Loading...
CODE NARRATIVE, IBC & IEBC 2009 ........... .............. ............... .......... ..... . ...... ........... ............ Paul R. Lessard, Architect . ....... 1.8 Leavitt St. Unit 2, Salem, Ma 01970 (978) 210-1960 paul(opaularchitect.com ------------ www.paularchitect.com ............ ................................. ................................. ...... ..... --- .... ....... .. ........ ............... December 8, 2016 Mr. Thomas St. Pierre, Director City of Salem Inspectional Services 120 Washington St. 3rd FIr Salem, MA 01970 tt Code Narrative: 21 Salem St., Salem, Mass. IBC 2009 & IEBC 2009 LES, NOTE: Owner will fully Spjjder existing building. � 4 Note: Owner will renovate 2nd Fir as (2) 1-Family apartments. M ass, 1. Use and Occupancy Group Classification: "if OF V, 2nd Floor- R-3 1-Family existing with proposed renovation as R-3 2-Family I st Floor- B Church with 49 or less occupants B Hair Salon renovated to Restaurant with 49 or less occupants B Variety Store with 49 occupants or less Basement: B Office as accessory space to I st Flr Church (Section 508.2) S-1 Storage Note: No Change of Occupancy 2. Section 503 Height and Area calculations - Type III B Construction Allowable Existing & Proposed (No Change) B Business 3 stories, 19,000 s.f. Church I story, 1,106 s.f. (See Section 303.1 where Assembly spaces is termed Group B Occupancy if Occupancy Load is less than 50 persons) Variety Store I story, 744 s.f. Restaurant 1. story, 1,026 s.f. S-1 Storage 2 stories, 17,500 s.f. Basement Storage I story, 768 s.f. Basement Storage I story, 1,212 s.f. Basement Storage I story, 1,059 R-3 2-Faintly 4 stories, Unlimited s.f (2) Single Family Apartments 3,134 s.f. Areas and Heights do not excede Allowable. Section 508.3 - R-3 residential units must have a rated separation from the B Business occupancies below according to Section 508.3.3. Table 508.4 prescribes a 1 hr fire rated floor assembly between the 2nd Flr residential and the 1 st floor Business occupancies given that this will be a Fully Sprinklered building. There is an existing 1 hr rated Floor/Ceiling assembly in place composed of plaster ceiling, wood joists, wood sub-floor and finished wood floor. Restaurant ceiling has also been given an extra layer of 5/8" Type X F.C. gypsum board for added safety. An extra layer of gypsum board has been added to both sides of the wall separating the church from the restaurant. 1st Floor Business and S-1 Storage occupancies do not need separation. Chapter 7 Fire & Smoke Protection Section 707.3.3 Interior Exit Stair Enclosures - Rating shall not be less than 1 hr (based on being less than 4 stories. Section 716.5 Fire doors must conform to fire protection rating called for in Table 716.5 Doors into 1 hr fire stair enclusures shall be 1 hr rated and have self closing devices. Exit doors to outside do not need to be fire rated. Section 1015.1 Exception: R-3 Residential Unit can have one (1) Means of Egress if it has an Automatic Sprinkler System and if the length of travel is 75 feet or less (See Section 1014.3). Table 1015.1 B Business Occupancy can have one (1) Means of Egress if the Occupant Load is 49 occupants or less. IEBC 2009 301.1.2 Work Area compliance method- Must comply with applicable requirements in Chapters 5-13 Alteration Level 2 - 1 st Flr Commercial Kitchen/Restaurant will receive new preparation and serving equipment. 2nd Flr space shall be re-partitioned to create (2) 1-Family living units. Code Compliant Fire Alarm System must be completed with modification of residential units. Conclusions: Church at 1st Flr needs to keep Maximum Occupancy to 49 persons or less as there is no op- portunity to create a 2nd means of egress. Church shall use basement as Pastor's office as an Accessory space of the Church. Additional basement rooms must not be used for child care, but, only Storage as there is additional diffuculty in egress from those spaces. Restaurant could be allowed to operate if upstairs is unoccupied prior to installation of Automatic Sprinkler System.