FINISHED GRADEMTDMOUNTEDAICAMPERE INTERRUPTINGCAPACITYMTGMOUNTINGALALUMINUMNECNATIONAL ELECTRIC CODEATAMPERE TRIPNTSNOT TO SCALEATSAUTOMATIC TRANSFER SWTICH#NUMBERAWGAMERICAN WIRE GAUGEPVCPOLYVINYL CHLORIDECCONDUITPWRPOWERCATVCABLE TELEVISIONRGSRIGID GALVANIZED STEELCCTVCLOSED CIRCUIT TELEVISIONSWBDSWITCHBOARDCBCIRCUIT BREAKERTELTELEPHONECKTCIRCUITTERMTERMINALȭCENTERLINETVSSTRANSIENT VOLTAGE SURGESUPPRESSIONDWGDRAWINGTSPTWISTED SHIELDED PAIRECELECTRICAL CONTRACTORTYPTYPICALEMTELECTRICAL METALLIC TUBINGUNOUNLESS OTHERWISE NOTEDFLMTFLEXIBLE LIQUID TIGHT METALLICTUBINGUPSUNINTERRUPTIBLE POWER SUPPLYGFIGROUND FAULT INTERRUPTINGUTPUNSHIELDED TWISTED PAIRGNDGROUNDVVOLTHHHANDHOLEVAVOLT AMPEREHPHORSEPOWERVFDVARIABLE FREQUENCY DRIVEHVACHEATING, VENTILATION AND AIRCONDITIONINGWWATTHZHERTZWPWEATHERPROOFIGISOLATED GROUNDKVAKILOVOLT - AMPEREKWKILOWATT##NOTE TAGSYMBOLDEMOLITION NOTES:1.REFER TO THE ARCHITECTURAL DRAWINGS FOR THE FULL EXTENT OF THE SCOPEOF DEMOLITION. DISCONNECT AND MAKE SAFE ALL ELECTRICAL EQUIPMENTIDENTIFIED FOR REMOVAL ON THE HVAC, PLUMBING AND FIRE PROTECTION PLANS.THE ELECTRICAL SCOPE MAY EXTEND BEYOND THE AREA DEFINED BY THEARCHITECTURAL DEMOLITION LIMITS TO FULLY COMPLY WITH VARIOUSREQUIREMENTS DEFINED BY THESE NOTES.2.THE ELECTRICAL DEMOLITION PLANS AND DETAILS INDICATE THE GENERAL INTENTAND ARE NOT INTENDED TO SHOW ALL ITEMS TO BE REMOVED OR RETAINED. THEELECTRICAL CONTRACTOR SHALL VISIT THE SITE PRIOR TO THE SUBMISSION OFBIDS TO BECOME FAMILIAR WITH THE ACTUAL CONDITIONS AND EXTENT OF WORK.DEVICES AND EQUIPMENT LOCATED ON WALLS AND/OR CEILINGS TO BE REMOVEDSHALL BE DISCONNECTED AND MADE SAFE. THE ELECTRICAL CONTRACTOR SHALLNOTIFY THE OWNER'S REPRESENTATIVE OF ANY UNANTICIPATED HIDDENCONDITIONS ENCOUNTERED DURING DEMOLITION.3.THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE REPAIR OF ALLSYSTEMS OR BUILDING COMPONENTS DAMAGED DURING THE EXECUTION OF THEWORK. DAMAGE SHALL INCLUDE BUT NOT BE LIMITED TO DESTRUCTION ORDISPOSAL OF ITEMS INTENDED TO REMAIN OR TO BE SALVAGED.4.THE ELECTRICAL CONTRACTOR SHALL CIRCUIT TRACE AND LABEL ALL EXISTINGBRANCH CIRCUITS AND FEEDERS WITHIN THE AREA OF DEMOLITION SCOPE PRIORTO DE-ENERGIZING AND DISCONNECTION. ALL CIRCUITS WITHIN PANELBOARDSIDENTIFIED FOR REMOVAL SHALL BE TRACED AND LABELED TO ENSURE THAT NOAREA OUTSIDE THE DEMOLITION SCOPE LIMIT IS AFFECTED.5.THE ELECTRICAL CONTRACTOR SHALL IDENTIFY ALL BRANCH CIRCUITS, FEEDERSAND SYSTEM COMPONENTS, WHICH ARE TO REMAIN WITHIN THE AREA OFDEMOLITION SCOPE. THERE SHALL BE NO INTERRUPTION OF SERVICE TO ANY AREAOUTSIDE THE SCOPE LIMITS WITHOUT APPROVAL FROM THE OWNER'SREPRESENTATIVE. EXISTING EQUIPMENT TO REMAIN SHALL BE LEFT IN A CODECOMPLIANT MANNER.6.THE ELECTRICAL CONTRACTOR SHALL DE-ENERGIZE AND REMOVE ALLCONDUCTORS AND RACEWAYS TO THEIR POINTS OF ORIGIN WITHIN THE AREA OFDEMOLITION SCOPE. ITEMS IDENTIFIED FOR DEMOLITION SHALL NOT BE ABANDONEDIN PLACE. RACEWAYS THAT ENTER MASONRY WALLS AND FLOORS SHALL BE CUTFLUSH AT THE SURFACE FOR PATCHING BY OTHERS. ALL CIRCUIT BREAKERSASSOCIATED WITH THE DEMOLITION SCOPE SHALL BE DE-ENERGIZED AND LABELEDSPARE.7.THE ELECTRICAL CONTRACTOR SHALL TEMPORARILY SUPPORT ALL ITEMS TOREMAIN THAT ARE AFFECTED BY THE DEMOLITION OF BUILDING STRUCTURALCOMPONENTS (WALLS, CEILINGS, ETC.). TEMPORARILY SUPPORTED ITEMS SHALL BEPERMANENTLY SUPPORTED AND INSTALLED WHEN FINALIZED STRUCTURES ARE INPLACE.8.ALL REMOVED ITEMS SHALL BE LEGALLY DISPOSED OF UNLESS IDENTIFIED FORREUSE. THE OWNER'S REPRESENTATIVE SHALL INSPECT ALL RETAINED ITEMS PRIORTO PLACEMENT IN THE IDENTIFIED STORAGE LOCATION BY THE ELECTRICALCONTRACTOR.9.THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN FULLY FUNCTIONAL DURING THEENTIRE DEMOLITION AND CONSTRUCTION PERIOD. REUSE OF EXISTING FIRE ALARMSYSTEM RACEWAYS SHALL NOT BE ALLOWED. ALL REQUIRED SYSTEM SHUTDOWNSSHALL BE COORDINATED WITH AND APPROVED BY THE OWNER'S REPRESENTATIVEAND THE AUTHORITY HAVING JURISDICTION. DEMOLITION OF THE EXISTING SYSTEMSHALL NOT COMMENCE UNTIL THE NEW SYSTEM HAS BEEN COMPLETELY INSTALLED,TESTED AND APPROVED BY THE AUTHORITY HAVING JURISDICTION.10.ALL DEMOLITION SCOPE ASSOCIATED WITH LOW VOLTAGE SYSTEMS INCLUDING BUTNOT LIMITED TO TELEPHONE, DATA, SECURITY, PAGING, CCTV, ETC. SHALL BEINCLUDED IN THIS CONTRACT.11.REMOVED FLUORESCENT AND HID LAMPS AND BATTERIES SHALL BE RECYCLED BY AFACILITY APPROVED BY THE OWNER'S REPRESENTATIVE. A UNIFORM HAZARDOUSWASTE MANIFEST SHALL BE PREPARED FOR ALL DISPOSALS AND RETURNED WITHALL APPLICABLE SIGN OFF'S PRIOR TO APPLICATION FOR FINAL PAYMENT.12.ALL BALLAST IN LIGHTING FIXTURES TO BE DISPOSED SHALL BE VERIFIED TO BE PCBFREE. ALL BALLAST MANUFACTURED PRIOR TO 1979 AND NOT LABELED AS PCB FREESHALL BE CONSIDERED TO CONTAIN PCBs. PROVIDE WRITTEN VERIFICATION TO THEOWNER'S REPRESENTATIVE THAT CONFIRMS PCB FREE WASTE. WHERE PCB FREEWASTE CANNOT BE VERIFIED, BALLAST SHALL BE RECYCLED BY A FACILITYAPPROVED BY THE OWNER'S REPRESENTATIVE, WITH PCB COMPONENTSELIMINATED BY A HIGH TEMPERATURE INCINERATION. A UNIFORM HAZARDOUSWASTE MANIFEST SHALL BE PREPARED FOR ALL DISPOSALS AND RETURNED WITHALL APPLICABLE SIGN OFF'S PRIOR TO APPLICATION FOR FINAL PAYMENT. ALLHANDLING SHALL CONFORM TO EPA REQUIREMENTS. PROVIDE BREAKOUT COST FORTHIS SCOPE.LIGHTING NOTES:1COORDINATE EXACT DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH ARCHITECTPRIOR TO ROUGH-IN. ALL DEVICES SHALL BE MOUNTED IN ACCORDANCE WITH THELATEST REQUIREMENTS OF THE ACCESSIBILITY CODE.2PROVIDE COMMON FACE PLATE AND REQUIRED METAL INTERIOR BOX BARRIERSFOR ALL MULTIPLE GANG SWITCH LOCATIONS.3CIRCUIT NUMBERS ARE DIAGRAMMATIC. EXACT NUMBERS SHALL BE DETERMINED INTHE FIELD AND REFLECTED ON AS-BUILT DOCUMENTATION BY THE ELECTRICALCONTRACTOR. THE ASSOCIATED CIRCUIT NUMBER AND SWITCH LEGNOMENCLATURE THAT ARE APPLIED TO EACH LIGHTING FIXTURE AND CONTROLLINGDEVICE INFER INTERCONNECTING BRANCH CIRCUITRY.4SURFACE MOUNTED FIXTURES (INCLUDING EXIT SIGNS) THAT CREATEOBSTRUCTIONS EXCEEDING 4 1/2 INCHES FROM THE CEILING SURFACE TO THEBOTTOM OF THE FIXTURE SHALL BE SPACED A MINIMUM OF 2'6" FROM ANYSPRINKLER HEAD. COORDINATE THE EXACT PLACEMENT OF ALL FIXTURES WITH THEREFLECTED CEILING PLAN AND THE FIRE PROTECTION CONTRACTOR.5PROVIDE CONSTANTLY ENERGIZED (UNSWITCHED) BRANCH CIRCUIT TO ALL EXITSIGNS AND EGRESS LIGHTS FROM THE DESIGNATED SOURCE.6LIGHTING BRANCH CIRCUITRY SHALL BE INSTALLED IN CONDUIT FROM THEPANELBOARD TO THE FIRST OUTLET AND/OR WHERE EXPOSED. LIGHTING BRANCHCIRCUITRY MAY BE TYPE MC CABLE WHERE CONCEALED ABOVE SUSPENDEDCEILINGS OR IN METAL STUD WALLS.7MAINTAIN CONTINUITY OF BRANCH CIRCUITRY ASSOCIATED WITH ALL EXISTINGLIGHTING TO REMAIN.8CONTRACTOR SHALL VERIFY ALL DOORS SWINGS BEFORE INSTALLING SWITCHBOXES.POWER NOTES:1COORDINATE EXACT DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH ARCHITECTPRIOR TO TOUGH-IN. ALL DEVICES SHALL BE MOUNTED IN ACCORDANCE WITH THELATEST REQUIREMENTS OF THE ACCESSIBILITY CODE.2CIRCUIT NUMBERS ARE DIAGRAMMATIC. EXACT NUMBERS SHALL BE DETERMINED INTHE FIELD AND REFLECTED ON AS-BUILT DOCUMENTATION BY THE ELECTRICALCONTRACTOR. THE ASSOCIATED CIRCUIT NUMBERS THAT ARE APPLIED TO EACHDEVICE AND PIECE OF EQUIPMENT INFERS INTERCONNECTING BRANCH CIRCUITRY.INTERCONNECTING BRANCH WIRING SHALL BE SIZED EQUAL TO THE HOMERUNUNLESS NOTED OTHERWISE.3VOLTAGE DROP HAS BEEN CONSIDERED IN THE DESIGN OF ALL BRANCH CIRCUITRYAND FEEDER SIZES BASED UPON THE ILLUSTRATED EQUIPMENT LAYOUTS ANDSHORTEST CONDUCTOR/RACEWAY ROUTING. THE ELECTRICAL CONTRACTOR SHALLBE RESPONSIBLE FOR DEVIATIONS TAKEN THAT WILL INCREASECONDUCTOR/RACEWAY ROUTING LENGTHS. BRANCH CIRCUITS LONGER THAN 75'FOR 120V FROM PANEL TO LAST OUTLET SHALL BE INCREASED A MINIMUM OF ONESIZE ABOVE THAT SPECIFIED TO LIMIT VOLTAGE DROP TO LESS THAN 3%. FEEDERSSHALL FOLLOW SIMILAR GUIDELINES AND BE LIMITED TO 2% DROP4POWER BRANCH CIRCUITRY SHALL BE INSTALLED IN CONDUIT FROM THE PANEL TOTHE FIRST DEVICE AND/OR WHERE EXPOSED. POWER BRANCH CIRCUITRY MAY BETYPE MC CABLE WHERE CONCEALED ABOVE SUSPENDED CEILINGS AND IN METALSTUD WALLS.5MAINTAIN CONTINUITY OF BRANCH CIRCUITRY ASSOCIATED WITH ALL EXISTINGPOWER DEVICES TO REMAIN.FIRE ALARM NOTES:1COORDINATE EXACT DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH ARCHITECTPRIOR TO TOUGH-IN. ALL DEVICES SHALL BE MOUNTED IN ACCORDANCE WITH THELATEST REQUIREMENTS OF THE ACCESSIBILITY CODE.2FIRE ALARM BRANCH CIRCUITRY SHALL BE INSTALLED IN CONDUIT FROM THE PANELTO THE FIRST DEVICE AND/OR WHERE EXPOSED. FIRE ALARM BRANCH CIRCUITRYMAY BE TYPE MC CABLE WHERE CONCEALED ABOVE SUSPENDED CEILINGS AND INMETAL STUD WALLS3MC CABLE FOR FIRE ALARM SERVICE SHALL HAVE A RED IDENTIFIER ALONG ITSENTIRE LENGTH. JUNCTION BOX COVERS AND CONDUIT COUPLINGS FOR ALL FIREALARM WIRING RACEWAYS SHALL BE PAINTED RED PRIOR TO INSTALLATION.4MAINTAIN CONTINUITY OF BRANCH CIRCUITRY ASSOCIATED WITH ALL EXISTING FIREALARM DEVICES TO REMAIN.SITE LEGENDSYMBOLDESCRIPTIONEXISTING UTILITY POLEUNDERGROUND ELECTRICPAD MOUNT TRANSFORMERUETAE1.0AE1.0SCHEDULE OF DRAWINGSDWG #DRAWING TITLEE-1.0LEGENDS, DETAILS, NOTES & ABBREVIATIONSE-2.0SITE PLANE-3.0ALIGHTING PLAN - FIRST FLOOR AE-3.0BLIGHTING PLAN - FIRST FLOOR BE-3.1LIGHTING PLAN - MEZZANINEE-4.0APOWER & DATA PLAN - FIRST FLOOR AE-4.0BPOWER & DATA PLAN - FIRST FLOOR BE-4.1POWER & DATA PLAN - MEZZANINEE-4.2AFIRE ALARM PLAN - FIRST FLOOR AE-4.2BFIRE ALARM PLAN - FIRST FLOOR BE-4.3FIRE ALARM PLAN - MEZZANINEE-4.4AROOF PLAN - AE-4.4BROOF PLAN - BE-5.0PANELBOARD SCHEDULES 1 OF 2E-5.1PANELBOARD SCHEDULES 2 OF 2E-5.2EQUIPMENT SCHEDULESE-6.0ONE-LINE, RISER DIAGRAMS & DETAILSE-7.0SPECIFICATIONSFIREEXISTING EQUIPMENT LEGENDSYMBOLDESCRIPTIONXMEXISTING EQUIPMENT TO REMAINEXISTING EQUIPMENT TO REMAIN FOR INFORMATION ONLY - (XM)INDICATED BY SYMBOL WITH LIGHT OUT OF FUNCTION LINE TYPELIGHTING FIXTURE LEGENDLIGHTING FIXTUREFIXTURE SYMBOLS SHOWN BELOW ARE REPRESENTATIVE. NOT ALL SYMBOLS FROMPLANS HAVE BEEN SHOWN ON LEGEND. FIXTURE TAG AND CIRCUIT # LOCATIONS AREALSO REPRESENTATIVE. ACTUAL TAG AND CIRCUIT # LOCATIONS MAY VARY ON PLANS.SYMBOLDESCRIPTIONLIGHTING FIXTURES (SEE LIGHTING FIXTURE SCHEDULE)"FR" - INDICATES LIGHTING FIXTURE TYPE"#" - INDICATES CIRCUIT NUMBER"a" - INDICATES SWITCH CONTROL"NL" - INDICATES NIGHT LIGHT (UNSWITCHED) CIRCUITSHADING INDICATES EMERGENCY FIXTUREFR#,aNLA#SWITCHING LEGENDSYMBOLDESCRIPTIONWALL MOUNTED SWITCH, RATED 20A, 120/277V"a" - LOWER CASE LETTER INDICATES FIXTURE SWITCH CONTROL(TYP)SWITCH TYPE: # OR LETTER"3" - INDICATES THREE WAY SWITCH"4" - INDICATES FOUR WAY SWITCH"L" - INDICATES LOW VOLTAGE"D" - INDICATES DIMMING"T" - INDICATES DIGITAL TIMER SWITCHSENSOR TYPE: (REFER TO SPEC FOR ADDITIONAL INFORMATION)"O" - INDICATES OCCUPANCY SENSOR"V" - INDICATES VACANCY SENSOR"1" - INDICATES SINGLE POLE SWITCH"D" - INDICATES DIMMINGOCCUPANCY/VACANCY SENSOR, LOW VOTLAGE, CEILINGMOUNTED WITH POWER PACKS AS REQUIRED."O" - INDICATES OCCUPANCY SENSOR"V" - INDICATES VACANCY SENSOR"P" - INDICATES DAY LIGHTING PHOTOCELL SENSOR"1" - INDICATES SINGLE POLE SWITCH"2" - INDICATES DUAL POLE SWITCHTIME CLOCK - TWO CIRCUIT.TIME CLOCK - FOUR CIRCUIT.PHOTOCELLS# or LETTERaO1aTC2TC4PCSECURITY LEGENDSYMBOLDESCRIPTIONCARD READERCRJOB NO.:SCALE:CHECKED:DRAWN:Phone (978) 927-0053152 Conant Street, Beverly, MA 01915 connollybrothers.com2017-010Engineering plumbinghvac electricalfire protection NSEWTRUENCALLED2017-06-01 ISSUED FOR PRICINGE-1.0& ABBREVIATIONSNTSRSCM DE2.0XM11E2.06" CONCRETEBOLLARD (TYP)1E2.02E2.02346587XRXR20'20'1"=20'0SCALE:SITE PLANGENERAL NOTES1.REFER TO DRAWING E1.0 FOR LEGENDS, ABBREVIATIONS & GENERALNOTES.2.COORDINATE ALL WORK WITH UTILITY CO. EXACT SCOPE OF WORK SHALLBE CONFIRMED & APPROVED BY THE UTILITY CO.3.SITE ELECTRICAL SERVICE WORK SHALL BE PHASED TO PROVIDE THELEAST AMOUNT OF SERVICE INTERRUPTIONS. FOR INTERRUPTIONSGREATER THAN 4 HOURS, OR BY DIRECTION OF THE OWNER, THECONTRACTOR SHALL PROVIDE POWER TO THE BUILDING FOR FULLOPERATIONS VIA A TEMPORARY GENERATOR.SHEET NOTES:1.EXISTING UNDERGROUND UTILITY CO OWNED PRIMARY CONDUIT.2.UTILITY CO DESIGN HAS NOT BEEN FINALIZED PRIOR TO ISSUE OF PRICINGSET. INTERCEPT EXISTING CONDUIT , PROVIDE NEW MANHOLE ANDPROVIDE NEW CONDUIT TO NEW PRIMARY SWITCH LOCATION. ALL WORKSHALL BE COORDINATED WITH THE UTILITY CO.3.EXISTING TRANSFORMER SHALL BE REMOVED. PORTIONS OF EXISTINGSECONDARY CONDUIT SHALL BE REUSED TO RE-FEED EXISTINGSWITCHBOARD. REFER TO PLANS FOR ADDITIONAL INFORMATION.4.EXISTING PRIMARY SWITCH TO BE REMOVED & RELOCATED. COORDINATEEXACT REQUIREMENTS WITH UTILITY CO.5.PROPOSED PRIMARY SWITCH LOCATION.6.PROPOSED TRANSFORMER LOCATION.7.BACK FEED EXISTING SWITCHBOARD FROM NEW8.REFER TO LIGHTING PLANS FOR BUILDING MOUNTED SITE LIGHTING.JOB NO.:SCALE:CHECKED:DRAWN:Phone (978) 927-0053152 Conant Street, Beverly, MA 01915 connollybrothers.com2017-010Engineering plumbinghvac electricalfire protection NSEWTRUENCALLED2017-06-01 ISSUED FOR PRICINGE-2.0SITE PLAN1" = 20'-0"RSCMDUCT BANK TABLE2'-6"MINIMUMTYPICAL DIMENSIONING 2 DETAILS SHOWN ABOVEFOR ACTUAL DUCT BANK CONFIGURATIONREFER TO TABLE BELOW3"712"3"3"3"NOTES:1.MINIMUM 12" SEPARATION FROM POWER & COMM CONDUITS. POWER ANDCOMM CONDUITS ARE ALLOWED IN THE SAME CONCRETE DUCTBANK WITHTHIS SEPARATION.POWERCOMM1'-0"(SEE NOTE 1)3000 PSI CONCRETEENCASEMENT. UNLESSNOTED OTHERWISE712"PVC CONDUIT(TYP)6" GRAVEL BORROW SUBBASECONTINUOUS RED CABLEWARNING TAPE4" LOAM AND SEEDIN UNPAVED AREASNOT TO SCALESCALE:DUCTBANK SECTION14" NON CONDUCTIVESEPARATOR(WHERE SHOWNBELOW)CONDUIT SPACERS5'-0" ON CENTER#1(2) 5" POWER#2(10) 4" POWERCONCRETECOMPACTEDSAND6"MINREINFORCINGREBAR 12"O.C.(TYP)NOTE 4GROUND GRIDNOTE 3GROUND ROD(TYPICAL FOR4)1 -1 1/2" DIAMETERCRUSHED STONE WELLTAMPED BELOW PADGROUND ROD*$/9$1,=('67((/ƒCONDUIT SWEEPS#4 REBAR 12" O.C.EXCEPT INCONDUIT SPACE3/4" CHAMFER ALLAROUNDNOTES:1.CONCRETE PAD DIMENSIONS AND EXACT BOLLARD REQUIREMENTS PER UTILITYCO. COORDINATE ALL EXACT REQUIREMENTS WITH UTILITY CO.2.E.C. SHALL INSTALL THREE FEET OF SLACK CABLE ABOVE PAD FOR GROUNDING.3.E.C. SHALL PROVIDE GROUND GRID-#1/0, 7 STRAND BARE COPPER, 1'-0" BELOWFINISHED GRADE/ BOND ALL METALLIC PARTS PER UTILITY CO SPECIFICATIONS.4.COORDINATE EXACT QUANTITY OF CONDUITS WITH SITE PLAN.10'-0"10'-0"NOTE #1NOTE #1NOTE 2#E2.0NOT TO SCALESCALE:UTILITY PAD DETAILAE2.0 PLAN A PLAN BPHASE 1PHASE 2PLAN A PLAN B PHASE 2PHASE 1N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.D1,z1D2,z3D2,z9D39,z12D3,z4D3,z4D3,z4D1,z7D1,z7D4,z10D4,z10D4,z10D39,z13D39,z13D3,z4D4,z10D39,z13D2,z5D2,z5D2,z5D1,z8D1,z8D2,z11D2,z11D2,z11D41,z14D41,z14D41,z14D1,z2DE39,z13D39,z13DE4,z10D4,z10DE1,z7D1,z7DE3,z4D3,z4D39,z12DE2,z9D2,z9DE1,z6D1,z6DE2,z3D2,z3DE1,z2F12010101ES11ES14ES139PB24B-(2)(VIA TC4)PB23B-(1)(VIA TC3)PB24B-(3)(VIA LTC4)PB22B-(4)(VIA TC2)PB21A-(39)(VIA TC4)LP22-(11)BE12F12F12F12B12BE12BE12B12BE12LP22-(12)ES111A11AA11AA11AA11AB12PB24B-(1)(VIA TC4)PB21A-(41)(VIA TC4)PB22B-(2)(VIA TC2)TC4z12,z13,z14TC4z9,z10,z11TC4z,6,z7,z8TC4z3,z4,z5TC2z1,z2S16S16S16SHEET NOTE21BTYP.B12B123JOB NO.:SCALE:CHECKED:DRAWN:Phone (978) 927-0053152 Conant Street, Beverly, MA 01915 connollybrothers.com2017-010Engineering plumbinghvac electricalfire protection NSEWTRUENCALLEDPLAN APLAN BKEY PLANNOT IN SCOPE2017-06-01 ISSUED FOR PRICING1/8"=1'-0"16'8'4'0SCALE:LIGHTING PLAN - FIRST FLOOR AGENERAL NOTES1.REFER TO DRAWING E1.0 FOR LEGENDS, ABBREVIATIONS & GENERALNOTES.2.CONFIRM ALL SWITCHING LOCATIONS WITH OWNER PRIOR TO ROUGH-IN.SHEET NOTES:1.VIA SITE LIGHTING CONTROL PANEL.2.ALL EXISTING EXTERIOR WALL PACKS ON EXISTING BUILDING TO BEREPLACED WITH TYPE S1 FIXTURES (ASSUME QUANTITY 10). WHEREMOUNTED NEAR EGRESS DOORS, PROVIDE TYPE S1E FIXTURES (ASSUMEQUANTITY 4). EXISTING FIXTURES SHALL BE REWIRED SUCH THAT THEY CANBE CONTROLLED VIA NEW SITE LIGHTING CONTROL PANEL. LIGHT THROWSHALL NOT EXTEND BEYOND PROPERTY LINE.3.REFER TO MEZZANINE LIGHTING PLAN, DRAWING E-3.1 FOR LOCATION OFEXTERIOR LIGHTING PHOTOCELL CONTROL.E-3.0ALIGHTING PLANFIRST FLOOR A1/8" = 1'-0"RSCM PLAN APLAN B PHASE 1PHASE 2PHASE 1PHASE 2PLAN APLAN B N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.BE2,aB2,aD41,z14D41,z15D41,z16D41,z16DE41,z15D41,z15DE39,z13H11HE11H11H11H11H11H11H11H11H11H11HE11F20101Di01010101iPCc01a01a01a01h01c,d01b01m,n3bhabed3nm3n01n01nPCmES11ES111ES12ES12ES11ES139LP22-(11)LP21-(2)LP21-(1)LP21-(3)LP21-(4)B4,hB4,hB4,hB4,hB4,iB4,iB4B4B2,aBE2,aB2,aBE2,aB2,aBE2,aB2,aBE2,aB2,aBE2,aB2,a01aB3B3B3B3B4B4B3,cB3,cB3,cB3,cB3,dB3,dB3,dB3,dB3,bB3,bB3,bB3,bB3,bB4B4B4,hB4,hB4,hB4,hB4,hB4,h01p01pES11ES11F2F2F2BE2B2BE2BE2B2BE2ES111A11A11A11A11A11A11A11AE11A11A11A11A11A11A11A11A11A11AE11A11A11B2B4,iB3,bB3,bAE1,mA1,mA1,mAE1,mA1,nA1,nA1,nA1,nA1,nA1,nAE1,nA1,nA1,nAE1,nA1,nA1,nA1,nA1,nA1,nA1,nA1,pA1,pA1,pA1,pA1,pAE1,pA1,pA1,pA1,pAE1,p3p3pB4,iB4B4B4B3B3B3,bB2,aJ5JE5JE5JE5J5J5JE53a3b3bLP21-(5)JE201hB2,aBE2,aA1,pA1,p01B3B3BE3B3B3BE3B3B3B3B3B3433B2,aBE2,a4CE4C4C4C4C4C4C4CD01BE2,aBE2,aES12ES141BE20BE2001TC2z15,z16TT3aS1E6S1E6S1E6S1E6S16ES120ES141B2B201BE20BBSITELIGHTINGCONTROLPANEL2TYP.3JOB NO.:SCALE:CHECKED:DRAWN:Phone (978) 927-0053152 Conant Street, Beverly, MA 01915 connollybrothers.com2017-010Engineering plumbinghvac electricalfire protection NSEWTRUENCALLEDPLAN APLAN BKEY PLANNOT IN SCOPE2017-06-01 ISSUED FOR PRICING1/8"=1'-0"16'8'4'0SCALE:LIGHTING PLAN - FIRST FLOOR BGENERAL NOTES1.REFER TO DRAWING E1.0 FOR LEGENDS, ABBREVIATIONS & GENERALNOTES.2.CONFIRM ALL SWITCH LOCATIONS WITH OWNER PRIOR TO ROUGH-IN.SHEET NOTES:1.SWITCH FOR STAIRWELL LIGHTING. REFER TO DRAWIN E-3.1 FOR FIXTURESCONTROLLED.2.REFER TO "TYPICAL ELEVATOR REQUIREMENTS" DETAIL ON DRAWING E6.0FOR ELEVATOR PIT LIGHTING IN THIS AREA.3.REFER TO MEZZANINE LIGHTING PLAN, DRAWING E-3.1 FOR LOCATION OFEXTERIOR LIGHTING PHOTOCELL CONTROL.E-3.0BLIGHTING PLANFIRST FLOOR B1/8" = 1'-0"RSCMNOTES:1.120V POWER SUPPLY2.TO PANEL. REFER TO PLANS & PANEL SCHEDULES FOR EXTERIOR LIGHTINGCIRCUITS.3.RELAY LIGHTING CONTROL PANEL WITH INTERNAL TIME CLOCK. LEVITON EZMAX CONTROL WITH MINIMUM OF FOUR CIRCUITS OF CONTROL.3.1.MODEL NUMBER #re4bd-104 (120-277V)3.2.MODEL NUMBER #re4bd-204 (208-480V) 2 POLE RELAYS4.EZ MAX OPTION PCOUT-000 FOR OUTDOOR 0-10V PHOTOCELL. PROVIDELOW VOLTAGE WIRING TO PHOTOCELL.5.EXISTING EXTERIOR LIGHTING CIRCUITS SHALL BE EXTENDED & RUNTHROUGH NEW EZ MAX PANEL. COORDINATE EXACT EXISTING LIGHTINGCONTROLS LOCATION WITH OWNER.NOT TO SCALESCALE:SITE LIGHTING CONTROL PANEL DETAILB B22,cB22,cB22,cB22,cBE20,aB20,aBE20,aB20,aBE20,aB20,aBE20,aB20,aB22B22B22B22B22B22B22BE22B22B22B22B22BE20B20,aBE20B20,aB24B24BE24B24B24B24BE20,bB20,bBE20,bBE20,aB20,aBE20,aB20,aBE20,aB20,aB24,fB24,fB24,fB24,fB24,fB24,fB24B24B24B24B24B24B24B24B24B20,bBE20B22BE20B22J22J22J22J22JE22J22J223a24C24C3a01010101013b010101Dc0101c01f01a01a01a01a01a010101DPO22-(22)P022-(20)PO22-(24)1101B22B22B22B22B2201PC2JOB NO.:SCALE:CHECKED:DRAWN:Phone (978) 927-0053152 Conant Street, Beverly, MA 01915 connollybrothers.com2017-010Engineering plumbinghvac electricalfire protection NSEWTRUENCALLED2017-06-01 ISSUED FOR PRICINGE-3.1LIGHTING PLANMEZZANINE1/8" = 1'-0"RSCM1/8"=1'-0"16'8'4'0SCALE:LIGHTING PLAN - MEZZANINEMEZZANINEKEY PLANGENERAL NOTES1.REFER TO DRAWING E1.0 FOR LEGENDS, ABBREVIATIONS & GENERALNOTES.2.CONFIRM ALL SWITCH LOCATIONS WITH OWNER PRIOR TO ROUGH-IN.SHEET NOTES:1.PROVIDE LVS MODEL CR-1-120 "TIMESAVER" RELAY FOR CLOSET LIGHTCONTROL.2.REFER TO FIRST FLOOR LIGHTING DRAWINGS E-3.0 & E-3.1 FOR EXTERIORBUILDING MOUNTED LIGHTING FIXTURES CONTROLLED. PLAN A PLAN BPHASE 1PHASE 2PLAN A PLAN B PHASE 2PHASE 1N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.KNIGHT PRESSKNIGHT PRESS KNIGHT PRESSLAY UPKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESS KNIGHT PRESS LAY UPLAY UPLAY UPLAY UPLAY UPLAY UPSupply RackLAY UPLAY UPLAY UPLAY UPLAY UPLAY UPLAY UPSupply RackLAY UPLAY UPLAY UPLAY UPLAY UPLAY UPLAY UPSupply RackLAY UPLAY UPLAY UPLAY UPLAY UPLAY UPGROUP LEADERSupply RackM32 LASER PUREX 800i M32CUTTINGLASERC P U M32 LASERPUREX800iPUREX800iABLATION LASER PUREX800iABLATION LASER ABLATIONLASERABLATIONLASERC32C3232PB21APB22APB23APB23B32TF1aTF1eTF1dTF1cTF1bJPB24A-(31)PB24A-(32)33PB24A-(33)34343434PB24-(34)PB23-(35)35PB22-(35)PB21-(25)2025EF5aEF5bEF5cEF5dEF5eEF5fEF5gEF5hJ6J5J2J3PB21A-(1,3)50A2P50A2P50A2P50A2P50A2P50A2P50A2P50A2P50A2P50A2P50A2P50A2P50A2P50A2P50A2P50A2P50A2P50A2P50A2P50A2P50A2P50A2P50A2P50A2P50A2P50A2P50A2P50A2PPB21A-(10,12)PB21A-(13,15)PB21A-(14,16)PB21A-(17,19)PB21A-(18,20)PB21A-(21,23)PB22A-(1,3)PB22A-(2,4)PB22A-(5,7)PB22A-(6,8)PB22A-(9,11)PB22A-(10,12)PB22A-(13,15)PB22A-(14,16)PB23A-(1,3)PB23A-(2,4)PB23A-(5,7)PB23A-(6,8)PB23A-(9,11)PB23A-(10,12)PB23A-(13,15)PB23A-(14,16)PB24A-(1,3)PB24A-(2,4)PB24A-(5,7)PB24A-(6,8)PB24A-(9,11)PB24B-(29)PB24B-(31)PB24B-(33)PB24B-(35)PB24B-(37)PB24B-(39)PB24B-(17)PB24B-(19)PB24B-(21)PB24B-(23)PB24B-(25)PB24B-(27)PB24B-(5)PB24B-(7)PB24B-(9)PB24B-(11)PB24B-(13)PB24B-(15)PB23B-(27)PB23B-(29)PB23B-(31)PB23B-(33)PB23B-(35)PB23B-(37)PB23B-(15)PB23B-(17)PB23B-(19)PB23B-(21)PB23B-(23)PB23B-(25)PB23B-(3)PB23B-(5)PB23B-(7)PB23B-(9)PB23B-(11)PB23B-(13)PB23A-(17)PB23A-(19)PB23A-(21)PB23A-(23)PB23A-(25)PB23A-(27)PB22B-(25)PB22B-(27)PB22B-(29)PB22B-(31)PB22B-(33)PB22B-(35)PB22B-(13)PB22B-(15)PB22B-(17)PB22B-(19)PB22B-(21)PB22B-(23)PB22B-(1)PB22B-(3)PB22B-(5)PB22B-(7)PB22B-(9)PB22B-(11)PB22A-(17)PB22A-(19)PB22A-(21)PB22A-(23)PB22A-(25)PB22A-(27)PB21B-(26)PB21B-(28)PB21B-(30)PB21B-(32)PB21B-(34)PB21B-(36)PB21B-(14)PB21B-(16)PB21B-(18)PB21B-(20)PB21B-(22)PB21B-(24)PB21B-(2)PB21B-(3)PB21B-(4)PB21B-(6)PB21B-(8)PB21B-(10)PB21B-(12)PB21A-(22)PB21A-(27)PB21A-(29)PB21A-(31)PB21A-(33)PB21A-(35)PB21A-(37)PB21A-(24)PB21A-(26)PB21A-(28)PB21A-(30)PB21A-(32)50A2PPB24A-(10,12)50A2PPB24A-(13,15)50A2PPB24A-(14,16)50A2PPB24A-(17,19)PB24APB24BPB22BPB21BPB21B-(15)PB21B-(13)PB21B-(17)PB21B-(19)PB21B-(21)PB21B-(23)PB21B-(27)PB21B-(25)PB21B-(29)PB21B-(31)PB21B-(33)PB21B-(35)PB21B-(38)PB21B-(37)PB21B-(39)PB21B-(40)PB21B-(41)PB21B-(42)PB22A-(20)PB22A-(18)PB22A-(22)PB22A-(24)PB22A-(26)PB22A-(28)PB22B-(16)PB22B-(14)PB22B-(18)PB22B-(20)PB22B-(22)PB22B-(24)PB23A-(20)PB23A-(18)PB23A-(22)PB23A-(24)PB23A-(26)PB23A-(28)PB23B-(16)PB23B-(14)PB23B-(18)PB23B-(20)PB23B-(22)PB23B-(24)PB23B-(4)PB23B-(2)PB23B-(6)PB23B-(8)PB23B-(10)PB23B-(12)PB23B-(28)PB23B-(26)PB23B-(30)PB23B-(32)PB23B-(34)PB23B-(36)PB24B-(6)PB24B-(4)PB24B-(8)PB24B-(10)PB24B-(12)PB24B-(14)PB24B-(18)PB24B-(16)PB24B-(20)PB24B-(22)PB24B-(24)PB24B-(26)PB24B-(30)PB24B-(28)PB24B-(32)PB24B-(34)PB24B-(36)PB24B-(38)PB21B-(5)PB21B-(7)PB21B-(9)PB21B-(11)PB21B-(1)MP21-(1)MP21-(2)MP21-(3)MP21-(16)MP21-(18)MP21-(4)PB22B-(28)PB22B-(26)PB22B-(30)PB22B-(32)PB22B-(34)PB22B-(36)PB22B-(4)PB22B-(2)PB22B-(6)PB22B-(8)PB22B-(10)PB22B-(12)4321J1J450A2P50A2P50A2P50A2PPB21A-(2,4)PB21A-(5,7)PB21A-(6,8)PB21A-(9,11)1BE6.0CE6.0TYP.TYP.(2)#8,(1)#10G,3/4"C(TYP.)JPB24A-(24)JPB24A-(28)32TYP.JJPB24B-(26)PB24B-(27)TYP. FOR 44PB24B-(25)5EWH1TSFS1/8"=1'-0"16'8'4'0SCALE:POWER & DATA PLAN - FIRST FLOOR AGENERAL NOTES1.REFER TO DRAWING E1.0 FOR LEGENDS, ABBREVIATIONS & GENERALNOTES.SHEET NOTES:1.PROVIDE J-BOX FOR GARAGE DOOR POWER. COORDINATE EXACTREQUIREMENTS WITH SUBMITTED EQUIPMENT.2.ALL LAZERS IN THIS ROOM SHALL BE CIRCUITED TO PANEL LZ21A TO THECIRCUIT DESIGNATION AS SHOWN.3.ALL AIR PURIFIERS IN THIS ROOM SHALL BE CIRCUITED TO PANEL LZ21B TOTHE CIRCUIT DESIGNATION AS SHOWN.4.J-BOX FOR POWER CONNECTION TO HAND DRYER. COORDINATE EXACTLOCATION AND MOUNTING HEIGHT WITH ARCHITECT PRIOR TO ROUGH-IN.5.EXISTING WALL TO BE REMOVED. ALL EXISTING ELECTRICAL DEVICESSHALL BE REMOVED AND MADE SAFE FOR DEMOLITION OF WALL.E-4.0APOWER & DATA PLANFIRST FLOOR A1/8" = 1'-0"RSCMJOB NO.:SCALE:CHECKED:DRAWN:Phone (978) 927-0053152 Conant Street, Beverly, MA 01915 connollybrothers.com2017-010Engineering plumbinghvac electricalfire protection NSEWTRUENCALLEDPLAN APLAN BKEY PLANNOT IN SCOPE2017-06-01 ISSUED FOR PRICING1/8"=1'-0"16'8'4'0SCALE:FIRE ALARM PART PLANFIRE ALARMPART PLAN PLAN APLAN B PHASE 1PHASE 2PHASE 1PHASE 2PLAN APLAN B N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.PUREX800iABLATIONLASERPUREX800iABLATIONLASERABLATIONLASERABLATIONLASERPUREX800iABLATIONLASERPUREX800iABLATIONLASERABLATIONLASERABLATIONLASERPUREX800iABLATIONLASERPUREX800iABLATIONLASERABLATIONLASERABLATIONLASERPUREX800iABLATIONLASERPUREX800iABLATIONLASERABLATIONLASERABLATIONLASERPUREX800iABLATIONLASERPUREX800iABLATIONLASERABLATIONLASERABLATIONLASERPUREX800iABLATIONLASERPUREX800iABLATIONLASERABLATIONLASERABLATIONLASERPUREX800i ABLATIONLASER PUREX800iABLATIONLASERABLATIONLASERABLATIONLASERPUREX800iABLATIONLASERPUREX800iABLATIONLASERABLATIONLASERABLATIONLASERPUREX800iABLATIONLASERPUREX800iABLATIONLASERABLATIONLASERABLATIONLASERM32 LASERPUREX800iABLATIONLASERABLATIONLASERN.I.C.88CCCC88888554119989PO21LP21PO21-(5)PO21-(4)PO21-(1)PO21-(8)PO21-(9)PO21-(11)8MP21MP21-(8)1313PO21-(13)JJJMP21-(9,11)MP21-(13,15)MP21-(17,19)CCCCPO21-(19)PO21-(20)PO21-(21)PO21-(22)12101010101212MP21-(10)MP21-(12)PT20MP21-(20)26262626PO21-(26)MAINMTRSEC1SEC2XM1XM2XMLZ21BJ31J30J7J6J32J33J36J37J40J41J42J29J1250A2PMP21-(33,35)MP21-(29,31)50A2P50A2P50A2PMP21-(25,27)MP21-(21,23)MP21-(22)MP21-(34)MP21-(39)MP21-(26)MP21-(38)MP21-(43)MP21-(44)MP21-(30)MP21-(42)MP21-(45)MP21-(20)MP21-(24)MP21-(28)MP21-(40)MP21-(36)MP21-(32)MP21-(37)MP21-(41)PTPTPT4200AS125AF20AS20AFMDP-(3)PO21-(1)PO21-(7)PO21-(12)PO21-(27)16654171819202115CCC12111413J28J27J18J17J16J15J24J23J26J11J25J10J39J38J1J4J8J21J34J9J22J35J13J14J19J2010987LZ21APTPT32TYP.1JMP21-(49)JMP21-(50)REFER TO TYPICALELEVATOR REQUIREMENTSDETAIL ON DRAWING E6.0CCCCMICROWAVE(TYP. FOR 3)REFRIGERATOR(TYP. FOR 2)AE6.0BE6.0BE6.0TYP.4N.I.C.JJMP21-(47)MP21-(48)TYP. FOR 4526PO21-(15)PO21-(16)PO21-(17)PO21-(18)TYP. FOR 36MDPDP1PTPTPO21-(3)PTPTPO21-(29)PO21-(30)PO21-(31)PO21-(32)PO21-(33)PO21-(34)PO21-(35)PO21-(36)77G38393737404141PO21-(37)PO21-(38)PO21-(40)PO21-(41)HP21EF5iEF7C42C42C42C42CPO21-(42)HP1HP2EWH2PO21-(10)1414PO21-(2)PO21-(14)TYP. FOR 2830A3PPO21-(44,46,48)30A3PPO21-(28)PO21-(45,47,49)99CRCRCRPO21-(39)CRCR1/8"=1'-0"16'8'4'0SCALE:POWER & DATA PLAN - FIRST FLOOR BGENERAL NOTES1.REFER TO DRAWING E1.0 FOR LEGENDS, ABBREVIATIONS & GENERALNOTES.SHEET NOTES:1.E.C. SHALL CUT EXISTING MAIN SWITCHBOARD CONDUITS 2'-0" FROM THEEDGE OF THE EXISTING EXTERIOR WALL. E.C. SHALL PROVIDE (5) NEW 4"UNDERGROUND CONDUITS FROM PROPOSED SWITCHBOARD ANDCONNECT TO THE EXISTING UNDERGROUND CONDUITS FEEDING THEEXISTING SWITCHBOARD.2.ALL LAZERS IN THIS ROOM SHALL BE CIRCUITED TO PANEL LZ21A TO THECIRCUIT DESIGNATION AS SHOWN.3.ALL AIR PURIFIERS IN THIS ROOM SHALL BE CIRCUITED TO PANEL LZ21B TOTHE CIRCUIT DESIGNATION AS SHOWN.4.COORDINATE WIRING CONFIGURATION WITH SUBMITTED FURNITURE.5.J-BOX FOR POWER CONNECTION TO HAND DRYER. COORDINATE EXACTLOCATION AND MOUNTING HEIGHT WITH ARCHITECT PRIOR TO ROUGH-IN.6.J-BOX FOR POWER CONNECTION TO OVEN.7.EXISTING WALL TO BE REMOVED. ALL EXISTING ELECTRICAL DEVICESSHALL BE REMOVED AND MADE SAFE FOR DEMOLITION OF WALL.8.PROVIDE LEGRAND MODEL 880 SINGLE SERVICE FLOORBOX WITH DUPLEXRECEPTACLE.9.208V EQUIPMENT T.B.D., COORDINATE EXACT REQUIREMENTS WITH OWNERPRIOR TO ROUGH-IN.JOB NO.:SCALE:CHECKED:DRAWN:Phone (978) 927-0053152 Conant Street, Beverly, MA 01915 connollybrothers.com2017-010Engineering plumbinghvac electricalfire protection NSEWTRUENCALLEDPLAN APLAN BKEY PLANNOT IN SCOPE2017-06-01 ISSUED FOR PRICINGE-4.0BPOWER & DATA PLANFIRST FLOOR B1/8" = 1'-0"RSCM PTPTPTPT101313141414C13C80"13114999933333888C17CCC191922222211111111212PO22-(1)PO22-(2)PO22-(3)PO22-(4)PO22-(5)PO22-(6)PO22-(7)PO22-(8)PO22-(9)PO22-(10)PO22-(11)PO22-(12)PO22-(13)PO22-(14)PO22-(15)PO22-(16)PO22-(17)PO22-(18)PO22-(19)PO22TYP.2EF4EF3EF6EWH3GENERAL NOTES1.REFER TO DRAWING E1.0 FOR LEGENDS, ABBREVIATIONS & GENERALNOTES.SHEET NOTES:1.E.C. SHALL COORDINATE EXACT MOUNTING HEIGHT IN FIELD WITHARCHITECT/OWNER PRIOR TO ROUGH-IN.2.E.C. SHALL SPLIT SINGLE CIRCUIT TO ACCOMMODATE MULTI-CIRCUITFURNITURE FEED.JOB NO.:SCALE:CHECKED:DRAWN:Phone (978) 927-0053152 Conant Street, Beverly, MA 01915 connollybrothers.com2017-010Engineering plumbinghvac electricalfire protection NSEWTRUENCALLED2017-06-01 ISSUED FOR PRICINGE-4.1POWER & DATA PLANMEZZANINE1/8" = 1'-0"RSCM1/8"=1'-0"16'8'4'0SCALE:POWER & DATA PLAN - MEZZANINEMEZZANINEKEY PLAN PLAN A PLAN BPHASE 1PHASE 2PLAN A PLAN B PHASE 2PHASE 1N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.KNIGHT PRESSKNIGHT PRESS KNIGHT PRESSLAY UPKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESSKNIGHT PRESS KNIGHT PRESS LAY UPLAY UPLAY UPLAY UPLAY UPLAY UPSupply RackLAY UPLAY UPLAY UPLAY UPLAY UPLAY UPLAY UPSupply RackLAY UPLAY UPLAY UPLAY UPLAY UPLAY UPLAY UPSupply RackLAY UPLAY UPLAY UPLAY UPLAY UPLAY UPGROUP LEADERSupply RackM32 LASER PUREX 800i M32CUTTINGLASERC P U M32 LASERPUREX800iPUREX800iABLATION LASER PUREX800iABLATION LASER ABLATIONLASERABLATIONLASER110cdCEF110cdCEF110cdCEF110cdCEF110cdCEF110cdCEF110cdCEF110cdCEF75cdFF75cdF75cdF15cdL15cdLFSDSD22TYP.11/8"=1'-0"16'8'4'0SCALE:FIRE ALARM PLAN - FIRST FLOOR AGENERAL NOTES1.REFER TO DRAWING E1.0 FOR LEGENDS, ABBREVIATIONS & GENERALNOTES.SHEET NOTES:1.FIRE ALARM DEVICES SHALL BE MOUNTED 6" BELOW LIGHTING FIXTURES.COORDINATE EXACT MOUNTING HEIGHT IN FIELD PRIOR TO ROUGH-IN.2.PROVIDE POWER CONNECTION TO SMOKE DAMPER. COORDINATE EXACTREQUIREMENTS WITH VENDOR. UTILIZE CIRCUIT PB22A-(31).E-4.2AFIRE ALARM PLANFIRST FLOOR A1/8" = 1'-0"RSCMJOB NO.:SCALE:CHECKED:DRAWN:Phone (978) 927-0053152 Conant Street, Beverly, MA 01915 connollybrothers.com2017-010Engineering plumbinghvac electricalfire protection NSEWTRUENCALLEDPLAN APLAN BKEY PLANNOT IN SCOPE2017-06-01 ISSUED FOR PRICING PLAN APLAN B PHASE 1PHASE 2PHASE 1PHASE 2PLAN APLAN B N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.KNIGHT PRESSKNIGHT PRESSLAY UPLAY UPPUREX800iABLATIONLASERPUREX800iABLATIONLASERABLATIONLASERABLATIONLASERPUREX800iABLATIONLASERPUREX800iABLATIONLASERABLATIONLASERABLATIONLASERPUREX800iABLATIONLASERPUREX800iABLATIONLASERABLATIONLASERABLATIONLASERPUREX800iABLATIONLASERPUREX800iABLATIONLASERABLATIONLASERABLATIONLASERPUREX800iABLATIONLASERPUREX800iABLATIONLASERABLATIONLASERABLATIONLASERPUREX800iABLATIONLASERPUREX800iABLATIONLASERABLATIONLASERABLATIONLASERPUREX800iABLATIONLASER PUREX800iABLATIONLASERABLATIONLASERABLATIONLASERPUREX800iABLATIONLASERPUREX800iABLATIONLASERABLATIONLASERABLATIONLASERPUREX800iABLATIONLASERPUREX800iABLATIONLASERABLATIONLASERABLATIONLASERM32 LASERPUREX800i M32CUTTINGLASERCPU M32 LASERPUREX800iPUREX800iABLATIONLASER PUREX800iABLATIONLASERABLATIONLASER ABLATIONLASERN.I.C.110cdCEF15cdL15cdL75cdFFF110cdF75cdF75cdF110cdF75cdF75cdF75cdF75cdF75cdF75cdF75cdFSMP21-(14)FSER75cdF75cdFFACP ANNN.I.C.75cdF75cdFFSSDSD2211/8"=1'-0"16'8'4'0SCALE:FIRE ALARM PLAN - FIRST FLOOR BGENERAL NOTES1.REFER TO DRAWING E1.0 FOR LEGENDS, ABBREVIATIONS & GENERALNOTES.SHEET NOTES:1.REFER TO TYPICAL ELEVATOR REQUIREMENTS ON E6.0 FOR ADDITIONALINFORMATION.2.PROVIDE POWER CONNECTION TO SMOKE DAMPER. COORDINATE EXACTREQUIREMENTS WITH VENDOR. UTILIZE CIRCUIT PO21-(43).JOB NO.:SCALE:CHECKED:DRAWN:Phone (978) 927-0053152 Conant Street, Beverly, MA 01915 connollybrothers.com2017-010Engineering plumbinghvac electricalfire protection NSEWTRUENCALLEDPLAN APLAN BKEY PLANNOT IN SCOPE2017-06-01 ISSUED FOR PRICINGE-4.2BFIRE ALARM PLANFIRST FLOOR B1/8" = 1'-0"RSCM 75cdFFF75cdF75cdF75cdF75cdF75cdF75cdF75cdF15cdL15cdL75cdF75cdF75cdF75cdFSERSS75cdFFF75cdF75cdF75cdF75cdF75cdF75cdF75cdF15cdL15cdL75cdF75cdF75cdF75cdFSERSSGENERAL NOTES1.REFER TO DRAWING E1.0 FOR LEGENDS, ABBREVIATIONS & GENERALNOTES.JOB NO.:SCALE:CHECKED:DRAWN:Phone (978) 927-0053152 Conant Street, Beverly, MA 01915 connollybrothers.com2017-010Engineering plumbinghvac electricalfire protection NSEWTRUENCALLED2017-06-01 ISSUED FOR PRICINGE-4.3FIRE ALARM PLANMEZZANINE1/8" = 1'-0"RSCM1/8"=1'-0"16'8'4'0SCALE:FIRE ALARM PLAN - MEZZANINE1/8"=1'-0"16'8'4'0MEZZANINEKEY PLAN HV1 HV2 PLAN A PLAN BPHASE 1PHASE 2PLAN A PLAN B PHASE 2PHASE 1N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.RTSSRTSS(TYP.)1(TYP.)21/8"=1'-0"16'8'4'0SCALE:ROOF PLAN - AGENERAL NOTES1.REFER TO DRAWING E1.0 FOR LEGENDS, ABBREVIATIONS & GENERALNOTES.SHEET NOTES:1.CONVENIENCE RECEPTACLE POWERED BY MECHANICAL EQUIPMENT.2.COORDINATE EXACT LOCATION WITH LOCAL FIRE DEPARTMENT PRIOR TOROUGH-IN.JOB NO.:SCALE:CHECKED:DRAWN:Phone (978) 927-0053152 Conant Street, Beverly, MA 01915 connollybrothers.com2017-010Engineering plumbinghvac electricalfire protection NSEWTRUENCALLEDPLAN APLAN BKEY PLANNOT IN SCOPE2017-06-01 ISSUED FOR PRICINGE-4.4AROOF PLAN - A1/8" = 1'-0"RSCMNOTES:SCALE:MECHANICAL ROOF TOP DETAIL6'-6"MECHANICAL EQUIPMENTREFER TO DRAWINGS FORBRANCH CIRCUIT HOMERUNROOFROOF CURBLBPROVIDE METAL CHANNELWHERE REQUIRED120 VOLT DUPLEX, GROUND FAULTRECEPTACLE IN WEATHERPROOFENCLOSURE1.LOCATION OF RECEPTACLE AND DISCONNECT SWITCH ISREPRESENTATIVE AND SHALL BE INSTALLED PER MECHANICALEQUIPMENT MANUFACTURERS RECOMMENDATIONS.COORDINATE WITH MECHANICAL CONTRACTOR IN FIELD.2.NO MECHANICAL HEATING OR AIR CONDITIONING EQUIPMENTSHALL BE MORE THAN 25'-0" AWAY FROM A SERVICERECEPTACLE. ADDITIONAL RECEPTACLES SHALL BE PROVIDEDWHERE THE ABOVE REQUIREMENTS ARE NOT MET.NOT TO SCALEWEATHERPROOF LIGHTINGFIXTURE WITH GUARD(HUBBELL #VWX-152-VCG-15) PLAN APLAN B PHASE 1PHASE 2PHASE 1PHASE 2PLAN APLAN B RTSS(TYP.)1RTU1RTU5RTU3RTU4RTU2ACCU1ACCU2WP211/8"=1'-0"16'8'4'0SCALE:ROOF PLAN - BJOB NO.:SCALE:CHECKED:DRAWN:Phone (978) 927-0053152 Conant Street, Beverly, MA 01915 connollybrothers.com2017-010Engineering plumbinghvac electricalfire protection NSEWTRUENCALLEDPLAN APLAN BKEY PLANNOT IN SCOPE2017-06-01 ISSUED FOR PRICINGE-4.4BROOF PLAN - B1/8" = 1'-0"RSCMGENERAL NOTES1.REFER TO DRAWING E1.0 FOR LEGENDS, ABBREVIATIONS & GENERALNOTES.SHEET NOTES:1.E.C. SHALL PROVIDE POWER TO BUILT-IN CONVENIENCE RECEPTACLE ATROOF TOP UNITS.2.COORDINATE EXACT LOCATION WITH LOCAL FIRE DEPARTMENT PRIOR TOROUGH-IN. DISTRIBUTION PANELBOARD SCHEDULEPANEL: MDP VOLT: 208/120 3 PHASE 4 WIREBUS: 4000 AMPS MAIN: 4000 AMPS AIC: 100k AMPS SYMCIR.LOAD DESIGNATIONOVERCURRENT DEVICELOADREMARKSFRAMETRIPPOLEKVAHP1PANEL DP11600160033902LP2110010034.773ELEVATOR2251253212054PANEL PB21A-B6006003158.885PANEL PB22A-B6006003127.086PANEL PB23A-B6006003126.307PANEL PB24A-B6006003137.448PANEL PO21400300320.009PANEL MP21400400383.6310PANEL LZ214004003100.3911PANEL HP214004003107.4412SPACE13SPACE14SPACETOTAL KVA1276.93TOTAL AMPS3547.02NOTES:1. PROVIDE LUGS TO ACCOMMODATE FEEDER SIZES AS IDENTIFIED ON THE RISER DIAGRAM FOR SUPPLY AND ALL LOADS. (THIS NOTE APPLICABLE TO ALLTERMINATIONS.)2. NOTES 3-5 ARE OPTIONS WHICH SHALL BE SPECIFICALLY NOTED IN REMARKS FOR INCLUSION.3. PROVIDE WITH FEED THRU LUGS.4. PROVIDE WITH 200% NEUTRAL.5. EXACT ELEVATOR REQUIREMENTS SHALL BE COORDINATED WITH SUBMITTED EQUIPMENT.6. SHORT CIRCUIT RATING IS BASED ON 500kVA TRANSFORMER, WITH 2.5% IMPEDANCE. CONTRACTOR SHALL CONFIRM WITH UTILITY CO. EXACT EQUIPMENT TO BEUSED AND FORWARD TO ENGINEER FOR REVIEW.PANELBOARD SCHEDULE (SECTION #1)PANEL: PB21A VOLTS:120/208 NEW/EXISTING.: NEWMAIN: MCBBUS AMPS:600A MOUNT.: SURFACEPH/WIRE: 3/4AIC:- LOC: PRODUCTION BCIR.AMPS/POLESDESCRIPTION OF LOADLOADkVANOTENOTELOADkVADESCRIPTION OF LOADAMPS/POLESCIR.150/2KNIGHT PRESS 18--8KNIGHT PRESS 250/2234550/2KNIGHT PRESS 38--8KNIGHT PRESS 450/2678950/2KNIGHT PRESS 58--8KNIGHT PRESS 650/21011121350/2KNIGHT PRESS 78--8KNIGHT PRESS 850/21415161750/2KNIGHT PRESS 98--8KNIGHT PRESS 1050/21819202150/2KNIGHT PRESS 118--1.2WORKSTATION DROP20/12223-1.2WORKSTATION DROP20/1242520/1COMMON RECEPTACLES.54--1.2WORKSTATION DROP20/1262720/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1282920/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1303120/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1323320/1WORKSTATION DROP1.2--2.52EF-5g, EF-5h15/3343520/1WORKSTATION DROP1.2-363720/1WORKSTATION DROP1.2-383920/1LIGHTING1.19--.4TF-1e15/1404120/1LIGHTING1.36--0-20/14258.2950.12CONNECTED kVA TUB #1:108.41CONNECTED kVA TUB #2:50.40TOTAL CONNECTED AMPERES:441.34NOTES:1. PROVIDE WITH FEED-THRU LUGS.PANELBOARD SCHEDULE (SECTION #1)PANEL: PB22A VOLTS:120/208 NEW/EXISTING.: NEWMAIN: MCBBUS AMPS:600A MOUNT.: SURFACEPH/WIRE: 3/4AIC:- LOC: PRODUCTION BCIR.AMPS/POLESDESCRIPTION OF LOADLOADkVANOTENOTELOADkVADESCRIPTION OF LOADAMPS/POLESCIR.150/2KNIGHT PRESS 128.00--8KNIGHT PRESS 1350/2234550/2KNIGHT PRESS 148.00--8KNIGHT PRESS 1550/2678950/2KNIGHT PRESS 168.00--8KNIGHT PRESS 1750/21011121350/2KNIGHT PRESS 188.00--8KNIGHT PRESS 1950/21415161720/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1181920/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1202120/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1222320/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1242520/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1262720/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1282915/1TF-1d.40--2.52EF-5e, EF-5f15/3303120/1SMOKE DAMPERS.10-323320/1SPARE0-343520/1COMMON RECEPTACLES.36--0SPARE20/1363720/1SPARE0--0SPARE20/13839--0--0--4041--0--0--4240.0641.72CONNECTED kVA TUB #1:81.78CONNECTED kVA TUB #2:45.24TOTAL CONNECTED AMPERES:352.99NOTES:1. PROVIDE WITH FEED-THRU LUGS.PANELBOARD SCHEDULE (SECTION #1)PANEL: PB23A VOLTS:120/208 NEW/EXISTING.: NEWMAIN: MCBBUS AMPS:600A MOUNT.: SURFACEPH/WIRE: 3/4AIC:- LOC: PRODUCTION BCIR.AMPS/POLESDESCRIPTION OF LOADLOADkVANOTENOTELOADkVADESCRIPTION OF LOADAMPS/POLESCIR.150/2KNIGHT PRESS 208--8KNIGHT PRESS 2150/2234550/2KNIGHT PRESS 228--8KNIGHT PRESS 2350/2678950/2KNIGHT PRESS 248--8KNIGHT PRESS 2550/21011121350/2KNIGHT PRESS 268--8KNIGHT PRESS 2750/21415161720/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1181920/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1202120/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1222320/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1242520/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1262720/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1282915/1TF-1c.4--2.52EF-5c, EF-5d15/3303120/1-0-323320/1-0-343520/1COMMON RECEPTACLES.36--0-20/1363720/1-0--0-20/1383920/1-0--0-20/1404120/1-0--0-20/14239.9641.72CONNECTED kVA TUB#1:81.68CONNECTED kVA TUB#2:44.56TOTAL CONNECTED AMPERES:350.82NOTES:1. PROVIDE WITH FEED-THRU LUGS.PANELBOARD SCHEDULE (SECTION #2)PANEL: PB21B VOLTS:120/208 NEW/EXISTING.: NEWMAIN: MLOBUS AMPS:600A MOUNT.: SURFACEPH/WIRE: 3/4AIC:- LOC: PRODUCTION BCIR.AMPS/POLESDESCRIPTION OF LOADLOADkVANOTENOTELOADkVADESCRIPTION OF LOADAMPS/POLESCIR.120/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/12320/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/14520/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/16720/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/18920/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1101120/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1121320/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1141520/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1161720/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1181920/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1202120/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1222320/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1242520/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1262720/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1282920/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1303120/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1323320/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1343520/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1363720/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1383920/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1404120/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/14225.2025.20 CONNECTED kVA TUB #2:50.40PANELBOARD SCHEDULE (SECTION #2)PANEL: PB22B VOLTS:120/208 NEW/EXISTING.: NEWMAIN: MLOBUS AMPS:600A MOUNT.: SURFACEPH/WIRE: 3/4AIC:- LOC: PRODUCTION BCIR.AMPS/POLESDESCRIPTION OF LOADLOADkVANOTENOTELOADkVADESCRIPTION OF LOADAMPS/POLESCIR.120/1WORKSTATION DROP1.2--1.02LIGHTING20/12320/1WORKSTATION DROP1.2--1.02LIGHING20/14520/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/16720/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/18920/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1101120/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1121320/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1141520/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1161720/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1181920/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1202120/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1222320/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1242520/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1262720/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1282920/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1303120/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1323320/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1343520/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1363720/1SPARE0--1.2WORKSTATION DROP20/1383920/1SPARE0--1.2WORKSTATION DROP20/1404120/1SPARE0--0SPARE20/14221.6023.64 CONNECTED kVA TUB #2:45.24PANELBOARD SCHEDULE (SECTION #2)PANEL: PB23B VOLTS:120/208 NEW/EXISTING.: NEWMAIN: MLOBUS AMPS:600A MOUNT.: SURFACEPH/WIRE: 3/4AIC:- LOC: PRODUCTION BCIR.AMPS/POLESDESCRIPTION OF LOADLOADkVANOTENOTELOADkVADESCRIPTION OF LOADAMPS/POLESCIR.120/1LIGHTING1.36--1.2WORKSTATION DROP20/12320/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/14520/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/16720/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/18920/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1101120/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1121320/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1141520/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1161720/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1181920/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1202120/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1222320/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1242520/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1262720/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1282920/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1303120/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1323320/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1343520/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1363720/1WORKSTATION DROP1.2--0-20/1383920/1-0--0-20/1404120/1-0--0-20/14222.9621.60 CONNECTED kVA TUB #2:44.56PANELBOARD SCHEDULEPANEL: HP21 VOLTS:120/208 NEW/EXISTING.: NEWMAIN: MLOBUS AMPS:400A MOUNT.: SURFACEPH/WIRE: 3/4AIC:- LOC: ELECTRICAL ROOMCIR.AMPS/POLESDESCRIPTION OF LOADLOADkVANOTENOTELOADkVADESCRIPTION OF LOADAMPS/POLESCIR.140/3RTU-19.36--9.36RTU-240/323456750/3RTU-315.48--15.55RTU-460/3891011121325/3RTU-55.70--21.13HV-180/314151617181980/3HV-221.13--1.83ACCU-115/220212223-1.83ACCU-215/2242515/3EF-5i1.26-2627-.31EF-715/12829-4.50EWH-230/23031--0-3233--0--0--3435--0--0--3637--0--0--3839--0--0--4041--0--0--4252.9354.51TOTAL CONNECTED kVA:107.44TOTAL CONNECTED AMPERES:298.58NOTES:1.JOB NO.:SCALE:CHECKED:DRAWN:Phone (978) 927-0053152 Conant Street, Beverly, MA 01915 connollybrothers.com2017-010Engineering plumbinghvac electricalfire protection NSEWTRUENCALLED2017-06-01 ISSUED FOR PRICINGE5.0PANELBOARDSCHEDULES 1 OF 2NTSRSCM PANELBOARD SCHEDULEPANEL: LP21 VOLTS:120/208 NEW/EXISTING.: NEWMAIN: MCBBUS AMPS:100A MOUNT.: SURFACEPH/WIRE: 3/4AIC:- LOC: ELEC-2CIR.AMPS/POLESDESCRIPTION OF LOADLOADkVANOTENOTELOADkVADESCRIPTION OF LOADAMPS/POLESCIR.120/1LIGHTING1.20--.95LIGHTING20/12320/1LIGHTING.86--.95LIGHTING20/14520/1LIGHTING.34--.47EXTERIOR LIGHTING20/16720/1-0--0-20/18920/1-0--0-20/1101120/1-0--0-20/1121320/1-0--0-20/1141520/1-0--0-20/1161720/1-0--0-20/1182.402.37TOTAL CONNECTED kVA:4.77TOTAL CONNECTED AMPERES:13.26NOTES:1.PANELBOARD SCHEDULE (SECTION #1)PANEL: PB24A VOLTS:120/208 NEW/EXISTING.: NEWMAIN: MCBBUS AMPS:600A MOUNT.: SURFACEPH/WIRE: 3/4AIC:- LOC: PRODUCTION BCIR.AMPS/POLESDESCRIPTION OF LOADLOADkVANOTENOTELOADkVADESCRIPTION OF LOADAMPS/POLESCIR.150/2KNIGHT PRESS 288--8KNIGHT PRESS 2950/2234550/2KNIGHT PRESS 308--8KNIGHT PRESS 3150/2678950/2KNIGHT PRESS 328--8KNIGHT PRESS SPARE 350/21011121350/2KNIGHT PRESS SPARE 18--8KNIGHT PRESS SPARE 450/21415161750/2KNIGHT PRESS SPARE 28--2.52EF-5a, EF-5b15/31819202115/1TF-1a, TF-1b.8-222315/1EF-1.31--1.60HAND DRYER20/1242520/1HAND DRYER1.60--1.60HAND DRYER20/1262720/1HAND DRYER1.60--.60WATER COOLER20/1282920/1-0--0-20/1303120/1GARAGE DOOR1.5--.9BATHROOM 125, 126 RECEPTACLES20/1323320/1SHIPPING/RECIEVING REC.1.2--.9COMMON RECEPTACLES20/1343530/2EWH-14.5--0-20/13637-0-20/1383920/1-0--0-20/1404120/1-0--0-20/14251.5140.12CONNECTED kVA TUB #1:91.63CONNECTED kVA TUB #2:45.75TOTAL CONNECTED AMPERES:381.78NOTES:1. PROVIDE WITH FEED-THRU LUGS.PANELBOARD SCHEDULEPANEL: PO21 VOLTS:120/208 NEW/EXISTING.: NEWMAIN: MCBBUS AMPS:300A MOUNT.: FLUSHPH/WIRE: 3/4AIC:- LOC: COPY ROOMCIR.AMPS/POLESDESCRIPTION OF LOADLOADkVANOTENOTELOADkVADESCRIPTION OF LOADAMPS/POLESCIR.120/1SUPPLIES 111.36--.72PURCHASING 11020/12320/1PURCHASING 110.72--.9RECEP 10920/14520/1CONTROLLER OFFICE REC..72--1.0ELEVATOR CAB LIGHTING20/16720/1ENGINEERING 117.72--1.26OM/QM OFFICE RECEPTACLES20/18920/1OFFICE HALLWAY RECEPTACLES.9--.72ENGINEERING 11720/1101120/1ENGINEERING 117.72--.72ENGINEERING 11720/1121320/1LAB RECEPTACLES.54--.36FLOOR BOXES20/1141520/1BREAKROOM MICROWAVE1.2--1.2BREAKROOM TOASTER20/1161720/1BREAKROOM MICROWAVE1.2--1.2BREAKROOM TOASTER20/1181920/1BREAKROOM MICROWAVE1.2--1.2BREAKROOM TOASTER20/1202120/1BREAKROOM MICROWAVE1.2--1.2BREAKROOM TOASTER20/1222320/1SALES CUBICLES.72--1.26ADMIN & ACCOUNTING REC.20/1242520/1ADMIN & ACCOUNTING REC.1.26--1.08BREAKROOM RECEPTACLES20/1262720/1ENGINEERING 117.72--.72ENGINEERING 11720/1282920/1PURCHASING 110.72--.72PURCHASING 11020/130SECTION 2SECTION 23120/1BREAKROOM MICROWAVE1.2--1.2BREAKROOM MICROWAVE20/1323320/1BREAKROOM MICROWAVE1.2--1.2BREAKROOM MICROWAVE20/1343520/1BREAKROOM REFRIGERATOR1.5--1.5BREAKROOM REFRIGERATOR20/1363720/1LOBBY 100.54--1.0IT CLOSET20/1383920/1IT CLOSET1.0--.72PRODUCTION 106 RECEPTACLES20/1404120/1PRODUCTION 106 RECEPTACLES1.08--.90LAB COUNTER RECEPTS20/1424320/1SMOKE DAMPERS.10--5.00T.B.D.20/3444520/3T.B.D.5.00--4647-4849-0SPARE20/1505120/1SPARE0-0SPARE20/1525320/1SPARE0-0SPARE20/1545520/1SPARE027.23PANEL PO22150/3565720/1SPARE0585920/1SPARE06024.5253.01TOTAL CONNECTED kVA:77.53TOTAL CONNECTED AMPERES:215.46NOTES:1.PANELBOARD SCHEDULEPANEL: MP21 VOLTS:120/208 NEW/EXISTING.: NEWMAIN: MCBBUS AMPS:400A MOUNT.: SURFACEPH/WIRE: 3/4AIC:- LOC: PRODUCTION BCIR.AMPS/POLESDESCRIPTION OF LOADLOADkVANOTENOTELOADkVADESCRIPTION OF LOADAMPS/POLESCIR.120/1WORKSTATION DROP1.2--1.4WORKSTATION DROP20/12320/1WORKSTATION DROP1.2--1.4WORKSTATION DROP20/14520/1WORKSTATION DROP1.2--1.4WORKSTATION DROP20/16720/1WORKSTATION DROP1.2--.9BATHROOM 120, 121 REC.20/18920/2UNDERCOUNTER OVEN2.81-.9MAINT. ROOM RECEPTACLES20/11011-.72MAINT. ROOM RECEPTACLES20/1121320/2UNDERCOUNTER OVEN2.81-1.0FACP20/11415-1.2WORKSTATION DROP20/1161720/2UNDERCOUNTER OVEN2.81-1.2WORKSTATION DROP20/11819-1.2WORKSTATION DROP20/1202150/2KNIGHT PRESS 338--1.2WORKSTATION DROP20/12223--1.2WORKSTATION DROP20/1242550/2KNIGHT PRESS 348--1.2WORKSTATION DROP20/12627--1.2WORKSTATION DROP20/1282950/2KNIGHT PRESS 358--1.2WORKSTATION DROP20/13031--1.2WORKSTATION DROP20/1323350/2KNIGHT PRESS 368--1.2WORKSTATION DROP20/13435--1.2WORKSTATION DROP20/1363720/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1383920/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1404120/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1424320/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1444520/1WORKSTATION DROP1.2--.31EF-215/1464720/1HAND DRYER1.60--1.60HAND DRYER20/1484920/1HAND DRYER1.60--1.60HAND DRYER20/1505120/1-0--0-20/1525320/1-0--0-20/15454.4029.23TOTAL CONNECTED kVA:83.63TOTAL CONNECTED AMPERES:232.41NOTES:1. E.C. SHALL COORDINATE EXACT REQUIREMENTS WITH SUBMITTED EQUIPMENT.PANELBOARD SCHEDULE (SECTION #2)PANEL: PB24B VOLTS:120/208 NEW/EXISTING.: NEWMAIN: MLOBUS AMPS:600A MOUNT.: SURFACEPH/WIRE: 3/4AIC:- LOC: PRODUCTION BCIR.AMPS/POLESDESCRIPTION OF LOADLOADkVANOTENOTELOADkVADESCRIPTION OF LOADAMPS/POLESCIR.120/1LIGHTING.51--1.02LIGHTING20/12320/1LIGHTING1.02--1.2WORKSTATION DROP20/14520/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/16720/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/18920/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1101120/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1121320/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1141520/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1161720/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1181920/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1202120/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1222320/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1242520/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1262720/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1282920/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1303120/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1323320/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1343520/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1363720/1WORKSTATION DROP1.2--1.2WORKSTATION DROP20/1383920/1WORKSTATION DROP1.2--0-20/1404120/1-0--0-20/14223.1322.62 CONNECTED kVA TUB #2:45.75PANELBOARD SCHEDULEPANEL: PO22 VOLTS:120/208 NEW/EXISTING.: NEWMAIN: MCBBUS AMPS:150A MOUNT.: FLUSHPH/WIRE: 3/4AIC:- LOC: COPY ROOMCIR.AMPS/POLESDESCRIPTION OF LOADLOADkVANOTENOTELOADkVADESCRIPTION OF LOADAMPS/POLESCIR.120/1SPARE ROOM 219 RECEPTACLES1.08--1.26SECOND FLOOR HALLWAY REC.20/12320/1SALES/HR OFFICE RECEPTACLES1.4--1.08SALES CUBICLES20/14520/1SALES CUBICLES1.08--.72ADMIN/ACC. CUBICLES20/16720/1ADMIN/ACC. CUBICLES.72--.9PRES. OFFICE RECEPTACLES20/18920/1SM. CONF. 202.9--.36SECOND FLOOR BATHROOM REC.20/1101120/1SECOND FLOOR JC RECEPTACLES.36--.72CONTROLLER 201 RECEPTACLES20/1121320/1LARGE CONF. 208 RECEPTACLES.9--.9LARGE CONF. 208 RECEPTACLES20/1141520/1BREAKROOM MICROWAVE1.2--1.2BREAKROOM TOASTER20/1161720/1BREAKROOM COFFEE1.5--1.5BREAKROOM REFRIGERATOR20/1181920/1BREAKROOM RECEPTACLES.54--1.17LIGHTING20/1202120/1ROOFTOP RECEPTACLES.72--1.41LIGHTING20/1222315/1EF-3, EF-4 & EF-6.10--1.01LIGHTING20/1242530/2EWH-34.50--0SPARE20/12627-0SPARE20/1282920/1SPARE0--0SPARE20/1303120/1SPARE00SPARE20/1323320/1SPARE00SPARE20/13435--00--3637--00--3839--00--4041--00--4215.0012.23TOTAL CONNECTED kVA:27.23TOTAL CONNECTED AMPERES:75.67NOTES:1.PANELBOARD SCHEDULE (SECTION #1)PANEL: LZ21A VOLTS:120/208 NEW/EXISTING.: NEWMAIN: MCBBUS AMPS:400A MOUNT.: SURFACEPH/WIRE: 3/4AIC:- LOC: PRODUCTION BCIR.AMPS/POLESDESCRIPTION OF LOADLOADkVANOTENOTELOADkVADESCRIPTION OF LOADAMPS/POLESCIR.115/1LAZER1.3--1.3LAZER15/12315/1LAZER1.3-1.3LAZER15/14515/1LAZER1.3--1.3LAZER15/16715/1LAZER1.3-1.3LAZER15/18915/1LAZER1.3--1.3LAZER15/1101115/1LAZER1.3-1.3LAZER15/1121315/1LAZER1.3--1.3LAZER15/1141515/1LAZER1.3-1.3LAZER15/1161715/1LAZER1.3--1.3LAZER15/1181915/1LAZER1.3-1.3LAZER15/1202115/1LAZER1.3--1.3LAZER15/1222315/1LAZER1.3--1.3LAZER15/1242515/1LAZER1.3--1.3LAZER15/1262715/1LAZER1.3--1.3LAZER15/1282915/1LAZER1.3--1.3LAZER15/1303115/1LAZER1.3--1.3LAZER15/1323315/1LAZER1.3--1.3LAZER15/1343515/1LAZER1.3--1.3LAZER15/1363715/1LAZER1.3--1.3LAZER15/1383915/1LAZER1.3--1.3LAZER15/1404115/1LAZER1.3--1.3LAZER15/14227.3027.30CONNECTED kVA TUB #1:54.60CONNECTED kVA TUB #2:45.75TOTAL CONNECTED AMPERES:278.87NOTES:1. PROVIDE WITH FEED-THRU LUGS.PANELBOARD SCHEDULE (SECTION #2)PANEL: LZ21B VOLTS:120/208 NEW/EXISTING.: NEWMAIN: MLOBUS AMPS:400A MOUNT.: SURFACEPH/WIRE: 3/4AIC:- LOC: PRODUCTION BCIR.AMPS/POLESDESCRIPTION OF LOADLOADkVANOTENOTELOADkVADESCRIPTION OF LOADAMPS/POLESCIR.120/1AIR PURIFIER1.8--1.8AIR PURIFIER20/12320/1AIR PURIFIER1.8--1.8AIR PURIFIER20/14520/1AIR PURIFIER1.8--1.8AIR PURIFIER20/16720/1AIR PURIFIER1.8--1.8AIR PURIFIER20/18920/1AIR PURIFIER1.8--1.8AIR PURIFIER20/1101120/1AIR PURIFIER1.8--1.8AIR PURIFIER20/1121320/1AIR PURIFIER1.8--1.8AIR PURIFIER20/1141520/1AIR PURIFIER1.8--1.8AIR PURIFIER20/1161720/1AIR PURIFIER1.8--1.8AIR PURIFIER20/1181920/1AIR PURIFIER1.8--1.8AIR PURIFIER20/1202120/1AIR PURIFIER1.8--0-20/1222320/1-0--0-20/1242520/1-0--0-20/1262720/1-0--0-20/1282920/1-0--0-20/1303120/1-0--0-20/1323320/1-0--0-20/1343520/1-0--0-20/1363720/1-0--0-20/1383920/1-0--0-20/1404120/1-0--0-20/14219.8018.00 CONNECTED kVA TUB #2:37.80JOB NO.:SCALE:CHECKED:DRAWN:Phone (978) 927-0053152 Conant Street, Beverly, MA 01915 connollybrothers.com2017-010Engineering plumbinghvac electricalfire protection NSEWTRUENCALLED2017-06-01 ISSUED FOR PRICINGE5.1PANELBOARDSCHEDULES 2 OF 2NTSRSCM JOB NO.:SCALE:CHECKED:DRAWN:Phone (978) 927-0053152 Conant Street, Beverly, MA 01915 connollybrothers.com2017-010Engineering plumbinghvac electricalfire protection NSEWTRUENCALLED2017-06-01 ISSUED FOR PRICINGMECHANICAL EQUIPMENT SCHEDULEEQUIPTAGDESCRIPTIONLOADPANEL SOURCEBRANCH CIRCUITCONNECTIONNOTESHPKVAVOLTPHPANELC/BFLEXJBRECDISCROOFTOP UNIT-8.42083HP21-(1,3,5)40A/3P(3)#8, (1)#10G, 1"CXROOFTOP UNIT-8.42083HP21-(2,4,6)40A/3P(3)#8, (1)#10G, 1"CXROOFTOP UNIT-11.82083HP21-(7,9,11)50A/3P(3)#6, (1)#10G, 1"CXROOFTOP UNIT-15.62083HP21-(8,10,12)60A/3P(3)#6, (1)#10G, 1"CXROOFTOP UNIT-5.82083HP21-(13,15,17)25A/3P(3)#10, (1)#10G, 3/4"CXAIR COOLINGCONDENSINGUNIT-1.832081HP21-(20,22)15A/2P(2)#12, (1)#12G, 3/4"CXAIR COOLINGCONDENSINGUNIT-1.832081HP21-(24,26)15A/2P(2)#12, (1)#12G, 3/4"CXHEAT PUMP--2081FED VIA ACCU-1X11HEAT PUMP--2081FED VIA ACCU-2X11EXHAUST FAN-.311201PB24A-(23)15A/1P(2)#12, (1)#12G, 3/4"CX8EXHAUST FAN-.311201MP21-(46)15A/1P(2)#12, (1)#12G, 3/4"CX8EXHAUST FAN-.011201PO22-(23)15A/1P(2)#12, (1)#12G, 3/4"CX8EXHAUST FAN-.011201PO22-(23)15A/1P(2)#12, (1)#12G, 3/4"CX8EXHAUST FAN3/41.262083PB24A-(18,20,22)15A/3P(3)#12, (1)#12G, 3/4"CXEXHAUST FAN3/41.262083PB24A-(18,20,22)15A/3P(3)#12, (1)#12G, 3/4"CXEXHAUST FAN3/41.262083PB23A-(30,32,34)15A/3P(3)#12, (1)#12G, 3/4"CXEXHAUST FAN3/41.262083PB23A-(30,32,34)15A/3P(3)#12, (1)#12G, 3/4"CXEXHAUST FAN3/41.262083PB22A-(30,32,34)15A/3P(3)#12, (1)#12G, 3/4"CXEXHAUST FAN3/41.262083PB22A-(30,32,34)15A/3P(3)#12, (1)#12G, 3/4"CXEXHAUST FAN3/41.262083PB21A-(34,36,38)15A/3P(3)#12, (1)#12G, 3/4"CXEXHAUST FAN3/41.262083PB21A-(34,36,38)15A/3P(3)#12, (1)#12G, 3/4"CXEXHAUST FAN3/41.262083HP21-(25,27,29)15A/3P(3)#12, (1)#12G, 3/4"CXEXHAUST FAN-.011201PO22-(23)15A/1P(2)#12, (1)#12G, 3/4"CX8EXHAUST FAN-.311201HP21-(28)15A/1P(2)#12, (1)#12G, 3/4"CX8ELECTRIC WATERHEATER-4.502081PB24A-(35,37)30A/2(2)#10, (1)#10G, 3/4"CX12ELECTRIC WATERHEATER-4.502081HP21-(30,32)30A/2(2)#10, (1)#10G, 3/4"CX12ELECTRIC WATERHEATER-4.502081PO22-(25,27)30A/2(2)#10, (1)#10G, 3/4"CX12TRANSFER FAN1/6.401201PB24A-(21)15A/1P(2)#12, (1)#12G, 3/4"CX8TRANSFER FAN1/6.401201PB24A-(21)20A/1P(2)#12, (1)#12G, 3/4"CX8TRANSFER FAN1/6.401201PB23A-(29)15A/1P(2)#12, (1)#12G, 3/4"CX8TRANSFER FAN1/6.401201PB22A-(29)15A/1P(2)#12, (1)#12G, 3/4"CX8TRANSFER FAN1/6.401201PB21-(40)15A/1P(2)#12, (1)#12G, 3/4"CX8HEATING ANDVENTILATIONUNIT-21.132083HP21-(14,16,18)80A/3P(3)#4, (1)#8G, 1"CXHEATING ANDVENTILATIONUNIT-21.132083HP21-(19,21,23)80A/3P(3)#4, (1)#8G, 1"CXNOTES:1. BRANCH CIRCUIT WIRING METHODS SHALL BE AS NOTED ON THE DRAWINGS AND/OR SPECIFICATIONS FOR THE APPLICABLE LOCATION.2. "FLEX" - DENOTES FINAL THREE FEET (MAXIMUM) OF RACEWAY SHALL BE FLEXIBLE METAL OR LIQUIDTIGHT METAL CONDUIT.3. "JB" - JUNCTION BOX DENOTES FINAL CONNECTION TO BOX OR CONTROL PANEL PREWIRED TO THE EQUIPMENT.4. "REC" - PROVIDE RECEPTACLE IN THE NEMA CONFIGURATION NOTED.5. NOTES 6-9 ARE OPTIONS WHICH SHALL BE SPECIFICALLY NOTED IN REMARKS FOR INCLUSION.6. DISCONNECT SHALL BE FUSIBLE.7. DISCONNECT SHALL BE NEMA "3R"8. DISCONNECT SHALL BE MOTOR-RATED SWITCH WITH THERMAL OVERLOAD ELEMENT.9. DISCONNECT PROVIDED INTEGRAL (PREWIRED) TO EQUIPMENT BY OTHERS.10. INTEGRAL CONVENIENCE RECEPTACLE PROVIDED PREWIRED TO EQUIPMENT BY OTHERS.11. REFER TO MANUFACTURERS RECOMMENDED WIRING DIAGRAMS.12. E.C. TO CONVERT UNBALANCED THREE PHASE DELTA WATER HEATERS TO SINGLE PHASE AT TERMINAL BLOCK. REFER TO MANUFACTURERS WIRING DIAGRAMS.1RTU2RTU3RTU4RTU5RTU1ACCU2ACCU1HP2HP1EF2EF3EF4EF5aEF5bEF5cEF5dEF5eEF5fEF5gEF5hEF5iEF6EF7EF1EWH2EWH3EWH1aTF1bTF1cTF1dTF1eTF1HV2HVE5.2EQUIPMENTSCHEDULESNTSRSCMLIGHTING FIXTURE SCHEDULETYPESYMBOLMANUFACTURERSCATALOG NUMBERDESCRIPTIONLAMPSINPUTREMARKSNO.TYPEVOLTSWATTSALT-2-4-L43/835-AF-DIM-UNV2x4 LED TROFFER-LEDMVOLT40H.E. WILLIAMSAELT-2-4-L43/835-AF-EM/10W-DIM-UNV2x4 LED TROFFER W/EMERGENCY BATTERY-LEDMVOLT40H.E. WILLIAMSBLT-2-2-L34/835-AF-DIM-UNV2x2 LED TROFFER-LEDMVOLT36H.E. WILLIAMSBELT-2-2-L34/835-AF-EM/10W-DIM-UNV2x2 LED TROFFER W/EMERGENCY BATTERY-LEDMVOLT36H.E. WILLIAMSCL60-L20C/835-CS-M-DIM-1206" RECESSED LEDDOWNLIGHT-LEDMVOLT26H.E. WILLIAMSCEL60-L20C/835-CS-M-EM/12W-DIM-1206" RECESSED LEDDOWNLIGHT W/ EMERGENCYBATTERY-LEDMVOLT26H.E. WILLIAMSDGL-4-L200/840-OCCLVHB011-VOLT-6CPL-L7-15P/TWLK-DIM-277LED HIGH BAY 20000 LUMENS40K-LED120170H.E. WILLIAMSDEGL-4-L200/840-EM/12W/BMTD-OCCLVHB011-VOLT-6CPL-L7-15P/TWLK-DIM-277LED EMERGENCY HIGH BAY20000 LUMENS 40K W/EMERGENCY BATTERY-LED120170H.E. WILLIAMSES1TEX-EM-R-*EDGE LIT EXIT SIGN W/BATTERY BACKUP-LED2773.4*MOUNTING, NUMBER OFFACES AND DIRECTIONALARROWS PER PLANSEVENLITEFHP-4-R-*-S-835-FL-UNV-SC-VF-X4" RECESSED SLOT LED-LEDMVOLT10/FT*PROVIDE LENGTHS AS INDICATEDON PLANSFINELITEGLSL60-L20C/835-DPL-DRV-1206"' ROUND LED SHOWERLIGHT-LED12026H.E. WILLIAMSHHES-2-4-L50/835-A-DRV-UNVSURFACE MOUNT 2x4 LED-LEDMVOLT52H.E. WILLIAMSHEHES-2-4-L50/835-A-EM/10W-DRV-UNVSURFACE MOUNT 2x4 LED W/EMERGENCY BATTERY-LEDMVOLT52H.E. WILLIAMSJ76-4-L53/835-WG-7611-VBY-2-DRV-UNVLED STRIP W/ WIREGUARD-LEDMVOLT48H.E. WILLIAMSJE76-4-L53/835-EM/10W-WG-7611-VBY-2-DRV-UNVLED STRIP W/ WIREGUARDAND EMERGENCY BATTERY-LEDMVOLT48H.E. WILLIAMSS1TRP-30L-3K-053-4-1-DE-PC-SCP-20FEXTERIOR WALL MOUNT LED-LED12053SPAULDINGS1ETRP-30L-3K-053-4-1-DE-PC-SCP-20F-BBUEXTERIOR WALL MOUNT LEDWITH EMERGENCY BATTERY-LED12053SPAULDINGNOTES:1. NOTES 2-9 APPLY TO ALL APPLICABLE LIGHTING FIXTURES. THE REMARKS COLUMN SHALL NOTE ADDITIONAL REQUIREMENTS.2. FIXTURES SPECIFIED WITH CATALOG NUMBERS ESTABLISH QUALITY LEVEL FOR EQUAL FIXTURES FROM MANUFACTURERS LISTED WITHOUT CATALOG NUMBERS. WHERE ONLY ONE MANUFACTURER LISTED, THERE SHALL BE NO SUBSTITUTION.3. VERIFY EXACT MOUNTING CONDITIONS AND PROVIDE APPROPRIATE ACCESSORIES AND HARDWARE TO ACCOMMODATE REQUIREMENTS.4. FIXTURE TYPE INDICATED ONCE ON A CONTINUOUS ROW SHALL BE TYPICAL OF ALL FIXTURES IN THE ROW UNLESS NOTED OTHERWISE.5. CONTINUOUS ROWS OF FIXTURES SHALL BE PROVIDED WITH ALL NECESSARY HARDWARE AND FILLERS TO PROVIDE THE EXACT LENGTHS AS INDICATED ON THE PLANS. FIXTURES IN SOFFITS SHALL BE CONTINUOUS END TO END.6. PROVIDE ALL FLUORESCENT FIXTURES WITH ELECTRONIC BALLASTS WITH MAXIMUM THD OF 20%, PF GREATER THAN 97% AND BF GREATER THAN 0.9. BALLASTS SHALL BE PROGRAMMED RAPID START WITH END-OF-LAMP-LIFE PROTECTION.7. BALLAST EFFICIENCY SHALL BE GREATER THAN THAT REQUIRED TO ENSURE THAT THE VALUE LISTED FOR INPUT WATTS IS NOT EXCEEDED.8. FLUORESCENT LAMPS SHALL HAVE A MINIMUM CRI OF 82. LAMP COLOR SHALL BE AS LISTED IN THE SCHEDULE.9. PROVIDE EXIT SIGNS WITH ARROWS AND MOUNTING ACCESSORIES AS INDICATED ON THE PLANS. JOB NO.:SCALE:CHECKED:DRAWN:Phone (978) 927-0053152 Conant Street, Beverly, MA 01915 connollybrothers.com2017-010Engineering plumbinghvac electricalfire protection NSEWTRUENCALLED2017-06-01 ISSUED FOR PRICINGE6.0ONE-LINE &RISER DIAGRAMSNTSRSCMREFER TOSITE PLAN4000A3P1600AF1600ATPANELLP21100AF100ATPANELPB21A600AF600ATPANELPB22APANELPB23APANELPB24APANELPO21SEC. 1400AF300AT1(:0$,1',675,%87,216:,7&+%2$5'0'3$0&%6(59,&((175$1&(5$7('<9‘:.$&M110[(4)#600kCMIL,4"C]METERINGCT'S ATTRANSFORMERMCOLUMNONE-LINE DIAGRAM NOTES:1PROVIDE FULLY RATED CIRCUIT BREAKER2E.C. SHALL DISCONNECT EXISTING ELECTRICAL SERVICE FEEDING DP1. E.C.SHALL RE-FEED DP1 FROM NEW SWITCHBOARD. REFER TO E4.0B FORADDITIONAL INFORMATION.3EXISTING MAIN DISCONNECT SHALL HAVE TRIP SETTING ADJUSTED TO1600A.#NOT TO SCALESCALE:ONE-LINE DIAGRAMTELEPHONEBACKBOARD123GROUNDBAR JUMPERBONDSTRUCTURALSTEELTYP. REBARSERVICE GROUNDING DETAILNOTES:1.PROVIDE THREE (3) DRIVENGROUND RODS AND 20 FTGROUND RING ON BUILDINGEXTERIOR IN ACCORDANCE WITHNEC SECTION 250.2.#4 BARE GROUND WIRECONNECTED TO REBAR INFOOTING OR WALL. REBAR TIEWIRES SHALL BOND ALL OTHERREBARS IN ACCORDANCE WITHNEC SECTION 250.3.BOND TO METAL UNDERGROUNDWATER PIPE IN ACCORDANCEWITH NEC SECTION 250.4.GROUNDING ELECTRODECONDUCTOR SIZED INACCORDANCE WITH NECSECTION 250.66.4REFER TOONE-LINEREFER TOGROUNDINGDETAILGLEGEND OF FEEDER SIZES - COPPER CONDUCTORSFEEDERTAGSYMBOLCOPPER CONDUCTORS(3-PHASE, 3-WIRE WITHGROUND) OR (1-PHASE, 3-WIREWITH GROUND)FOR ALL FEEDERS ANDBRANCH CIRCUITS OTHERTHAN TENANT LOADCENTERFEEDERSRACEWAYSIZECONDUITCOPPER CONDUCTORS(3-PHASE, 4-WIRE WITHGROUND)FOR ALL FEEDERS AND BRANCHCIRCUITS OTHER THAN TENANTLOADCENTER FEEDERSRACEWAYSIZECONDUITNOMINAL AMPERERATING30.33#10 & 1#10G3/4"3030.44#10 & 1#10G3/4"40.33#8 & 1#10G1"4040.44#8 & 1#10G1"50.33#8 & 1#10G1"5050.44#8 & 1#10G1"60.33#6 & 1#10G1"6060.44#6 & 1#10G1-1/4"70.33#4 & 1#8G1"7070.44#4 & 1#8G1-1/4"80.33#4 & 1#8G1"8080.44#4 & 1#8G1-1/4"90.33#3 & 1#8G1-1/4"9090.44#3 & 1#8G1-1/2"100.33#3 & 1#8G1-1/4"100100.44#3 & 1#8G1-1/2"125.33#1 & 1#6G1-1/2"125125.44#1 & 1#6G2"150.33#1/0 & 1#6G1-1/2"150150.44#1/0 & 1#6G2"175.33#2/0 & 1#6G2"175175.44#2/0 & 1#6G2"200.33#3/0 & 1#6G2"200200.44#3/0 & 1#6G2"225.33#4/0 & 1#4G2"225225.44#4/0 & 1#4G2-1/2"250.33#250 KCMIL & 1#4G2-1/2"250250.44#250 KCMIL & 1#4G3"300.33#350 KCMIL & 1#4G3"300300.44#350 KCMIL & 1#4G3"350.33#500 KCMIL & 1#3G3-1/2"350350.44#500 KCMIL & 1#3G4"400.33#600 KCMIL & 1#3G3-1/2"400400.44#600 KCMIL & 1#3G4"500.32[3#250 KCMIL & 1#2G](2)2-1/2"500500.42[4#250 KCMIL & 1#2G](2)3"600.32[3#350 KCMIL & 1#1G](2)3"600600.42[4#350 KCMIL & 1#1G](2)3"NOTES:1.#1600.4100.4300.4236"FLOOR LEVELBEAM4" SQUARE BELL BOXWITH DOUBLE DUPLEXOUTLETS ANDSTAINLESS STEELCOVERPLATEWIRE MESH STRAINRELIEF GRIP SUPPORTWIRE MESH STRAINRELIEF GRIP SUPPORTPROVIDE SECURECONNECTION TO J-BOXCORD DROP DETAILScale: N.T.SSOJ CORD, SIZED PER BRANCHCIRCUIT CONDUCTORSJ-BOX WITH (2) TWIST LOCK20A 120V RECEPTACLES12"FLOOR LEVELSTRAIN RELIEF (TYP.)50A/2P DISCONNECTMOUNTED ONTO SIDEOF KNIGHT PRESSWIRE MESH STRAINRELIEF GRIP SUPPORTWIRE MESH STRAINRELIEF GRIP SUPPORTPROVIDE SECURECONNECTION TO J-BOXDISCONNECT CORD DROPDETAILScale: N.T.SSOJ CORD, (2)#8,(1)#10G4" SQUARE J-BOX COVERPANELMP21400A400AT400.4CONVENTIONAL FACPNOT TO SCALESCALE:FIRE ALARM RISER DIAGRAMXMFIRE ALARM RISER DIAGRAM NOTES:1QUANTITY OF DEVICES SHOWN ARE DIAGRAMMATIC ONLY, SEE FLOORPLANS FOR EXACT QUANTITIES AND LOCATIONS OF ALL DEVICES.2SEE SPECIFICATION FOR STANDARDS, SYSTEM OPERATION, MATERIALSAND TESTING REQUIREMENTS.3A NEW ADDRESSABLE FIRE ALARM CONTROL PANEL SHALL BE TIED INTO ASPARE ZONE ON THE CONVENTIONAL CONTROL PANEL.4COORDINATE ALL FIRE ALARM WORK WITH OWNER & FIRE ALARMMAINTENANCE COMPANY. (B.E.F. ENTERPRISES INC.)5EXISTING FIRE ALARM CONTROL PANEL IS A CONVENTIONAL TWELVE ZONEFIRE CONTROL INSTRUMENTS PANEL.#FSSXMXMXMSHTSXMFSXMFSXMXMSSFFFFXMXMXMXMXMXM5XMXMFXMFXMFXMFXMXMSFXMFXMFXMFXMRTSSRTSSXMXMXMXM600.4PANELLZ21A12345689101112137PANELPB21BPANELPB22BPANELPB23BPANELPB24BSPACESPACETYPICAL ELEVATOR REQUIREMENTSELEVATOR CONTROL ROOMELEV.LOBBY(TYP.)TYPICALLEVELMAINEGRESSLEVELNOTES:1.COORDINATE EXACT ELEVATOR REQUIREMENTS WITH ELEVATOR VENDOR PRIOR TOROUGH-IN/INSTALLATION.2.2" CONDUIT TO TELEPHONE BACKBOARD FOR ELEVATOR CAB EMERGENCY PHONE CONNECTION.3.PROVIDE AND INSTALL (3) ADDRESSABLE CONTROL MODULE DEVICES. (1) ONE TO INITIATEELEVATOR RECALL TO PRIMARY FLOOR, (1) ONE TO DIRECT RECALL TO ALTERNATE FLOOR, AND(1) ONE TO SIGNAL MACHINE ROOM SMOKE.4.TIE-IN OUTDOOR AIR DAMPER AT TOP OF SHAFT. INSTALL CONTROL MODULE WITHIN 3 FT OFDAMPER CONTROL.5.WHERE THERE IS A SPRINKLER IN THE MACHINE ROOM:5.1.3529,'(ƒ)),;('7(03(5$785(+($7'(7(&725:,7+,1)72)(9(5<635,1./(5HEAD. ACTIVATION OF HEAT DETECTOR SHALL SHUNT TRIP POWER TO THE ELEVATOR.6.FOR TIE-IN OF SHUNT TRIP BREAKER.CMSERSERHƒJ2SRAIACMACMACM31ACM6H5ELEVATORSHAFTDAMPER &CONTROLLER(BY OTHERS)4ELEV.DISC.CAB LTG.DISC.#ELEVATOR PITWPAPPLETON#VGAT1075G-AELEVCNTRLR200AS125AF20125.4BEAMLABEL EACH POLE WITH PANELAND CIRCUIT NUMBER"C" HANGER ASSEMBLYCONDUITJUNCTION BOX,LABELWITH PANEL &CIRCUITNUMBEREND CONNECTORLABELWITH PANEL &CIRCUITNUMBERFLEX CONDUITNOTCH CEILING PANELINSTALL TRIM PLATEPOWER POLEPANELPO22150.4GFIXM3(;,67,1*$<9‘:6:,7&+%2$5'3/8" J HOOKMOUNTED TOBEAM/UNISTRUT20A 120V TWIST LOCKRECEPTACLE PLUGNOTES:1. PROVIDE (2) 24'-0" EXTENSION CORD DROPS PER J-BOX DROPLOCATION.MOUNTING DETAILS FORPOWER POLESScale: N.T.SBE6.0CE6.0AE6.036"FLOOR LEVELBEAM4" SQUARE BELL BOXWITH TEL/DATAOUTLETS ANDSTAINLESS STEELCOVERPLATEWIRE MESH STRAINRELIEF GRIP SUPPORTWIRE MESH STRAINRELIEF GRIP SUPPORTPROVIDE SECURECONNECTION TO J-BOXTEL/DATA CORD DROP DETAILScale: N.T.SSOJ CORDJ-BOXNOTES:1. PROVIDE (2) 24'-0" EXTENSION CORD DROPS PER J-BOX DROPLOCATION.DE6.0WPPANELLZ21BL75cdF75cdF75cdF75cdFSFSFIRE ALARMCONTROLPANELRTSSTYP1AMMTSAMMANNTYP1PANELHP21225AF125AT600AF600AT600AF600AT600AF600AT400A400AT400A400ATELEVATORNEW UTILITYPAD ANDTRANSFORMERMPANELPO21SEC. 2 ELECTRICAL SPECIFICATIONSPART 1-GENERAL1.THE PROJECT INCLUDES INSTALLATION OF ELECTRICALSYSTEMS AT [ENTER JOB NAME AND ADDRESS].2.THE OWNERS GENERAL CONDITIONS, SPECIAL CONDITIONSAND SUPPLEMENTAL CONDITIONS OR REQUIREMENTS AREPART OF THIS WORK.3.EXAMINATION OF SITE AND CONTRACT DOCUMENT: BEFORESUBMITTING HIS PROPOSAL, THIS CONTRACTOR SHALL VISITTHE PREMISE AND REVIEW THE ENTIRE PROJECT. THECONTRACTOR SHALL DETERMINE THE DIFFICULTIES,CONDITIONS, AND DISPOSAL REQUIREMENTS WHICH MAY BEENCOUNTERED DURING THE WORK. ALL CHARGES RELATED TOMEETING THE INTENT OF THE DRAWINGS AND SPECIFICATIONSSHALL BE INCORPORATED INTO THE BID. IF DISCREPANCIESARISE BETWEEN THE DRAWINGS AND SPECIFICATIONS, THEMORE STRINGENT REQUIREMENT SHALL APPLY. NOADDITIONAL CHARGES WILL BE ALLOWED DUE TO EXISITNGCONDITIONS.4.THE EC SHALL FURNISH AND INSTALL ALL PANELBOARDS,METERING EQUIPMENT, CONDUIT, WIRE, BOXES, SWITCHES,LIGHTING FIXTURES, FIRE ALARM COMPONENTS, RECEPTACLESAND OTHER DEVICES REQUIRED FOR A COMPLETE ANDOPERATIONAL ELECTRICAL SYSTEM.5.THE INSTALLATION OF THE SYSTEMS SHALL CONFORM TO THEREQUIREMENTS OF THE MASSACHUSETTS ELECTRIC CODE,NATIONAL FIRE PROTECTION ASSOCIATION AND ALL OTHERAPPLICABLE FEDERAL, STATE AND LOCAL LAWS ANDORDINANCES.6.ALL MATERIALS SHALL BE NEW AND SHALL BEAR THEUNDERWRITERS' LABEL.7.OBTAIN AND PAY FOR ALL REQUIRED PERMITS, LICENSES ANDCERTIFICATES, INCLUDE ALL FEDERAL, STATE AND LOCALTAXES.8.WORKMANSHIP: THE ENTIRE WORK PROVIDED IN THISSPECIFICATION SHALL BE CONSTRUCTED AND FINISHED INEVERY RESPECT IN A WORKMANLIKE AND SUBSTANTIALMANNER. EQUIPMENT SHALL BE SECURELY INSTALLED PLUMBAND/OR LEVEL. NO ELECTRICAL EQUIPMENT SHALL BESUPPORTED BY WORK OF OTHER TRADES. OBTAIN DETAILEDINFORMATION FROM THE MANUFACTURERS OF APPARATUS ASTO THE PROPER METHOD OF INSTALLING AND CONNECTINGEQUIPMENT. OBTAIN ALL INFORMATION FROM THE GENERALCONTRACTOR AND OTHER SUBCONTRACTORS, WHICH MAY BENECESSARY TO FACILITATE WORK AND THE COMPLETION OFTHE WHOLE PROJECT.9.THE ELECTRICAL CONTRACTOR (EC) SHALL VERIFY THELOCATIONS AND MOUNTING HEIGHTS OF ALL EQUIPMENT,LIGHT FIXTURES, PANELBOARDS, OUTLETS AND MECHANICALEQUIPMENT WITH THE OWNER PRIOR TO COMMENCING ANYWORK.10.THE EC SHALL NOT BORE, NOTCH OR IN ANY WAY CUT INTOTHE STRUCTURAL MEMBER, WITHOUT PROPER WRITTENAPPROVAL OF THE STRUCTURAL ENGINEER.11.EXAMINE ALL DRAWINGS AND OTHER SECTIONS OF THESPECIFICATIONS FOR REQUIREMENTS WHICH AFFECT THEWORK OF THIS SECTION. COORDINATE WORK WITH OTHERTRADES.12.THE ELECTRICAL CONTRACTOR SHALL PROVIDE A COMPLETETEMPORARY LIGHTING AND POWER SYSTEM FOR THECONSTRUCTION OF THE PROJECT AND SHALL PAY FOR THECOST OF INSTALLATIONS. THE E.C. SHALL INCLUDE ALLCHARGES FROM THE UTILITY COMPANY TO CONNECT ANDDISCONNECT THE TEMPORARY SERVICE.13.RECORD DRAWINGS: IN ACCORDANCE WITH REQUIREMENTS,FURNISH AND KEEP IN THE JOB AT ALL TIMES, TWO (2)COMPLETE AND SEPARATE SETS OF BLACKLINE PRINTS OF THEELECTRICAL WORK ON WHICH SHALL BE CLEARLY, NEATLY ANDACCURATELY NOTED, PROMPTLY AS THE WORK PROGRESSES,ALL ELECTRICAL CHANGES, REVISIONS AND ADDITIONS TO THEWORK. WHENEVER WORK IS INSTALLED OTHERWISE THAN ASSHOWN ON THE CONTRACT DRAWINGS, SUCH CHANGES SHALLBE NOTED.AT THE CONCLUSION OF WORK, PREPARE RECORDDRAWINGS IN ACCORDANCE WITH GENERAL CONDITIONS.14.THE COMPLETED ELECTRICAL INSTALLATION SHALL BEGUARANTEED IN WRITING BY THE ELECTRICAL CONTRACTORTO BE FREE FROM DEFECTS OF MANUFACTURE ANDINSTALLATION FOR A PERIOD OF ONE YEAR FROM THE DATE OFWRITTEN ACCEPTANCE BY THE OWNER. ANY FAULT DUE TODEFECTIVE OR IMPROPER MATERIAL, EQUIPMENTWORKMANSHIP OR DESIGN WHICH MAY DEVELOP SHALL BEMADE GOOD FORTHWITH BY, AND AT THE EXPENSE OF THEELECTRICAL CONTRACTOR, INCLUDING ALL OTHER DAMAGESDONE TO AREAS, MATERIALS AND OTHER SYSTEMS RESULTINGFROM THIS FAILURE.15.THE EC SHALL NOTIFY THE OWNER UPON: (1) COMPLETION OFALL ROUGH WIRING BEFORE CLOSURE OF ALL WALLS AND (2)UPON "SUBSTANTIAL COMPLETION" OF ALL ELECTRICAL WORK.AFTER SUBSTANTIAL COMPLETION, THE OWNER'SREPRESENTATIVE SHALL PREPARE A PUNCH LIST OF ITEMS TOBE CORRECTED. THE EC SHALL CORRECT, AT NO ADDITIONALCOST, ANY DEFICIENCIES FOUND.16.RELATED WORK BY OTHERS16.1.THERMOSTATS AND CONTROL WIRING SHALL BE SUPPLIEDAND INSTALLED BY THE HVAC CONTRACTOR.16.2.STARTERS FOR MECHANICAL EQUIPMENT SHALL BESUPPLIED BY THE MECHANICAL CONTRACTOR, INSTALLEDAND WIRED BY THE ELECTRICAL CONTRACTOR.16.3.DUCT SMOKE DETECTORS ARE PURCHASED AND SUPPLIEDBY THE MECHANICAL CONTRACTOR. THE MECHANICALCONTRACTOR SHALL INSTALL DUCT SMOKE DETECTORS INDUCT AND PROVIDE SHUTDOWN CONTROL WIRING FROMTHE DUCT SMOKE DETECTOR TO THE MOTORCONTROLLER. WIRING FROM THE DUCT SMOKE DETECTORTO THE FIRE ALARM CONTROL PANEL SHALL BE PROVIDEDBY THE ELECTRICAL CONTRACTOR.16.4.CUTTING, PATCHING AND TRENCHING SHALL BE PROVIDEDBY THE GENERAL CONTRACTOR.17.SUBMITTALS: EC SHALL PROVIDE FOUR (4) COPIES OFSUBMITTALS FOR ELECTRICAL EQUIPMENT TO THE ENGINEERFOR APPROVAL PRIOR TO CONSTRUCTION. SUBMITTALS SHALLINDICATE ALL MATERIALS AND RATINGS. PROVIDEINFORMATION ON THE FOLLOWING ITEMS:a.SWITCHES AND RECEPTACLESb.PANELBOARDSc.SWITCHBOARDSd.LIGHTING FIXTURES AND CONTROLSe.ALL FIRE DETECTION SYSTEM COMPONENTSf.CIRCUIT BREAKERSg.FUSIBLE SWITCHESh.WIRING DEVICESi.CONDUITj.WIREk.TEST REPORTS17.1 THE ACCEPTANCE OF SYSTEMS, EQUIPMENT AND DATASHEETS IS A GENERAL APPROVAL SUBJECT TO THE CONTRACT DRAWINGS, SPECIFICATIONS, AND VERIFICATIONOF ALL MEASUREMENTS AT THE JOB. ACCEPTANCE DOESNOT RELIEVE THE ELECTRICAL CONTRACTOR FROM THE RESPONSIBILITY OF DATA SHEET ERRORS OR OMISSIONS.QUANTITY OF ITEMS INDICATED ON SUBMITTAL IS THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR.PART 2 - PRODUCTS1.GENERAL1.1.ALL MATERIALS AND EQUIPMENT NECESSARY TO MAKETHE INSTALLATION COMPLETE IN EVERY DETAIL SHALL BEFURNISHED AND INSTALLED UNDER THIS CONTRACT,WHETHER OR NOT SPECIFICALLY INDICATED ON THEDRAWINGS OR SPECIFIED HEREIN. ALL MATERIALS ANDEQUIPMENT SHALL BE NEW.1.2.IT IS THE INTENT OF THE SPECIFICATIONS THAT ONEMANUFACTURER BE SELECTED, NOT A COMBINATION, FORANY PARTICULAR CLASSIFICATION OF MATERIAL; FOREXAMPLE, ALL WIRE OF ONE MANUFACTURER, ALLSWITCHES OF ONE MANUFACTURER, ETC., EXCEPTSPECIFIC MATERIAL CLASSIFICATIONS IN WHICH DELIVERYTIME BECOMES A PROBLEM. THE ENGINEER MAY GIVESPECIFIC EXEMPTION FROM THE REQUIREMENTS.1.3.WHERE MATERIALS, EQUIPMENT, APPARATUS, OR OTHERPRODUCTS ARE SPECIFIED BY MANUFACTURER, BRANDNAME, TYPE OR CATALOG NUMBER, SUCH DESIGNATION ISTO ESTABLISH STANDARDS OF PERFORMANCE, QUALITY,TYPE, AND STYLE.2.FEEDERS: ALL FEEDERS BETWEEN PANELBOARDS ANDSWITCHBOARDS SHALL BE PROVIDED IN TYPE EMT CONDUIT;TYPE MC CABLE IS NOT PERMITTED.3.CONCEALED BRANCH CIRCUITS: ALL BRANCH CIRCUIT WIRINGSHALL BE CONCEALED WHENEVER POSSIBLE. WITHINCONCEALED SPACES SUCH AS ABOVE HUNG CEILING AREASAND WITHIN WALL PARTITIONS, BRANCH CIRCUIT WIRING SHALLBE TYPE MC CABLE, 12/2 WITH FULL SIZE INSULATED GROUNDWIRE.4.CONDUIT: ALL EXPOSED, OR SURFACE MOUNTED BRANCHCIRCUIT RUNS SHALL BE INSTALLED USING TYPE EMT CONDUIT.PROVIDE FIRE RESISTANT RATING AROUND ALL CONDUITSPENETRATING THROUGH FIRE RATED WALLS OR FLOORS.RATING OF FIRE PROOFING SHALL MATCH RATING OF WALLS.ALL CONDUIT AND EQUIPMENT SHALL BE INSTALLED ANDGROUNDED IN ACCORDANCE WITH THE LATEST RULES ANDREGULATIONS OF THE NATIONAL ELECTRICAL CODE. ALLCONDUITS SHALL HAVE A PROPER SIZE GROUNDINGCONDUCTOR. ALL CONNECTIONS TO MACHINERY ANDEQUIPMENT SUBJECT TO VIBRATION SHALL BE MADE WITHFLEXIBLE LIQUIDTIGHT CONDUIT. PROVIDE SUFFICIENT SLACKTO PREVENT VIBRATION TRANSMISSION.5.WIRING: WIRING SHALL BE A MINIMUM OF #12 AWG SOLID.NON-METALIC CONDUIT TYPE NMC/ROMEX SHALL NOT BE USED.ALL WIRE AND CABLE SHALL BE COPPER; NO ALUMINUM ISPERMITTED. WIRE AND CABLE SHALL BE MANUFACTURED BYPHELPS DODGE COPPER PRODUCTS CORP., GENERAL CABLECO., TRIANGLE CONDUIT AND CABLE CO., OR EQUAL.6.OUTLET BOXES AND ACCESSORIES:6.1.PROVIDE GALVANIZED SHEET STEEL OUTLET BOXES FORALL OUTLETS UNLESS OTHERWISE NOTED.6.2.ALL OUTLET BOXES FOR PENDANT-MOUNTED FIXTURESSHALL BE GALVANIZED, STAMPED STEEL FURNISHED WITHA FIXTURE STUD, SECURELY MOUNTED TO FRAMING6.3.ALL OUTLET BOXES FOR CONCEALED WORK SHALL BEGALVANIZED, STAMPED STEEL; THOSE FOR FIXTURES,FURNISHED WITH A FIXTURE STUD.6.4.OUTLET BOXES SHALL BE OF SIZE AND TYPE TOACCOMMODATE (1) STRUCTURAL CONDITIONS, (2) SIZE ANDNUMBER OF RACEWAYS, CONDUCTORS OR CABLESENTERING, AND (3) DEVICES OR FIXTURES FOR WHICHTHEY ARE REQUIRED.6.5.INSTALL BLANK PLATES ON ALL OUTLET BOXES, IN WHICHNO APPARATUS IS INSTALLED, WHICH DO NOT INTEGRALLYPROVIDE A COVER FOR THE BOX.6.6.SPECIAL CARE SHALL BE TAKEN TO SET ALL BOXESCORRECTLY SQUARE AND TRUE WITH THE BUILDINGFINISH.6.7.FIXTURE OUTLET BOXES SHALL HAVE 3/8" SOLID MALEFIXTURE STUDS AND AUXILIARY FIXTURE STEMS SHALL BESUPPORTED FROM 3/8" MALE FIXTURE STUDS.6.8.OUTLET BOXES AND ACCESSORIES SHALL BE ASMANUFACTURED BY STEEL CITY, APPLETON, RACO, OREQUAL.7.WIRING DEVICES: ALL WIRING DEVICES SHALL BE OF A SINGLEMANUFACTURER, AS MANUFACTURED BY PASS AND SEYMOUR,GENERAL ELECTRIC, HUBBELL, BRYANT ELECTRIC COMPANY,LEVITON, OR EQUAL. MANUFACTURERS LISTED BELOWESTABLISH MINIMUM REQUIREMENTS. COORDINATE COLORWITH ARCHITEALL7.1.20A COMMERCIAL GRADE RECEPTACLES SHALL BEGROUNDING TYPE, RATED AS INDICATED, AND 125V.RECEPTACLES SHALL BE BACK AND SIDE WIRED WITHSCREW TYPE TERMINALS OR PRESSURE TYPE,SCREWLESS TERMINALS EQUAL TO PASS & SEYMORE.7.2.SPECIAL EQUIPMENT RECEPTACLES AS REQUIRED SHALLHAVE AN ADDITIONAL GROUNDING LEG AND SHALL BE OFCAPACITY AND CONFIGURATION FOR THE EQUIPMENT TOBE CONNECTED.7.3.GFI RECEPTACLES SHALL EACH HAVE GFI TRIPPING (NOFEED THROUGH IS PERMITTED) AND EQUAL TO PASS &SEYMORE #2091-SI.7.4.DAMP LOCATION WEATHERPROOF RECEPTACLES SHALLHAVE AN ENCLOSURE THAT IS WEATHERPROOF WHEN THERECEPTACLE IS COVERED AND EQUAL TO HUBBELL MODELHBL5205WO.7.5.WET LOCATION WEATHERPROOF RECEPTACLES SHALLCONFORM TO NEC ARTICLE 406.8(B)(i) AND SHALL HAVE ANENCLOSURE THAT IS WEATHERPROOF WHETHER OR NOTTHE ATTACHMENT PLUG CAP IS INSERTED. PROVIDERECEPTACLE WITH COVER EQUAL TO PASS & SEYMOUR#WIUC107.6.FLOOR MOUNTED POKETHROUGH RECEPTACLES SHALL BELEGRAND MULTI-SERVICE POKE-THRU DEVICE, MODELNUMBER RC4, WITH ALL ACCESSORIES AS REQUIRED FORA COMPLETE INSTALLATION.7.7.THE INTENT OF THE SENSOR DESIGN IS FOR ALL WALLSWITCHES WORKING INDEPENDENTLY TO BE LINEVOLTAGE. CEILING SENSORS AND WALL SWITCHESWORKING IN CONJUNCTION WITH CEILING SENSORS SHALLBE LOW VOLTAGE. ALL LOW VOTLAGE SENSORS SHALL BEPROVIDED WITH ALL POWER PACKS AS REQUIRED:7.7.1.1.O1-CEILING MOUNTED, LOW VOLTAGE,INFRARED/ULTRASONIC, LEVITON #OSC10-RUW7.7.1.2.O1-HALLWAY SENSOR, LOW VOLTAGE,ULTRASONIC, MODEL #OSC20-RUW7.7.1.3.O1-WALL SWITCH, LINE VOLTAGE, ULTRASONIC,SINGLE POLE OCCUPANCY7.7.1.4.O2-WALL SWITCH, LINE VOLTAGE,INFRARED/ULTRASONIC, DUAL POLE OCCUPANCY7.7.1.5.VD-WALL SWITCH, LINE VOLTAGE, SINGLE POLEDIMMING VACANCY SENSOR LEVITON #OSD10-IOW7.7.1.4.V1-WALL SWITCH, LINE VOLTAGE,INFRARED/ULTRASONIC, SINGLE POLE VACANCYLEVITON #OSSMT-MD7.7.1.5.V2-WALL SWITCH, LINE VOLTAGE,INFRARED/ULTRASONIC, DUAL POLE VACANCYLEVITON #OSSMD-MD, 1000SQFT AREA CAN BELEVITON #OSC10-RMW7.7.1.6.V1-CEILING, LOW VOLTAGE,INFRARED/ULTRASONIC7.7.7.6.L - LOW VOLTAGE LIGHT SWITCH (MOMENTARY)FOR USE WITH CEILING MOUNT SENSORS. LEVITON#56081-2W. # OF BUTTONS REQUIRED SHALLMATCH SWITCH CONTROL INDICATED ON DWGS.7.7.7.6.LVD - LOW VOLTAGE DIMMING LIGHT SWITCH(MOMENTARY) FOR USE WITH CEILING MOUNTSENSORS. LEVITON #IP710-LFZ. # OF BUTTONSREQUIRED SHALL MATCH SWITCH CONTROLINDICATED ON DWGS.7.7.7.7.P - CEILING MOUNTED DAYLIGHT DIMMINGPHOTOCELL. LEVITON # ODCOP-DOW7.7.7.8.360 CEILING MOUNT DUAL TECH VACANCY SENSORLINE VOLTAGE WITH DIMMING PHOTOCELLLEVITON #05C20-MDW7.7.7.9.ON/OFF SWITCH (2 BUTTON) TO BE USED WITHLINE VOLTAGE CEILING SENSOR, SINGLE ZONELEVITON # PLVS-2LW OR DIMMING (4 BUTTON)LEVITON # PLVS-4LW.7.7.7.10.PROVIDE POWER PACKS WHERE REQUIREDLEVITON #OPP20-D2 OR OPP20-D4.7.7.7.11.TIME DELAY SETTINGS SHALL BE SET TO NO LESSTHAN 10 MINUTES.7.7.7.12.LEVITON WAS USED IN THE BASIS OF DESIGN. IFALTERNATIVE MANUFACTURER IS USED E.C. SHALLCONFIRM SENSORS PROVIDE FULL COVERAGE. .7.8.TIME CLOCKS AND DIGITAL TIME SWITCHES:7.8.1.DIGITAL TIMER SWITCH: INTERMATIC ST01.7.8.2.TIME CLOCK, TWO CIRCUIT: INTERMATIC ET2125C.7.8.3.TIME CLOCK, FOUR CIRCUIT: INTERMATIC ET2145C.8.CIRCUIT BREAKERS: ALL MULTI-POLE CIRCUIT BREAKERS SHALLBE COMMON INTERNAL TRIP. HANDLE TIES SHALL NOT BEPERMITTED. ALL CIRCUIT BREAKERS FEEDING BEDROOMRECEPTACLES SHALL BE ARC FAULT RATED AS REQUIRED BYCODE.9.EXISTING PANELBOARDS:9.1.THE EXISTING PANELBOARDS ARE SUITABLE FOR 120/208VOLTS, 3-PHASE, 4-WIRE AS PREVIOUSLY INSTALLED.9.2.WHERE CONNECTIONS ARE MADE IN EXISTINGPANELBOARDS, THE PANEL INDEX SHALL BE REVISED TOINDICATE THE NEW LOADS SERVED. ALL EXISTINGPANELBOARDS THAT DO NOT HAVE A CIRCUIT DIRECTORYCARD MOUNTED IN A FRAME WITH NONCOMBUSTIBLEPLASTIC COVER SHALL HAVE ONE INSTALLED ON THEINSIDE OF THE DOOR. ALL DIRECTORY CARDS SHALL BEPROPERLY FILLED IN, USING A TYPEWRITER, AND INDICATEAREAS AND DEVICES SERVED BY EACH UNIT.9.3.NEW CIRCUIT BREAKERS ADDED TO EXISTINGPANELBOARDS SHALL BE THE SAME FRAME SIZE ANDINTERRUPTING CAPACITY AS EXISTING PANELBORDS ANDCIRCUIT BREAKERS. CURRENT LIMITING CIRCUITBREAKERS SHALL NOT BE USED.10.PANELBOARDS: PROVIDE DEAD FRONT LIGHTING AND POWERPANEL BOARDS WITH PROPER VOLTAGE AND AMP RATING ASREQUIRED. PANELBOARDS SHALL BE SURFACE- ORFLUSH-MOUNTED AS REQUIRED. PROVIDE COPPER BUS BARSAND FULL SIZE INSULATED NEUTRAL BUS. PANEL BUSWORKSHALL BE RATED TO CARRY, AS MINIMUM, AMPERE RATING OFOVERCURRENT DEVICE THAT SERVES PANEL. PANELS WITHFEED_THROUGH BUSING SHALL NOT BE USED. PROVIDEANTI_TURN, SOLDERLESS LUGS SUITABLE FOR COPPER ORALUMINUM WIRE.PROVIDE SEPARATELY MOUNTED GROUNDBUS FOR EACH PANELBOARD. GROUND BUS SHALL BE BONDEDTO PANELBOARD ENCLOSURE. PROVIDE BOLT_ON, MOLDEDCASE, CIRCUIT BREAKERS WITH THERMAL _ MAGNETIC TRIPS.MULTIPLE POLE BREAKERS SHALL BE SINGLE HANDLE,COMMON TRIP. PROVIDE HANDLE LOCKS FOR EMERGENCYLIGHTING CIRCUITS, FIRE ALARM, SECURITY, OR OTHERSIMILAR FUNCTIONS. MAIN CIRCUIT BREAKERS SHALL BEMOUNTED VERTICALLY, SEPARATE FROM THE BRANCHBREAKERS. CURRENT LIMITING CIRCUIT BREAKERS SHALL NOTBE USED. PANELBOARD TRIM SHALL BE PROVIDED WITHDOOR-IN-DOOR CONSTRUCTION. PANELBOARD SHALL BECAPABLE OF SUPPORTING ADDITIONAL BOLT-ON CIRCUITBREAKERS WITHOUT MODIFICATION UP TO THE FRAME SIZESPECIFIED ON THE DRAWINGS. PROVIDE FULLY RATED CIRCUITBREAKERS EQUAL TO SHORT CIRCUIT INTERRUPTING CURRENTSPECIFIED. PROVIDE TYPED NAME CARD IN EACH PANELBOARD.CARD SHALL INDICATE EQUIPMENT, LIGHTING AREAS, ORRECEPTACLE AREAS FED BY EACH BRANCH CIRCUIT BREAKER.PANELBOARD DOORS SHALL HAVE FLUSH MOUNTED CATCHAND LOCK WITH TWO KEYS. ALL KEYS FOR PANELBOARDSSHALL BE KEYED ALIKE. PANELBOARDS SHALL BEMANUFACTURED BY GENERAL ELECTRIC, SIEMENS, SQUARE D,OR APPROVED EQUAL.11.LIGHTING FIXTURES: LIGHTING FIXTURES SHALL BE PROVIDEDCOMPLETE, WITH LAMPS, AS SHOWN ON THE FIXTURESCHEDULE. FURNISH ALL FITTINGS AND OTHERMISCELLANEOUS MATERIALS FOR COMPLETE INSTALLATION OFFIXTURES.12.DISCONNECT SWITCHES: ALL SAFETY SWITCHES SHALL BENEMA GENERAL-DUTY TYPE HD AND UNDERWRITERS'LABORATORIES LISTED12.1.ALL SWITCHES SHALL HAVE SWITCHBLADES WHICH AREFULLY VISIBLE IN THE OFF POSITION WITH THE DOOROPEN. ALL CURRENT_CARRYING PARTS SHALL BE PLATEDTHROUGH ELECTROLYTIC PROCESSES TO RESISTCORROSION AND PROMOTE COOL OPERATION.12.2.SWITCHES SHALL BE QUICK_MAKE AND QUICK_BREAKSUCH THAT DURING NORMAL OPERATION OF THE SWITCH,THE OPERATION OF THE CONTACTS SHALL BE NOTCAPABLE OF BEING RESTRAINED BY THE OPERATINGHANDLE AFTER THE CLOSING OR OPENING ACTION OF THECONTACTS HAS STARTED. THE HANDLE AND MECHANISMSHALL BE AN INTEGRAL PART OF THE BOX, NOT THECOVER, WITH POSITIVE PADLOCKING PROVISIONS IN THEOFF POSITION.12.3.SWITCHES SHALL BE FURNISHED IN NEMA 1 GENERALPURPOSE ENCLOSURES UNLESS NEMA 3R (RAINTIGHT).ENCLOSURES SHALL BE OF CODE GAUGE (UL 98) SHEETSTEEL (NEMA 1) OR CODE GAUGE PHOSPHATE TREATMENTAND GRAY BAKED ENAMEL FINISH.12.4.SWITCHES SHALL BE HORSEPOWER RATED FOR 600 VOLTSAC AND ALL SWITCHES SHALL BE FUSED TYPE WITH DUALELEMENT FUSES12.5.SAFETY SWITCHES SHALL BE SQUARE D CLASS 3130 ORAPPROVED EQUAL AS MANUFACTURED BY GENERALELECTRIC OR WESTINGHOUSE ELECTRIC13.FUSES: SHALL BE NON RENEWABLE TYPE, UL CLASS J UP TO600 AMP, AND CLASS L OVER 600 AMP. FUSES SHALL BECURRENT LIMITING TYPE WITH A MINIMUM INTERRUPTINGRATING OF 200,000 RMP AMP.13.1.FUSES FOR MOTOR FEEDERS OR MOTOR CIRCUITS SHALLBE CLASS K5 OF A VOLTAGE CLASSIFICATION RATED FORTHE MOTOR WITH A MINIMUM INTERRUPTING CAPACITY OF100,000 RMS AMP AND WITH TIME DELAY OF A MINIMUM OF10 SECONDS AT 500% OF MOTOR FULL LOAD AMPS.13.2.FURNISH AND INSTALL ALL FUSES AND ONE COMPLETE SETOF THREE SPARE FUSES FOR EACH SIZE USED.13.3.FUSES SHALL BE MANUFACTURED BY BUSSMAN, GOULDSHAWMUT, LITTLE OR APPROVED EQUAL.14.EMPTY TELEPHONE/DATA SYSTEM14.1.PROVIDE ACCESS FOR TELEPHONE, DATA, POS AND CABLETV CABLING TO BE INSTALLED BY OTHERS. AT ALLLOCATIONS SHOWN ON THE DRAWINGS PROVIDE ASINGLE-GANG BACKBOX AND A 1/2" CONDUIT TO THEACCESSABLE CEILING SPACE ABOVE.14.2.NYLON PULL STRINGS SHALL BE INSTALLED IN ALL EMPTYCONDUITS IN EXCESS OF TEN FEET LONG.SECURELY TIEPULL STRING AT EACH END14.3.SECURELY TIE PULL STRING AT EACH END.14.4.ALL CONDUITS SHALL BE CONCEALED UNLESS OTHERWISENOTED.14.5.PURCHASE AND INSTALLATION OF DATA, TELEPHONEWIRING AND JACKS SHALL BE PROVIDED BY OWNERSCHOSEN CONTRACTOR.15.NAMEPLATES: NAMEPLATES CONSISTING OF BLACK PLASTICWITH WHITE CENTER, LETTERING TO BE 3/16" HIGH, ENGRAVEDTHROUGH TO WHITE LAYER AND PROPERLY FASTENED WITHBRASS SCREWS SHALL BE PROVIDED FOR THE FOLLOWINGEQUIPMENT:15.1.ALL PANELBOARDS AND DISTRIBUTION SWITCHBOARDS15.1.TERMINAL CABINETS15.2.JUNCTION BOXES LARGER THAN 4-11/16"16.FIRE DETECTION AND ALARM SYSTEM16.1.GENERAL16.1.1.FIRE ALARM SYSTEM MODIFICATIONS: MODIFICATIONSMADE TO THE BASE BUILDING FIRE ALARM SYSTEMSHALL BE MADE IN COMPLIANCE WITH ALL APPLICABLECODES AND REQUIREMENTS. ALL NEW COMPONENTSSHALL BE UL LISTED FOR THEIR INTENDED PURPOSEAND CROSS-LISTED FOR USE ON THE EXISTING YSTEM.16.1.2.THE ADDITION OF NEW INITIATING DEVICES ORNOTIFICATION APPLIANCES TO THE EXISTING SLC ANDNAC SHALL NOT ADVERSELY EFFECT SUPERVISION.THE WIRING CLASS AND STYLE FOR THE ADDITION OFDEVICES SHALL BE CONSISTENT WITH EXISTING.16.1.3.NEW DEVICES SHALL BE PROGRAMMED TO INITIATEACTION IN ACCORDANCE WITH THE EXISTINGSEQUENCE OF OPERATION AS APPROVED BY THE AHJ.SYSTEM SUBMITTAL SHALL INCLUDE AN INPUT/OUTPUTMATRIX CLEARLY DEFINING THE SEQUENCE FOR EACHADDED DEVICE.16.1.4.CSI HAS BASED OUR DESIGN ON AN EXISTINGADDRESSABLE SYSTEM. E.C SHALL COORDINATE WITHOWNER AND DETERMINE THE REQUIREMENTS OF THEEXISTING SYSTEM. E.C. SHALL PROVIDE ALLCOMPONENTS NEEDED TO PROVIDE AN OPERATIONALFIRE ALARM SYSTEM FOR [JOB NAME AND ADDRESS]THAT IS COMPATIBLE WITH THE EXISTING SYSTEMSREQUIREMENTS.16.1.5.OWNER SHALL PROVIDE FIRE ALARM TERMINALCABINET, ADDRESSABLE/DETECTION LOOP, AND AUDIOVISUAL CIRCUIT TO SPACE.16.2.SEQUENCE OF OPERATIONS16.2.1.THE ACTIVATION OF MANUAL FIRE ALARM PULLSTATION, OR THE AUTOMATIC ACTUATION OF ANYTHERMAL DETECTOR, SYSTEM SMOKE DETECTOR,SPRINKLER FLOW SWITCH, OR OTHER ALARMACTUATING DEVICES SHALL RESULT IN THEFOLLOWING:16.2.1.1.THE ADDRESS OF THE DEVICE IN ALARM SHALL BEDISPLAYED AT THE FIRE ALARM CONTROL PANEL,(FACP).16.2.1.2.ALL ALARM NOTIFICATION DEVICES (HORNSTROBES) SHALL SOUND AND STROBES SHALLFLASH.16.2.1.3.IF ALARM SIGNALS ARE SILENCED FOR ANYREASON, THEY SHALL AUTOMATICALLY RESOUNDIF FIRE ALARM DEVICES GOES INTO ALARM16.2.1.4.TRANSMIT SIGNAL TO THE FIRE DEPARTMENT VIAEXISTING MASTER BOX OR DIGITAL DIALER.16.3.REMOTE DEVICES16.3.1.REMOTE ALARM INDICATOR (LED) SHALL BE PROVIDEDAS SHOWN ON THE DRAWINGS. LED SHALL HAVESTAINLESS STEEL FACEPLATE AND SHALL BEENGRAVED "ALARM" UNLESS OTHER WISE NOTED.16.3.2.DUCT SMOKE DETECTORS SHALL BE ADDRESSABLEPHOTOELECTRIC TYPE, COMPLETE WITH REMOTETEST STATION AND SAMPLING TUBES. REMOTE TESTSTATION SHALL HAVE RED LED INDICATING LIGHT ANDSTAINLESS STEEL FACEPLATE. DUCT SMOKEDETECTORS SHALL SHUT OFF ASSOCIATED AIRHANDLING UNIT UPON ACTIVATION.16.3.3.PULL STATIONS SHALL BE ADDRESSABLE, SEMI-FLUSH,DOUBLE ACTION BREAK ROD STATIONS.16.3.4.HORN AND STROBE UNITS SHALL BE PROVIDED IN ACOMMON ENCLOSURE. THE VISUAL STROBE SHALLMEET ALL REQUIREMENTS OF THE ADA CODE.16.3.5.STROBE ONLY UNITS SHALL BE PROVIDED AND SHALLMEET ALL REQUIREMENTS OF NFPA AND ADA CODES.16.1.WIRING16.1.4.ALL FIRE ALARM WIRE AND CABLE SHALL BE UL LISTEDFOR FIRE ALARM USE.16.1.5.THE FIRE ALARM SYSTEM SHALL BE A COMPLETEAUTOMATIC AND MANUAL, CLOSED CIRCUIT, CLASS A,4 WIRE, CONNECTED AND LEFT IN FIRST-CLASSOPERATING CONDITION.16.1.6.FOR FIRE ALARM WIRING IN ENCLOSED SPACES,PROVIDE PLENUM RATED, TYPE FPLP, WITH REDOUTER JACKET. INSTALLATION SHALL MEETREQUIREMENTS OF NEC ARTICLE 770 AND 725.CONDUCTORS SHALL BE SOLID COPPER #14 MINIMUM,WITH LOW SMOKE, LOW FLAME TYPE JACKET.16.1.7.FOR FIRE ALARM WIRING IN EXPOSED AREAS, PROVIDETYPE THHN INSULATION. WIRE SIZE SHALL BE #14 AWGMINIMUM. ALL SURFACE MOUNTED WIRING RELATEDTO THE FIRE ALARM SYSTEM SHALL BE INSTALLED INTYPE EMT CONDUIT.16.1.8.ALL JUNCTION BOXES SHALL BE SPRAYED RED ANDLABELED "FIRE ALARM". CONDUIT COUPLINGS SHALLBE SPRAY PAINTED RED PRIOR TO INSTALLATION.16.1.9.CONNECTIONS AND SPLICES SHALL BE MADE USINGSCREW TERMINAL BLOCKS. THE USES OF WIRE NUTTYPE CONNECTORS ARE PROHIBITED IN THE SYSTEM.16.2.SHOP DRAWINGS16.2.1.PROVIDE THE FOLLOWING DOCUMENTS FOR REVIEWAND EVALUATION16.2.2.POINT TO POINT WIRING DIAGRAMS OF THE PROPOSEDMODIFICATION INCLUDING ALL CONDUCTOR QUANTITYAND SIZING16.2.3.PANEL LAYOUTS INDICATING MODULE PLACEMENTAND SPARE CAPACITY ALLOWANCE FOR FUTUREEXPANSION16.2.4.MANUFACTURERS CATALOG CUT SHEETS OF ALLCOMPONENTS AND DEVICES WITH INTERCONNECTIONDIAGRAMS16.2.5.BATTERY CAPACITY CALCULATIONS INDICATINGREQUIRED AND SPARE CAPACITY16.2.6.POWER SUPPLY CAPACITY CALCULATIONS INCLUDINGEACH CIRCUIT LOAD, VOLTAGE DROP AND SPARECAPACITY16.2.7.WRITTEN TEST REPORT FOR NOTIFICATION OFSUCCESSFUL COMPLETION OF EACH REQUIRED TESTAND SYSTEM RECORD OF COMPLETION.16.2.8.AS-BUILT DRAWINGS INCLUDING ALL DEVICEADDRESSES AND ALPHANUMERIC DESCRIPTORSASSIGNED IN THE CONTROL PANEL.16.3.TESTING16.1.4.THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALLFIRE ALARM TESTING AND CERTIFICATION CHARGES.16.1.5.THE ELECTRICAL CONTRACTOR SHALL CONDUCT THEACCEPTANCE TEST WITH THE LOCAL FIREDEPARTMENT IN ACCORDANCE WITH NFPA 72. UPONACCEPTANCE, A CERTIFICATE TO MAINTAIN A FIREALARM SYSTEMS SHALL BE ISSUED AND DISPLAYED ATTHE FIRE CONTROL ALL NEW DETECTORS SHALL BELABELED WITH ASSIGNED ADDRESS ON BOTH THEDETECTOR HOUSING AND THE BASE WITH A BLACK ONCLEAR TYPED LABEL EQUAL TO KROY. THE BASEADDRESS SHALL BE LEGIBLE WITHOUT REMOVAL OFTHE DETECTOR. THE DETECTOR ADDRESS SHALL BECONCEALED WHEN PLACED INTO THE BASE.16.1.6.THE CONTRACTOR SHALL PERFORM INSULATIONTESTING (MEGGER), CONTINUITY AND LOOPRESISTANCE CHECKS ON ALL SYSTEM CONDUCTORSTO DETERMINE THAT THE SYSTEM IS FREE FROMGROUNDED, SHORTED, OR OPEN CIRCUITS. THESETESTS SHALL BE CONDUCTED PRIOR TO THEINSTALLATION OF FIRE ALARM EQUIPMENT. LOOPRESISTANCE MEASUREMENT SHALL VERIFY THAT THELOOP RESISTANCE DOES NOT EXCEED THEMANUFACTURERS SPECIFIED LIMITS. CORRECTIONSSHALL BE MADE AND THE SYSTEM SHALL BE RETESTEDIF DEFICIENCIES ARE FOUND. A WRITTEN REPORTSHALL BE SUBMITTED DETAILING THE RESULTS OF THEPRELIMINARY TESTS SHALL ACCOMPANY THEREQUEST FOR FINAL ACCEPTANCE TEST.16.1.7.THE FIRM WHO HOLDS THE EXISTING SYSTEMMAINTENANCE CONTRACT SHALL PERFORM FINALCONNECTIONS, PROGRAMMING, AND TESTING. THECONTRACTOR SHALL CARRY ALL COSTS ASSOCIATEDWITH FINAL CONNECTIONS, PROGRAMMING ANDTESTING AS WELL AS DISABLING CONNECTIONS TOTHE MUNICIPAL LOOP DURING FINAL CONNECTIONSAND TESTING.16.1.8.CERTIFY INSTALLATION WITH THE SUCCESSFULCOMPLETION OF ALL ASSOCIATED NFPA 72 TESTS ANDMEASURE SOUND PRESSURE LEVELS IN ALL ROOMSWITHIN THE SCOPE OF THIS PROJECT. SUBMIT THETEST REPORTS FOR REVIEW PRIOR TO REQUEST FORFINAL PUNCH LIST INSPECTION.PART 3 - EXECUTION1.SERVICE TO THE FACILITY: ELECTRICAL POWER OUTAGESMUST BE MINIMIZED AS NOT TO INTERFERE WITH THEBUILDING'S OPERATION. THE TIME AND DURATION OF ANYPOWER OUTAGE MUST BE APPROVED BY AND SCHEDULEDWITH THE BUILDING OWNER/AUTHORITY. THE ELECTRICALCONTRACTOR SHALL NOTIFY THE OWNER/AUTHORITY AT LEASTTEN CALENDAR DAYS FROM THE DATE OF PROPOSED POWEROUTAGE IN THE FACILITY.2.DEMOLITION, RELOCATION AND REMOVAL OF EXISTING WIRING2.1.THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALLELECTRICAL DEMOLITION, RELOCATION OF CIRCUITS, ANDREMOVAL OF EXISTING WIRING NECESSARY FOR THEELECTRICAL WORK. THE ELECTRICAL CONTRACTOR SHALLCOMPLETELY REMOVE ALL ELECTRICAL SYSTEMS WITHINTHE BUILDING INCLUDING - BUT NOT LIMITED TO - THEFOLLOWING:2.1.1.REMOVE ALL EXISTING LIGHTING FIXTURES,SWITCHING AND TIME CLOCKS, AND ASSOCIATEDBRANCH CIRCUITS.2.1.2.REMOVE ALL EXISTING BRANCH CIRCUIT WIRING.2.1.3.REMOVE ALL EXISTING PANELBOARDS.2.1.4.REMOVE ALL EXISTING FIRE ALARM DEVICES AND ALLEXISTING FIRE ALARM WIRING.2.1.5.REMOVE ALL EXISTING RECEPTACLES.2.2.OUTLETS THAT ARE EXISTING FOR USE AS LIGHTING ORRECEPTACLES MAY BE USED AS JUNCTION BOXES FORTHE RE_WIRING OF THE BUILDING IF NECESSARY.2.3.THE CONTRACTOR SHALL MAINTAIN, EXTEND, ANDCONNECT EXISTING BRANCH CIRCUITS WHICH PASSTHROUGH THE CONSTRUCTION AREA, MAINTAININGPOWER TO ALL EQUIPMENT AND LIGHTING OUTSIDE OFTHE CONSTRUCTION AREA.3.SPECIAL COORDINATION INSTRUCTIONS3.1.COORDINATION WITH WORK OF OTHER TRADES ISREQUIRED. THE FOLLOWING SPECIAL INSTRUCTIONSSHALL ALSO BE CAREFULLY NOTED:3.1.1.LOCATIONS AND MOUNTING HEIGHT OF ALL WALLOUTLETS AND LIGHTING FIXTURES SHALL BE VERIFIEDWITH THE ENGINEER PRIOR TO ROUGHING_INCONDUITS. REFER TO DETAILS AND WALL ELEVATIONSON THE ARCHITECTURAL DRAWINGS; MOUNTINGHEIGHTS INDICATED ON THESE ARCHITECTURALDRAWINGS AND/OR SPECIFIC DIMENSIONALINFORMATION GIVEN TO THIS CONTRACTOR BY THEENGINEER SHALL TAKE PRECEDENCE OVER SUCHINFORMATION INDICATED ON THE ELECTRICALDRAWINGS.3.1.2.ALL FEEDER, BRANCH CIRCUIT OR AUXILIARY SYSTEMWIRING PASSING THROUGH PULL BOXES AND/ORBEING MADE UP IN PANELBOARDS SHALL BEPROPERLY GROUPED, BOUND, AND TIED TOGETHER INA NEAT AND ORDERLY MANNER, IN KEEPING WITH THEHIGHEST STANDARDS OF THE TRADE, WITH PLASTICCABLE TIES.3.1.3.ALL DUPLEX CONVENIENCE AND POWERRECEPTACLES SHALL BE MOUNTED VERTICALLY WITHTHE GROUNDING POST TO THE BOTTOM AS THEOUTLET IS VIEWED FROM THE FRONT.3.1.4.ALL MISCELLANEOUS HARDWARE AND SUPPORTACCESSORIES, INCLUDING SUPPORT RODS, NUTS,BOLTS, SCREWS, AND OTHER SUCH ITEMS, SHALL BEOF A GALVANIZED OR CADMIUM PLATED FINISH, OR OFOTHER APPROVED RUST_INHIBITING COATINGS. CARESHOULD BE TAKEN THAT FIXTURES SHALL NOT BEINSTALLED ON BOTH SIDES OF EXISTING OR NEWBUILDING EXPANSION JOINTS.3.1.5.THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALLMATERIALS, EQUIPMENT, AND WORKMANSHIP TOPROVIDE FOR ADEQUATE PROTECTION OF ALLELECTRICAL EQUIPMENT DURING THE COURSE OFCONSTRUCTION OF THE PROJECT.3.1.6.THE ELECTRICAL CONTRACTOR SHALL FURNISH ANDINSTALL APPROVED INSULATION AT TERMINALCONNECTION POINTS FOR ALL ELECTRICALCONDUCTING MATERIALS, SUCH AS TRANSFORMERTERMINALS, TERMINAL STUDS, AND AT ANY OTHERSPECIAL LOCATIONS AS DIRECTED BY THE ENGINEER.3.1.7.PRIOR TO INSTALLATION OF CONDUIT AND WIRE, THEELECTRICAL CONTRACTOR SHALL COORDINATEWIRING REQUIREMENTS WITH ACTUAL EQUIPMENTSUPPLIED.3.1.8.THE ELECTRICAL DRAWINGS INDICATE WIRE, CONDUIT,AND OVERCURRENT PROTECTIVE DEVICES TO BEINSTALLED FOR CERTAIN HVAC UNITS. THESE SIZESARE BASED ON CERTAIN MANUFACTURERSREQUIREMENTS. SHOULD THE GENERAL CONTRACTORALLOW THE MECHANICAL CONTRACTOR TOSUBSTITUTE HVAC EQUIPMENT DIFFERENT THANSPECIFIED, THEN THE GENERAL CONTRACTOR SHALLPROVIDE THE REQUIRED REVISED ELECTRICALWIRING, CONDUIT, AND OVERCURRENT PROTECTIVEDEVICES IN ACCORDANCE WITH THE MANUFACTURERSRECOMMENDATIONS AT NO ADDITIONAL CHARGE TOTHE OWNER.4.CUTTING, PATCHING, AND DRILLING: THE GENERALCONTRACTOR SHALL PERFORM PLASTER CUTTING ANDCHANNELING AND DRILLING THROUGH STRUCTURAL BEAMSNECESSARY FOR THE INSTALLATION OF ELECTRICAL WORK.THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALLPAINTING AND PATCHING WHICH SHALL MATCH EXISTING BASEMATERIALS IN LOOKS AND COLOR. THE ELECTRICALCONTRACTOR SHALL PROVIDE ROUTINE DRILLING THROUGH 2X 4 AND/OR 2 X 6 WOOD FRAME WALLS AND 2 X 10 AND/OR 2 X12 FLOOR JOISTS IN ORDER TO INSTALL WIRING.5.COOPERATION AND WORK PROGRESS5.1.THE ELECTRICAL WORK SHALL BE CARRIED ON UNDER THEUSUAL CONSTRUCTION CONDITIONS, IN CONJUNCTIONWITH ALL OTHER WORK AT THE SITE. THE ELECTRICALCONTRACTOR SHALL COOPERATE WITH THE ENGINEERAND ALL CONTRACTORS AND EQUIPMENT SUPPLIERSWORKING ON THE SITE, COORDINATE THE WORK, ANDPROCEED IN A MANNER SO AS NOT TO DELAY THEPROGRESS OF THE PROJECT.5.2.THE ELECTRICAL CONTRACTOR HAS A RESPONSIBILITY TOCOORDINATE THE EXACT MOUNTING ARRANGEMENT ANDLOCATION OF EQUIPMENT INDICATED ON THE DRAWINGSTO ALLOW FOR PROPER SPACE REQUIREMENTS FOREQUIPMENT ACCESS, OPERATION, AND MAINTENANCE.5.3.IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICALCONTRACTOR TO COORDINATE THE DELIVERY OFELECTRICAL EQUIPMENT TO THE PROJECT PRIOR TO THETIME INSTALLATION OF EQUIPMENT WILL BE REQUIRED.6.INSTALLATION OF WIRING AND CONDUIT6.1.ALL CONDUITS SHALL BE INSTALLED CONCEALED.6.2.UNLESS OTHERWISE INDICATED, ALL WIRING SHALL BE(2)#12 AND (1)#12 GROUND, 3/4"C.6.3.CONDUIT ENDS SHALL BE CUT SQUARE, THREADED, ANDREAMED TO REMOVE BURRS AND SHARP EDGES. OFFSETSAND BENDS FOR CHANGES IN ELEVATION OF EXPOSEDCONDUIT RUNS SHALL BE MADE AT WALLS OR BEAMS ANDNOT IN OPEN SPACES BETWEEN WALLS OR BEAMS.CONDUITS SHALL BE ROUTED SO AS NOT TO INTERFEREWITH THE OPERATION OR MAINTENANCE OF ANYEQUIPMENT. THE ENTIRE JOB SHALL BE DONE IN A NEATAND WORKMANLIKE MANNER, AS APPROVED BY THEENGINEER. STEEL SUPPORTS OR RACKS SHALL BEGALVANIZED STEEL CHANNEL AND FITTINGS. SUPPORTSSHALL BE MANUFACTURED BY UNISTRUT, KINDORF, HUSKYPRODUCTS COMPANY, OR EQUAL.6.4.EXPOSED CONDUITS SHALL BE RUN PARALLEL TO, OR ATRIGHT ANGLES TO, THE WALLS OF THE BUILDING, AND ALLBENDS SHALL BE MADE WITH STANDARD CONDUIT ELLS ORCONDUITS BENT TO - NOT LESS THAN - THE SAME RADIUS.HORIZONTAL RUNS OF EXPOSED CONDUITS SHALL BECLOSE TO CEILING BEAMS, PASSING OVER WATER OROTHER PIPING WHERE POSSIBLE AND SHALL BESUPPORTED BY PIPE STRAPS OR BY OTHER APPROVEDMEANS, NOT MORE THAN 5' APART. INSTALLATION OFEXPOSED CONDUITS IN FINISHED AREAS OF THE BUILDINGSHALL BE CHECKED WITH THE ENGINEERS FOR LAYOUTBEFORE INSTALLATION TO CONFORM TO THE PATTERN OFTHE STRUCTURAL MEMBERS, AND WHEN COMPLETED, ISTO PRESENT THE MOST UNOBTRUSIVE APPEARANCEPOSSIBLE. NO EXPOSED CONDUITS WILL BE PERMITTED ONWALLS OR PARTITIONS IN PUBLIC AREAS, UNLESSSPECIFICALLY NOTED.6.5.CONDUITS SHALL NOT BE INSTALLED WITHIN 3" OF HOTWATER PIPES, OR APPLIANCES, EXCEPT WHERE CROSSINGIS UNAVOIDABLE AND, IN THAT CASE, THE CONDUIT SHALL%(.(37$7/($67´)520&29(5,1*253,3(&5266('6.6.CONDUITS SHALL BE SUPPORTED ON APPROVED TYPEGALVANIZED WALL BRACKETS, CEILING TRAPEZE, STRAPHANGERS, OR PIPE STRAPS, SECURED BY MEANS OFTOGGLE BOLTS ON HOLLOW MASONRY UNITS OREXPANSION BOLTS IN CONCRETE OR BRICK.6.7.IN GENERAL, NO SPLICES OR JOINTS WILL BE PERMITTED INEITHER FEEDER OR BRANCHES EXCEPT AT OUTLETS ORACCESSIBLE JUNCTION BOXES.6.8.ALL SPLICES IN WIRE #8 AWG AND SMALLER SHALL BESTANDARD PIGTAIL, MADE MECHANICALLY TIGHT ANDINSULATED WITH PROPER THICKNESS OF INSULATINGTAPE. WIRE SPLICING NUTS AS MANUFACTURED BYMINNESOTA MINING AND MANUFACTURING COMPANY(SCOTCH LOCK) OR IDEAL WIRE NUTS MAY BE USED,SUBJECT TO THE LOCAL WIRE INSPECTOR.6.9.WIRE #6 AND LARGER SHALL BE CONNECTED TO PANELSAND APPARATUS BY MEANS OF APPROVED LUGS ORCONNECTORS. CONNECTORS SHALL BE SOLDERLESSTYPE, SUFFICIENTLY LARGE TO ENCLOSE ALL STRANDS OFTHE CONDUCTOR AND SECURELY FASTENED.6.10.PROVIDE ALL REQUIRED BRANCH CIRCUIT WIRING FORELECTRICAL DEVICES AND LIGHTING FIXTURES.DESIGNATIONS SHOWN ON DRAWINGS ARE DIAGRAMMATICONLY. CIRCUIT NUMBERS BESIDE RECEPTACLES ANDLIGHTING FIXTURES CONVEY THAT A COMPLETE BRANCHCIRCUIT IS REQUIRED BACK TO ELECTRICALPANELBOARD.SWITCH CONTROL LETTERS ADJACENT TOLIGHTING FIXTURES INDICATE BRANCH WIRING REQUIREDFROM LIGHTING FIXTURE TO LIGHT SWITCH OR DIMMER.7.COLOR CODING7.1.PROVIDE COLOR CODING FOR SECONDARY SERVICE,FEEDERS, AND BRANCH CIRCUITS AS FOLLOWS:PHASECOLOR120/208V, 3-PHASE, 4-WIRE, WYE:ABLACKBREDCBLUENEUTRAL WHITEEQUIPMENT GROUND GREEN7.2.MAKE CONNECTIONS TO TERMINALS FROM LEFT TO RIGHTARRANGED PHASE A, B, AND C.7.3.PROVIDE SAME COLOR CODING FOR SWITCH LEGS ASCORRESPONDING PHASE CONDUCTOR. PROVIDECOLORED PLASTIC TAPE OF SPECIFIED COLOR CODEIDENTIFICATION FOR LARGE SIZE CONDUCTORS AVAILABLEONLY IN BLACK.8.MOTORS, CONNECTIONS, AND CONTROLS8.1.SPLICES AND TERMINATIONS:8.1.1.MAKE SPLICES AND TERMINATIONS EQUIVALENTELECTRICALLY AND MECHANICALLY TO CONDUCTORINSULATION.8.1.2.MAKE SPLICES IN BRANCH CIRCUIT WIRING WITHSOLDERLESS, SCREW_ON CONNECTORS IDEAL,SCOTCHLOK, T&B OR EQUAL, RATED 600V, OF SIZE ANDTYPE REQUIRED BY MANUFACTURER'S8.1.3.RECOMMENDATION, WITH TEMPERATURE RATINGSEQUAL TO THOSE OF CABLE INSULATION. INSULATESPLICES WITH INTEGRAL COVERS OR WITH PLASTIC,RUBBER, OR FRICTION TAPE, PERMACAL OR EQUAL, TOMAINTAIN INTEGRITY OF CABLE INSULATION.8.1.4.MAKE SPLICES AND TERMINATIONS TO CONDUCTORS#8 AND LARGER WITH CORROSION_RESISTANT, HIGHCONDUCTIVITY, PRESSURE INDENT, HEX SCREW ORBOLT CLAMP CONNECTIONS, WITH OR WITHOUTTONGUES, DESIGNED SPECIFICALLY FOR INTENDEDSERVICE. CONNECTORS FOR CABLES 250 MCM ANDLARGER SHALL HAVE TWO CLAMPING ELEMENTS ORCOMPRESSION INDENTS. TERMINALS FOR BUSCONNECTIONS SHALL HAVE TWO BOLT HOLES. SPLITBOLT CONNECTORS, BURNDY OR EQUAL, SHALL BEACCEPTABLE FOR ALL SPLICES OF CONDUCTORS #8AND LARGER.8.1.5.MAKE SPLICES AT MOTOR JUNCTION BOXES WITHPRESSURE INDENT CONNECTORS OR SPLIT_BOLTCONNECTORS AS SPECIFIED HEREIN.8.1.6.PROVIDE STANDARD BOLT_ON LUGS WITH ALLEN CAPSCREWS TO ATTACH COPPER WIRE AND CABLE TODISCONNECT SWITCHES AND OTHER ELECTRICALEQUIPMENT.9.TEMPERATURE CONTROL WIRING: THE TEMPERATURECONTROL SYSTEM SHALL BE AN ELECTRIC SYSTEM INSTALLEDBY THE HEATING AND AIR-CONDITIONINGITIONINGCONTRACTOR. ALL ELECTRIC WIRING AND WIRINGCONNECTIONS REQUIRED FOR THE INSTALLATION OF THETEMPERATURE CONTROL SYSTEM SHALL BE PROVIDED BY THETEMPERATURE CONTROL CONTRACTOR.10.SALVAGE: THE ELECTRICAL CONTRACTOR SHALL REMOVE ALLELECTRICAL EQUIPMENT NOT TO BE USED. ALL ELECTRICALEQUIPMENT REMOVED AND DEEMED SALVAGEABLE BY THEOWNER SHALL BE STORED IN AN AREA DESIGNATED BY THEOWNER.ANY ELECTRICAL EQUIPMENT REMOVED THAT IS NOTDESIRED BY THE OWNER SHALL BE DISPOSED OF AT THEEXPENSE OF THE ELECTRICAL CONTRACTOR.11.SUPPORTS AND ATTACHMENTS: BOXES AND PENDANTS FORSURFACE-MOUNTED FIXTURES SHALL BE SUPPORTED IN ANAPPROVED MANNER. BOXES AND SUPPORTS SHALL BEFASTENED WITH BOLTS AND EXPANSION SHIELDS ONCONCRETE OR BRICK, WITH TOGGLE BOLTS ON HOLLOWMASONRY UNITS, WITH MACHINE SCREWS ON STEEL WORKWITH LOCKNUTS.THREADED STUDS SHALL BE PROVIDED WITHLOCK_WASHERS AND NUTS.12.QUIET OPERATION: ALL EQUIPMENT AND MATERIAL FURNISHEDBY THE ELECTRICAL CONTRACTOR SHALL OPERATE UNDER ALLCONDITIONS OF LOAD WITHOUT OBJECTIONABLE NOISES ORVIBRATIONS, WHICH, IN THE OPINION OF THE ENGINEER, ISOBJECTIONABLE. WHERE SOUND OR VIBRATION CONDITIONSARISE WHICH ARE CONSIDERED OBJECTIONABLE BY THEENGINEER, THE ELECTRICAL CONTRACTOR SHALL ELIMINATESAME IN A MANNER APPROVED BY THE ENGINEER.13.TESTS: FURNISH ALL LABOR, MATERIAL, INSTRUMENTS,SUPPLIES, AND SERVICES AND BEAR ALL COSTS FOR THEACCOMPLISHMENT OF TESTS HEREIN SPECIFIED. CORRECT ALLDEFECTS APPEARING UNDER TEST. REPEAT THE TESTS UNTILNO DEFECTS ARE DISCLOSED. LEAVE THE EQUIPMENT CLEANAND READY FOR USE.A.THE ELECTRICAL CONTRACTOR SHALL PERFORM ANY TESTOTHER THAN HEREIN SPECIFIED WHICH MAY BE SPECIFIEDBY LEGAL AUTHORITIES OR BY AGENCIES TO WHOSEREQUIREMENTS THIS WORK IS TO CONFORM.14.FINAL INSPECTION AND TEST: PRIOR TO TEST, FEEDERS ANDBRANCHES SHALL BE CONTINUOUS FROM SERVICE CONTACTPOINT TO EACH OUTLET; ALL PANELS, FEEDERS, AND DEVICESCONNECTED AND FUSES IN PLACE. TEST SYSTEM FREE FROMSHORT CIRCUITS AND GROUNDS WITH INSULATIONRESISTANCES NOT LESS THAN OUTLINES IN THE NATIONALELECTRICAL CODE. PROVIDE TESTING EQUIPMENT NECESSARYAND CONDUCT TEST IN PRESENCE OF THE OWNER'SAUTHORIZED REPRESENTATIVE. THE FINAL INSPECTION ANDTEST SHALL INCLUDE THE FOLLOWING:14.1.TESTING OF THE EMERGENCY LIGHTING SYSTEM.14.2.TESTING OF THE IMPEDANCE OF THE GROUNDING SYSTEM.14.3.TESTING OF EACH OUTLET.14.4.TESTING OF THE FIRE ALARM SYSTEM.14.5.TESTING OF BRANCH AND FEEDER CONDUCTORS FORCONTINUITY.14.6.TESTING OF PANELBOARDS TO VERIFY PROPER CURRENTBALANCE AND VOLTAGE.14.7.TESTING OF MOTORS, VERIFYING PROPER CURRENTBALANCE AND VOLTAGE.14.8.TESTING, TARGETING, AND FOCUSING OF ALL ADJUSTABLELIGHTING FIXTURES.14.9.TESTING OF ALL GROUND FAULT PROTECTIVE DEVICES INACCORDANCE WITH THE NATIONAL ELECTRICAL CODE,SECTION 230-95.13MAIN DISTRIBUTION SWITCHBOARDA.DESCRIPTION1.SWITCHBOARDS SHALL BE POWER R LINE C EATON, OREQUAL WITH AN INDIVIDUALLY MOUNTED MAIN DEVICESECTION FEEDING A GROUP_MOUNTED DISTRIBUTIONSECTIONS. THE SWITCHBOARD SHALL BE FRONTACCESSIBLE AND MANUFACTURED FOR SERVICEENTRANCE USE. THE SERVICE VOLTAGE IS 277/480 VOLT,3-PHASE, 4-WIRE. MAXIMUM MAIN DEVICE RATING SHALLBE 2000 AMPERE AND SHALL BE AS INDICATED ON THEDRAWINGS.2.THE CONTRACTOR SHALL FURNISH AND COMPLETELYINSTALL ALL SWITCHBOARDS AS SHOWN ON THEDRAWINGS AND DESCRIBED IN THESE SPECIFICATIONS.3.MAIN CIRCUIT BREAKER SHALL BE INSULATED CASE TYPE.FEEDER BREAKERS LESS THAN 1200A SHALL BE MOLDEDCASE TYPE.B.STANDARDS1.THE SWITCHBOARDS SHALL BE DESIGNED, BUILT, ANDTESTED IN ACCORDANCE WITH NEMA PB_2 ANDUNDERWRITERS LABORATORIES NO. UL891 AND THELATEST REQUIREMENTS OF THE NATIONAL ELECTRICALCODE. ALL SECTIONS AND DEVICES SHALL BE UL LISTEDAND LABELED.C.STRUCTURE1.THE SWITCHBOARDS SHALL BE A COMPLETELY6(/)B6833257,1*6758&785(:,7+´+,*+9(57,&$/SECTIONS BOLTED TOGETHER TO FORM THE REQUIREDARRANGEMENT.2.ALL SECTIONS SHALL BE REAR ALIGNED AND MAY BEROLLED, MOVED, OR LIFTED INTO THE INSTALLATIONPOSITION AND BOLTED DIRECTLY TO THE FLOOR WITHOUTTHE ADDITION OF FLOOR SILLS. THE STRUCTURE FRAMESHALL BE DIE-FORMED 12 GAUGE STEEL WITHREINFORCING CORNER GUSSETS. BOLT_ON ENCLOSURECOVERS SHALL BE CODE GAUGE STEEL. ALL STEELSURFACES SHALL BE CHEMICALLY CLEANED PRIOR TOPAINTING. EXTERIOR PAINT COLOR SHALL BE ANSI 61LIGHT GRAY.3.BUS BARS SHALL BE SOLID TIN PLATED COPPER OR TINPLATED ALUMINUM RATED FOR FULL AMPACITY ASSHOWN ON THE DRAWINGS. BUS BARS SHALL BEMOUNTED ON SUPPORTS OF HIGH IMPACT NON_TRACKINGINSULATED MATERIAL, AND SHALL BE BRACED TOWITHSTAND THE MECHANICAL FORCE EXERTED DURINGSHORT CIRCUIT CONDITIONS.4.A FULL-LENGTH GROUND BUS IS SECURED TO EACHVERTICAL SECTION. A_B_C TYPE BUS ARRANGEMENT(LEFT_TO_RIGHT, TOP_TO_BOTTOM, FRONT_TO_REAR)SHALL BE USED THROUGHOUT TO ASSURE CONVENIENTAND SAFE TESTING AND MAINTENANCE.5.WHERE SPECIAL CIRCUITRY PRECLUDES THISARRANGEMENT, BUS BAR SHALL BE LABELED.6.ALL LUGS SHALL BE UL LISTED FOR USE WITH COPPER ORALUMINUM CABLE WITH AMPACITY BASED ON 75OCCONDUCTOR TEMPERATURE RATINGS.7.SWITCHBOARD CURRENT RATINGS INCLUDING DEVICESSHALL BE BASED ON OPERATION IN A 25OC ROOMAMBIENT, PER UL 891.8.GROUP_MOUNTED BRANCH DEVICES MUST BE CAPABLEOF BEING INSTALLED OR REMOVED WITHOUT LOOSENINGOR REMOVING BUS BARS OR DISTURBING DEVICE LINETERMINATIONS.9.THE GROUP_MOUNTED SWITCHBOARD INTERIOR MUST BEUL LISTED TO ACCEPT BOTH CIRCUIT BREAKER ANDFUSIBLE SWITCHES, INTERMIXED, BOTH FACTORY ANDFIELD INSTALLED.10.THE SWITCHBOARD DEVICES AND BUS BAR BRACINGSHALL BE FULLY RATED FOR THE AIC SPECIFIED ON THEDRAWINGS. SERIES RATED EQUIPMENT IS NOTACCEPTABLE.D.METERING1.PROVIDE INDUSTRIAL SWITCHBOARD STYLE AMP METER, 4ò´648$5($&&85$&<3529,'(&855(17TRANSFORMERS WITH VA BURDEN RATINGS SUITABLE TOSUPPLY THE METERING. PROVIDE AMP METER ROTARYTYPE INSTRUMENT SWITCH. SWITCH SHALL HAVETOTALLY ENCLOSED CONTACTS, ESCUTCHEON PLATESUITABLY MARKED FOR EACH POSITION, PHASE A, PHASEB, AND PHASE C.2.PROVIDE INDUSTRIAL SWITCHBOARD STYLE VOLT METER,ò´648$5($&&85$&<3529,'(327(17,$/TRANSFORMERS WITH VA BURDEN RATINGS SUITABLE TOSUPPLY METERING. PROVIDE VOLTMETER ROTARY TYPEINSTRUMENT SWITCH. SWITCH SHALL HAVE TOTALLYENCLOSED CONTACTS, ESCUTHEON PLATE SUITABLYMARKED FOR EACH POSITION. VOLT METER SHALLMEASURE LINE TO LINE VOLTAGE (PHASE A-B, B-C, A-C)AND LINE TO NEUTRAL VOLTAGE (PHASE A-N, B-N, C-N).3.PROVIDE CONTROL FUSES FOR METERING. FUSES SHALLBE MOUNTED IN A LOCATION WHERE THEY ARE READILYACCESSIBLE. PULL-OUT TYPE FUSES SHALL BE PROVIDEDFOR ALL PRIMARY CIRCUITS AND SHALL BE OF THECURRENT LIMITING TYPE.E.CIRCUIT BREAKERS1.INSULATED CASE _ MAIN BREAKERa)PROVIDE INSULATED CASE MAIN CIRCUIT BREAKERWHICH IS UL LISTED TO UL STANDARD 489 AND MEETTHE REQUIREMENTS OF NEMA STANDARD AB1_1975.b)THE INSULATED CASE CIRCUIT BREAKER SHALL BERATED TO CARRY 100% CURRENT CONTINUOUSLY INACCORDANCE WITH UL_489 AND SHALL BE OFSTATIONARY CONSTRUCTION. THE BREAKER SHALLHAVE CURRENT_INTERRUPTING RATINGS EQUAL TOOR GREATER THAN SPECIFIED AT THE SYSTEMVOLTAGE. CURRENT LIMITING CIRCUIT BREAKERSSHALL NOT BE USED.c)THE BREAKER SHALL BE ELECTRICALLY OPERATEDAND SHALL HAVE A STORED_ENERGY CHARGINGMECHANISM AND INDEPENDENT CLOSING FUNCTION.THE CLOSING FUNCTION SHALL BE LOCAL ONLY WITHTHE CLOSING BUTTON ON THE FACE OF THE BREAKER.d)TRIP UNIT FUNCTIONS - THE TRIP UNIT SHALL INCLUDETHE FOLLOWING STANDARD FEATURES:(1)TRUE RMS SENSING.(2)TIME_CURRENT CHARACTERISTIC ADJUSTMENTSENTERED WITH A DIGITALKEYPAD.(3)LCD READOUT FOR TIME_CURRENTCHARACTERISTICS.(4)EPOXY CONFORMAL COATING ON ALL INTERNALSOLID_STATE CIRCUIT CONNECTIONS TO RESISTENVIRONMENTAL CONTAMINATION.(5)INTERCHANGEABLE RATING PLUGS TO VARY TRIPRATINGS.(6)ADJUSTABLE LONG_TIME CURRENT SETTING OF 0.5TO 1.1 TIMES THE RATING PLUG VALUE.(7)ADJUSTABLE LONG_TIME DELAY WITH FOUR BANDS.(8)INTEGRAL LONG_TIME PICKUP INDICATOR.(9)ADJUSTABLE INSTANTANEOUS TRIP.(10)INTEGRAL ABILITY FOR FULLSECONDARY_CURRENT INJECTION.(11)PHASE_SELECTABLE AMMETER METER DISPLAY,LOCAL OVERLOAD, SHORT_CIRCUIT AND GROUNDFAULT TRIP_CAUSE INDICATION.(12)SHORT_TIME PICKUP AND DELAY WITH I2T RAMP INOR OUT.(13)GROUND-FAULT PICKUP AND DELAY WITH I2T RAMPIN OR OUT.2.MOLDED CASE _ DISTRIBUTION BREAKERSa)THE BREAKER FRAME SHALL HAVE LEGIBLE,TAMPER_PROOF NAMEPLATES CONTAININGCATALOG NUMBER; MAXIMUM FRAME AMPERE RATING;MAXIMUM VOLTAGE RATING AND INTERRUPTINGRATINGS IN ACCORDANCE WITH UL STANDARD 489.b)ALL MOLDED CASE CIRCUIT BREAKERS SHALL HAVE ANOVER_CENTER, TOGGLE HANDLE OPERATED,TRIP_FREE MECHANISM WITH QUICK_MAKE,QUICK_BREAK ACTION INDEPENDENT OF THE SPEEDOF THE TOGGLE HANDLE OPERATION. THE DESIGNSSHALL PROVIDE COMMON TRIPPING OF ALL POLES.THE ESCUTCHEON AREA OF THE BREAKER COVERSHALL HAVE MOLDED_IN ON AND OFF MARKINGS.CURRENT LIMITING CIRCUIT BREAKERS SHALL NOT BEUSED.3.CT CABINETa)SWITCHBOARD SHALL HAVE INTEGRAL CT CABINETMEETING REQUIREMENTS OF LOCAL UTILITY COMPANY.b)CT CABINET SHALL HAVE DOUBLE DOORS WITHCONTINUOUS PIANO TYPE HINGES ON EITHER SIDE.CABINET SHALL HAVE LOCKING PROVISIONS ANDSHALL HAVE INTERIOR MOUNTING RACK FOR CTS.4.SPACESa)SWITCHBOARD SHALL HAVE CIRCUIT BREAKER SPACESPROVIDED WITH NECESSARY HARDWARE TO ACCEPTFUTURE CIRCUIT BREAKERS OF THE FRAME SIZE ASNOTED ON THE DRAWINGS.b)SWITCHBOARD "PROVISIONS" FOR SPARE CIRCUITBREAKERS WITHOUT MOUNTING HARDWARE IS NOTACCEPTABLE.F.TVSS PROTECTION1.WITHIN THE SWITCHBOARD, PROVIDE TVSS (TRANSIENTVOLTAGE SURGE SUPPRESSION) DEVICE.2.TVSS DEVICE SHALL HAVE INDIVIDUAL WAFER (UTILITYGRADE MOV) IN EACH L-N MODE AND ALSO IN THE N-GMODE PROVIDING COMMON MODE PROTECTION.3.MAXIMUM SURGE CURRENT BASED ON AN 8/20MICROSECOND TEST WAVEFORM SHALL BE 100KA L-L,100KA L-N, 100KA N-G, AND 100KA L-G.4.MAXIMUM CONTINUOUS OPERATING VOLTAGE SHALL BE115% OF NOMINAL.5.THE DEVICE SHALL BE CAPABLE OF SURVIVING 25,000IMPULSES WITHOUT FAILURE OR PERFORMANCEDEGRADATION MEASURED WITH TEST WAFEFORMERS PERANSI/IEEE C62.41-1991 AND ANSI/IEEE C62.45-1992.6.THE SUPPRESSION VOLTAGE RATING (SVR) SHALL BETESTED IN ACCORDANCE WITH THE TEST PROCEDURESSET FORTH BY UL-1449 SECOND EDITION. THE SVRVALUES SHALL NOT EXCEED THE FOLLOWING:NOMINAL VOLTAGEL-NN-G L-G L-L120/208400330 700 700277/48080080015001500240N/AN/A 7001500480N/AN/A100020007.THE FILTER SHALL BE CAPABLE OF PROVIDINGATTENUATION OF UP TO -44 DB AT 100 KHZ, MEASURED INACCORDANCE WITH PROCEDURES OUTLINED IN NEMA LS1-1992.8.EACH PHASE OF THE TVSS SHALL BE FUSED WITH THECAPABILITY TO ALLOW RATED MAXIMUM SURGE CURRENTTO PASS THROUGH THE DEVICE WITHOUT FUSEOPERATION. THE FUSING SHALL BE CAPABLE OFINTERRUPTING 200,000 AMPS SYMMETRICAL FAULTCURRENT WITH 600V APPLIED.9.THE TVSS SHALL INCLUDE REMOTE DISPLAY PANEL,GIVING COMPLETE VISUAL SYSTEM STATUS INDICATION.THE DISPLAY PANEL SHALL BE FACTORY MOUNTED ONTHE SWITCHBOARD. THREE AMBER INDICATING LAMPS (1PER PHASE) SHALL BE ILLUMINATED UNDER NORMALOPERATING CONDITIONS. IN ADDITION, AN AUDIBLEALARM SHALL BE PROVIDED TO INDICATE PROTECTIONFAILURE. THE PANEL SHALL ALSO INCLUDE THE TVSSTRANSIENT VOLTAGE SURGE COUNTER WITH BATTERYBACK-UP. SUMMARY CONTACTS SHALL BE PROVIDED SOTHAT REMOTE MONITORING OF THE TVSS CAN BE$&&203/,6+('3529,',1*)250³&´'5<&217$&7610.THE TVSS DEVICE SHALL BE GENERAL ELECTRIC -INTEGRATED GE TRANQUELL TVSS DEVICE, OR APPROVEDEQUAL.G.STUDIES1.PROVIDE SHORT CIRCUIT AND BREAKER COORDINATIONSTUDIES FOR APPROVAL BY ENGINEER.H.MANUFACTURERS1.SWITCHBOARD SHALL BE MANUFACTURED BY GENERALELECTRIC, OR EQUAL BY SIEMENS/ITE, SQUARE D, OREATON/WESTINGHOUSE.JOB NO.:SCALE:CHECKED:DRAWN:Phone (978) 927-0053152 Conant Street, Beverly, MA 01915 connollybrothers.com2017-010Engineering plumbinghvac electricalfire protection NSEWTRUENCALLED2017-06-01 ISSUED FOR PRICINGE-7.0SPECIFICATIONSNTSRSCM