Loading...
12 Pope Street Sprinkler test New England Fire & Sprinkler Protection, Inc. 80 Brick Kiln Road Chelmsford, MA 01824 (978) 452-2895 (978) 453-5475 - Fax LOCATION: SALEM HEIGHTS 100%ANNUAL SPRINKLER TEST 12 POPE ST. SALEM, MA 10/23/15 VALVE MANUFACTURE AMES SIZE 10" MODEL YEAR WET X DRY ACCELERATOR: YES NO X WATER FLOW TEST: (THROUGH 2" DRAIN VALVE,WIDE OPEN) 1. PRESSURE: STATIC 150 PSI RESIDUAL PSI 65 2. APPROXIMATE LENGTH OF DRAIN PIPE 20 FEET 3. DRAIN DISCHARGE: INSIDE: OUTSIDE: X OTHER: ALARM TEST: 2" DRAIN INSPECTORS TEST 1. WATER MOTOR GONG- SATISFACTORY? YES X NO SEC 15 2. INSIDE HORNS/STROBES YES N/A NO SEC 3. EXPLAIN ANY"NO"ANSWERS: 4A. IS SYSTEM SUPERVISED: YES X NO By Whom FACP 4B. WAS A SIGNAL RECEIVED: YES X NO Explain: MASTERBC #4121 SUPPLIES: 1. NUMBER: 1 2. SIZE #1 10" #2 #3 #4 3. FROM WHAT STREET POPE ST. ADDITIONAL DATA(I.E. - FIRE PUMP TANK, COMMENTS, ETC) -NOTE#1 —THERE IS A CORRODED NIPPLE LEAKING WATER ON THE 2ND FLR STAIRWAY#6 -NOTE#2—LEAKING DRAIN/INSPECTORS TEST ON STAIRWAY#1 ON THE 7TH &THE 8TH FLOOR -NOTE#3—LEAKING DRAIN/INSPECTORS TEST ON THE 3RD FLR IN STAIRWAY#3 Page 1 of 2 ti� Y New England Fire & Sprinkler Protection, Inc. 'f 80 Brick Kiln Road i Chelmsford, MA 01824 (978) 452-2895 • (978) 453-5475 - Fax LOCATION: SALEM HEIGHTS 100%ANNUAL SPRINKLER TEST 12 POPE ST. SALEM, MA 10/23/15 CONTROL VALVES: 1. NUMBER: 6 INSIDE X OUTSIDE 2. INDICTING TYPE? YES X NO 3. FOUND OPEN? YES X NO 4. LEFT OPEN? YES X NO IS SYSTEM TAGGED YES X NO DATE OF TEST 10/23/2015 NEXT TESTING DUE DATE 10/2016 m w New England Fire & Sprinkler Protection, Inc. 80 Brick Kiln Road - Chelmsford, MA 01824 (978) 452-2895 • (978) 453-5475 - Fax LOCATION: SALEM HEIGHTS 100%ANNUAL SPRINKLER TEST 12 POPE ST. SALEM, MA 10/23/15 VALVE MANUFACTURE STAR SIZE 3" MODEL A YEAR 1995 WET DRY X ACCELERATOR: YES NO X WATER FLOW TEST: (THROUGH 2" DRAIN VALVE, WIDE OPEN) 1. PRESSURE: STATIC 150 PSI RESIDUAL PSI 70 2. APPROXIMATE LENGTH OF DRAIN PIPE 15 FEET 3. DRAIN DISCHARGE: INSIDE: X OUTSIDE: OTHER: ALARM TEST: 2" DRAIN INSPECTORS TEST 1. WATER MOTOR GONG- SATISFACTORY? YES N/A NO SEC 2. INSIDE HORNS/STROBES YES X NO SEC 25 3. EXPLAIN ANY"NO"ANSWERS: 4A. IS SYSTEM SUPERVISED: YES X NO By Whom FACP 4B. WAS A SIGNAL RECEIVED: YES X NO Explain: MASTERBc #4121 SUPPLIES: 1. NUMBER. 1 2. SIZE #1 10" #2 #3 #4 3. FROM WHAT STREET POPE ST. ADDITIONAL DATA(I.E. - FIRE PUMP TANK, COMMENTS, ETC) -NOTE#1 —THE GAUGE BETWEEN COMPRESSOR AND THE FIRST CHECK NEEDS TO BE REPLACED Page 1 of 2 New England Fire & Sprinkler Protection, Inc. a f 80 Brick Kiln Road Chelmsford, MA 01824 (978) 452-2895 • (978) 453-5475 - Fax LOCATION: SALEM HEIGHTS 100%ANNUAL SPRINKLER TEST 12 POPE ST. SALEM, MA 10/23/15 CONTROL VALVES: 1. NUMBER: 3 INSIDE X OUTSIDE 2. INDICTING TYPE? YES X NO 3. FOUND OPEN? YES X NO 4. LEFT OPEN? YES X NO IS SYSTEM TAGGED YES X NO DATE OF TEST 10/23/2015 NEXT TESTING DUE DATE 10/2016 I '